SIFANG CSC-326 V1.00 Numerical Transformer Protection Equipment Manual 2010-08
SIFANG CSC-326 V1.00 Numerical Transformer Protection Equipment Manual 2010-08
Equipment Manual
(CD2009277, CD2009278)
V1.00
Document Code:F0SF.450.062(E)
CSC-326 Numerical Transformer Protection
Equipment Manual
Version: V1.00
Doc.Code:F0SF.450.062(E)
Issued Date:2010-8-20
Important notes
¾ Scope of Application
This manual only caters to CSC-326, including CSC-326 M1 and CSC-326 M2.
Please read the manual carefully and the specification of the installation, adjustment, testing,
operation and maintenance with the protective relay.
¾ Restricted liability
Electrical equipment should be serviced and maintained only by qualified personnel. No
responsibility is assumed by SIFANG for any consequences arising out of the use of this manual.
This document is not intended as an instruction manual for untrained persons.
¾ Device operation
The user is responsible for checking that the rated characteristics of the device are suitable for its
application. The user is responsible for reading and following the device’s operating and installation
instructions before attempting to commission or maintain it. Failure to follow these instructions can
affect device operation and constitute a hazard for people and property.
Please use the testing instruments which comply with the relevant standards for test and detection
as well.
To prevent damage from equipment, don’t hot-plug and hot-unplug any module of the relay;
touching the chips and components in printed circuit board is inhibited.
If any abnormity occurred in the equipment or unusual maintenance needed, please promptly
contact with the agents or our service hotline.
¾ Operation password
The operation password is: 8888, the system setup password is: 7777.
¾ Protective grounding
The user is responsible for compliance with all the existing international and national electrical
codes concerning protective grounding of any device.
Safety instructions
Read these instructions carefully and look at the protective relay to become familiar with the device
before trying to install, operate, service or maintain it. The following special messages may appear
throughout this bulletin or on the equipment to warn of potential hazards or to call attention to
information that clarifies or simplifies a procedure.
¾ Safety alert
This is the safety alert symbol. It is used to alert you to potential personal injury
hazards and prompt you to consult the manual. Obey all safety instructions that follow
this symbol in the manual to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death,
serious injury or property damage.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death,
serious injury or property damage.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor or
moderate injury or property damage.
NOTE
NOTE indicates matters need attention regarding a certain special application, functions or
characteristics of the HW/SW.
COPYRIGHT
®
is registered trademark of Beijing Sifang Automation Co., Ltd.
We reserve all rights to this document, even in the event that a patent is issued and a different
commercial proprietary right is registered. Improper use, in particular reproduction and dissemination to
third parties, is not permitted.
This document has been carefully checked. If the user nevertheless detects any errors, he is asked to
notify us as soon as possible.
The data contained in this manual is intended solely for the product description and is not to be deemed
to be a statement of guaranteed properties. In the interests of our customers, we constantly seek to
ensure that our products are developed to the latest technological standards as a result; it is possible that
there may be some differences between the hardware/software product and this information product.
Manufacturer:
Beijing Sifang Automation Co., Ltd.
Tel: +86-10-62961515
Fax: +86-10-62981900
Internet: http://www.sf-auto.com
Add: No.9, Shangdi 4th Street, Haidian District, Beijing, P.R.C.100085
CONTENTS
1 Introduction ................................................................................. 1
1.1 Application............................................................................................... 1
1.2 Features ................................................................................................... 4
1.3 Functions ................................................................................................. 5
2 Design .......................................................................................... 6
1 Introduction
1.1 Application
CSC-326 numerical transformer protection equipment applies to small, medium and large power
transformers. in all voltage levels.
Equipments included in the CSC-326 series see Table 1-1 and 1-2.
1
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Overload protection Χ √
Backup protection in LV (low voltage) side
Overload protection
√ √
Overload for LV winding (inside delta) Χ √
Circuit breaker failure (CBF)
HV1 CBF
√ √
MV CBF
Χ √
LV CBF
√ Χ
Other auxiliary protection
Disturbance records for body protection function √ √
VT Failure detection
√ √
DI1~2 trip DO1~2
√ √
2
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
CT1 CT2
* *
50BF [HV1] ●
(optional)
97FF [HV]
50 [HV]
51 [HV]
67 [HV]
50N [HV]
●
51N [HV]
●
67N [HV]
49 [HV]
24 [HV]
87TN [HV] 87T
Overload (alarm)
50G [HV]
51G [HV]
●
67G [HV]
*
50 [LV]
51 [LV]
67 [LV]
50N [LV]
51N [LV]
●
50G [MV] 67N [LV]
87TN [MV] 51G [MV] 24 [LV]
67G [MV] Overload (alarm)
50 [MV]
51 [MV] 97FF [LV]
67 [MV]
●
50N [MV]
*
51N [MV]
67N [MV]
97FF [MV]
49 [MV]
24 [MV]
50BF [MV]
Overload (alarm)
3
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
1.2 Features
The equipment has characteristics as follows:
z The microprocessor combined 32 bits DSP with MCU, high performance hardware systems
ensures the parallel real-time calculation in all components of the equipment.
z Protective functions man-machine interface and also communications functions are
completely separated in equipment. This improves the reliability and makes debugging
installation, maintenance and use much easier.
z Internal module was intelligent designed so that a comprehensive real-time self-inspection
can be carried out.
z Double A/D sampling in analog circuit Acquisition, performing real time self-testing for each
other.
z The equipment provides convenient automatic testing scheme in field, it can achieve a
comprehensive, perfect test.
z Main protection and Backup protection are integrated in one set of equipment, and the analog
input, binary input and binary output are shared by all protections.
z Reliable and powerful treble slope percent Differential protection is main advantage of the
relay.
z Selective inrush stabilization schemes are provided, 2nd harmonic stabilization and Fuzzy
recognition of inrush based on the waveform are widely used in transformer inrush
recognition.
z Reliable CT fail and CT saturation used method guaranty the safe relay operation whenever
the CT abnormity is detected and blocked the corresponding protection.
z Fault wave recorder with great capacity, memory up to 4M bytes, can record full process of
any fault, and can save no less than 24 records. Optional data format or wave format is
provided when the records need to be printed, and also fault wave recorder can be exported
to serial port or Ethernet port by COMTRADE format.
z Event recorder can store operating reports, alarm reports, start reports and general operation
records, every kind of record isn’t less than 2 000 events, and is memorized when power is off.
z The product can record protection operating process, logic flow and varied calculation values
that can be analyzed in whole process by analyzing software CSPC developed by us. PC
which installed this fault analyzing software, can manipulate the protection system via series
ports RS-232 on faceplate in front of the equipment, and get information such as recorded
fault data and wave to analyze.
z 2-channel high speed reliable electric Ethernet ports (optional optical fiber Ethernet ports),
2-channel LonWorks ports, RS-485 port and series printing port are provided; the user can
select any of these according to the requirements. The protocol supports IEC60870-5-103,
IEC61850 or CSC-2000 of Sifang Company, easy to interface with substation automatic
system and protection management information system.
z Liquid crystal display with backlight: Application to display various messages such as current,
voltage, power, frequency, strip state, setting zones etc. The menu is easy to operate, and four
shortcut keys are set to finish operation with one key for local operator.
4
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
1.3 Functions
The following protection functions listed in table 1-3 are integrated:
5
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
2 Design
6
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
2.2 Dimensions
Dimension drawings for CSC-326 are shown in Fig 2-2.
Fig. 2-2 Flush-mounted enclosure of CSC-326 with panel cutout (dimensions in mm)
7
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
3 Technical data
Current transformer
Number 16 for CSC-326(M1) (at most)
24 for CSC-326(M2) (at most)
Rated current Inom 1 or 5 A (orderable)
Voltage transformer
Power consumption
at Vnom = 100 V ≤ 0.5 VA per phase
at Vnom = 110 V ≤ 0.5 VA per phase
Thermal Overload capability in voltage path
(phase-neutral voltage) 250V for 1s
200V for 10s
120V continuous
Accuracy
8
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Auxiliary voltage
Rated auxiliary voltage Vaux 125 VDC
110 VDC
220 VDC
Permissible tolerance ±%10Un VDC
Power consumption
Quiescent Less than 30 W
Energized Less than 50 W
9
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
10
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Shock Semi-sinusoidal
IEC 60255-21-2, Class 1 Acceleration 15 g, duration 11 ms
IEC 60068-2-27 6 shocks in both directions of 3 axes
Continuous shock Semi-sinusoidal
IEC 60255-21-2, class 1 Acceleration 10 g, duration 16 ms
IEC 60068-2-29 2000 shocks in both directions
of 3 axes
11
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Serial interfaces
Operating interface (front of unit)
Connection Non-isolated, RS232; front panel, 9-pin
subminiature connector , CSPC
Transmission rate Factory setting 9600 baud,
min. 1200 baud, max. 19200 baud
Service/modem interface
Isolated interface for data transfer Front Port : RS232,CSPC
Rear Port :RS485 in MASTER module
Transmission rate Factory setting 9600 baud,
min. 1200 baud, max. 19200 baud
RS232/RS485
Connection RS232: 9-pin subminiature connector, Front Port
RS485:2-wire connector, Rear Port in CPU
module
Distance RS232 15 m /49.2 ft
Distance RS485 Max. 1 km/3300 ft
Test voltage 500 V AC against earth
12
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
RS485 Interface
Connection
2-wire connector, Rear Port in MASTER module
Distance RS485 Max. 1 km/3300 ft
Test voltage 500 V AC against earth
Fiber Optic Interface (optional)
Functions
Differential protection (ANSI-87)
13
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Setting ranges
High-current stage ID>> 0.5A~20*In (“In” means CT secondary current, 1A
Differential current ID> or 5A)
0.3Ie~1.0Ie (Ie: nominal current of the reference
side)
Restraint current IR1 0.2Ie~1.0Ie
Restraint current IR2 2Ie~10Ie
Percentage of Slope 1 0.0~0.2
Percentage of Slope 2 0.2~0.7
Percentage of Slope 3 0.25 …. 0.95
2nd harmonic restraint ratio 0.05~0.80
3rd / 5th harmonic restraint ratio 0.05~0.80
Times
Operating time less than 30ms
(At 3 times of current setting)
Operating time less than 20ms
(At 10 times of current setting -value
without restraint)
Drop-off time approx. 40ms
Times
Operating time less than 30ms
( At 3 times of set value)
Drop-off time approx. 40ms
14
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Setting Ranges
Reference voltage UN 40~130V
U /U N 1.00~1.50
Ratio( > ):
f / fN
0.1s~9999.0s
Time Delay T 1.05 /1.10 /1.15 /1.20 /1.25 /1.30 /1.35 /1.40 /1.45
Pair of Values for Characteristic of V/f /1.50
Times
At 1.2 times of set value
Drop-off time less than 70ms
Times
Pickup time I> approx. 20ms
Operating time At 1.2 times of set value less than 40ms
Drop-off time I> approx. 40ms
Tolerance
Current pickup I> ±3% of set value or ±0.02IN
Angle of the directional element ±3°
Time delays not more than 40ms
(at 100ms and 1.2 times setting-value or above)
Drop-off ratio
I>,
not more than 0.95
Directional element:
Voltage threshold 1V
170°±2°
Angle of the directional element
15
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Setting ranges
Current I> 0.08A to 20 * IN
The sensitive angle of directional element 0°, -15°, -30°, -45° or -60°, selectable
Times
Pickup time I> approx. 20ms
Operating time At 1.2 times of set value less than 100ms
Drop-off time I> approx. 40ms
Minimum operating time 100ms
Maximum operating time 100s
Tolerance
Current pickup I> ±3% of set value or ±0.02IN
Angle of the directional element ±3°
Time delays not more than ±5% or 0.1s
Directional element:
Voltage threshold 1V
Angle of the directional element 170°±2°
Times
Pickup time 3I0> approx. 20ms
Operating time At 1.2 times of set value less than 40ms
Drop-off time 3I0> not more than 40ms
(at 100ms and 1.2 times setting-value or above)
Tolerance
Current pickup 3I0> ±3% of set value or ±0.02IN
Angle of the directional element ±3°
Time delays not more than 40ms
Drop-off ratio
3I0> approx. 0.9
Directional element:
Zero voltage threshold 0.5V
Angle of the directional element 160°±3°
16
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Tolerance
Current pickup 3I0> ±3% of set value or ±0.02IN
Angle of the directional element ±3°
Time delays not more than ±5% or 0.3s
Directional element:
Voltage threshold 1V
Angle of the directional element 160°±3°
Times
Operating times are calculated from IEC
Cold Curve and IEC Hot Curve. ⎧⎪ I eq 2 ⎫⎪
IEC Cold Curve t = τ ln ⎨ 2 2 ⎬
⎪⎩ I eq − I θ ⎪⎭
Tolerance
Current pickup I> ±3% of set value or ±0.02IN
Thermal trip time not more than ±5% or 0.1s
Overload protection
Setting ranges
Current I> 0.1A to 20×IN
Delay times T 0.1 to 20s
17
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
(ANSI-50G/67G)
Setting ranges
Current 3I0> 0.08A to 20*IN
Time delay T 0 to 60s
Times
Pickup time 3I0> approx. 20ms
Operating time At 1.2 times of set value less than 40ms
Drop-off time 3I0> not more than 40ms
(at 100ms and 1.2 times setting-value or above)
Tolerance
Current pickup 3I0> ±3% of set value or ±0.02IN
Angle of the directional element ±3°
Time delays not more than 40ms
Drop-off ratio
3I0> approx. 0.9
Directional element:
Zero voltage threshold 0.5V
Angle of the directional element 160°±3°
Directional element:
Voltage threshold 1V
Angle of the directional element 160°±3°
18
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
4 Hardware functions
X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11
AI1 AI2 CPU1 CPU2 MASTER BI BO1 BO2 BO3 BO4 POWER
Manage
Binary Input 1
Binary Output 1
Binary Output 2
Binary Output 3
Binary Output 4
Relay
Relay
DC
AC AC
Power
Input Input
Supply
Binary Input 1
Binary Output 1
Binary Output 2
Binary Output 3
Binary Output 4
Relay
Relay
DC
AC AC AC
Power
Input Input Input
Supply
19
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
20
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5 Protection functions
Main protection
z Differential protection
9 Instantaneous differential protection
9 Treble slope percent differential protection
9 Individually selectable Inrush inhibit with 2nd harmonic
9 Individually selectable Fuzzy recognition of inrush based on waveform
9 Individually selectable Overflux stabilization (3rd or 5th harmonic)
9 Eliminate zero sequence current and vector group adaption
9 CT Failure supervision and CT saturation recognition
9 Differential current alarm
z Restricted earth fault protection
9 Restricted earth fault protection for HV
9 Restricted earth fault protection for MV (CSC-326(M2))
9 Restricted earth fault protection for LV (CSC-326(M1))
9 REF zero differential current alarm
z Overflux protection
9 Individually selectable (HV or LV side) Overflux (definite and inverse)
9 A definite-time alarm stage and a definite-time trip stage
9 The inverse characteristic can be set via ten points derived from the manufacturer data
Backup protection in HV (high voltage) side
z Thermal overload protection
9 2 Stages (Alarm and Trip)
9 Thermal profile considering (memory capability) according to IEC 60255-8
z Definite and IDMTL overcurrent protection
9 2 definite-time stages and 1 inverse-time stage
9 7 kind curves (covers all IEC/ANSI characteristics)
9 5 kind OC Angle SELs
9 Individually selectable direction detection for each stage
9 Individually selectable Direction to transformer/ system for each stage
9 Individually selectable inrush blocking for each stage
9 Cross blocking for inrush detection
9 Settable maximum inrush current
9 VT fail monitoring for directional overcurrent protection
21
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
22
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
23
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
9 One alarm and two definite-time tripping stages(low-setting tripping/ high-setting tripping)
9 The two tripping stage can be set respective to initiate each side CBF or not
9 Voltage independent
Circuit breaker failure (CBF) protection
9 HV1 CBF
9 MV CBF(CSC-326(M2))
9 LV CBF(CSC-326(M1))
24
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
9 2 trip stages
9 Internal/ External initiation
9 Selectable internal functions for CBF initiation
9 Current criteria checking (including phase, zero and negative sequence current)
9 Selectable CB Auxiliary contact checking
Other auxiliary protection
9 Disturbance records for body protection function
9 VT Failure detection
9 BI1~2 trip BO1~2
9 The two tripping stage can be set respective to initiate each side CBF or not
25
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
For example, the setting “HV VOLTAGE CHAN SEL” can be set as 1, 2 and 3 which means voltage
channel is connected to the corresponding analog input module (see Table 5-1). If “HV VOLTAGE
CHAN SEL” is set 1, it means that HV voltage transformers must be connected to U1A/B/C in AI1
module, if it is set 2, it means that HV voltage transformers must be connected to U2A/B/C in AI2
module and if it is set 3, it means that HV voltage transformers must be connected to U3A/B/C in AI3
module.
In CSC-326(M1) as mentioned, “HV VOLTAGE CHAN SEL” is the only setting which is needed to be
set. If HV voltage transformers are supposed to connect to U1A/B/C, then LV voltage transformers
must be connected to U3A/B/C if it is necessary. In case HV voltage transformers are connected to
U3A/B/C, then LV voltage transformers must be connected to U1A/B/C. In CSC-326(M1) series
setting value 2 has no meaning for “HV VOLTAGE CHAN SEL” and if it is set by mistake, “SetErr”
alarm report will be given by the device and denied to be set.
