Specification Guide - Gas 320 620 Ace
Specification Guide - Gas 320 620 Ace
Specification guide
What’s
inside.
03 Remeha, the expert choice 24 Gas 320/620 Ace fault
03 Introducing the Remeha reporting /outputs
Gas 320/620 Ace Range 25 Safety interlocks
04 Gas 320/620 Ace 26 Boiler controls
boiler construction 28 Gas 320 Ace flue data
07 Gas 320/620 Ace 29 Gas 320/620 Ace flue data
operating principle 30 Gas 620 Ace flue data
08 Gas 320/620 Ace 31 Technical support
technical information 31 Declaration
12 Gas 320 Ace suggested of compliance
engineering specification
13 Gas 620 Ace suggested
engineering specification
14 Gas 320 Ace boiler dimensions
16 Gas 620 Ace boiler dimensions
18 Gas 320/620 Ace
module partial disassembly
– for restricted access
19 Gas 320/620
Ace configurations
22 Electrical connections
and controls
Remeha, From using the latest materials and manufacturing
techniques to meticulously designing and engineering each
03
Gas 320
GasAce620
650Ace 1150 652 kW 10 section
1147 kW
Gas 620 Ace 570 558 kW 2 x 5 sectio
Gas 620 Ace 1300 1303 kW
Gas 320/620 Ace Gas 620 Ace 710 701 kW
(1) Nominal output Pnc 50/30 °C
2 x 6 sectio
boiler construction.
Gas 620 Ace 860 849 kW 2 x 7 sectio
Gas 620 Ace 1000 994 kW 2 x 8 sectio
Gas 620 Ace 1150 1147 kW 2 x 9 sectio
3.2 Main components
Fig. 1 General – Front Gas 620 Ace 1300 Fig. 1 Key 1303 kW 2 x 10 sec
(1) Nominal output Pnc 50/30 °C
1 Burner
Fig.1 General - front 1 Burner
2 Ignition2 / ionisation
Ignition / ionisation transformer
transformer
3.2 Main components 3 Heat exchanger
3 Heat exchanger
5 4 Inspection 4 hatch
Inspection hatch
Fig.1
1 General - front 1 5 Air inlet
Burner 5 connection
Air inlet connection
2 6 Flame
Ignition 6inspection
/ ionisation transformer glass glass
Flame inspection
3 Heat7 exchanger
Ignition7 / ionisation electrode
Ignition / ionisation electrode
2 5
6 4 8 Heat
Inspection exchanger temperature sensor
hatch
8 Heat exchanger temperature sensor
1 5 Air inlet connection
9 Data plate
3 7 6 Flame
10 inspection
Siphon9 glass Data plate
8 7 Ignition / ionisation
10 electrode
Siphon
4
2 11 Document holder
6 8 Heat exchanger temperature sensor
11 Document holder
9 9 Data plate
3 7
8 10 10 Siphon
4 11 Document holder
9 11
10
AD-3001552-01
9 2 4 Flue
Second returngas outlet
2connection
Secondconnection
return connection
3 5 temperature
Return Return connection
sensor (when no second return is fitted)
Return temperature sensor
1 4 Flue6gasFlue gas
outlet measuring
3connection point
(when no second return is fitted)
5 Return
7 connection
Flue gas temperature sensor
4 Flue gas outlet connection
1 6 Flue8gas measuring point
Condensate collector cap
7 Flue gas temperature
5 sensor
Return connection
2 9 Air pressure differential switch
8 Condensate collector
6 cap
Flue gas measuring point
Air1pressure
0 Heatdifferential
exchanger insulation kit (optional)
3
2 10 9 switch
4 1 1 Return 7 temperature
Flue gas temperature
sensor sensor
(when a second re
3 10 10 Heat exchanger insulation kit (optional)
5
4 11 12 temperature
Return Levelling
8 footCondensate
sensor (when collector cap return is fitted)
a second
5 12 Levelling foot 9 Air pressure differential switch
11
6 Heat exchanger insulation kit
11 10
6 (optional)
7 12
7 12 Return temperature sensor
8 11
8 AD-3001553-01 (when a second return is fitted)
AD-3001553-01
12
12 7734324 - v.03773
- 29
04
Gas 320/620 Ace
boiler construction.
