0% found this document useful (0 votes)
52 views2 pages

EM341 5ID2 - Rev00 Transformer Bulk - EN 1

The document describes the SmartG-02 EM341-5ID2 three phase indirect meter. It is a four wire, prepay/postpay electronic meter that measures active and reactive energy and complies with IEC and EN standards, making it suitable for transformer and bulk applications. It operates on a three phase, four wire network at 220V/380V, 50Hz and measures energy consumption from 1-6 amps. The modular nature allows for upgradeable communication options like GPRS, PLC and RF.

Uploaded by

Amr Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views2 pages

EM341 5ID2 - Rev00 Transformer Bulk - EN 1

The document describes the SmartG-02 EM341-5ID2 three phase indirect meter. It is a four wire, prepay/postpay electronic meter that measures active and reactive energy and complies with IEC and EN standards, making it suitable for transformer and bulk applications. It operates on a three phase, four wire network at 220V/380V, 50Hz and measures energy consumption from 1-6 amps. The modular nature allows for upgradeable communication options like GPRS, PLC and RF.

Uploaded by

Amr Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

SMARTG-02 INDIRECT

THREE PHASE METER


EM341-5ID2
Transformer / Bulk Applications

INTRODUCTION
The SmartG-02 electricity meter series are modern, electronic, fully programmable
devices, designed for application in AMI systems for monitoring and control of
electricity consumption.
The SmartG-02 electricity meter series meet remote data transmission
requirements and enable readouts of various measurands. The meters are
compliant with IEC and DLMS/COSEM standards and have been designed to
serve billing purposes.
EM341-5ID2, is a four wire, Prepaid/Postpaid compact electronic meter (indirect
connection meter), with accuracy class 0.2, capable of measuring Active &
Reactive Energy and is type approved according to IEC & EN standards. This
makes it perfectly suitable for Transformer / Bulk Applications.
The indirect connection meter is used to measure energy consumption in 220
VAC, 50 Hz, and 1-6 Ampere, and operates in a three-phase four wire power
network. It contains an independent measuring element allowing consumed
energy to be measured. There is a LED mounted on the front panel of the meter,
pulsing at a rate of 1000 pulses per KWh or KVAr for energy registration.
The modular nature of the meter means that its communications interface
supports a broad range of field-upgradable communications options including
GPRS, PLC, and RF among others.

STANDARDS
• IEC 62052-11 • IEC 62056-42
• IEC 62053-23:2003 • IEC 62056-46
• EN 50470 • IEC 62056-53
• IEC 695-2-1 • IEC 62056-61
• IEC62055 (for contactor) • IEC 60068

www.elsewedyemg.com
[email protected]
METER SPECIFICATIONS METER FEATURES
Electrical Characteristics Feature Description
Nominal Voltage 3X220/380 V Display • Fully electronic (LCD) with backlight

Voltage Variation (Min) -40% Vn • The meter is capable of storing two profiles. One
for energy and one for other parameters.
Voltage Variation (Max) 30% Vn
Load Profile • Each profile has an integration period of 1 to 60
Nominal Current (Ibase) 1A minutes

Maximum Current (Imax) 6A • The profiling period extends for at least 45 days

Nominal Frequency 50 Hz • The EM341-5-SmartG-02 records a considerable


amount of data for extended periods of time
Frequency Variations ±5%
Events • In addition, the EM341-5-SmartG-02 stores up to
0.2 Active according to IEC 400 events
Accuracy Class 62053-22
2 Reactive • Events are logged with a date/time stamp

0.1 % Ib according to IEC


Starting Current
62053-22 • The EM341-5-SmartG-02 has the ability to detect
the following types of tamper attempts:
Wiring 3 PH, 4 wires Network
3  Meter Cover Open
Number of elements 3 3  Terminal Cover Open
3  Module Cover Open
Power Consumption ≤ 2W 3  Reverse Connection
Tamper Proofing
KWh 3  Earth or Current Bypass Connection
Measurements 3  Overload
MD(A)(KW)
3  Over Voltage
Back-up Battery Type Lithium Battery 3  Under Voltage
3  Phase Sequence
Back-up Battery Lifetime 10 Years
3  Missing Potential
Memory
• The meter supports two alarm methods
Type Flash memory
3  LED Indicator
Retention Period More than 20 Years 3  Audible Alarm
Alarms
3  Messages on LCD
Environmental Conditions
• The meter can be configured to give any
IP Rating IP54 combination of alarms as required

Temperature Range -5°C to +70°C • The relay control modes include:

Storage Temperature -25°C to +80°C 3  Remote Disconnect


3  Local Disconnect
Humidity Range <90%
• The relay is configurable to be triggered in the
event of:
Altitude 0-3600M
3  Meter cover open
Service Life 20 Years 3  Meter Terminal Cover Open
Relay Operation 3  Module Cover Open
Communication 3  Energy Reverses
Standard Optical Port (IEC 3  Earth or Current Bypass Connection
62056-21) 3  Meter Current Overload
Optical Interface 3  Meter Over Voltage and Under Voltage
Complies with DLMS/COSEM
HDLC mode-E protocol 3  At Low Battery
3  Phase Sequence
RS-485 3  Missing Potential
Serial Communication Port Complies with DLMS/COSEM 3  Low Credit
direct HDLC protocol
Supported through the use • With each power-up or firmware update, the
AMI/AMM Module of a GSM/GPRS Modem, PLC meter shall diagnose:
Modem or RF Modem
Auto-diagnostics 3  Meter and memory integrity
Optical Port: 9600 bit/s 3  Display, alarms & battery status
Data Transmission Rate RS-485: 9600 bit/s GPRS: 3  External communication module status
56–114 Kbit/s
D
MECHANICAL SPECIFICATIONS
4 Dimensions: (L x W x D) = W
277.3 mm x 177.4 mm x 88.5 mm L

4 Weight: Approximately 1.8Kg


4 Meter Housing: Flame Retardant Polycarbonate