For CSC-326(M2), if the HV voltage transformers are connected to U1A/B/C then MV voltage
transformers can be marshaled to U2A/B/C or U3A/B/C. In case MV voltage transformers are
connected to U2A/B/C, LV voltage transformers must be connected to U3A/B/C and vice versa. If
the setting “HV VOLTAGE CHAN SEL” and “MV VOLTAGE CHAN SEL” are set a same value, alarm
report “SetErr” will be given by the device.
If the voltage channels are marshaled to the specific analog input module, the corresponding
overflux protection, directional element and VT fail supervision etc. are detected according to that
configuration.
26
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5.3.1. Introduction
The numerical current differential protection represents the main protection function of CSC-326. It
provides a fast short-circuit protection for power transformers. The protected zone is selectively
limited by the CTs at its ends. The device is able to perform this function on 2 or 3 winding
transformers in a variety of voltage levels and protected object types.
I A.1
I B.1
I C .1
I B .1
I C .1
27
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
I A.1
I B .1
I C .1
MV
I a.2
a
I b .2
b
I A.1 HV I c .2
c
A
I B .1
B
I C .1 LV
C I a.3
a
I b .3
b
I c .3
c
CSC-326
28
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
operation condition. This current flows into one side of the protected object and leaves it again on
the other side. A difference in currents is an indication of a fault within this section. An example of
this condition is shown in Fig.5-5, when a fault inside the protected zone causes a current I1prim. +
I2prim. flowing in from both sides of the protected object.
Fig.5-5 Basic principle of differential protection for two ends (single phase)
For protected objects with three or more sides, the basic principle is expanded in that the total of all
currents flowing into the protected object is zero in healthy operation, whereas in case of a fault the
total in-flowing current is equal to the fault current.
When an external fault causes a heavy current to flow through the protected transformer,
differences in the magnetic characteristics of the current transformers CT-1 and CT-2 under
saturation condition may cause a significant difference in the secondary currents I1 + I2 connected to
CSC-326 relay. If the difference is greater than the respective pickup threshold, the differential
protection function can trip even though no fault occurred in the protected zone. To prevent the
protection function from such erroneous operation, a restraint (stabilizing) current is brought in. In
differential protection relays, the restraint current is normally derived from the i1 and i2. The next
subsection goes on to demonstrate how the differential and restraint currents are calculated in
CSC-326.
Where I&i is the current vector of side i, corresponding to HV, MV and LV windings;
N is total current inputs of the relay. In other words, it is number of the protected object sides;
I& j (max) is the maximum current vector among the N current inputs of the relay, suppose it is side j;
N −1 •
∑I
i =1
i (i ≠ j ) is sum of the other current inputs of the relay, not including side j.
29
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Idiff is derived from the fundamental frequency current and produces the tripping effect quantity,
whereas Ires counteracts this effect.
To clarify the situation, three important operating conditions with ideal and matched measurement
qualities are examined.
1. External fault under undisturbed conditions:
I1 flows into the protected zone, I2 leaves the protected zone, i.e. is negative according to the
definition of signs, therefore I2 = –I1.
Idiff = I1 + I2 = I1 – I1 = 0
Ires = 0.5×| I1 - (–I1) | = 0.5×|2I1| = |I1|
No tripping effect (Idiff = 0); the restraint (Ires) corresponds to the external fault current flowing
through the protected object.
2. Internal fault, fed with equal currents from both sides:
The following applies I2 = I1
Idiff = I1 + I2 = I1 + I1 = 2 I1
Ires = 0.5×| I1 - I1| = 0
Tripping effect (Idiff) corresponds to double the fault current, and restraint value (Ires) are equal to
zero.
3. Internal fault, fed from one side only:
The following applies when assuming I2 = 0
Idiff = I1 + I2 = I1 + 0 = I1
Ires = 0.5×|I1 - I2| =0.5× |I1 - 0| = 0.5×|I1|=0.5 I1
Tripping quantity (Idiff) and restraint quantity (Ires) are equal and correspond to the single-sided fault
current.
The results show that the device is capable to properly discriminate internal and external faults by
using the definitions proposed for differential and restraint current. However, the device is still
subjected to some influences that induce differential currents even during normal operation
condition. These influences should be compensated in appropriate manners. The specific
treatments designed to cope with these influences includes automatic ratio compensation and
automatic vector group compensation which are explored in the next subsections.
30
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
SN
I 1N = (1-2)
3U 1N
Where SN is rated apparent power of the transformer and U1N is rated voltage of the corresponding
side.
The rated secondary current of each side, I2N, is then calculated by (1-3).
I 1N
I 2N = (1-3)
nCT
Rated secondary current of the High voltage side is then taken as the reference current. The
currents of the other sides are automatically matched to the rated current of the high voltage side by
calculation of correction factor KCT for MV and LV side, according to (1-4) and (1-5), respectively:
I 2 N − HV I /n S / 3U 1N − HV nCT − MV U 1N − MV nCT − MV
K CT − MV = = 1N − HV CT − HV = N ⋅ = ⋅ (1-4)
I 2 N − MV I 1N − MV / nCT − MV S N / 3U 1N − MV nCT − HV U 1N − HV nCT − HV
SN=160MVA
U1N-HV=230kV U1N-LV=63kV
CTRATIO=500/1A CTRATIO=2000/1A
31
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
160 MVA
I 1N − HV = = 402 A (1-6)
3 × 230
I 1N − HV 402
I 2 N − HV = = = 0.804 A (1-7)
nCT 500
160 MVA
I 1N − LV = = 1466 A (1-8)
3 × 63
1466
I 2 N − LV = = 0.733 A (1-9)
2000
0.804
K CT −LV = = 1.097 (1-10)
0.733
Concerning three-winding power transformers, the windings may have different power ratings. In
order to compare secondary currents in an appropriate manner, all currents are matched to the
rated secondary current of HV winding having highest power rating. This apparent power is
nominated as the rated apparent power of the transformer.
Fig.5-7 shows an example of a three-winding power transformer. HV winding and MV winding are
rated for 160MVA. The rated primary and secondary currents of these windings are calculated as
shown in previous example. However, the LV winding has 25MVA rating (e.g. for auxiliary supply).
The rated current of this winding may result in 721A. However, differential protection has to process
comparable currents. Therefore, the currents of LV winding should be referred to the rated apparent
power of the transformer, i.e. 160MVA. This results in a rated current of 4619A. This is the base
value for the LV winding, which should be further multiplied by KCT-LV to be used in calculation
process of differential protection.
160 MVA
I 1N − LV = = 4619 A (1-11)
3 × 20
I 1N − LV 4619
I 2 N − HV = = = 1.848 A (1-12)
nCT 2500
0.804
K CT −LV = = 0.435 (1-13)
1.848
If three-winding transformer with a delta LV winding (with no CB installed) is used to supply
substation LVAC loads, it may be desired that LV current should not be integrated in differential
protection. In this case, control word “Diff Includes LV Cur” is used to select whether LV current
should be included in differential protection calculation procedure or not. By applying setting “0-Diff
NOT Includes LV Cur” only HV and MV currents would be included in differential protection
32
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
calculation. On the contrary, when a three-winding transformer is equipped with three CBs in its
sides, it may be desired to include LV current in differential protection. This can be achieved by
applying setting “1- Diff Includes LV Cur” to respective control word.
(1). Take example for Yy0 connection, including similar ones of Yy0 (separate or auto-connected
windings), YNy0, Yyn0, YNyn0 (separate or auto-connected windings) and so on. Fig.5-8 shows an
example in case of Yy0 connection group with no earthed starpoint. The figure shows the windings
(left) and the vector diagrams of symmetrical currents (right).
Fig. 5-8 Vector Group and zero sequence compensation for Yy0 transformer
The equations including the coefficient matrix are as follow:
33
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
⎡ I&A′ ⎤ ⎡1 -1 0 ⎤ ⎡ I&A ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I B′ ⎥ = ⋅ 0 1 -1⎥⎥ ⋅ ⎢ I&B ⎥ (1-14)
⎢ I&′ ⎥ 3 ⎢
⎢⎣ -1 0 1 ⎥⎦ ⎢ I&C ⎥
⎣ C⎦ ⎣ ⎦
⎡ I&a′ ⎤ ⎡1 -1 0 ⎤ ⎡ I&a ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I b′ ⎥ = ⋅ ⎢0 1 -1⎥⎥ ⋅ ⎢ I&b ⎥ (1-15)
⎢ I&′ ⎥ 3
⎢⎣-1 0 1 ⎥⎦ ⎢ I&c ⎥
⎣ c⎦ ⎣ ⎦
According to these matrices, if we deduct side 1 currents I&A − I&B , the resulting current I&′A has the
same direction as I&′A on side 2. Multiplying it with 1 3 , matches the absolute value. The matrices
describe the conversion for all three phases. Using these matrices, the elimination of zero sequence
currents are warranted regardless of starpoint earth connection.
As mentioned previously, equations (1-14) and (1-15) can be used similarly for auto-transformers,
as the auto-connected windings in auto-transformers can only be connected Y(N)y(n)0. If the
starpoint is earthed, both the auto-connected HV and LV windings are affected. The zero sequence
components in current flowing through both sides of the transformer are then coupled because of
the common starpoint. These zero sequence components are eliminated by the application of the
matrices presented in (1-14) and (1-15).
(2). Take example for Yd1 connection, including similar ones of Yd1 and YNd1 without earthing
transformer installed at delta side. Fig.5-9 shows an example in case of Yd1 connection group with
no earthed starpoint.
A B C
A
a
Yd1 c
C b B
a b c
Fig.5-9 Vector Group compensation for Yd1 transformer
The equation including the coefficient matrix is as follows:
⎡ I&A′ ⎤ ⎡1 0 -1⎤ ⎡ I&A ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I B′ ⎥ = ⋅ ⎢ -1 1 0 ⎥⎥ ⋅ ⎢ I&B ⎥ (1-16)
⎢& ⎥ 3
1 ⎦⎥ ⎢ I&C ⎥
⎣ I C′ ⎦ ⎣⎢ 0 -1 ⎣ ⎦
If an earthing transformer/reactor is installed inside the protected zone on delta side, the CSC-326
should be informed about it by control word “HV D_side Eliminate I0”, “MV D_side Eliminate I0” or
34
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
“LV D_side Eliminate I0”. The control word related to delta side with earthing connection should be
set to “1-eliminate” in such condition. By taking example for Yd1 connection with earthing
transformer installed at delta side, control word “LV D_side Eliminate I0” is set to “1-eliminate”, and
thus, device performs a zero sequence current elimination on delta side. In this case, the equations
including the coefficient matrices are as follow:
⎡ I&A′ ⎤ ⎡1 0 -1⎤ ⎡ I&A ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I B′ ⎥ = ⋅ -1 1 0 ⎥⎥ ⋅ ⎢ I&B ⎥ (1-17)
⎢ I&′ ⎥ 3 ⎢
⎢⎣ 0 -1 1 ⎥⎦ ⎢ I&C ⎥
⎣ C⎦ ⎣ ⎦
⎡ •′ ⎤ ⎡•⎤
I
⎢ ⎥ I
a
⎡ 2 − 1 − 1⎤ ⎢ a ⎥
⎢• ⎥ 1 ⎢ ⎥.⎢ I• ⎥
⎢ ⎥ ′ = − − (1-18)
I b .⎢ 1 2 1⎥ ⎢ b⎥
⎢ • ⎥ 3 ⎢− 1 − 1 2 ⎥ ⎢ • ⎥
⎢ I ′c ⎥ ⎣ ⎦ ⎢I c ⎥
⎣ ⎦ ⎣ ⎦
(3). Take example for Ydd3 connection, including similar ones of Ydd3 and YNdd3 without earthing
transformer installed at delta sides. Fig.5-10 shows an example in case of Ydd3 connection group
with no earthed starpoint in Wye side.
(4). Take example for Yd5 connection, including similar ones of Yd5 and YNd5 with earthing
transformer installed at delta side. Fig.5-11 shows an example in case of Yd5 connection group with
no earthed starpoint.
35
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
(5). Take example for Dy1 connection, including similar ones of Dy1 and Dyn1 without earthing
transformer installed at delta side. Fig.5-12 shows an example in case of Dy1 connection group with
no earthed starpoint.
36
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
⎡ I&a′ ⎤ ⎡1 -1 0 ⎤ ⎡ I&a ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I b′ ⎥ = ⋅ 0 1 -1⎥⎥ ⋅ ⎢ I&b ⎥ (1-22)
⎢ I&′ ⎥ 3 ⎢
⎢⎣ -1 0 1 ⎥⎦ ⎢ I&c ⎥
⎣ c⎦ ⎣ ⎦
If an earthing transformer/reactor is installed inside the protected zone on delta side, control word
“HV D_side Eliminate I0” is set to “1-eliminate”, and thus, device performs a zero sequence current
elimination on delta side. In this case, the equations including the coefficient matrices are as follow:
⎡ •′ ⎤ ⎡• ⎤
I
⎢ A ⎥ I
⎡ 2 − 1 − 1⎤ ⎢ A ⎥
⎢• ⎥ 1 ⎢ ⎥ ⎢• ⎥
⎢ I ′ B ⎥ = .⎢− 1 2 − 1⎥.⎢ I B ⎥ (1-23)
⎢ • ⎥ 3 ⎢− 1 − 1 2 ⎥ ⎢ • ⎥
⎢ I ′C ⎥ ⎣ ⎦ ⎢I C ⎥
⎣ ⎦ ⎣ ⎦
⎡ I&a′ ⎤ ⎡1 -1 0 ⎤ ⎡ I&a ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I b′ ⎥ = ⋅ 0 1 -1⎥⎥ ⋅ ⎢ I&b ⎥ (1-24)
⎢ I&′ ⎥ 3 ⎢
⎢⎣ -1 0 1 ⎥⎦ ⎢ I&c ⎥
⎣ c⎦ ⎣ ⎦
Subsequent to application of the magnitude, vector group and zero sequence compensation, the
CSC-326 relay use the following calculated quantities (per phase) to discriminate between internal
and external faults: fundamental component of differential and restraint currents together with
instantaneous value, 2nd and 5th harmonic contents of differential current. The following sections
go on to demonstrate the fault recognition criteria using these derived quantities.
37
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
As mentioned previously and can be seen from Fig.5-13, the stage operates as an unrestrained
protection function. In other words, it is not inhibited by any of harmonic stabilization features of the
percent differential element as well as the CT failure detection. This means that it can operate even
when, for example, a considerable second harmonic is present in the differential current, which is
caused by current transformer saturation by a DC component in the fault current, and which could
be interpreted by the inrush inhibit function as an inrush current.
This high current stage evaluates the fundamental component of the differential current as well as
the instantaneous values. Instantaneous value processing ensures fast tripping even in case the
fundamental component of the current is strongly reduced by current transformer saturation. Fast
trip area is shown in Fig.5-14.
38
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
characteristics can be enabled or disabled by using control word “PER DIFF ON” (1-on, 0-off). If
setting 1-on is selected, the stage calculates differential and restraint current separately in each
phase to obtain operating point in each operation condition. The derived point is then mapped into
Idiff-Ires plane to examine whether it lies in trip or block area which is defined according to
predefined operating characteristic. The operation characteristic is shown in Fig.5-14.
IDiff
ID>> Fast trip area
(INST DIFF ID)
Slope 3
Trip area
Slope 2
block area
Slope 1
ID> IRest
(PER DIFF ID)
IR1 IR2 Restraint current
Fig. 5-14 Differential protection characteristics for transformers
In this characteristic, branch 1 represents the sensitivity threshold of the differential protection. The
setting of ID> (setting "PER DIFF ID") defines the minimum differential current required for operation.
The setting is chosen based on the amount of differential current that might be seen under normal
operating conditions which corresponds to constant error currents such as magnetizing currents and
CT errors under no-load conditions. The setting for slope of branch 1 is applicable for restraint
currents of zero to the first break-point indicated on restraint axis (setting "DIFF IR1"). The slope
(setting “DIFF SLOPE S1”) defines the ratio of differential to restraint current above which the
percent differential stage will operate. The first break-point on restraint axis defines the end of the
slope 1 region and the start of the second branch region. This setting should be set just above the
maximum operating current level of the transformer. This level is somewhere between the maximum
forced-cooled rated current of the transformer and the maximum emergency overload current level.
Branch 2 considers current-proportional errors which may result from transformation errors of the
main CTs or the input CTs of the relay. This may also contain the error caused by the influence of tap
changers in power transformers with voltage control. The setting for slope of branch 2 (setting “DIFF
SLOPE S2”) is applicable for restraint currents of the first break-point to the second one on restraint
axis, and defines the ratio of differential to restraint current above which the element will operate.
This slope is set to ensure sensitivity to internal faults at normal operating current levels. The
second break-point on restraint axis (setting “DIFF IR2”) defines the end of the slope 2 region and
the beginning of the slope 3 region. This setting should be set to the level at which any of the
protection CTs is probable to saturate.
In the range of high through fault currents which may give rise to high differential currents as a result
of CT saturation, branch 3 is applicable to provide additional stabilization. The setting for the slope
of this branch (setting “DIFF SLOPE S3”) is applicable up to the point at which the branch intersects
the characteristic of instantaneous differential protection.