3 Description of the product
1
4 3 Return connection
1 3 Description of the product
2
4 Flue gas collector
2
11 4 Service connector
Fig.6 Flow pipe 51 Control
Temperature sensor
part -(external control) immersion tube (½")
AD-3001555-01
box rear for expansion PCBs with wire connections
62 Control
Air ventbox
(⅛")front part - for the control unit and connectivity 3 Control panel
7734324 - v.03 - 29092020 13
Fig.5 Control box 3 1 Display
3 expansion
Safety valve cover
connection (1½")
PCBs
1 2 Power button
4 Pressure gauge (½") 4 Service connector
4
2
1 3 Control
5 Flow panel sensor (M6)
temperature
4 Service connector
2 5 Control box rear part - for expansion PCBs with wire 5 Control box rear part – for expansion
connections
5 6 Control box front part - for the control unit and connectivity PCBs with wire connections
3 5
4
expansion PCBs
Control box front part – for the
6
AD-3001556-01
AD-3001557-01
05
06
Gas 320/620 Ace
operating principle.
This mixing system ensures that the correct gas/air ratio is A vapour cloud will form at the flue gas terminal due to the
delivered to the pre-mix burner at all times. Depending on low flue gas exit temperature – this isn’t smoke, simply water
demand (under the dictates of flow/return sensor and other vapour formed during the combustion process. When the
external/internal control inputs) the burner control system flue gas temperature falls below dew point (55°C), water
determines the required boiler output. The burner control vapour created during the combustion process will begin to
then varies the speed of the air supply fan which alters the condense out in the boiler, transferring its latent heat into
volume of air being drawn into the venturi. This change in the system water, increasing the output of the boiler without
volume is measured using air pressure differential which increasing the gas consumption. Condensation formed within
directly controls the volume of gas also being delivered to the the boiler and flue system is discharged from the boiler to an
venturi. The resultant controlled mixture is delivered to the external drain via the drain pan and siphon supplied.
premix burner.
07
Gas 320 Ace
technical information.
Performance
Nominal input (Hi) (min-max) 54-266 68-333 82-402 95-469 109-539 122-610
Efficiency
SBEM seasonal efficiency GCV 96.48 96.34 9 6.19 96.05 95.89 95.75
Efficiency – full load 100% NCV 98% 9 8.1% 98.2% 98.3% 98.4% 98.5%
Efficiency – part load 30% NCV 109.2% 109% 108.8% 108.6% 108.3% 108.1%
Gas
Standard fuel Natural gas Natural gas Natural gas Natural gas Natural gas Natural gas
Max gas consumption m3/h 5.7-28.1 7.2-35.2 8.7-42.5 10.1-49.6 11.5-57.0 12.9 -64.6
Min/max gas inlet pressure mbar 17-25 17-25 17-25 17-25 17-25 17-25
Flue (supplied as standard for conventional flue, option for room-sealed available)
Flue diameter mm I/D 250 250 250 250 250 250
Air inlet diameter mm I/D 250 250 250 250 250 250
Flue gas mass flow rate kg/h 91-448 115-561 138-677 160-790 184-907 205-1027
Residual fan duty Pa 130 120 130 150 150 150
Hydraulics
Water content litres 49 60 71 82 93 104
Hydraulic resistance
34 (3.4 kPa) 33 (3.3 kPa) 36 (3.6 kPa) 33 (3.3 kPa) 38 (3.8 kPa) 39 (3.9 kPa)
@ 40°C ΔT mbar (kPa)
Hydraulic resistance
60 (6 kPa) 59 (5.9 kPa) 64 (6.4 kPa) 59 (5.9 kPa) 67 (6.7 kPa) 69 (6.9 kPa)
@ 30°C ΔT mbar (kPa)
Hydraulic resistance
113 (11.3 kPa) 110 (11.0 kPa) 120 (12.0 kPa) 110 (11.0 kPa) 125 (12.5 kPa) 130 (13.0 kPa)
@ 20°C ΔT mbar (kPa)
Hydraulic Resistance
374 (37.4 kPa) 364 (37.4 kPa) 397 (39.7 kPa) 364 (36.4 kPa) 413 (41.3 kPa) 435 (43.5 kPa)
@ 11°C ΔT mbar (kPa)
08
Gas 320 Ace
technical information.
Hydraulics
Nominal flow rate @ 40°C ΔT l/s 1.6 1.9 2.3 2.7 3.2 3.6
Nominal flow rate @ 30°C ΔT l/s 2.1 2.6 3.1 3.6 4.2 4.8
Nominal flow rate @ 20°C ΔT l/s 3.1 3.9 4.7 5.5 6.3 7.1
Nominal flow rate @ 11°C ΔT l/s 5.6 7.1 8.5 9.9 11.5 13.0
Standard operating temperature °C 20-90 20-90 20-90 20-90 20-90 20-90
Max operating temperature °C 90* 90* 90* 90* 90* 90*
High limit temperature °C 110 110 110 110 110 110
Max water operating pressure bar 7 7 7 7 7 7
Min water operating pressure bar 1 1 1 1 1 1
General
707 x 1550 707 x 1550 707 x 1550 707 x 1550 707 x 1550 707 x 1550
Dimensions (WxHxD)
x 1862 x 1862 x 1862 x 2172 x 2172 x 2172
09
Gas 620 Ace
technical information.