As a summary of the fault detection using operating characteristics of Fig.5-14, the calculated
differential and restraint currents, IDiff and IRest, are compared by the differential protection with the
39
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
I diff − A , I rest − A
I diff − B , I rest − B
I diff −C , I rest −C
It should be noted that when the CSC-326 is delivered, the both the instantaneous and percent
differential protection functions are switched off. Setting of “0-off” is applied for control words “INST
DIFF ON” and “PER DIFF ON”. This is because the fact that these protection functions should not
be used before at least the vector group and other essential parameters for each side is correctly set.
Without these settings the equipment may show unpredictable behavior. (E.g. tripping)
40
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
enter the protected zone. However, it does not exit it again. They thus produce differential quantities,
as they seem like single-end fed fault currents. Therefore, they should be recognized in an
appropriate manner. By this way, it is possible to prevent false operation of differential protection
caused by inrush current. This possibility is provided in the CSC-326. Selective inrush stabilization
can be enabled or disabled by control word “Inrush BLK DIFF”, (1-Block, 0-Not Block). If setting
“1-Block” is applied, the function monitors differential current to detect an inrush condition. If the
condition is detected, it is possible to block differential protection phase-selectively. Furthermore,
alarm report entitled “DIFF 2HAR BLK” is issued whenever inrush detection impose a blocking
condition to differential protection. It should be noted that the latter, is generated when any condition
(2nd harmonic, 3rd/5th harmonic, CT fail) leads to blocking of differential protection.
The CSC-326 provides two schemes to detect inrush conditions. The first scheme is 2nd harmonic
stabilization; the second scheme is fuzzy recognition of inrush conditions based on the waveform.
The two schemes are convenient for user to be selected by the setting “2nd HAR NOT WAVE”
(1-2nd harmonic on; 0-waveform on). The two implemented algorithm work alternatively. As soon as
an inrush condition is recognized by each of them, a restraint condition is applied to the respective
phase evaluation of percent differential protection. Since the applied restraint by 2nd harmonic
detection operates individually per phase, the protection is fully operative even when the protected
transformer is switched onto a single-phase fault, whereas inrush currents may possibly be present
in one of the healthy phases. It is, however, possible to set the protection in a way that when the 2nd
harmonic recognition is fulfilled only in one single phase, not only the phase with the inrush current,
but also the remaining phases of the percent differential protection are blocked. This is achieved by
cross-blocking the differential protection for a certain period to avoid spurious tripping. The setting
corresponds to “2nd HAR BLOCK TIME”. Within this time, all three phases are blocked as soon as
an inrush current is detected in any one phase. After the timer is expired, only the phase with inrush
current content is blocked.
41
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
samples per cycle, each of the samples is nominated as I(k), k=1, 2, …, 2n. Then the value of X(k) is
calculated according to (1-27).
I ( k ) + I ( k + n)
X (k ) = , k = 1,2,..., n (1-27)
I ( k ) + I ( k + n)
The smaller values of X(k) represent that the calculated point corresponds to fault condition with
higher confidence level. Alternatively, the larger values of X(k) gives a picture that there is large
content of inrush current in the waveform. Assume that X(k) belongs to “inrush Fuzzy class” with
membership function of A[X(k)]. Then, the fuzzy similarity coefficient for the n calculated values of
X(k) in one cycle is defined as (1-28).
n
N= ∑ A[ X (k )] / n
k =1
(1-28)
The derived value of N is used in the CSC-326 to assess the differential current corresponds to
inrush condition or not. To do so, the value of N is compared with a threshold K, and inrush content
is recognized in the current waveform, if N>K.
I diff − A−φ 2
> Kϕ 2
I diff − A−φ
I diff − B −φ 2
> Kϕ 2
I diff − B −φ
I diff −C −φ 2
> Kϕ 2
I diff −C −φ
42
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
I diff − A−φ 3
> Kϕ −3 / 5
I diff − A−φ
I diff − A−φ 5
> K ϕ −3 / 5
I diff − A−φ
I diff − B −φ 3
> Kϕ −3 / 5
I diff − B −φ
I diff − B −φ 5
> K ϕ −3 / 5
I diff − B −φ
I diff −C −φ 3
> Kϕ −3 / 5
I diff −C −φ
I diff −C −φ 5
> K ϕ −3 / 5
I diff −C −φ
43
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
at CT failure detection through setting "Blk DIFF at CT FAIL" (1-Block, 0-Not Block). By setting
“1-Block”, the percent differential protection is blocked immediately in all phases. Blocking condition
is cancelled as soon as the device is again supplied with a normal current in the relevant faulty
phase(s). It should be noted that the setting "Blk DIFF at CT FAIL" is not relevant if the differential
current is very high. In other words, blocking conditions takes place only for treble slope percent
differential protection. This means that the instantaneous differential protection will issue trip if a
differential current greater than setting “INST DIFF ID” is present, even if "Blk DIFF at CT FAIL" is
set to 1-Block.
The criteria for CT failure detection are as follow:
The currents flowing through all three phases of CT secondary are normal at each side of the
protected object. As a result, the differential current is near to zero. When one or two phase current
of one side is decreased to less than a threshold (half of the memory current), at the same time all
three phase currents in other side(s) are normal, and differential current is more than a threshold
(0.3ID>) at least in one phase, the condition maybe an indication of CT failure in the mutative
phase(s). CT failure detection logic is illustrated in Fig.5-18.
44
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Iφ 2 Iφ 3
+ > K har (1-30)
Iφ Iφ
Where:
Iφ2 is 2nd harmonic magnitude of phase current at each side,
Iφ3 is 3rd harmonic magnitude of phase current at each side,
Khar is the setting for comprehensive harmonic ratio, fixed in the software.
If the 2nd and 3rd harmonic contents of any phase current are more than Khar, then CT satisfies the
formula (1-30) and it is saturated. Usually before the CT saturation status, there is a short time
period in which CT still works in its linear characteristic. By very fast CT saturation detection of
CSC-326 relay, it needs only 4ms before any CT saturation happening to detect the fault which is
internal or external fault. In order to distinguish saturation caused by internal faults and external
faults effectively, percent differential protection based on sample values is used. If CT saturation is
induced by external fault, differential protection will be blocked. However if CT saturation is induced
by internal fault, differential protection will send its trip signal.
45
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
DANGER: Before Differential protection is put into operation on site, polarity of current
transformer must have been checked right by an energizing test of every side of the transformer or a
test of simulating an external fault of the side in primary system. Otherwise a mal-operation may occur
during an external fault.
46
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
9. DIFF 3/5th HAR RATIO 0.05..0.80 0.35 3rd / 5th harmonic(HAR) ratio
Within the delay 2nd harmonic block
all three phases. After the delay,
10. 2nd HAR BLOCK TIME 0.05…20s 10
then only the local phase is
blocked.
Within the delay 5th harmonic block
all three phases. After the delay,
11. 3rd/5th HAR BLK TIME 0.05…20s 10
then only the local phase is
blocked.
47
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5.3.6. Annunciations
Table 5-6 List of event report
Abbr. (LCD
No. Comment
Display)
1. PER DIFF Trip A
2. PER DIFF Trip B Treble slope percent Differential protection (ID>) trip for
phase A/B/C
3. PER DIFF Trip C
4. INST DIFF Trip A
Instantaneous Differential protection (ID>>) trip for phase
5. INST DIFF Trip B
A/B/C
6. INST DIFF Trip C
48
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
⎡ I&A′ ⎤ ⎡1 -1 0 ⎤ ⎡ I&A ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I B′ ⎥ = ⋅ ⎢0 1 -1⎥⎥ ⋅ ⎢ I&B ⎥
⎢ I&′ ⎥ 3
⎢⎣ -1 0 1 ⎥⎦ ⎢ I&C ⎥
⎣ C⎦ ⎣ ⎦
⎡ I&a′ ⎤ ⎡1 -1 0 ⎤ ⎡ I&a ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I b′ ⎥ = ⋅ 0 1 -1⎥⎥ ⋅ ⎢ I&b ⎥
⎢ I&′ ⎥ 3 ⎢
⎢⎣-1 0 1 ⎥⎦ ⎢ I&c ⎥
⎣ c⎦ ⎣ ⎦
A
a
⎡ I&A′ ⎤ ⎡1 0 -1⎤ ⎡ I&A ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
c
⎢ I B′ ⎥ = ⋅ ⎢ -1 1 0 ⎥⎥ ⋅ ⎢ I&B ⎥
⎢ I&′ ⎥ 3
⎢⎣ 0 -1 1 ⎥⎦ ⎢ I&C ⎥
C b B ⎣ C⎦ ⎣ ⎦
c
⎡ •′ ⎤ ⎡•⎤
I
⎢ a ⎥ I
⎡ 2 − 1 − 1⎤ ⎢ a ⎥
C b B ⎢ ⎥ 1⎢
•
⎥.⎢ I• ⎥
⎢ ⎥ ′ = − −
I b
3
.⎢ 1 2 1⎥ ⎢ b⎥
⎢• ⎥ ⎢⎣− 1 − 1 2 ⎥⎦ ⎢ • ⎥
⎢ I ′c ⎥ ⎢I c ⎥
⎣ ⎦ ⎣ ⎦
Yy2, YNy2, Yyn2, YNyn2
49
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
A B C
⎡ I&A′ ⎤ ⎡1 -1 0 ⎤ ⎡ I&A ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I B′ ⎥ = ⋅ ⎢0 1 -1⎥⎥ ⋅ ⎢ I&B ⎥
⎢ I&′ ⎥ 3
⎢⎣ -1 0 1 ⎥⎦ ⎢ I&C ⎥
⎣ C⎦ ⎣ ⎦
⎡ I&a′ ⎤ ⎡0 -1 1 ⎤ ⎡ I&a ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I b′ ⎥ = ⋅ 1 0 -1⎥⎥ ⋅ ⎢ I&b ⎥
⎢ I&′ ⎥ 3 ⎢
⎢⎣-1 1 0 ⎥⎦ ⎢ I&c ⎥
b c a ⎣ c⎦ ⎣ ⎦
c a b
⎡ •′ ⎤ ⎡•⎤
I
⎢ ⎥ I
a
⎡ 2 − 1 − 1⎤ ⎢ a ⎥
⎢• ⎥ 1 ⎢ ⎥ ⎢• ⎥
⎢ I ′b ⎥ = .⎢− 1 2 − 1⎥.⎢ I b ⎥
⎢ • ⎥ 3 ⎢− 1 − 1 2 ⎥ ⎢ • ⎥
c a b
⎢ I ′c ⎥ ⎣ ⎦ ⎢I c ⎥
⎣ ⎦ ⎣ ⎦
Yy4, YNy4, Yyn4, YNyn4
⎡ I&A′ ⎤ ⎡1 -1 0 ⎤ ⎡ I&A ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I B′ ⎥ = ⋅ 0 1 -1⎥⎥ ⋅ ⎢ I&B ⎥
⎢ I&′ ⎥ 3 ⎢
⎢⎣ -1 0 1 ⎥⎦ ⎢ I&C ⎥
⎣ C⎦ ⎣ ⎦
50
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
⎡ I&A′ ⎤ ⎡ -1 1 0 ⎤ ⎡ I&A ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I B′ ⎥ = ⋅ 0 -1 1 ⎥⎥ ⋅ ⎢ I&B ⎥
⎢ I&′ ⎥ 3 ⎢
⎢⎣1 0 -1⎥⎦ ⎢ I&C ⎥
⎣ C⎦ ⎣ ⎦
⎡ •′ ⎤ ⎡•⎤
I
⎢ a ⎥ I
⎡ 2 − 1 − 1⎤ ⎢ a ⎥
⎢• ⎥ 1 ⎢ ⎥ ⎢• ⎥
⎢ I ′b ⎥ = .⎢− 1 2 − 1⎥.⎢ I b ⎥
⎢ • ⎥ 3 ⎢− 1 − 1 2 ⎥ ⎢ • ⎥
⎢ I ′c ⎥ ⎣ ⎦ ⎢I c ⎥
⎣ ⎦ ⎣ ⎦
Yy6, YNy6, Yyn6, YNyn6
⎡ I&A′ ⎤ ⎡1 -1 0 ⎤ ⎡ I&A ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
-1⎥⎥ ⋅ ⎢ I&B ⎥
A
⎢ I B′ ⎥ = ⋅ ⎢0 1
⎢ I&′ ⎥ 3
⎢⎣ -1 0 1 ⎥⎦ ⎢ I&C ⎥
b c
⎣ C⎦ ⎣ ⎦
A
b ⎡ I&A′ ⎤ ⎡-1 0 1 ⎤ ⎡ I&A ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I B′ ⎥ = ⋅ 1 -1 0 ⎥⎥ ⋅ ⎢ I&B ⎥
c
⎢ I&′ ⎥ 3 ⎢
⎢⎣0 1 -1⎥⎦ ⎢ I&C ⎥
⎣ C⎦ ⎣ ⎦
a
C B
51
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
⎡ •′ ⎤ ⎡•⎤
I
⎢ a ⎥ I
⎡ 2 − 1 − 1⎤ ⎢ a ⎥
⎢• ⎥ 1 ⎢ ⎥ ⎢• ⎥
⎢ I ′b ⎥ = .⎢− 1 2 − 1⎥.⎢ I b ⎥
⎢ • ⎥ 3 ⎢− 1 − 1 2 ⎥ ⎢ • ⎥
⎢ I ′c ⎥ ⎣ ⎦ ⎢I c ⎥
⎣ ⎦ ⎣ ⎦
Yy8, YNy8, Yyn8, YNyn8
⎡ I&A′ ⎤ ⎡1 -1 0 ⎤ ⎡ I&A ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I B′ ⎥ = ⋅ ⎢0 1 -1⎥⎥ ⋅ ⎢ I&B ⎥
⎢ I&′ ⎥ 3
⎢⎣ -1 0 1 ⎥⎦ ⎢ I&C ⎥
⎣ C⎦ ⎣ ⎦
A
b ⎡ I&A′ ⎤ ⎡ 0 -1 1 ⎤ ⎡ I&A ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
a ⎢ I B′ ⎥ = ⋅ ⎢1 0 -1⎥⎥ ⋅ ⎢ I&B ⎥
⎢ I&′ ⎥ 3
⎢⎣ -1 1 0 ⎥⎦ ⎢ I&C ⎥
⎣ C⎦ ⎣ ⎦
C c B
a
⎡ •′ ⎤ ⎡•⎤
I
⎢ a ⎥ I
C c B ⎡ 2 − 1 − 1⎤ ⎢ a ⎥
⎢• ⎥ 1 ⎢ ⎥ ⎢• ⎥
⎢ I ′b ⎥ = .⎢− 1 2 − 1⎥.⎢ I b ⎥
⎢ • ⎥ 3 ⎢− 1 − 1 2 ⎥ ⎢ • ⎥
⎢ I ′c ⎥ ⎣ ⎦ ⎢I c ⎥
⎣ ⎦ ⎣ ⎦
52
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
⎡ I&A′ ⎤ ⎡1 -1 0 ⎤ ⎡ I&A ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I B′ ⎥ = ⋅ ⎢0 1 -1⎥⎥ ⋅ ⎢ I&B ⎥
⎢ I&′ ⎥ 3
⎢⎣ -1 0 1 ⎥⎦ ⎢ I&C ⎥
⎣ C⎦ ⎣ ⎦
⎡ •′ ⎤ ⎡•⎤
I
⎢ a ⎥ I
⎡ 2 − 1 − 1⎤ ⎢ a ⎥
⎢• ⎥ 1 ⎢ ⎥ ⎢• ⎥
⎢ I ′b ⎥ = .⎢− 1 2 − 1⎥.⎢ I b ⎥
⎢ • ⎥ 3 ⎢− 1 − 1 2 ⎥ ⎢ • ⎥
⎢ I ′c ⎥ ⎣ ⎦ ⎢I c ⎥
⎣ ⎦ ⎣ ⎦
Dy1, Dyn1 [HV D_side Eliminate I0=0- not eliminate]
⎡ I&a′ ⎤ ⎡1 -1 0 ⎤ ⎡ I&a ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I b′ ⎥ = ⋅ ⎢0 1 -1⎥⎥ ⋅ ⎢ I&b ⎥
⎢ I&′ ⎥ 3
⎢⎣ -1 0 1 ⎥⎦ ⎢ I&c ⎥
⎣ c⎦ ⎣ ⎦
53
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
⎡ I&a′ ⎤ ⎡1 -1 0 ⎤ ⎡ I&a ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I b′ ⎥ = ⋅ 0 1 -1⎥⎥ ⋅ ⎢ I&b ⎥
⎢ I&′ ⎥ 3 ⎢
⎢⎣ -1 0 1 ⎥⎦ ⎢ I&c ⎥
⎣ c⎦ ⎣ ⎦
⎡ I&a′ ⎤ ⎡0 -1 1 ⎤ ⎡ I&a ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I b′ ⎥ = ⋅ ⎢1 0 -1⎥⎥ ⋅ ⎢ I&b ⎥
⎢ I&′ ⎥ 3
⎢⎣-1 1 0 ⎥⎦ ⎢ I&c ⎥
⎣ c⎦ ⎣ ⎦
⎡ I&a′ ⎤ ⎡0 -1 1 ⎤ ⎡ I&a ⎤
⎢& ⎥ 1 ⎢ ⎢ ⎥
⎢ I b′ ⎥ = ⋅ 1 0 -1⎥⎥ ⋅ ⎢ I&b ⎥
⎢ I&′ ⎥ 3 ⎢
⎢⎣-1 1 0 ⎥⎦ ⎢ I&c ⎥
⎣ c⎦ ⎣ ⎦
54
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
A B C
c a b
55
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
56
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
⎡ •′ ⎤ ⎡• ⎤
I
⎢ ⎥ I
A
⎡ 2 − 1 − 1⎤ ⎢ A ⎥
⎢ ⎥ 1⎢
•
⎥.⎢ I• ⎥
⎢ ⎥ ′ = − −
I B
3
.⎢ 1 2 1⎥⎢ B⎥
⎢• ⎥ ⎢⎣− 1 − 1 2 ⎥⎦ ⎢ • ⎥
⎢ I ′C ⎥ ⎢I C ⎥
⎣ ⎦ ⎣ ⎦
57
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5.4.1. Introduction
The restricted earth fault protection detects earth faults in power transformers with earthed starpoint
or in non-earthed power transformers with a starpoint former (earthing transformer/reactor) installed
inside the protected zone. A precondition for using this function is that a CT should be installed in the
starpoint connection, i.e. between the starpoint and earth. The starpoint CT and the phase CTs
define the limits of the protected zone by restricted earth fault protection.
I&a′ .2
I&b′ .2
I&c′.2
3I&01
′
3I&02
′ = I&a′ .2 + I&b′ .2 + I&c′.2
58
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
I& A.2
I&a′ .2
I&B.2
I&b′ .2
I&C .2 I&c′ .2
3I&01 3I&01
′
3I&02
′ = I&a′ .2 + I&b′ .2 + I&c′.2
Fig. 5-23 Application of restricted earth fault protection on both sides of transformer
I& A.2
I&B.2
I&C .2
59
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
With the described situations, it may seem to be simple to discriminate an internal fault from an
external one. However, there are some difficulties to do so. For instance, when a strong fault without
earth connection occurs outside the protected zone, a residual current may appear in the residual
current path of the phase CTs. The residual current is caused by different degrees of saturation in
phase CTs and could simulate a fault in the protected zone. Thus, additional measures should be
taken to prevent this current to cause false tripping. To achieve this objective, the restricted earth
fault protection provides a restraint quantity.
Idiff0 and Irest0 are compared by the restricted earth fault protection with a dual-slope operating
characteristic defined by (1-33) and shown in Fig. 5-25.
⎧⎪I diff 0 ≥ I 0 D if I res 0 ≤ I 0 D / S 0 D
⎨
⎪⎩I diff 0 ≥ S 0 D × I res0 if I res 0 > I 0 D / S 0 D (1-33)
Where I0D is the setting for sensitivity threshold of restricted earth fault protection (setting “HV REF
I0D”, “MV REF I0D” or “LV REF I0D”), and S0D is slope of the branch (setting “HV REF SLOPE”, “MV
REF SLOPE” or “LV REF SLOPE”).
This characteristic can be enabled or disabled by using control word “HV REF TRIP ON”, “MV REF
TRIP ON” or “LV REF TRIP ON”). If setting “1-on” is selected, a trip signal is issued by restricted
earth fault protection when the operating point lies into tripping area (see Fig.5-25) and the preset
time delay is expired (setting “HV REF TRIP T”, “MV REF TRIP T” or “LV REF TRIP T”).
The trip logic for restricted earth fault protection is shown in Fig.5-26.
I Diff0
S0D
I 0D
I Res0
60
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
To clarify the proper operation of CSC-326 during various situations, three important operating
conditions are examined.
1. External fault:
3I01 enters the protected zone, whereas 3I02 leaves the protected zone, i.e. is negative
according to the definition of signs, therefore 3I02 = –3I01.
Idiff0 = |3I01 + 3I02| = |3I01 – 3I02|= 0
Ires0 = max {|3I01|, |3I02|} = |3I01|
No tripping quantity (Idiff0 = 0); the restraint quantity (Irest0) corresponds to the external fault
current flowing through the starpoint connection.
2. Internal fault, fed only from the starpoint:
In this case, 3I02=0, thus,
Idiff0 = |3I01 + 3I02| = |3I01 + 0| = |3I01|
Ires0 = max {|3I01|, |3I02|} = |3I01|
Both the tripping (Idiff0) and the restraint (Irest0) quantities correspond to the fault current flowing
through the starpoint.
3. Internal fault, fed from the starpoint and from the system, e.g. with equal earth current
magnitude:
Both the 3I01 3I02 enter the protected zone, thus having positive sign. The condition results
in 3I02 = 3I01.
Idiff0 = |3I01 + 3I02| = |3I01 + 3I02|= 2×|3I01|
Ires0 = max {|3I01|, |3I02|} = |3I01|
Tripping quantity (Idiff0) corresponds to double the fault current flowing through the starpoint
connection, and restraint quantity (Irest0) is equal to the fault current.
The results show that the device is capable to properly discriminate internal and external earth faults
by using the definitions proposed for differential and restraint current. However, the device is still
subjected to some influences that induce differential currents even during normal operation
condition. These influences should be compensated in appropriate manner. The specific treatments
designed to cope with these influences includes automatic ratio compensation which is explored as
follows.
61
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
ratio of phase and starpoint CTs. The difference may result in a differential current in normal
operation condition. To remove this problem, the input currents of the relay from starpoint CTs
should be converted according to primary rated currents of phase and starpoint CTs. In the
CSC-326, this objective is achieved by taking a common reference value and converting all
secondary currents of starpoint CTs into the same reference. The conversion is performed by
calculation of ratio compensation factor for starpoint CTs. The compensation factors are then
multiplied by the secondary current of starpoint CTs to make them comparable with those current
measured at phase CTs. The conversion procedure is performed inside the device. The ratio
compensation factors are calculated as follow:
nStarpo int − HV
K Starpo int − HV =
nPhase− HV (1-34)
nStarpo int − MV
K Starpo int − MV =
nPhase− MV (1-35)
nStarpo int − LV
K Starpo int − LV = (1-36)
nPhase− LV
Where K Starpo int − HV is the ratio compensation factor for HV starpoint CT; K Starpo int − MV is the ratio
compensation for MV starpoint CT and K Starpo int − LV is the ratio compensation for LV starpoint CT;
For auto-transformer, in addition to the common winding starpoint CT, the measured current from
phase winding of MV winding should also be converted to the common reference current. in this
context, the ratio compensation factors are calculated as follow:
nPhase−MV
K MV =
nPhase− HV (1-37)
nStarpo int
K Starpo int =
nPhase− HV (1-38)
Where K MV is the ratio compensation factor for MV phase CT, and K Starpo int is the ratio
compensation factor for common winding starpoint CT.
The reference current is selected as is shown in Table 5-9.
62
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
current exceeds the threshold value “HV REF ALARM I0D”, “MV REF ALARM I0D” or “LV REF
ALARM I0D”. The alarm is an indication of miss-connection in phase or starpoint CT secondary
windings, and therefore is released to remind user to detect the faulty connection in secondary
circuit and remove it. The function can be enabled or disabled by using setting “HV REF ALARM
ON”, “MV REF ALARM ON” or “LV REF ALARM ON”, (1-On, 0-Off). The setting range of the
threshold differential current to release restricted earth fault current alarm is on [0.08-10A]. However,
to avoid incorrect alarm indications, the threshold value is increased to 0.1A (in 1A nominal current
inputs) and to 0.3A (in 5A nominal current inputs), if the set value is less than 0.1A.
DANGER: Before Restricted Earth Fault protection is put into operation on site, polarity of
neutral current transformer for REF must have been checked right by an energizing test of every side
of the transformer or a test of simulating an external fault of the side in primary system. Otherwise a
mal-operation may occur during an external earth fault.
5.4.4. Settings, Control Words and operation data of restricted earth fault
protection
Table 5-10 Settings of Restricted earth fault protection
N Setting Default
Setting Title Comment
o options setting
Current setting for HV Restricted Earth
1. HV REF I0D 0.08..10A 2
Fault protection
Slope setting for HV Restricted Earth Fault
2. HV REF SLOPE 0.25..0.95 0.5
protection
3. HV REF TRIP T 0…60s 0.03 HV Restricted Earth Fault trip time setting
HV REF ALARM HV Restricted Earth Fault alarm current
4. 0.08..10A 2
I0D setting
HV Restricted Earth Fault alarm time
5. HV REF ALARM T 0…60s 0.03
setting
Current setting for MV Restricted Earth
6. MV REF I0D 0.08..10A 2
Fault protection
Slope setting for MV Restricted Earth Fault
7. MV REF SLOPE 0.25..0.95 0.5
protection
8. MV REF TRIP T 0…60s 0.03 MV Restricted Earth Fault trip time setting
MV REF ALARM MV Restricted Earth Fault alarm current
9. 0.08..10A 2
I0D setting
MV Restricted Earth Fault alarm time
10. MV REF ALARM T 0…60s 0.03
setting
Current setting for LV Restricted Earth
11. LV REF I0D 0.08..10A 2
Fault protection
Slope setting for LV Restricted Earth Fault
12. LV REF SLOPE 0.25..0.95 0.5
protection
13. LV REF TRIP T 0…60s 0.03 LV Restricted Earth Fault trip time setting
LV Restricted Earth Fault alarm current
14. LV REF ALARM I0D 0.08..10A 2
setting
LV Restricted Earth Fault alarm time
15. LV REF ALARM T 0…60s 0.03
setting
63
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5.4.5. Annunciations
Table 5-13 List of event report
64
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
65
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5.5.1. Introduction
The overflux protection is used to detect impermissible overflux conditions which can endanger
power transformers. An increase in transformer flux beyond the rated values leads to saturation of
the iron core and to large eddy current losses which cause impermissible temperature rise in
transformer core.
V < 0.7 × Un
66
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
The overflux protection includes two definite characteristics (alarm and trip) and one thermal
characteristic. The latter characteristic provides an approximate replica of the temperature rise
caused by overflux in the protected object. The definite alarm stage can be enabled or disabled by
using control word “DEF V/F ALARM ON”. Similarly, the definite trip stage can be enabled or
disabled by using control word “DEF V/F TRIP ON”. Furthermore, the thermal characteristic can be
set by control word “IVR V/F TRIP ON”. It should be mentioned that the overflux protection can be
applied at HV, MV or LV side of the protected transformer. However, it is not recommended to apply
the function on the transformer side with variable winding turns such as the transformer side with an
installed tap changer. To enable the protection on a given side, setting of “HV OverFlux ON”, “MV
OverFlux ON” and “LV OverFlux ON” should be applied to corresponding control words. However,
these settings should be applied to 1 only on one side at the same time. If any two of “HV OverFlux
ON”, “MV OverFlux ON” and “LV OverFlux ON” are set to 1 at the same time, alarm report “SetErr”
will be given by the device.
All the three available stages of the overflux protection use phase-to-phase voltage or phase-neutral
voltage of the corresponding side in their calculations, based on the setting applied at control word
“V/F Voltage (0-VPP,1-VPN)”.
If the definite alarm stage is enabled in one side, and the calculated volt/hertz ration exceeds the
threshold defined by setting “DEF ALARM V/F”, an alarm report “DEF V/F Alarm” is generated by
the device, after the time delay “Time DEF V/F Alarm” elapsed. The logic for the definite alarm stage
of overflux protection is shown in Fig.5-28 when it is applied to HV side. The logic is the same when
the protection function is applied to other sides.
67
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Fig. 5-28 Logic of the definite alarm stage for overflux protection
Similarly, if the definite trip stage is enabled in one side, and the calculated volt/hertz ration exceeds
the threshold defined by setting “DEF TRIP V/F”, an event report “DEF V/F Trip” is generated by the
device, subsequent to the expiration of time delay “Time DEF V/F Trip”. Tripping Logic of the definite
trip stage of overflux protection is shown in Fig. 5-29.
68
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
N (U A _ Hv , f ) 〉 DEF Trip V / F
N (U B _ Hv , f ) 〉 DEF Trip V / F
Fig. 5-29 Tripping logic of the definite trip stage for overflux protection
If thermal characteristic is set to “1-on” in one of transformer sides, it uses the measured voltage and
frequency of the corresponding side (depending on the setting applied at control word “V/F Voltage
(0-VPP,1-VPN)”), together with ten points derived from the manufacturer data (see Fig.5-30). The
points correspond to the desired tripping times for a given volt/hertz ratios. Intermediate values are
determined by performing linear interpolation by the device. The ratios range from N=1.05 to N=1.50.
They are entered into the device by settings “T1 IVR V/F=1.05”, “T2 IVR V/F=1.10”, “T3 IVR
V/F=1.15”, “T4 IVR V/F=1.20”, “T5 IVR V/F=1.25”, “T6 IVR V/F=1.30”, “T7 IVR V/F=1.35”, “T8 IVR
V/F=1.40”, “T9 IVR V/F=1.45” and “T10 IVR V/F=1.50”. The device uses these points to form an
inverse characteristic such as those shown in Fig. 5-30.
69
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
As can be seen from Fig. 5-30, N=1.05 works as a pickup threshold for thermal stage. The thermal
replica is implemented in CSC-326 by a counter which is incremented from 0% to 100%, as soon as
the calculated voltage/hertz ratio of (1-38) exceeds the pickup threshold (N=1.05). If the counter
reaches to 100% corresponding to expiration of trip time delay according to the trip characteristic,
the event report “IVR V/F Trip” is given. The trip signal is cancelled as soon as the calculated
voltage/hertz ratio falls below the pickup threshold (N=1.05). However, the counter is decremented
to zero according to cool down time of the transformer (the time by which the thermal replica counter
reaches from 100% to 0%). The cool down time is informed to the device by setting “Cool down
Time”.
Tripping Logic of the inverse thermal trip stage of overflux protection is shown in Fig.5-31.
70
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
N (U AB− HV , f )
N (U BC − HV , f )
N (U AC − HV , f )
N (U A− HV , f )
N (U B− HV , f )
N (U C − HV , f )
Fig. 5-31 Tripping logic of the thermal trip stage for overflux protection
NOTE: If it is possible for a given transformers to operate continuously under the condition of
N=1.05, corresponding time delay setting (“T1 IVR V/F=1.05”) should be set to 9999s. The same
approach can be taken when, for example, it is permissible for a transformer to operate continuously
71
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
under the condition N=1.10, N=1.15 and so on. It means that the thermal characteristic is compound of
10 points at most, and it maybe contains less than 10 points. The thermal characteristic would be
disabled if all the delay time settings are set to 9999s.
HV overflux, MV overflux and LV overflux functions should be applied only one side at the same time,
so settings of “HV VOLTAGE CHAN SEL” and “MV VOLTAGE CHAN SEL” (only for CSC-326(M2))
under “Comm Para” submenu are used to select the voltage channel.
For example of HV side; the setting “HV VOLTAGE CHAN SEL” can be set as 1, 2 and 3 which
means voltage channels are connected to the corresponding analog input module (see Table 5-16).
If control word “HV OverFlux ON” is set 1 and “HV VOLTAGE CHAN SEL” is set 2 or 3 (not 1), alarm
report “SetErr” will be given by the device. If control word “MV OverFlux ON” is set 1 and “MV
VOLTAGE CHAN SEL” is set 2 or 3 (not 1), alarm report “SetErr” will be given by the device. If “LV
OverFlux ON”, anyone of “HV VOLTAGE CHAN SEL” and “MV VOLTAGE CHAN SEL” is set 1,
alarm report “SetErr” will be given by the device.
72
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
73
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5.5.5. Annunciations
74
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5.6.1. Introduction
The non-directional overcurrent elements can be applied as backup protection functions for
transformer as well as power system protection in networks with radial nature and those which are
supplied from a single source. The directional overcurrent protection can also be applied in systems
where protection coordination depends on both the magnitude of the fault current and the direction
of power flow to the fault location, for instance in case of parallel transformers supplied from a
single source.
75
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
The pickup value for the inverse time-current stage can be defined by setting “IDMTL HV OC I”,
“IDMTL MV OC I” and “IDMTL LV OC I” for HV, MV and LV sides, respectively. Each phase current is
separately compared with corresponding setting value. If a current exceeds 1.1 times the setting
value, corresponding stage picks up. If an inverse time-current stage picks up, the tripping time is
calculated from the actual fault current flowing, using the selected tripping curve. Maximum tripping
time is limited to 100s.
The tripping curve can be selected from IEC or ANSI standard curves. The provided curves
comprise four types of IEC curves and three types of ANSI curves. The IEC curves include Normal
Inverse (NI), Very Inverse (VI), Extremely Inverse (EI), and Long Inverse (LI). The ANSI curves
include Moderately Inverse (MI), Very Inverse (VI) and Extremely Inverse (EI). Selection among the
curves can be carried out by settings “IDMTL HV OC CRV SEL”, “IDMTL MV OC CRV SEL” and
“IDMTL LV OC CRV SEL” for HV, MV and LV sides, respectively. The possible choices for each
setting word include the curve no. 1, curve no.2,…, curve no. 7. All the curves can be expressed by
following formula:
⎡ ⎤
⎢ ⎥
⎢ A ⎥
t = M ×⎢ P
+ B⎥ (1-41)
⎢⎡ I ⎤ ⎥
⎢⎢ ⎥ −1 ⎥
⎣⎣IS ⎦ ⎦
Where I is the fault current;
Is is the current setting;
M is the time multiplier;
A, P and B are the characteristic parameters for IDMTL curves. These characteristic parameters
have been defined for each curve in IEC and ANSI standards. Table 5-23 provides a summary of the
parameter values for each selected curve.