Performance
Nominal input (Hi) (min-max) 80-532 91-666 128-804 127-938 153-1078 170-1220
Efficiency
SBEM seasonal efficiency GCV 96.48 96.34 9 6.19 96.05 95.89 95.75
Efficiency – full load 100% NCV 98% 9 8.1% 98.2% 98.3% 98.4% 98.5%
Efficiency – part load 30% NCV 109.2% 109% 108.8% 108.6% 108.3% 108.1%
Gas
Standard fuel Natural gas Natural gas Natural gas Natural gas Natural gas Natural gas
Max gas consumption m /h 3
8.5-56.3 9.6-70.5 13.5-85.1 13.4-99.3 16.2-114.1 18-129.1
Min/max gas inlet pressure mbar 17-25 17-25 17-25 17-25 17-25 17-25
Flue (supplied as standard for conventional flue, option for room-sealed available)
Air inlet diameter mm I/D 250/350 250/350 250/350 250/350 250/350 250/350
Flue gas mass flow rate kg/h 135-896 153-1121 216-1354 214-1579 258-1815 286-2054
Flue gas temperature (80/60°C) 30-60 30-61 30-64 30-63 30-66 30-65
Hydraulics
Water content litres (per module) 49 60 71 82 93 104
Hydraulic resistance
34 (3.4 kPa) 33 (3.3 kPa) 36 (3.6 kPa) 33 (3.3 kPa) 38 (3.8 kPa) 39 (3.9 kPa)
@ 40°C ΔT mbar (kPa)
Hydraulic resistance
60 (6 kPa) 59 (5.9 kPa) 64 (6.4 kPa) 59 (5.9 kPa) 67 (6.7 kPa) 69 (6.9 kPa)
@ 30°C ΔT mbar (kPa)
Hydraulic resistance
113 (11.3 kPa) 110 (11.0 kPa) 120 (12.0 kPa) 110 (11.0 kPa) 125 (12.5 kPa) 130 (13.0 kPa)
@ 20°C ΔT mbar (kPa)
Hydraulic Resistance
374 (37.4 kPa) 364 (37.4 kPa) 397 (39.7 kPa) 364 (36.4 kPa) 413 (41.3 kPa) 435 (43.5 kPa)
@ 11°C ΔT mbar (kPa)
10
Gas 620 Ace
technical information.
Hydraulics
2x 2x 2x 2x 2x 2x
Nominal power supply
230v-1ph-50hz 230v-1ph-50hz 230v-1ph-50hz 230v-1ph-50hz 230v-1ph-50hz 230v-1ph-50hz
11
Gas 320 Ace
suggested engineering specification.
Construction Controls
The boiler consists of a sectional cast aluminium heat The boiler includes a controls package that allows the actual
exchanger with other major components contained within and set values to be read and adjusted on the built-in digital
a rigid steel frame with removable casing parts for display, which also provides normal operating and fault code
maintenance purposes. The boiler comes complete with indication. The controls come as standard with the following:
wheels to enable the assembled unit to be easily manoeuvred > 0-10V input (flow or load control)
into position within the plant room on site with the minimum
of effort. All major electrical and electronic controls are
> Common alarm
contained within the instrument panel mounted on top of > High limit lock out
the boiler at the opposite end to the connections facing to the > External gas valve control (optional)
front (long side) but can be rotated 90˚ towards the short side > Low water protection (optional)
to suit site location. The boiler can pass through a 720mm > Frost protection
standard door and shall be delivered fully assembled. > External pump control
The boiler will be available with flow and return connections > Min gas pressure switch (optional)
on the left or right hand end of the boiler (this must be > Release input
decided when ordering the boiler) with the gas connection > Volt free (enable signal)
on the top of the boiler. The flue gas outlet, complete with > Open therm control
a condensate connection shall be at a low level on the same > Cascade control (optional)
end as the F/R connections. The combustion air inlet is > System zone, valve and pump control (optional)
located at the top of the boiler. The boiler will be suitable for > Modbus connectivity (optional)
room-sealed or conventional flue applications and designed > Bluetooth connectivity
to operate at working pressures not exceeding seven bar.