76
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
As mentioned previously, selection among the curves can be carried out by settings “IDMTL HV OC
CRV SEL”, “IDMTL MV OC CRV SEL” and “IDMTL LV OC CRV SEL” for HV, MV and LV sides,
respectively. For example by applying “5” to setting “IDMTL HV OC CRV SEL”, ANSI moderately
inverse characteristic is applied to HV side overcurrent IDMTL stage. By applying this selection,
corresponding parameter values of Table 23 are automatically activated by the relay. Furthermore,
the time multiplier M can be set by user to coordinate the integrated inverse time-current
characteristic of the device with other overcurrent relays installed for power system protection. This
can be performed by settings “IDMTL HV OC TimeMult”, “IDMTL MV OC TimeMult” and “IDMTL LV
OC TimeMult” in case of HV, MV and LV overcurrent elements, respectively.
By applying pickup current and time multiplier settings, the device calculates the tripping time from
the measured current in each phase separately, based on the selected inverse curve. Once the
calculated time has been elapsed, a trip signal is issued provided that no inrush current is detected
or inrush restraint is disabled. If the inrush restraint feature is enabled and an inrush condition exists,
the overcurrent protection would be blocked and therefore no tripping takes place. However, an
alarm report is generated as “HV Inrush Blk BU”, “MV Inrush Blk BU” or “LV Inrush Blk BU”,
indicating the blocking condition which is imposed to overcurrent element by detection of inrush
condition.
The trip signals and corresponding event reports are available separately for each stage. These
include “HV OC_1 Trip”, “HV OC_2 Trip” and “HV IDMTL OC Trip” for HV side, “MV OC_1 Trip”, “MV
OC_2 Trip” and “MV IDMTL OC Trip” for MV side, “LV OC_1 Trip”, “LV OC_2 Trip” and “LV IDMTL
OC Trip” for LV side overcurrent elements.
77
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
applied to make them blocked in inrush condition detection (“HV OC_1 Inrush Detect ON”, “HV
OC_2 Inrush Detect ON” and “HV IDMTL OC Inrush Detect ON” for HV side, “MV OC_1 Inrush
Detect ON”, “MV OC_2 Inrush Detect ON” and “MV IDMTL OC Inrush Detect ON” for MV side, “LV
OC_1 Inrush Detect ON”, “LV OC_2 Inrush Detect ON” and “LV IDMTL OC Inrush Detect ON” for LV
side.).
Since the applied restraint by second harmonic detection operates individually per phase, the
protection is fully operative even when the protected transformer is switched onto a single-phase
fault, whereas inrush currents may possibly be present in one of the healthy phases. It is, however,
possible to set the protection in a way that when the second harmonic recognition is fulfilled only in
one single phase, not only the phase with the inrush current, but also the remaining phases of the
overcurrent protection are blocked. This is achieved by cross-blocking the overcurrent protection for
a certain period to avoid spurious tripping. The setting corresponds to “2nd HAR BLOCK TIME”.
Within this time, the overcurrent protection in all three phases is blocked as soon as an inrush
current is detected in any one phase. After the timer is expired, the overcurrent protection is blocked
only in the phase with inrush current content. To put it more simply, cross blocking is reset if there is
no more inrush in any phase, or the cross blocking time interval is elapsed. It should be noted that
inrush currents flowing in the earth/ground path will not cross-block tripping by the phase elements.
Furthermore, if the fundamental component of phase current exceeds the upper limit value “HV OC
2HAR BLK Imax”, “MV OC 2HAR BLK Imax” or “LV OC 2HAR BLK Imax”, the inrush restraint will no
longer effective in respective side, since a high-current fault is assumed in this case. The setting can
be applied for each overcurrent element in each side of the protected transformer.
NOTE: The direction mentioned above is based on that the positive polarity is at the side of the
busbar and the negative polarity is at the side the transformer. Details are shown in Fig.1-1.
78
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Table 5-24 Voltage and current measurement used for direction determination
Phase Current Voltage
A Ia U bc
B Ib U ca
C Ic U ab
As can be seen from Table 5-24, the healthy voltages are used in direction determination. This
allows for a correct direction determination even if the fault voltage has collapsed entirely because
of a single-phase short-line fault. With three-phase short-line faults, memory voltage values are
used to clearly determine the direction if the measurement voltages are not sufficient. The
directional element of each side uses the voltage on itself side.
In a single-phase fault, the cross-polarized voltage (reference voltage) is 90° out of phase with the
fault voltage. With phase-to-phase faults, the position of the reference voltage changes up to 30°,
depending on the degree of collapse in the fault voltages. In order to satisfy different network
conditions and applications, the reference voltage can be rotated by an adjustable angle. For each
side of the protected transformer, the directional angle can be set independently. The settings
include “HV OC Angle SEL”, “MV OC Angle SEL” and “LV OC Angle SEL”, for HV, MV and LV sides,
respectively. It should be noted that the settings affect all the directional stages of the corresponding
overcurrent element. Take an example of HV side; the setting “HV OC Angle SEL” can be set as 0, 1,
2, 3 and 4 which means rotation angles of 0°, 15°, 30°, 45° and 60° are applied to the reference
voltage (see Table 5-25). In this way, the vector of rotated reference voltage can be closely adjusted
to the vector of fault current in order to provide the best possible result for the direction
determination. The rotated reference voltage defines the forward and reverse area. The forward
area is a range of ±85° around the rotated reference voltage. If the vector of the fault current is in
this area, the device detects forward direction. In the mirrored area, the device detects reverse
direction, and in the intermediate area, the direction result is undefined.
Table 5-25 Rotation angle setting of reference voltage for phase directional
elements
Angel setting
Rotation angle of reference voltage
“OC Angle SEL”
0 0 degree
1 15 degree
2 30 degree
45 degree
3
(This case is demonstrated in Fig. 5-32)
4 60 degree
79
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
⋅ ⋅
⋅ Ubc rotated ⋅
Ubc rotated I a Ia
850 ⋅
⋅
450 450 U bc
U bc 850
850
850
During direction decision by directional function, a VT Fail condition (a short circuit or broken wire in
the voltage transformer's secondary circuit or operation of the voltage transformer fuse) may result
in false or undesired tripping by directional overcurrent elements. In such a situation, it is possible to
select operation status of the directional overcurrent protection elements in each side by using a
number of control worlds to block the overcurrent protection elements or keep them in operational
state with no direction decision (block direction decision). The corresponding control words include
“Blk HV OC at HV VT FAIL”, “Blk MV OC at MV VT FAIL” and “Blk LV OC at LV VT FAIL”, for HV,
MV and LV sides, respectively. When the control words are set as 0 to select “Direct OK at VT Fail”,
corresponding overcurrent protection elements will not judge direction at the local side VT failure.
When they set as 1 to select “Blk O/C at VT Fail”, no operation is possible by the overcurrent
protection elements. It is noted that the control words affect all the stages of corresponding
overcurrent elements at each side. For instance, by applying setting “0-HV Direct OK at HV VT Fail”,
all the three stages of the overcurrent element will remain operative without direction determination
in case of any fault in secondary circuit of HV side voltage transformer. On the other hand, setting
“1- Blk HV OC at HV VT Fail” makes them blocked.
The logic for Definite and Inverse time IDMTL overcurrent protection is shown in Fig. 5-33.
80
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
O/C DIR ON
VT failure
Direct OK AND
at VT FAIL
O/C ON
(Definite Stg1, 2)
I>Iset AND T OC Trip
Direction Unit OK
Inrush BLK OC
Inverse IDMTL
O/C ON
Inverse Curve> AND T IDMTL OC Trip
Direction Unit OK
Inrush BLK OC
Fig. 5-33 Tripping logic for definite and IDMTL overcurrent protection
81
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
The timer is set to count up to a user-defined time delay. The time delay can be set for each definite
stage individually through settings “T HV EF I01” and “T HV EF I02” for HV side, “T MV EF I01” and
“T MV EF I02” for MV side, “T LV EF I01” and “T LV EF I02” for LV side. After the user-defined time
delay has been elapsed, a trip signal is issued if the inrush restraint feature is applied and no inrush
current is detected or inrush restraint is disabled. The earth fault protection would be blocked and
therefore, no tripping takes place if the inrush restraint feature is enabled and an inrush condition
exists. However, an alarm report is issued nominated as “HV Inrush Blk BU”, “MV Inrush Blk BU” or
“LV Inrush Blk BU”, indicating the blocking condition of earth fault element caused by inrush
condition detection.
Pickup value for the inverse time-current stage can be set by setting “IDMTL HV EF I0”, “IDMTL MV
EF I0” and “IDMTL MV EF I0” for HV, MV and LV sides, respectively. Each earth current (quantity 3I0)
calculated from the three phase currents is separately compared with corresponding setting value. If
a current exceeds 1.1 times the setting value, corresponding stage picks up. When an inverse
time-current stage picks up, the tripping time is calculated from the calculated quantity 3I0, using the
selected tripping curve. Maximum tripping time is limited to 100s.
Tripping curves can be selected from IEC or ANSI standard. The provided curves comprise four
types of IEC curves and three types of ANSI curves. The IEC curves include Normal Inverse (NI),
Very Inverse (VI), Extremely Inverse (EI), and Long Inverse (LI). The ANSI curves include
Moderately Inverse (MI), Very Inverse (VI) and Extremely Inverse (EI). Selection among the curves
can be carried out by settings “IDMTL HV EF CRV SEL”, “IDMTL MV EF CRV SEL” and “IDMTL LV
EF CRV SEL” for HV, MV and LV sides, respectively. The possible choices for each setting word
includes curve no. 1, curve no.2,…, curve no. 7. All the curves can be expressed by following
formula:
82
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
⎡ ⎤
⎢ ⎥
⎢ A ⎥
t = M ×⎢ P
+ B⎥ (1-43)
⎢⎡ I ⎤ ⎥
⎢⎢ ⎥ −1 ⎥
⎣⎣IS ⎦ ⎦
Where I is the calculated earth fault current;
Is is the current setting;
M is the time multiplier;
A, P and B are the characteristic parameters for IDMTL curves. They have been defined for each
curve in IEC and ANSI standards.
As mentioned previously, selection among the curves can be carried out by settings “IDMTL HV EF
CRV SEL”, “IDMTL MV EF CRV SEL” and “IDMTL LV EF CRV SEL” for HV, MV and LV sides,
respectively. For example by applying “5” to setting “IDMTL HV EF CRV SEL”, ANSI moderately
inverse characteristic is applied to HV side earth fault IDMTL stage. By applying this setting,
corresponding parameter values of Table 23 are automatically activated by the relay. Furthermore,
the time multiplier M can be applied by user to coordinate the integrated inverse time-current
characteristic of the device with other earth fault relays installed for power system protection. This
can be performed by settings “IDMTL HV EF TimeMult”, “IDMTL MV EF TimeMult” and “IDMTL LV
EF TimeMult” in case of HV, MV and LV earth fault elements.
By applying pickup current and time multiplier settings, the device determines the tripping time from
the calculated earth current, based on the selected inverse curve. Once the calculated time has
been elapsed, a trip signal is issued provided that no inrush current is detected or inrush restraint is
disabled. If the inrush restraint feature is enabled and an inrush condition exists the earth fault
protection would be blocked and therefore no tripping takes place. However, an alarm report is
issued designated as “HV Inrush Blk BU”, “MV Inrush Blk BU” or “LV Inrush Blk BU”, indicating the
blocking condition of overcurrent element caused by inrush condition detection.
The trip signals and corresponding event reports are available separately for each stage. They
include “HV EF_1 Trip”, “HV EF_2 Trip” and “HV IDMTL EF Trip” for HV side, “MV EF_1 Trip”, “MV
EF_2 Trip” and “MV IDMTL EF Trip” for MV side, “LV EF_1 Trip”, “LV EF_1 Trip” and “LV IDMTL EF
Trip” for LV side earth fault elements.
83
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
absent during a fault current, the inrush restraint operates based on the evaluation of the second
harmonic content which is present in the phase currents. The inrush condition is recognized if the
ratio of second harmonic current to the fundamental component exceeds the setting value “HV EF
2HAR RATIO”, “MV EF 2HAR RATIO” or “LV EF 2HAR RATIO” in each phase current. The setting is
applicable to both the definite stages of earth fault protection element as well as the inverse
time-current stage. As soon as the measured ratio exceeds the set threshold, a restraint is applied
to those stages for which corresponding setting is applied to make them blocked in inrush condition
detection (“HV EF_1 Inrush Detect ON”, “HV EF_2 Inrush Detect ON” and “HV IDMTL EF Inrush
Detect ON” for HV side, “MV EF_1 Inrush Detect ON”, “MV EF_2 Inrush Detect ON” and “MV IDMTL
EF Inrush Detect ON” for MV side, “LV EF_1 Inrush Detect ON”, “LV EF_2 Inrush Detect ON” and
“LV IDMTL EF Inrush Detect ON” for LV side).
Furthermore, if the fundamental component of each phase current exceeds the upper limit value
“HV EF 2HAR BLK Imax”, “MV EF 2HAR BLK Imax” or “LV EF 2HAR BLK Imax”, the inrush restraint
will no longer effective in respective side, since a high-current fault is assumed in this case.
84
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
NOTE: The direction mentioned above is based on that the positive polarities of three phases CT.
The voltage used by directional element is calculated by three phase voltage. Details are shown in
Fig.1-1.
3I 0 3I 0
3U 0 rotated 3U 0 rotated
3U0 3U 0
During direction decision by directional function, a VT Fail condition (a short circuit or broken wire in
the voltage transformer's secondary system or an operation of the voltage transformer fuse) may
result in false or undesired tripping by directional earth fault elements. In such a situation, it is
possible to select operation status of the directional earth fault protection elements in each side by
using a number of control words to block the earth fault protection elements or keep them in
operational state with no direction decision (block direction decision). The control words are
designated as “Blk HV EF at HV VT FAIL”, “Blk MV EF at MV VT FAIL” and “Blk LV EF at LV VT
FAIL”, for HV, MV and LV sides, respectively. When the control words are set as 0 to select “Direct
OK at VT Fail”, corresponding earth fault protection elements will not judge direction at the local side
VT failure. When they set as 1 to select “Blk EF at VT Fail”, no operation is possible by the earth
fault protection elements. It is noted that the control words affect all the stages of corresponding
earth fault elements at each side. For instance, by applying setting “0-HV Direct OK at HV VT Fail”,
all the three stages of the earth fault element will remain operative without direction determination in
case of any fault in secondary circuit of HV side voltage transformer. On the other hand, setting “1-
Blk HV EF at HV VT Fail” makes them blocked.
85
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
It is possible to block earth fault protection elements in each side of the protected transformer if a CT
fail is detected in the same side. This can be performed by control words “Blk HV EF at HV CT FAIL”,
“Blk MV EF at MV CT FAIL” and “Blk LV EF at LV CT FAIL” in each voltage side. If setting 1 is
applied to these control words, any CT fail detection in a given side of the power transformer would
bring blocking condition to all stages of the earth fault element which is applied in the same side.
The logic for definite and inverse time IDMTL earth fault protection is shown in Fig.5-35.
Fig. 5-35 Tripping logic for definite and inverse IDMTL earth fault protection
86
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
The timer is set to count up to a user-defined time delay. The time delay can be set for each definite
stage individually through settings “T HV Neutral OC I1” and “T HV Neutral OC I2” for HV side, “T
MV Neutral OC I1” and “T MV Neutral OC I2” for MV side, “T LV Neutral OC I1” and “T LV Neutral
OC I2” for LV side. After the user-defined time delay has been elapsed, a trip signal is issued if the
inrush restraint feature is applied and no inrush current is detected or inrush restraint is disabled.
The neutral overcurrent protection would be blocked and therefore, no tripping takes place if the
inrush restraint feature is enabled and an inrush condition exists. However, an alarm report is issued
nominated as “HV Inrush Blk BU”, “MV Inrush Blk BU” or “LV Inrush Blk BU”, indicating the blocking
condition of neutral overcurrent element caused by inrush condition detection.
Pickup value for the inverse time-current stage can be set by setting “IDMTL HV NOC I0”, “IDMTL
MV NOC I0” and “IDMTL MV NOC I0” for HV, MV and LV sides, respectively. Each neutral current
(quantity IN) measured by installed neutral CT is separately compared with corresponding setting
value. If a current exceeds 1.1 times the setting value, corresponding stage picks up. When an
inverse time-current stage picks up, the tripping time is calculated from the measured quantity IN,
using the selected tripping curve. Maximum tripping time is limited to 100s.
Tripping curves can be selected from IEC or ANSI standard. The provided curves comprise four
types of IEC curves and three types of ANSI curves. The IEC curves include Normal Inverse (NI),
Very Inverse (VI), Extremely Inverse (EI), and Long Inverse (LI). The ANSI curves include
Moderately Inverse (MI), Very Inverse (VI) and Extremely Inverse (EI). Selection among the curves
can be carried out by settings “IDMTL HV Neu CRV SEL”, “IDMTL MV Neu CRV SEL” and “IDMTL
LV Neu CRV SEL” for HV, MV and LV sides, respectively. The possible choices for each setting
word includes curve no. 1, curve no.2,…, curve no. 7. All the curves can be expressed by following
formula:
87
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
⎡ ⎤
⎢ ⎥
⎢ A ⎥
t = M ×⎢ P
+ B⎥ (1-45)
⎢⎡ I ⎤ ⎥
⎢⎢ ⎥ −1 ⎥
⎣⎣IS ⎦ ⎦
Where I is the calculated neutral current;
Is is the current setting;
M is the time multiplier;
A, P and B are the characteristic parameters for IDMTL curves. They have been defined for each
curve in IEC and ANSI standards (see Table 5-20 for more details).
As mentioned previously, selection between the curves can be carried out by settings “IDMTL HV
Neu CRV SEL”, “IDMTL MV Neu CRV SEL” and “IDMTL LV Neu CRV SEL” for HV, MV and LV
sides, respectively. For example by applying “5” to setting “IDMTL HV Neu CRV SEL”, ANSI
moderately inverse characteristic is applied to HV side neutral overcurrent IDMTL stage. By
applying this setting, corresponding parameter values of Table 23 are automatically activated by the
relay. Furthermore, the time multiplier M can be applied by user to coordinate the integrated inverse
time-current characteristic of the device with other relays installed for power system protection. This
can be performed by settings “IDMTL HV NeuTimeMult”, “IDMTL MV NeuTimeMult” and “IDMTL LV
NeuTimeMult” in case of HV, MV and LV neutral overcurrent elements.
By applying pickup current and time multiplier settings, the device determines the tripping time from
the measured neutral current, based on the selected inverse curve. Once the calculated time has
been elapsed, a trip signal is issued provided that no inrush current is detected or inrush restraint is
disabled. If the inrush restraint feature is enabled and an inrush condition exists, the neutral
overcurrent protection would be blocked and therefore no tripping takes place. However, alarm
report of “HV Inrush Blk BU”, “MV Inrush Blk BU” or “LV Inrush Blk BU” is issued, indicating the
blocking condition of neutral overcurrent element caused by inrush condition detection.
The trip signals and corresponding event reports are available separately for each stage. They
include “HV Neu OC_1 Trip”, “HV Neu OC_2 Trip” and “HV Neu OC IDMTL” for HV side, “MV Neu
OC_1 Trip”, “MV Neu OC_2 Trip” and “MV Neu OC IDMTL” for MV side, “LV Neu OC_1 Trip”, “LV
Neu OC_1 Trip” and “LV Neu OC IDMTL” for LV side neutral overcurrent elements.
88
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
detected.
Since the inrush current contains a relatively large second harmonic component which is nearly
absent during a fault current, the inrush restraint operates based on the evaluation of the second
harmonic content which is present in the measured neutral current (quantity IN), or in the phase
currents, based on setting. The inrush condition is recognized if the ratio of second harmonic current
to the fundamental component exceeds the setting value “HV NOC 2HAR RATIO”, “MV NOC 2HAR
RATIO” or “LV NOC 2HAR RATIO” in the measured neutral current. The setting is applicable to both
the definite stages of neutral overcurrent protection element as well as the inverse time-current
stage. As soon as the measured ratio exceeds the set threshold, a restraint is applied to those
stages for which corresponding setting is applied to make them blocked in inrush condition detection
(“HV Neu OC_1 Inrush Detect ON”, “HV Neu OC_2 Inrush Detect ON” and “H_IDMTL NOC Inrush
Detect ON” for HV side, “MV Neu OC_1 Inrush Detect ON”, “MV Neu OC_2 Inrush Detect ON” and
“M_IDMTL NOC Inrush Detect ON” for MV side, “LV Neu OC_1 Inrush Detect ON”, “LV Neu OC_2
Inrush Detect ON” and “L_IDMTL NOC Inrush Detect ON” for LV side).
Furthermore, if the fundamental component of the measured neutral current exceeds the upper limit
value “HV NOC 2HAR BLK Imax”, “MV NOC 2HAR BLK Imax” or “LV NOC 2HAR BLK Imax”, the
inrush restraint will no longer effective in respective side, since a high-current fault is assumed in
this case.
89
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
current in order to provide the best possible result for the direction determination. The rotated
reference voltage defines the forward and reverse area. The forward area is a range of ±80° around
the rotated reference voltage. If the vector of the fault current is in this area, the device detects
forward direction. In the mirrored area, the device detects reverse direction. In the intermediate area,
the direction result is undefined.
NOTE: The direction mentioned above is based on that the positive polarities of three phases CT.
The voltage used by directional element is calculated by three phase voltage. Details are shown in
Fig.1-1.
Angel setting
Rotation angle of reference voltage
“NOC Angle SEL”
100 degree
0
(This case is demonstrated in Fig. 5-36)
1 110 degree
2 120 degree
3 130 degree
4 140 degree
5 150 degree
3I 0 3I 0
3U 0 rotated 3U 0 rotated
3U0 3U 0
90
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
words affect all the stages of corresponding neutral overcurrent elements at each side. For instance,
by applying setting “0-HV Direct OK at HV VT Fail”, all the three stages of the neutral overcurrent
element will remain operative without direction determination in case of any fault in secondary circuit
of HV side voltage transformer. On the other hand, setting “1- Blk HV EF at HV VT Fail” makes them
blocked.
The logic for definite and inverse time IDMTL neutral overcurrent protection is shown in Fig.5-37.
Fig. 5-37 Tripping logic for definite and inverse IDMTL neutral overcurrent protection
91
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
More detail information about the initiation conditions and related control words can be found in
Section 5.8.
5.6.3. Settings and Control Words of definite and IDMTL overcurrent, earth
fault and neutral overcurrent protection
92
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
93
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
94
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
95
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
96
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
IDMTL MV EF
17. 0.08A.. 20*In 5
I0
MV EF 2HAR Inrush 2nd harmonic ratio setting for
18. 0.07..0.5 0.07
RATIO blocking MV E/F protection
The maximum 1st -harmonic current setting
MV EF 2HAR
19. 0.05... 100A 5 to remove the inrush block, in MV E/F
BLK Imax
protection
MV EF Angle The angle setting for voltage ahead of
20. 0…5 0
SEL current.
LV earth fault (E/F) protection current
21. LV EF I01 0.08A.. 20*In 5
setting for Stage 1
22. T LV EF I01 0...60s 60 Time setting for LV E/F, Stage 1
LV earth fault (E/F) current setting for
23. LV EF I02 0.08A.. 20*In 5
Stage 2
24. T LV EF I02 0...60s 60 Time setting for LV E/F, Stage 2
IDMTL LV EF
25. 0.025..2 1
TimeMult
IDMTL LV EF Ref to IEC and ANSI Curves
26. 1.. 7 7
CRV SEL
27. IDMTL LV EF I0 0.08A.. 20*In 5
LV EF 2HAR Inrush 2nd harmonic ratio setting for
28. 0.07..0.5 0.07
RATIO blocking LV E/F protection
The maximum 1st -harmonic current setting
LV EF 2HAR
29. 0.05... 100A 5 to remove the inrush block, in LV E/F
BLK Imax
protection
LV EF Angle The angle setting for voltage ahead of
30. 0…5 0
SEL current.
97
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
1-on; 0-off.
Direction unit of HV EF Stage 2 points to
HV EF_2 DIR TO system
7. 1/0 0
SYS 0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection HV EF
HV EF_2 Inrush
8. 1/0 0 Stage 2 is switched ON
Detect ON
1-on; 0-off.
The IDMTL inverse time stage of HV EF
9. HV IDMTL EF ON 1/0 0 protection is switched ON
1-on; 0-off.
Direction (DIR) detection of HV EF IDMTL
HV IDMTL EF DIR
10. 1/0 0 inverse time is switched ON
ON
1-on; 0-off.
Direction unit of HV EF IDMTL inverse
HV IDMTL EF DIR time points to system
11. 1/0 0
TO SYS 0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection HV EF
H_IDMTL EF Inrush
12. 1/0 0 IDMTL inverse time is switched ON
Detect ON
1-on; 0-off.
Select to block HV EF protection or exit
Blk HV EF at HV VT 1/0 0 direction unit, when HV VT fails
13.
FAIL 0 - HV Direct OK at HV VT Fail
1 - Blk HV EF at HV VT Fail
Blk HV EF at HV CT Block HV EF when there is HV CT failure
14. 1/0 0
FAIL 1-Block; 0-NOT block
HV EF protection initiate LV side CBF
15. Start LV CBF ON 1/0 0
0 - initiate, 1 – not initiate
98
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
99
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
T HV Neutral OC
4. 0...60s 60 Time setting for HV NOC, Stage 1
I2
100
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
IDMTL HV
5. 0.025..2 1
NeuTimeMult
IDMTL HV Neu Ref to IEC and ANSI Curves
6. 1.. 7 7
CRV SEL
IDMTL HV NOC
7. 0.08A.. 20*In 5
I0
HV NOC 2HAR Inrush 2nd harmonic ratio setting for
8. 0.07..0.5 0.07
RATIO blocking HV NOC protection
The maximum 1st -harmonic current
HV NOC 2HAR
9. 0.05... 100A 5 setting to remove the inrush block, in HV
BLK Imax
NOC protection
HV NOC Angle The angle setting for voltage ahead of
10. 0…5 0
SEL current.
MV neutral over-current (NOC) protection
11. MV Neutral OC I1 0.08A.. 20*In 5
current setting for Stage 1
T MV Neutral OC
12. 0...60s 60 Time setting for MV NOC, Stage 1
I1
IDMTL LV Neu
26. 1.. 7 7
CRV SEL
101
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
IDMTL LV NOC
27. 0.08A.. 20*In 5
I0
LV NOC 2HAR Inrush 2nd harmonic ratio setting for
28. 0.07..0.5 0.07
RATIO blocking LV NOC protection
Table 5-33 Control words of definite and IDMTL neutral overcurrent protection
Setting Default
No Setting Title Comment
options setting
The 1st stage of HV neutral OC (OC_1)
1. HV NEU OC_1 ON 1/0 0 protection is switched ON
1-on; 0-off.
Direction (DIR) detection of HV neutral OC
2. HV NEU OC_1 DIR ON 1/0 0 Stage 1 is switched ON
1-on; 0-off.
Direction unit of HV neutral OC Stage 1
HV NEU OC_1 DIR TO points to system
3. 1/0 0
SYS 0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection HV neutral
HV NEU OC_1 Inrush
4. 1/0 0 OC Stage 1 is switched ON
Detect ON
1-on; 0-off.
The 2nd stage of HV neutral OC (OC_2)
5. HV NEU OC_2 ON 1/0 0 protection is switched ON
1-on; 0-off.
Direction (DIR) detection of HV neutral OC
6. HV NEU OC_2 DIR ON 1/0 0 Stage 2 is switched ON
1-on; 0-off.
Direction unit of HV neutral OC Stage 2
HV NEU OC_2 DIR TO points to system
7. 1/0 0
SYS 0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection HV neutral
HV NEU OC_2 Inrush
8. 1/0 0 OC Stage 2 is switched ON
Detect ON
1-on; 0-off.
The IDMTL inverse time stage of HV
9. HV IDMTL NEU OC ON 1/0 0 neutral OC protection is switched ON
1-on; 0-off.
Direction (DIR) detection of HV neutral OC
HV IDMTL NEU OC DIR
10. 1/0 0 IDMTL inverse time stage is switched ON
ON
1-on; 0-off.
Direction unit of HV neutral OC IDMTL
HV IDMTL NEU OC DIR
11. 1/0 0 inverse time stage points to system
TO SYS
0 - point to the protected transformer
102
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
1- point to system
Inrush 2nd harmonic detection HV neutral
H_IDMTL NOC Inrush OC IDMTL inverse time stage is switched
12. 1/0 0
Detect ON ON
1-on; 0-off.
Select to block HV neutral OC protection or
Blk HV NEU OC at HV VT 1/0 0 exit direction unit, when HV VT fails
13.
FAIL 0 - HV Direct OK at HV VT Fail
1 - Blk HV NOC at HV VT Fail
HV neutral OC protection initiate LV side
14. Start LV CBF ON 1/0 0 CBF
0 - initiate, 1 – not initiate
HV neutral OC protection initiate MV side
Start MV CBF ON
15. 1/0 0 CBF
(for CSC-326(M2))
0 - initiate, 1 – not initiate
The 1st stage of MV neutral OC (OC_1)
16. MV NEU OC_1 ON 1/0 0 protection is switched ON
1-on; 0-off.
Direction (DIR) detection of MV neutral OC
17. MV NEU OC_1 DIR ON 1/0 0 Stage 1 is switched ON
1-on; 0-off.
Direction unit of MV neutral OC Stage 1
MV NEU OC_1 DIR TO points to system
18. 1/0 0
SYS 0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection MV neutral
MV NEU OC_1 Inrush
19. 1/0 0 OC Stage 1 is switched ON
Detect ON
1-on; 0-off.
The 2nd stage of MV neutral OC (OC_2)
20. MV NEU OC_2 ON 1/0 0 protection is switched ON
1-on; 0-off.
Direction (DIR) detection of MV neutral OC
21. MV NEU OC_2 DIR ON 1/0 0 Stage 2 is switched ON
1-on; 0-off.
Direction unit of MV neutral OC Stage 2
MV NEU OC_2 DIR TO points to system
22. 1/0 0
SYS 0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection MV neutral
MV NEU OC_2 Inrush
23. 1/0 0 OC Stage 2 is switched ON
Detect ON
1-on; 0-off.
The IDMTL inverse time stage of MV
24. MV IDMTL NEU OC ON 1/0 0 neutral OC protection is switched ON
1-on; 0-off.
Direction (DIR) detection of MV neutral OC
MV IDMTL NEU OC DIR
25. 1/0 0 IDMTL inverse time stage is switched ON
ON
1-on; 0-off.
Direction unit of MV neutral OC IDMTL
MV IDMTL NEU OC DIR inverse time stage points to system
26. 1/0 0
TO SYS 0 - point to the protected transformer
1- point to system
103
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
104
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
105
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5.7.1. Introduction
The insulating material surrounding the transformer windings ages rapidly if the temperature
exceeds the design limit value. Furthermore, by using less and less metal per MVA of transformed
power, the designed limit value is reduced in modern power transformers. Hence, it represents an
essential requirement to provide thermal protection to supplement the winding temperature device.
The thermal overload protection estimates winding temperature and therefore prevents damage to
transformer caused by thermal overloading.
106
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
the device by setting “HV Cool down Time”, “MV Cool down Time” and “LV Cool down Time”.
The cold and hot curves used in each thermal overload stages, is based on thermal curves defined
in IEC 60255-8 Std.
The curves provide an operating current/time characteristic that corresponds to the current overload
characteristic of the transformer windings. The formulas corresponding to cold and hot curve is
denoted by (1-46) and (1-47), respectively. The cold curve provides no memory regarding to
previous thermal condition of the transformer, whereas, by using the hot curve, the protection
function is able to represent a memorized thermal profile of the protected transformer.
⎧⎪ I ph 2
⎫⎪
t = τ ln ⎨ 2 2⎬
(1-46)
⎪⎩ I ph − I θ ⎪⎭
⎧⎪ I ph
2
− I P2 ⎫⎪
t = τ ln ⎨ 2 2 ⎬
(1-47)
⎪⎩ I ph − I θ ⎪⎭
Where,
t is alarm/trip time of thermal overload protection function in seconds,
τ is thermal time constant of heating for the power transformer, in seconds. It is usually provided
by the manufacturer. The device is informed about it by settings “HV THERM TimeConst”, “MV
THERM TimeConst” and “LV THERM TimeConst”.
Iph is the current flowing through corresponding side of the transformer, in each phase. It means
that the calculation is performed separately for each phase, based on fundamental component
measurement and also includes the effect of harmonic contents up to 7th harmonic. Thus, the
minimum calculated alarm/ trip time is decisive for evaluation of the thresholds.
IΘ is the setting for alarm and trip stages of the thermal overload protection, in rms. It should be set
considering the maximum permissible thermal continuous overload current of the transformer
windings and insulations. The setting is applied by using “HV THERM OVLD ALM I” and “HV
THERM OVLD TRIP I” for HV side, “MV THERM OVLD ALM I” and “MV THERM OVLD TRIP I” for
MV side, and “LV THERM OVLD ALM I” and “LV THERM OVLD TRIP I” for LV side of the power
transformer.
IP is the prior current to overload, assuming sufficient time to reach steady-state temperature.
NOTE: When control word “xx Curve/Hot Curve” is set to 0, and fundamental current is less than
the settings, and the heat accumulation is cleared and set as “0” automatically.
107
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
108
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
⎧⎪ I ph
2
− I P2 ⎫⎪
IEC Hot Curve t = τ ln ⎨ 2 2 ⎬
⎪⎩ I ph − I θ ⎪⎭
5.7.4. Annunciations
Table 5-37 List of event report
109
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
110
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5.8.1. Introduction
The circuit breaker failure (CBF) protection function monitors proper tripping of the relevant circuit
breaker. There are two separate CBF protection integrated in CSC-326. In M1 module, they are
dedicated to HV and LV sides, whereas in case of M2 module, they are dedicated to HV and MV
sides of the protected transformer.