Features
Operation
The boiler comes complete with a modulating control system
> Ultra-low NO2 from 15mg/kWh
that limits the maximum difference in temperature between > Fully modulating
the heating flow and return and the maximum speed at which > Supplied on fully built-in wheels
the flow temperature increases. The boiler comes complete > Air pressure differential sensor (LDS)
with a pre-mix burner (NG) with the gas/air ratio control
system controlled internally. An intelligent, advanced boiler
> ErP compliant
control continuously monitors the boiler conditions, varying > Digital diagnostic display
the heat output to suit the system load. The controls can > Pre-mix burner
react to external negative influences in the rest of the system > Left or right hand versions available
maintaining boiler output for as long as possible without
resorting to a lock out condition. Should a negative effect
> In-built passive flue gas non-return valve
happen in the system the boiler will reduce its output and/or
shuts down (shut-off mode), awaiting the negative conditions
Dimensions and connections
to return to normal before restarting. The small footprint of this range alongside its easy
The boiler is equipped with multiple sensors to detect and disassembly and its space saving configurations, makes
respond on low to no-flow conditions. Using an in-built it ideal for modular arrangement and particularly suitable
PI control, the boiler maintains active control during flow for retrofit applications.
variations. This ensures that during temperature related stop
conditions the boiler immediately responds when heat is
required. This also protects the heat exchanger if a zero flow
condition occurs during normal operation. The control cannot
override the standard flame safety controls. Standard frost
protection activates below 6°C with stage one activating the
system/shunt pump. Stage two activates below 3°C with
boiler switching on to 10°C flow.
12
Gas 620 Ace
suggested engineering specification.
Construction Controls
The boiler consists of a sectional cast aluminium heat The boiler includes a controls package that allows the actual
exchanger with other major components contained within and set values to be read and adjusted on the built-in digital
a rigid steel frame with removable casing parts for display, which also provides normal operating and fault code
maintenance purposes. The boiler consists of two modules indication. The controls come as standard with the following
connected together to share the same air-box. Each section inputs/outputs:
is able to perform independently to each other and should > 0-10V input (flow or load control)
one module go to fault, the other will remain operational.
The boiler is complete with wheels to enable the assembled
> Common alarm
unit to be easily manoeuvred into position within the plant > High limit lock out
room on site with the minimum effort. All major electrical > External gas valve control (optional)
and electronic controls are contained in the instrument > Low water protection (optional)
panel mounted on top of the boiler at the opposite end to > Frost protection
the connections facing to the front (long side) but can be > External pump control
rotated 90˚ towards the short side to suit site location. The > Hydraulic pressure sensor (optional)
boiler can pass through a 720mm wide standard door fully > Shutdown interlock
assembled in two modules to allow ease of positioning.
> Min gas pressure switch (optional)
The boiler is available with flow and return connections > Open therm control
on the left or right hand end of the boiler (this must be decided > Cascade control (optional)
during coordination), with the gas connection on the top of > System zone, valve and pump control (optional)
the boiler. The combustion air inlet is located at the top of the > Modbus connectivity (optional)
boiler. The boiler is suitable for room-sealed or conventional > Bluetooth connectivity
flue applications and designed to operate at working pressures
not exceeding seven bar. The boiler has two flows and returns
at one end with a combined flue gas outlet. The control panel
Features
can be rotated to enable the boiler connections to be on > Ultra-low NO2 from 15mg/kWh
the left or right hand side > Fully modulating
Operation
> Supplied on fully built-in wheels
> Air pressure differential sensor (LDS)
The boiler comes complete with a modulating control system
that limits the maximum difference in temperature between
> ErP compliant
the heating flow and return and the maximum speed at which > Digital diagnostic display
the flow temperature increases. The boiler comes complete > Pre-mix burner
with a pre-mix burner (NG) with the gas/air ratio control > Left or right hand versions available
system controlled internally. An intelligent, advanced boiler
control continuously monitors the boiler conditions, varying
> In-built passive flue gas non-return valve
the heat output to suit the system load. The controls can
react to external negative influences in the rest of the system
Dimensions and connections
maintaining boiler output for as long as possible without The small footprint of this range alongside its easy
resorting to a lock out condition. Should a negative effect disassembly and its space saving configurations, makes
happen in the system the boiler will reduce its output and/or it ideal for modular arrangement and particularly suitable
shuts down (shut-off mode), awaiting the negative conditions for retrofit applications.
to return to normal before restarting.
The boiler is equipped with multiple sensors to detect and
respond on low to no-flow conditions. Using an in-built
PI control, the boiler maintains active control during flow
variations. This ensures that during temperature related
stop conditions the boiler immediately responds when heat
is required. This protects the heat exchanger if a zero flow
condition occurs during normal operation. The control cannot
override the standard flame safety controls. Standard frost
protection will activate below 7°C with stage one activating the
system/shunt pump. Stage two will activate below 3°C with
boiler switching on to 10°C flow.
13
Gas 320 Ace
dimensions for the 285, 355 and 430 models.