Normally, the circuit breaker should be tripped and therefore interrupt the fault current whenever a
short circuit protection function issues a trip command. The circuit breaker failure protection
provides rapid back-up fault clearance, in the event of circuit breaker malfunction to respond to a trip
command. This feature, can be enabled or disabled at each side of the protected transformer via
control words “HV1 CBF ON”, “MV CBF ON (for CSC-326(M2))” and “LV CBF ON (for
CSC-326(M1))”. If setting “1-On” is applied at these control words, respective CBF protection will be
switched on. In this case, by operation of a protection function, and subsequent CBF initiation by
respective protection function, a report nominated as “HV1 CBF INIT”, “MV CBF INIT” or “LV CBF
INIT” is generated by the CSC-326. Furthermore, CBF initiation causes a programmed timer to run
toward a preset time delay limit. This time delay is set by user under the settings “HV1 CBF T1”, “MV
CBF T1” or “LV CBF T1”. If the circuit breaker has not been opened after expiration of the preset
time limit, the circuit breaker failure protection issues a command to trip circuit breaker (e.g. via a
second trip coil). Furthermore, event report of “HV1 CBF T1”, “MV CBF T1” or “LV CBF T1” is
generated by the device. If the circuit breaker doesn’t respond to the repeated trip command, until
another preset delay time which is set at “HV1 CBF T2”, “MV CBF T2” or “LV CBF T2”, the
protection issues a trip command to isolate the fault by tripping other surrounding backup circuit
breakers (e.g. the other CBs connected to the same bus section as the faulty CB). Furthermore,
event report of “HV1 CBF T2”, “MV CBF T2” or “LV CBF T2” is generated in this case.
Initiation of CBF protection can be carried out by both the internal and external protection functions.
If it is desired to initiate the CBF protection by means of external protection functions, they should be
marshaled to Binary input (BI) of “HV1 CBF EXT. INT”, “MV CBF EXT. INT”or “LV CBF EXT. INT” for
HV, MV, LV CBF protection respectively. Internal protection functions can initiate the CBF protection
integrated in CSC-326 M1 (HV and/or LV CBF) or that of CSC-326 M2 (HV and/or MV CBF),
according to the mapping shown in Table 5-40.
CBF INITIATION
PROTECTION FUNCTIONS
HV1 M2 [MV] / M1 [LV]
111
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
In Table 5-40, sign ● means that the protection function working at a given side of the protected
transformer always initiate the CBF protection applied in specified side of the power transformer. As
can be seen, differential, restricted earth fault and overflux protection functions initiate CBF
protection in each side of protected transformer with no additional settings. The statement CW [0/1]
means that the protection function can initiate CBF protection according to the setting which is
applied at respective control word. The setting includes “1: Initiate the CBF” and “0: Don’t initiate the
CBF”. Related control words are available for specific functions which include thermal overload,
overcurrent, earth fault and neutral overcurrent protections. Furthermore, the dash sign in Table 40
means that it is not possible to initiate CBF protection of respective side by operation of a protection
function working at a given side of the protected transformer.
There are two criteria for breaker failure detection: the first one is to check whether the actual
112
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
current flow effectively disappeared after a tripping command had been issued. The second one is
to evaluate the circuit breaker auxiliary contact status. Since circuit breaker is supposed to be open
when current disappears from the circuit, the first criterion (current monitoring) is the most reliable
means for relay to be informed about proper operation of circuit breaker. Therefore, in CSC-326,
current monitoring is applied to detect circuit breaker failure condition. In this context, the monitored
current of each phase is compared with the pre-defined setting. The settings are applied at “HV1
CBF OC I”, “MV CBF OC I” or “LV CBF OC I”, for HV or MV/LV CBF protection.
For protection functions where the tripping criterion is not dependent on current, current flow is not a
suitable criterion for proper operation of the breaker. In this case, the position of the circuit breaker
auxiliary contact should be used to determine if the circuit breaker properly operated. It is possible in
CSC-326 to evaluate the circuit breaker operation from its auxiliary contact status. To do so, control
words “HV1 CB Status Check ON”, “MV CB Status Check ON” or “LV CB Status Check ON” should
be set to “1-On” to integrate circuit breaker auxiliary contacts into CBF function. A precondition for
evaluating circuit breaker auxiliary contact is that close status of CB should be marshaled to binary
inputs of “HV1 CB Close”, “MV CB Close”or “LV CB Close”.
It should be noted that evaluation of circuit breaker auxiliary contacts is carried out in CBF function
only when the current flow monitoring has not picked up. Once the current flow criterion has picked
up during the running time of CBF timers, the circuit breaker is assumed to be open as soon as the
current disappears, even if the associated auxiliary contacts don’t indicate that the circuit breaker
has opened. This gives preference to the more reliable current criterion and avoids over functioning
due to a defect e.g. in the auxiliary contact mechanism or circuit.
The following figure shows the logic diagram for the breaker failure protection function.
113
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Ia>
Ib> OR
3I0/3I2 Check Off
OR Curr. Crit.
Ic>
3I0> AND
OR
3I2>
AND
OR
3I0/3I2 Check On
AND
AND
CB is closed
CONT Check On
OR
Curr. crit. CBF
AND T1 CBF stg1
CBF INIT
T2 CBF stg2
Fig. 5-40 The logic for CBF protection
114
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
115
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
1-on; 0-off.
116
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5.9.1. Introduction
Overload protection is equipped for each voltage side and LV delta winding. The function is to
protect all sides of windings of transformer continuous overload currents.
HV or MV or LV overload protection only comprises a definite time alarm stage.
The LV winding overload includes one alarm and two definite time tripping stages, namely
low-setting tripping stage and high-setting tripping stage. The two tripping stage can be set
respective to initiate each side CBF or not
The logic for overload protection is shown in Fig. 5-42.
117
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
118
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5.10.1. Introduction
In the event of a measured voltage failure due to a broken conductor or a short circuit fault in the
secondary circuit of voltage transformer, those protection functions which work based on voltage
criteria may mistakenly see a voltage of zero. VT failure supervision function is provided to inform
those functions about a voltage failure.
1- The calculated zero sequence voltage 3U0 as well as maximum of three phase-to-earth
voltages of respective side of the protected transformer are less than the setting of “HV
Upe_VT Fail”, “MV Upe_VT Fail” or “LV Upe_VT Fail” and at the same time, maximum of three
phase currents of respective side is higher than setting of “HV I_VT Fail”, “MV I_VT Fail” or
“LV I_VT Fail”. This condition may correspond to three phase broken fault in secondary circuit
of the voltage transformer in respective side of the protected transformer.
2- The calculated zero sequence voltage 3U0 of respective side of the protected transformer is
more than the setting of “HV Upe_VT Fail”, “MV Upe_VT Fail” or “LV Upe_VT Fail”. This
condition may correspond to single or two-phase broken fault in secondary circuit of the
voltage transformer in respective side of the protected transformer, if the system starpoint is
solidly earthed.
3- The calculated zero sequence voltage 3U0 of respective side of the protected transformer is
more than the setting of “HV Upe_VT Fail”, “MV Upe_VT Fail” or “LV Upe_VT Fail”, and at the
same time, the difference between the maximum and minimum phase-to-phase voltages of
respective side is more than the setting of “HV Upp_VT Fail”, “MV Upp_VT Fail” or “LV
Upp_VT Fail”. This condition may correspond to single or two-phase broken fault in secondary
circuit of the voltage transformer in respective side of the protected transformer, if the system
starpoint is isolated or resistance earthed.
In addition to the mentioned conditions, the device has the capability to be informed about the VT
MCB failure through its binary inputs. These inputs include “HV MCB FAIL BI”, “MV MCB FAIL BI”
and “LV MCB FAIL BI”. In this context, VT fail is detected in corresponding side, if the respective
binary inputs are active.
119
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
If VT failure supervision detects a failure in voltage transformer secondary circuit, either by means of
the above mentioned criteria or reception of a VT MCB fail indication, all the protection functions
which operate based on direction determination would be blocked in corresponding side of the
protected transformer, depending on the setting. Furthermore, an alarm report of “HV VT Fail”, “MV
VT Fail” or “LV VT Fail”, is issued after 10s delay time. The blocking condition would be removed if
one of the following conditions is met within the 10s delay time.
1- Minimum phase voltage of corresponding side of the protected transformer becomes more
than setting of “HV Upe_VT Normal”, “MV Upe_VT Normal” or “LV Upe_VT Normal” for
500ms.
2- Minimum phase voltage of corresponding side becomes more than setting of “HV Upe_VT
Normal”, “MV Upe_VT Normal” or “LV Upe_VT Normal” and at the same time, the calculated
zero sequence and negative sequence current of corresponding side becomes more than
the setting of “HV 3I02_VT Fail”, “MV 3I02_VT Fail” or “LV 3I02_VT Fail”.
Subsequent to reporting VT fail alarm, the blocking condition of respective protection functions
would be removed if the minimum phase voltage of corresponding side becomes more than the
setting of “HV Upe_VT Normal”, “MV Upe_VT Normal” or “LV Upe_VT Normal” for a duration more
than 10s.
120
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
121
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
122
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5.11.1. Introduction
Two special binary inputs (BI1, BI2) are provided in CSC-326 which can be used to activate
respective binary outputs (BO1 and BO2), according to the setting applied at control words “BI1
ENABLE BO1” and “BI2 ENABLE BO2”. By applying setting “1-enable” to these control words, BO1
will be activated if BI1 is energized. Similarly, BO2 will be activated if BI2 is energized. Furthermore,
7th LED in front plate of the device would be lighted when BO1 or BO2 is activated.
Since the trip command of mechanical protection has latched nature, two operating modes are
provided for the Bos activation. The operating modes include direct and pulse tripping modes. In
direct tripping mode, each BO contact is active as long as respective BI is energized, and after BI
disappearance 20ms the BO contacts are deactivated. Whereas in pulse tripping mode, by each
up-edge of BI, respective BO contacts remain active during a settable pulse time, and after the
settable time, the BO contacts are inactive. The tripping modes can be selected for the BOs by
control words “BO1 Pulse Tripping” and “BO2 Pulse Tripping”. Pulse tripping mode would be
possible if setting “1-Pulse Tripping” is applied to the control words. Similarly, setting “0-Direct
Tripping” activates direct tripping mode for respective BOs. The logic is shown in Fig. 5-44.
1-enable
0-disable
AND
BOx Pulse Tripping Pulse Tripping Time
1
1-enable 0
0-disable
AND BIx trip BO
1
BIx up edge 0
1
0
AND AND BIx trip BO
Furthermore, it is possible to set BIs to initiate CBF protection in HV, MV or LV sides of protected
transformer via a number of control words. The control words include “BI1 Start HV1 CBF ON”, “BI1
123
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Start MV CBF ON” (for CSC-326(M2)) and “BI1 Start LV CBF ON” for the first BI. Similarly, control
words “BI2 Start HV1 CBF ON”, “BI2 Start MV CBF ON” (for CSC-326(M2)) and “BI2 Start LV CBF
ON” correspond to the second BI.
BI1 Start HV1 whether BI1 initiate HV1 side CBF or not
5. 1/0 0
CBF ON 0 - initiate, 1 – not initiate
BI1 Start MV
CBF ON whether BI1 initiate MV side CBF or not
6. 1/0 0
(for 0 - initiate, 1 – not initiate
CSC-326(M2))
BI1 Start LV whether BI1 initiate LV side CBF or not
7. 1/0 0
CBF ON 0 - initiate, 1 – not initiate
BI2 Start HV1 whether BI2 initiate HV1 side CBF or not
8. 1/0 0
CBF ON 0 - initiate, 1 – not initiate
BI2 Start MV
CBF ON whether BI2 initiate MV side CBF or not
9. 1/0 0
(for 0 - initiate, 1 – not initiate
CSC-326(M2))
BI2 Start LV whether BI2 initiate LV side CBF or not
10. 1/0 0
CBF ON 0 - initiate, 1 – not initiate
124
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
125
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
126
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
When BI “REM ACCESS BLK” is activated, or the content of control word “NOT Blk Remote Access”
is set to 0, SCADA remote access is blocked to the device and therefore, only local operation is
permitted.
When BI “REM ACCESS BLK” is deactivated, and the content of control word “NOT Blk Remote
Access” is set to 1, both SCADA commands and local operation can be executed by the device.
Similarly, there are two methods to select test or normal operating mode of the device, BI “RELAY
TEST” or making change in the content of special control word “Relay Test Mode” which can be set
under “Common Para” submenu.
When BI “RELAY TEST” is activated, or the content of control word “Relay Test Mode” is set to 1,
the relay is in test mode.
When BI “RELAY TEST” is deactivated, and the content of control word “Relay Test Mode” is set to 0,
the relay is in normal operation mode
127
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
128
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
6 Operation
6.1 Safety precautions
During the equipment tests and start-up, the general safety regulations applicable to electrical
systems must be complied with. Failure to comply with these regulations might cause harm to the
working staff and damage to property. All the inspections and tests must only be carried out by
specially trained personnel.
• Check the enclosure shell has been grounded reliably and maintain electric continuity to earth.
• The general safety regulations applicable to equipments must be strictly complied with.
• Insert or pull out models must be strictly prohibit during the equipment tests and operation.
• During operation, nobody is allowed to press the keyboard on the panel optionally.
• During operation, nobody is allowed to operate the following commands:
▪ Burst into drive.
▪ Modification and solidify settings.
▪ Set up numbers of running CPU.
▪ Change setting group.
▪ Change equipment address in communication net.
129
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Abbr. Remarks
Meaning
(LCD Display)
OpStatus Operating Status
AI Analog Input Inspecting the analog input of the
equipment.
Status Equipment Status Inspecting the equipment status.
Version Version Showing the version information of the
CPU in the equipment.
EquipCode Equipment Code Showing the code information of any
module in the equipment.
DI Digital Input Inspecting the status of digital inputs.
Measure Measuring Values Showing the measure quantities of the
equipment (the value of the current has
been altered basing on the CT adjusting
coefficient).
QueryRep
EventRpt Event Report
Latest Rpt The latest report Listing the time of the latest operating
report, inspecting the content by
pressing the SET key.
Last 6 Rpts Last 6 reports Listing the time of the latest six
operating report, selecting the report
with ▲ and ▼ key, inspecting the
content with SET key.
QueryRpt Query report by date Listing the time of the operating reports
which is searched by time sect,
selecting the report with ▲ and ▼ key,
inspecting the content by pressing the
SET key.
130
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Print Print
ProtSet Protection Setting Printing setting.
Report Report
EventRpt Event Report
Latest Rpt The latest report Listing the time of the latest operating
report, inspecting the content with
pressing the SET key.
Last 6 Rpts Last 6 reports Listing the time of the latest six
operating report, selecting the report
with ▲ and ▼ key, inspecting the
content with SET key.
QueryRpt Query report by date Listing the time of the operating reports
which is searched by time sect,
selecting the report with ▲ and ▼ key,
131
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Testing Testing
SimuReSig Simulate Remote
Signal
Simu Alarm Simulate Alarm
Simu Trip Simulate Tripping
Simu Connt Simulate Connector
Simu DI Simulate Digital
Input(DI)
TransRec Data Simulate
transmitting record
data
Simu MST Alarm
SwSetGr Switch Setting
Group
132
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
You can enter the MainMenu by pressing the SET key when the screen is in circularly-displaying
state. You can enter the DebuggingMenu by pressing the QUIT+SET keys (only for manufacturer).
There are four shortcut keys and two functional keys at the bottom of liquid crystal screen. The main
intention is to predigest user’s manipulation. The descriptions of these keys are as Table 6-3.
133
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
134
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
135
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
136
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
137
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
138
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
139
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
NOTICE:The former six bits in the TRIP setting control-words in Table 54 are of meaning, which is
“DO TRIP-1 ON/OFF” ~ “DO TRIP-16 ON/OFF” respectively.
140
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
4. VET GRP ANGLE 0-12 11 Vector Group Angle( VET GRP ANGLE)
141
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Note: “In” stands for CT secondary current, 1A or 5A, here and hereafter.
142
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
5. HV REF ALARM T 0…60s 0.03 HV Restricted earth fault alarm time setting
15. MV REF ALARM T 0…60s 0.03 LV Restricted earth fault alarm time setting
5. Time DEF V/F Trip 0.1..9999s 10 Time setting for definite volt/herz stage
143
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
16. Cool Down Time 0.1..9999s 25 Time setting for transformer cool down
144
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
⎡ ⎤
⎢ ⎥
⎢ A ⎥
[NOTE1]: IDMTL characteristic is: t = M × ⎢ P
+ B⎥
⎢⎡ I ⎤ ⎥
⎢⎢ ⎥ −1 ⎥
⎣⎣IS ⎦ ⎦
145
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
[NOTE2]: The angle setting “OC Angle SEL” for voltage ahead of current.
1 15 degree
2 30 degree
3 45 degree
4 60 degree
[NOTE3]: The angle setting “EF Angle SEL” and “NOC Angle SEL” for voltage ahead of current.