Secondary return shown is an optional extra and does not come as standard.
14
Gas 320 Ace
dimensions for the 500, 575 and 650 models.
Secondary return shown is an optional extra and does not come as standard.
15
Gas 620 Ace
dimensions for the 570, 710 and 860 models.
16
Gas 620 Ace
dimensions for the 1000, 1150 and 1300 models.
17
Gas 320/620 Ace
module partial disassembly – for restricted access.
1107
1160
700
1107
1469
700
18
Gas 320 Ace
configurations.
The service side with the inspection hatch on the heat exchanger is considered to be the
front of the boiler. This boiler is available in both a left-hand and right-hand version. This means
that the hydraulic connections and the flue gas discharge are situated on either the left or the
right-hand side of the boiler. The control panel is on the front as standard, but can easily be
rotated so that it is on the short side. To make the boiler level and to raise the wheels off the
floor, the adjustment jacks must be used. Turn the adjustment bolts out as soon as the boiler
is placed in the correct position. The picture shows the support surface of the boiler.
This is the position of the adjustment bolts.
19
Gas 620 Ace
configurations.
The Gas 620 Ace boiler is not available with a choice between left or right hand versions,
but the control panel can easily be rotated to enable the boiler connections to be on
the left or right hand side. To make the boiler level and to raise the wheels off the floor,
the adjustment bolts must be used. Turn the adjustment bolts out as soon as the boiler
is placed in the correct position. The picture shows the support surface of the boiler.
This is the position of the adjustment bolts.
20
Gas 320/620 Ace
configurations.
Typical clearances are shown below on the schematic.
We recommend a clearance of at least 45cm above the boiler.
If the air supply filter is used, there must be a clearance of at least 65cm.
21
Electrical connections
and controls.
Temperature control
The boiler is equipped with electronic temperature control
based on flow, return, and boiler block temperature sensors.
The flow temperature can be set between 20 and 90°C.
The boiler reduces its power when the set outlet-temperature
is attained. The cut-out temperature is the set heating
outlet temperature + 5°C.
22
Electrical connections and controls
wiring layout.
The Gas 320/620 Ace boiler is equipped with the e-Smart controls platform.
This is a modular system, and offers compatibility and connectivity between
all products that make use of the same platform.
Electrical diagram
R-Bus C
RU
CU B
SCB CB A
GTW
L-Bus
S-Bus
MK
GTW
CU Control Unit The control unit handles all basic functionality of the appliance
RU Room Unit: (for example, a thermostat) A room unit measures the temperature in a reference room
L-Bus Local Bus: Connection between devices The local bus provides communication between devices
S-Bus System Bus: Connection between appliances The system bus provides communication between appliances
R-Bus Room Unit Bus: Connection to a room unit The room unit bus provides communication to a room unit
Specific devices delivered with the Gas 320/620 Ace boiler can be found within the installation and user manual located at remeha.co.uk
23
Gas 320/620 Ace
fault reporting/outputs.
The Gas 320/620 Ace are complete with the SCB-01 as standard.
This board allows for fault reporting via the 2 x status relays and
pump control or modular reporting via the 1 x 0-10V output.
Status relay
The status relay can be used in a normally open (NO) or
normally closed (NC) configuration for activation. The main
functions are as follows (please see the installation manual
for more options):
> Boiler alarm
0-10V output
The 0-10V output can be used to control:
> Modulate Wilo/Grundfos pump speed
SCB-01
24
Safety
interlocks.
This applies to the Gas 320 Ace and to each module on the Gas 620 Ace.
The boilers are supplied with two interlocks as standard.
be connected to the BL terminals of the connector. If the > Minimum gas pressure switch > Air filter
contact is opened, the boiler will be blocked from firing:
> Second return > Recom kit
Change the function of the input using parameter AP001.
The parameter has the following 3 configuration options: > Cleaning tool
> Combined roof flue kit
1 Complete blocking: no frost protection with the outdoor > Water pressure sensor
1 If the contact is closed during a heat demand, the boiler > Switch off the boiler electrical power supply
2 If
the contact is closed when there is no heat demand, the > nsure that the boiler and system are protected
E
boiler will be blocked after a waiting time. The waiting time against frost damage
of the input can be changed using Parameter AP008
CAUTION: In the event of low temperatures, we recommend
that the installation continues to operate at a lower
Hydraulic pressure sensor
temperature. This prevents freezing.
The hydraulic pressure sensor registers the water pressure
and can shut the boiler down when the minimum water Frost protection
pressure is reached. To activate this blocking option, a
CAUTION: Drain the boiler and central heating system if you
minimum pressure must be set with the boiler parameters.
are not going to use the building for a long time and there
is a chance of frost.
SCB-01
Set the temperature control low, for example at 10°C.
The boiler is supplied as standard with an SCB-01, If there is no demand for heat, the boiler will only switch on
the SCB-01 has the following features: in order to prevent frost damage. When the heating water
1 T
wo potential-free contacts for status notifications temperature in the boiler falls by too much, the integrated
2 0-10V
output connection for a PWM pump protection system in the boiler starts up. This protection
functions as follows:
The two potential-free contacts can be configured as
required by using Parameters EP018 and EP019. 1 The circulation pump switches on if the water temperature
is <6°C (if pump is electrically connected to the boiler)
Maximum voltage 230vac maximum current 1 amp.
2.If the water temperature is <3°C, the boiler starts up.
The inbuilt frost protection programme is for the sole use
of the heat exchanger protection
3.If the water temperature is >10°C, the boiler shuts down
and the heating pump continues to run for a short time
CAUTION: The integrated protection system only protects
the boiler, not the installation.
25
Boiler
controls.
achieved) the boiler fires and modulates to achieve and > Analogue modulation control
control a pre-set temperature set point.
The Gas 320 Ace requires 1 x 0-10V and the Gas 620 Ace
required 2x 0-10V (one of each module).
CB-01 PCB
26
Boiler
controls.
Cascade control
Using the optional SCB-10 expansion board, the boilers The supplied temperature sensor must be installed onto the
can control their own cascade arrangement. The SCB-10 common flow header or low loss header. The cascade can
is mounted internally into the master boiler and connects function stand alone using configurable parameters or using
using the S-Bus ports to slave boiler(s) via the CB-01 a 1 x 0-10V connection from the BMS allowing set point
supplied as standard. temperature control.
27
Diameter 250 mm 300 mm 350 mm
Diameter (1)
L=
250 mm 300 mm 350 mm Gas 620 Ace 570
according to the reduction table.
50 m(1) 50 m(1) 50 m(1)
Gas 620 Ace 570 50 m(1) 50 m(1) 50 m(1) Gas 620 Ace 710 Use approved flue
31 m
reducers
50 m (1)
for adaptatio
50 m(1)
50 m(1) Gas 620 Ace 860 The boiler also 20
supports50 other flue
50 m(1)length
Gas 320
Gas 620 Ace 860 Ace
Gas 620 Ace 710 31 m
20 m
50 m(1)
50 m (1)
50 m(1)
Gas 620 Ace 1000specified in the11
m
tables.
m
m(1)
Contact
39 m usm(1)for mor
50
flue data.
Gas 620 Ace 1000
Gas 620 Ace 1150
11 m
5m
39 m
26 m
50 m(1) Gas 620 Ace 1150
50 m Gas 620 Ace 1300
5m
3m
26 m
Room-ventilated system (B , B
19 m
50 m
2AD-3001564-0
50 3m 23P )
Gas 620 Ace 1300 3m 19 m 50 m (1) While maintaining maximum length, additional 5 times 90º or 10 times 45º
(1) While maintaining maximum length, additional 5 times 90º or 10 times 45º bends can be used (indicated for each boiler type and diameter).
Open flue
bends can (B23,
be used B23
(indicated)
AD-3001564-01
(2) for each boiler type and diameter). With(C33,
Room-sealed a room-ventilated
C63) system, only the flue
Room-seaislednot
systconnected
em (C 33, C 63, Cand will draw the combust
01564-01
93)
WithRoaoroom-ventilated
m-sealed systemsystem,
(C33, Conly the flue is connected. With a room-sealed system, both the flue and the air supply
63, C93)
The air supply is not connected and will draw the combustion installation
are aconnected.
With room-sealed system, botharea.
the flue and the air supply are
air directly
With from the
a room-sealed installation
system, both thearea.
flue and the air supply are connected.