The angle means voltage calculated 3U 0 ahead of 3I 0 . As for 3I 0 , it is calculated current in E/F
protection, but it is neutral measuring current in NOC protection.
Table 6-12 Angle setting “EF Angle SEL” and “NOC Angle SEL”
Angel setting
“EF Angle SEL” and “NOC 3U 0 ahead of 3I 0
Angle SEL”
0 100 degree
1 110 degree
2 120 degree
3 130 degree
4 140 degree
5 150 degree
146
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
147
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Remark: All settings for MV Backup protections are used for CSC-326 (Model 2), they can not be seen in
CSC326 (Model 1) because the functions are not configured.
Setting Default
No Setting Title Comment
options setting
LV overcurrent (O/C) current setting
1. LV OC I1 0.08A.. 20*In 5
for Stage 1
2. T LV OC I1 0.1..60s 60 Time setting for LV OC, Stage 1
LV overcurrent (O/C) current setting
3. LV OC I2 0.08A.. 20*In 5
for Stage 2
4. T LV OC I2 0.1..20s 60 Time setting for LV OC, Stage 2
148
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
41. LW OVLD Low Trip T 0.1..3600s 10 Low stage tripping time setting
42. LW OVLD High Trip I 0.1..20A 20 High stage tripping current setting
43. LW OVLD High Trip T 0.1..3600s 10 High stage tripping time setting
149
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
150
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
151
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Remarks:
1. These settings are only used for test; they are calculated by software automatically according to
the common parameters. These settings cannot be modified by user.
152
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
153
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
154
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
1-on; 0-off.
155
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
156
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
157
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
158
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
159
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
ON ON
1-on; 0-off.
The 2nd stage of MV neutral OC
MV NEU OC_2
119. 1/0 0 (OC_2) protection is switched ON
ON
1-on; 0-off.
Direction (DIR) detection of MV
MV NEU OC_2 neutral OC Stage 2 is switched
120. 1/0 0
DIR ON ON
1-on; 0-off.
Direction unit of MV neutral OC
Stage 2 points to system
MV NEU OC_2
121. 1/0 0 0 - point to the protected
DIR TO SYS
transformer
1- point to system
Inrush 2nd harmonic detection MV
MV NEU OC_2 neutral OC Stage 2 is switched
122. Inrush Detect 1/0 0
ON
ON
1-on; 0-off.
The IDMTL inverse time stage of
MV IDMTL MV neutral OC protection is
123. 1/0 0
NEU OC ON switched ON
1-on; 0-off.
Direction (DIR) detection of MV
MV IDMTL neutral OC IDMTL inverse time
124. NEU OC DIR 1/0 0
stage is switched ON
ON
1-on; 0-off.
Direction unit of MV neutral OC
IDMTL inverse time stage points
MV IDMTL to system
125. NEU OC DIR 1/0 0
0 - point to the protected
TO SYS
transformer
1- point to system
Inrush 2nd harmonic detection MV
M_IDMTL NOC neutral OC IDMTL inverse time
126. Inrush Detect 1/0 0
stage is switched ON
ON
1-on; 0-off.
Select to block MV neutral OC
Blk MV NEU protection or exit direction unit,
127. OC at MV VT 1/0 0 when MV VT fails
FAIL 0 - MV Direct OK at MV VT Fail
1 - Blk MV NOC at MV VT Fail
MV neutral OC protection initiate
Start HV1 CBF
128. 1/0 0 HV1 side CBF
ON
0 - initiate, 1 – not initiate
Thermal overload in MV side is
MV THERM
129. 1/0 0 switched on
OVLD ON
0 - OFF, 1 - ON
MV Curve/Hot MV side using hot/cold curve type
130. 1/0 0
Curve 0 – Hot curve, 1 – Cold curve
MV thermal overload protection
131. Start HV1 CBF 1/0 0 initiate HV side CBF
0 - initiate, 1 – not initiate
160
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
161
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
162
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
163
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
164
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
165
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
166
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
6.4 Annunciations
6.4.1 Event report
Table 6-20 List of event report
Abbr.
No. Comment
(LCD Display)
1. Relay Start Relay Startup(Start)
2. PER DIFF Trip A
PER DIFF Trip B Treble slope percent Differential protection (IDIFF>) tripping for
3.
phase A/B/C
4. PER DIFF Trip C
5. INST DIFF Trip A
Instantaneous Differential protection (IDIFF>>)tripping for phase
6. INST DIFF Trip B
A/B/C
7. INST DIFF Trip C
8. HV REF Trip HV Restricted Earth fault (REF) protection tripping
9. MV REF Trip MV Restricted Earth fault (REF) protection tripping
10. LV REF Trip LV Restricted Earth fault (REF) protection tripping
11. DEF V/F Trip Overflux protection(V/F) tripping with definite (DEF) and
12. IVR V/F Trip inverse(IVR) time characteristics
19. HV Neu OC IDMTL HV inverse time IDMTL Neutral current (NC) tripping
20. HV Neu OC_1 Trip Neutral Current protection (NC) definite-time Stage 1 (_1) or
21. HV Neu OC_2 Trip Stage 2 (_2) tripping in High Voltage (HV) side with time delay
26. MV IDMTL EF Trip MV inverse time IDMTL Earth Fault (EF) tripping
27. MV EF_1 Trip Earth Fault (EF) protection definite-time Stage 1 (_1) or Stage 2
28. MV EF_2 Trip (_2) tripping in Mid- Voltage (MV) side with time delay
29. MV Neu OC IDMTL MV inverse time IDMTL Neutral current (NC) tripping
30. MV Neu OC_1 Trip Neutral Current protection (NC) definite-time Stage 1 (_1) or
31. MV Neu OC_2 Trip Stage 2 (_2) tripping in Mid- Voltage (MV) side with time delay
167
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
35. LV OC_2 Trip (_2) tripping in Low Voltage (LV) side with time delay
36. LV IDMTL EF Trip LV inverse time IDMTL Earth Fault (EF) tripping
37. LV EF_1 Trip Earth Fault (EF) protection definite-time Stage 1 (_1) or Stage 2
38. LV EF_2 Trip (_2) tripping in Low Voltage (LV) side with time delay
39. LV Neu OC IDMTL LV inverse time IDMTL Neutral current (NC) tripping
40. LV Neu OC_1 Trip Neutral Current protection (NC) definite-time Stage 1 (_1) or
41. LV Neu OC_2 Trip Stage 2 (_2) tripping in Mid- Voltage (LV) side with time delay
168
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
169
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
170
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
171
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
172
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
The following items are only provided to be referred. Users should formulate the corresponding
rules for maintenance and operation according to the actual situation in locale.
a) Check the setting lists inerrably, and then turn on DC power supply. Now the green light - LED
<Run> on panel is lit, other lights are extinguished. Under normal conditions, LCD display on loop
“year-month-day, hour : minute : second, magnitude and phase angle of analog quantities, channel
state, current setting zone: 00. Press SET key to display main menu. Press one or several times
QUIT key,exit current menu one time or step by step to return normal state of display. Then
re-check the clock by turning off DC power and then on.
b) Connect currents (load current must be larger than 0.1In) and voltages to the device, under
normal state of loop display, press SET key to enter into main menu, then enter into every sub-menu
to check whether the polarity and the phase sequence of each analog input are correct or not. Verify
the sampled data of the protection in accordance with the actual ones.
c) Check the protection settings. Print each set of settings that are possibly employed in the actual
operating modes, in order to check them with informed sheet of setting and backup debugging
notes.
d) Check the digital inputs in accord with the practical state, and make note. Especially notice that
there is not display of “small hand” on the upper right of LCD under normal conditions (that means
relay test state).
173
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
174
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
175
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
•The equipment should be visually checked to ensure that there are no external traces of
damage. Verify that the conformity certificates, matched documents, accessories are
consistent with the order requirements, and ensure that the type, nameplate, numbers of the
equipments are perfect and consistent with packing list.
• The transport packing can be re-used for further transport when applied in the same way. The
storage packing of the individual equipments is not suited to transport. If alternative packing is
used, this must also provide the same degree of protection against mechanical shock, as laid
down in IEC 60255-21-1 class 2 and IEC 60255-21-2 class 1.
• Before initial energizing with supply voltage, the equipment shall be situated in the operating
area for at least two hours in order to ensure temperature equalization and to avoid humidity
influences and condensation.
176
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
7.2 Mounting
• The equipment ought to be fixed on panel or cabinet, and every connection bolt of the
equipment must be firmed.
• Using earthing coppery wires connect the equipment ground and panel (cabinet) ground with
bus line and verify the earthing is reliably.
177
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
• Check the type tag of the equipment on faceplate, the lighting tag, backboard terminal figure,
terminal number tag and nameplate label of the equipment are intact and right.
• Each module withdrawal and insertion is flexible, space between module and plug slot are
suitable right, and the insertion depth is satisfied. Verify the lock-up is reliable. The slice of
current connecter for short circuit ought to be opened reliably when module is inserted.
• Test insulation resistance in turn between analog circuits and ground, and the circuits to each
others every resistance must not be less than 100 MΩ.
178
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Energized DC power supply, the equipment for loss of power alarm ought to be excited reliably, and
its contacts as X12-c16 and X12-a16 must be opened reliably. Cut off rating DC power supply, the
relay for loss of power alarm ought to be lost magnetism reliably, and its contacts as X12-c16 and
X12-a16 must be closed reliably.
179
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
8 Maintenance
180
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
181
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
182
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
8.4 Repairs
• Users should not change modules circuit or backboard circuit in repair.
• It’s appropriate to change power board when power supply is fault.
• It’s suggested that power board should purchased per 4 or 6 years because it can’t storage for
a long time.
183
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
b) If all the relays of the device are to be quitted from operation, open the tripping strap at first, and
then turn off the DC power. If one of the relays is to be quitted during operation, only the
corresponding strap of the relay needs to be quitted.
c) When fault occurs during operation, if the protection operates to trip, the corresponding LED of
tripping signal is lit and MMI displays the newest operating report. If autoreclosing operates to
reclose, the “reclose” LED is lit. The operating report, record report should be printed automatically
and the detail notes must be written down.
d) If the DC power supply disappears during operation, quit the tripping strap at first.
e) If alarm Ⅰ occurs during operation, the corresponding relay should be stop employing, record
the alarm message and inform the operator in charge of the protection. Here, prohibit pressing the
reset button. If alarm Ⅱ occurs, record the alarm message and inform the operator in charge of the
protection to analyze and handle it.
184
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
9 Storage
• Although protection equipments are generally of robust construction, they require a careful
treatment prior to installation on site, since they must be carefully packed and unpacked, without
applying any force to the equipment and using suitable tools. Once supplied, the equipment
must be thoroughly inspected to ensure that they have not undergone shipping damages. If the
equipment is not immediately installed upon reception, they must be stored in places free from
dust and moisture, causticity in their original packing.
• The equipment must only be stored and carried in the special antistatic bag.
185
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
10 Ordering
Model Nos.
Two Winding Transformer-Model M1 M1
Three Winding Transformer-Model M2 M2
Rated current for High Voltage side
1A 1
5A 5
Rated current for Middle Voltage side
1A 1
5A 5
Rated current for Low Loltage side
1A 1
5A 5
Rated auxiliary voltage
110V DC 1
220V DC 2
186
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
187
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
11 Appendix
This appendix is primarily a reference for the experienced user. General diagrams indicating the
terminal connections of the CSC326(M1) and CSC-326(M2) are included. Connection examples
show the proper connections of the device to primary equipment in typical power system
configurations. Tables with all information available in a CSC-326 equipped with all options are
provided.
188
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
189
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
190
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Differential protection embraces protection of the high voltage side and low voltage side of the
transformer cable. The permissible cable length and the CT design (permissible load) are
mutually dependent. Recalculation is advisable as for lengths of more than 100m.
Typical connection 1
191
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
Typical connection 2
192
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
193
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
2 2
4 4
6 6
8 8
10 10
12 12
14 14
16 16
18 18
20 20
22 22
24 24
26 26
28 28
30 30
32 32
Fig. 11-6 Connection for tripping binary output modules (X8 and X9)
2 2
4 4
6 6
8 8
10 10
12 12
14 14
16 16
18 18
20 20
22 22
24 24
26 26
28 28
30 30
32 32
Fig. 11-7 Connection for signaling binary output modules (X10 and X11) in CSC-326(M1)
194
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
2 2
4 4
6 6
8 8
10 10
12 12
14 14
16 16
18 18
20 20
22 22
24 24
26 26
28 28
30 30
32 32
Fig. 11-8 Connection for signaling binary output modules (X10 and X11) in CSC-326(M2)
195
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
196
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
11.6.1 Overview
This port introduces the data modeling, communication principles that are used in the IEDs.
The purpose of supporting IEC61850 series is to provide interoperability between devices from
different venders.
For some advanced applications, the reader should have intensive knowledge about
IEC61850.
197
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
198
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
199
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
M4 Data set C5 C5 Y
M5 Substitution O O N
Reporting
M7 Buffered report control O O Y
M7-1 sequence-number Y Y Y
M7-2 report-time-stamp Y Y Y
M7-3 reason-for-inclusion Y Y Y
M7-4 data-set-name Y Y Y
M7-5 data-reference Y Y Y
M7-6 buffer-overflow Y Y Y
M7-7 entryID Y Y Y
M7-8 BufTm Y Y Y
M7-9 IntgPd N Y Y
M7-10 GI Y Y Y
M8 Unbuffered report M M Y
control
M8-1 sequence-number Y Y Y
M8-2 report-time-stamp Y Y Y
M8-3 reason-for-inclusion Y Y Y
M8-4 data-set-name Y Y Y
M8-5 data-reference Y Y Y
M8-6 BufTm Y Y Y
M8-7 IntgPd N Y Y
M8-8 GI N Y Y
Logging
M9 Log control O O N
M9-1 IntgPd N N N
M10 Log O O N
GSE
M12 GOOSE O O N
M13 GSSE O O N
M14 Multicast SVC O O N
M15 Unicast SVC O O N
M16 Time M M Y
M17 File Transfer O O Y
200
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
S6 LogicalNodeDirectory M M Y
S7 GetAllDataValues O M Y
Data
S8 GetDataValues M M Y
S9 SetDataValues O O Y
S10 GetDataDirectory O M Y
S11 GetDataDefinition O M Y
Data set
S12 GetDataSetValues O M Y
S13 SetDataSetValues O O Y
S14 CreateDataSet O O Y
S15 DeleteDataSet O O Y
S16 GetDataSetDirectory O O Y
Substitution
S17 SetDataValues M M N
Setting group control
S18 SelectActiveSG O O Y
S19 SelectEditSG O O Y
S20 SetSGValues O O Y
S21 ConfirmEditSGValues O O Y
S22 GetSGValues O O Y
S23 GetSGCBValues O O Y
Reporting
Buffered report control block (BRCB)
S24 Report C6 C6 Y
S24-1 data-change (dchg) C6 C6 Y
S24-2 qchg-change (qchg) C6 C6 Y
S24-3 data-update (dupd) C6 C6 Y
S25 GetBRCBValues C6 C6 Y
S26 SetBRCBValues C6 C6 Y
Unbuffered report control block (URCB)
S27 Report C6 C6 Y
S27-1 data-change (dchg) C6 C6 Y
S27-2 qchg-change (qchg) C6 C6 Y
S27-3 data-update (dupd) C6 C6 Y
S28 GetURCBValues C6 C6 Y
S29 SetURCBValues C6 C6 Y
c6 – shall declare support for at least one (BRCB or URCB)
Logging
Log control block
S30 GetLCBValues M M N
201
CSC-326 Numerical Transformer Protection Equipment ( M1 / M2 ) Manual
S31 SetLCBValues O M N
Log
S32 QueryLogByTime C7 M N
S33 QueryLogAfter C7 M N
S34 GetLogStatusValues M M N
c7 – shall declare support for at least one (QueryLogByTime or QueryLogAfter).
Generic substation event model (GSE)
GOOSE-CONTROL-BLOCK
S35 SendGOOSEMessage C8 C8 N
S36 GetGoReference O C9 N
S37 GetGOOSEElementNumber O C9 N
S38 GetGoCBValues O O N
S39 SetGoCBValues O O N
GSSE-CONTROL-BLOCK
S40 SendGSSEMessage C8 C8 N
S41 GetGsReference O C9 N
S42 GetGSSEElementNumber O C9 N
S43 GetGsCBValues O O N
S44 SetGsCBValues O O N
c8 – shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage).
c9 – shall declare support if TP association is available.
S51 Select M M N
S52 SelectWithValue M M N
S53 Cancel O M N
S54 Operate M M Y
S55 Command-Termination M M N
S56 TimeActivated-Operate O O N
File transfer
S57 GetFile O M Y
S58 SetFile O O Y
S59 DeleteFile O O Y
S60 GetFileAttributeValues O M Y
Time
SNTP O
server
SNTP Y
client
T1 Time resolution of internal T1
clock
T2 Time accuracy of internal T0
clock
T3 Supported Timestamp 10
resolution
202
Address:Building 9, Fourth Avenue, Shangdi Information Industry Base, Haidian District,
Beijing
Zip:100085
Tel:+8610-62961515, +8610-62985012 (Marketing Department)
+8610-62986668(Technical Support)
Fax:+8610-62981004 +8610-62978952 (Marketing Department)
http://www.sf-auto.com E-mail: [email protected]