Fig.12
connected. Room-ventilated
Fig.14
system Gas 320
Room-sealed system Gas 320 Ace
L the flue andofairthe
L Combined length ofLength flue to roof terminal
supply channel to the roof
L Ace
Combined length of the flue and air supply channel to the roof Fig.14
terminal Room-sealed
Flue gas outletsystem Gas 320 Ace
connection
terminal Flue gas outlet connection
Flue gas outlet L
connection
= + Tab.12
Air supply connection Maximum length (L)
Air supply connection
Tab.14 Maximum length (L) (1)
Tab.14 Maximum length (L) Diameter 250 mm 300 mm
L= Diameter (1) L= +
Diameter (1) 250 mm 300 mm Gas
Gas 320 Ace 285 320 Ace 285 100 m(1) 100 m(1)
Gas 320 Ace 285 100 m (1)
100 m (1)
Gas 320 Ace 355 100 m (1)
100 m(1)
Gas 320 Ace 355 100 m (1)
100 m (1) Gas
Gas 320 Ace 430
320 Ace 355 100 m 100 m(1)
Gas 320 Ace 430 100 m 100 m(1)
AD-3001562-01 Gas
Gas 320 Ace 500 320 Ace 430 100 m 100 m(1)
Gas 320 Ace 500 100 m 100 m(1) Gas 320 Ace 575 68 m 100 m(1)
Gas 320 Ace 500
01562-01
28
Diameter 250 mm 300 mm 350 mm
Gas 620 Ace 570 50 m(1) 50 m(1) 50 m(1) Diameter
(1)
250 mm 300 mm 350 mm
L=
Gas 620 Ace 710 31 m 50 m (1)
50 m(1) Gas 620 Ace 570 50 m(1) 50 m(1) 50 m(1)
flue
Gas data.
620 Ace 1150
Gas 620 Ace 1300
5m
3m
26 m
19 m
50 m
50 m
Gas 620 Ace 1000
Gas 620 Ace 1150
11 m
5m
39 m
26 m
50 m(1)
50 m
(1) While maintaining maximum length, additional 5 times 90º or 10 times 45º Gas 620 Ace 1300 3m 19 m 50 m
bends can be used (indicated for each boiler type and diameter). (1) While maintaining maximum length, additional 5 times 90º or 10 times 45º
Different pressure zones Open flue
can (B23, B23(2)) for each boiler type and diameter).
3001564-01
4 4 Before
Beforeinstallation
installation AD-3001564-01
bends be used (indicated
Room-sealed system (C 33, C 63, C 93)
The maximum permitted height difference between WithRoaoroom-ventilated
m-sealed system system,
(C33, only
C63, the
C93flue
) is connected.
the aairroom-sealed
With supply terminal and
system, thethe
both flue
fluegas
andoutlet
the airissupply
36m. are The air supply is not connected and will draw the combustion
connected. With aFig.13
air directly from the
room-sealed Room-ventilated
installation
system, area.
both the system
flue and the air supplyGas
are 620
ce
e
Fig.16
Fig.16 Different
Different
L Combined
pressure
length ofpressure
zones
zones
the flue and air
Gas
supply Gas
320
channel320
to the roof
LL
connected. Combined Ace length
Combined lengthofofthe theflue
flueand
andair airsupply
supplyc
Ace
Ace Fig.14 Room-sealed system Gas 320 Ace
terminal L Flue
Combined Flue gas
length of outlet
gas outlet
the connection
connection
flue and air supply channel to the roof
Flue gas outlet connection terminal
Air supply connection Air
Flue gas Airsupply
supply
outlet connection
connection
connection
Air supply connection
Tab.14 Maximum length
Tab.16 L =Maximum
Maximumlength
length(L)
L = (L) +
Tab.16
Tab.14 Maximum length (L)
(L)
L a=
DiLm=
eter (1) ++ 250 mm 300 mm
Gas 320 Ace 285 100 m(1) 100 m(1) DiaDeia
mD teim
ar (meteetrer(1)(1)
1)
250 mm 300 mm 25
20
Gas 320 Ace 355 100 m 100 m Gas 320 Ace 285 100 m (1)
100 m (1)
Gas
Gas320320AceAce285 10
(1) (1)
Gas 320 Ace 650 48 m 100 m (1) Gas 320 Ace 575 68 m 100 m(1)
(1) While maintaining maximum length, additional 5 times 90º or 10 times 45º Gas
Gas Gas
320 320
Ace 650Ace
320 Ace500
500 48 m 100 m(1) 7
bends can be used (indicated for each boiler type and diameter). (1) While maintaining maximum length, additional 5 times 90º or 10 times 45º
Gas
Gas320
320Ace Ace575 575
bends can be used (indicated for each boiler type and diameter). 5
ce
e L Combined length of the flue and air supply channelAD-3001563-01
to the roof
Gas
Gas320
320Ace Ace650 3
AD-3001563-01
L Combined
terminal length of the flueRoom-sealed
Fig.15 and air supply channel
system Gas 620 Ace
650
L Combined length of the flue and air supply channel to the roof
AD-3001564-
Fluegas
Flue gas outlet
outlet connection
connection L (1)
(1) While maintainingmaximum
While
terminal
Length maintaining
of the flue
maximumlength,
to roof terminal
length,additional
additional5 5tim
t
Airsupply
Air supply connection
connection Fluegas
Flue gas outlet
outlet connection
connection
bends
bends can be used (indicated for each boiler typea
can be used (indicated for each boiler type
L =(L) + Air supply connection
Tab.15 Maximum length
Diameter (1) 300 mm 350 mm 400 mm Tab.15 Maximum length (L)
Fig.17
Fig.17
Gas Different
Different
620 Ace
Maximum 570 pressure zones
length (L) pressure 100 m(1) Gas
zones 100620
Gas m620
(1) meteL 1) Combined
r (L
100 m(1) DiaMaximum Combined
length (L)
length 3of
length the
00ofm theflue
m 350 and
flue m air
mand 00supply
4air supply
m m c
Ace
Ace
Gas 620 Ace 710 86 m 100 m(1) 100 m(1) Gas 620 AceFlue
Fluegas
570 gasoutlet
outletconnection
connection
100 m(1) 100 m(1) 100 m(1)
Diameter52 m Diameter 100 m Gas 620 Ace 710 Diameter 86 Diameter
m 100 Diameter
m (1)
100 m(1)
Gas 620 Ace 860 100 m Air
Airsupply
supplyconnection
connection
(1) (1)
Boiler type Boiler type
250MM 300MM 250MM 300MM 350MM
Fig.14
100 m(1) Gas 620 Ace 860 Room-sealed52 system
m Gas
100 m 320 100Ace
m(1)
(1)
Gas 620 Ace 1000 26 m 70 m
Gas
620320
AceAce 285 100m(1) 10 m 100m Gas
620620
Tab.17
Gas AceAce 570 50m
Maximum
1000 50m
length26(L)
m (1) 70 m50m(1)100 m(1)
Tab.17 Maximum length (L)
(1) (1)
Gas 1150 32 m 48 m
3001565-01
LL==
Gas 620320
Gas AceAce
1300
355 ++ 100m(1) - 20 m (1)
100m 24 m
Gas 620 Ace 710 Gas 620 Ace 1150
31m 10 m
50m(1) 32 m
50m(1) 48 m
D620
(1) While maintaining maximum length, additional 5 times 90º or 10 times 45º Gas iaim
D etee
aAce
AD-3001565-01
m trer(1)(1)
1300 - 20 m 30
30240m
mmmm
Gas 320can
bends Acebe430 88m
used (indicated for 100m(1)
each boiler type and diameter). Gas
(1) 620maintaining
While Ace 860 maximum20m 50m
length, additional
(1)
50m
5 times 90º or
(1)
10 times 45º(1)(1)
Gas
Gas620 = Ace
L620 Ace570 570
+
bends can be used (indicated for each boiler type and diameter).(1) 100
100mm
Gas 320 Ace 500 76m 100m(1) Gas 620 Ace 1000 11m 39m 50m
Connection in different pressure zones (C53)
Gas
Gas 620
Con620 620
nectAce
Ace
Ace
ion i1150
710
710
n different p5m
ressure zone26m
s (C
48
48mm
Gas 320 Ace 575 53m 100m(1) Gas 53) 50m
The maximum permitted height difference between the air supply terminal
andGas 320gas
Aceoutlet
650 is 36 m. 38m 100m(1) GasGas 620
620 Ace
Ace860 860difference between 50m24 24mm
the flue TheGas 620
maximum Ace 1300
permitted height3m 19m the air supply terminal
andGas
the flue620
Gas 620
gas Ace
Ace
outlet is1000
1000
36 m. --
(1) While maintaining maximum length, additional 5 times 90º or 10 times (1) While maintaining maximum length, additional 5 times 90º or 10 times
45º bends can be used (indicated for each boiler type and diameter). Gas
Gas620
620Ace
Ace1150
1150
45º bends can be used (indicated for each boiler type and diameter). --
(2) When installing a boiler with connection type B23 , B23P the IP rating
Gas
Gas620
620Ace
Ace1300
1300
of the boiler is lowered to IP20. --
AD-3001566-01
AD-3001566-01 (1)
(1) While
Whilemaintaining
maintainingmaximum
maximumlength,
length,additional
additional5 5tim
AD-3001562-t
21 bends
bendscan
canbebeused
used(indicated
(indicatedfor
foreach
eachboiler
boilertype
typea
7734324 - v.03 - 29092020 Maximum length (L) 21
RR
eedd
uDiameter
uctcio
250MM
nntata
tio b300MM
lele
b
Diameter Diameter
350MM
Diameter
400MM
45° bend 2.0m 2.4m 2.8m 3.2m
Fig.18
Fig.18 Bend
Bendradius
radius1D
1D Tab.18
Tab.18 Pipe
Pipereduction
reductionfor
foreach
eachbend
bend- -radius
radius1D
1D
90° bend 3.5m 4.2m 4.9m 5.6m
R=1D
R=1D DD
iaim
ameteetrer 25
2050mmmm 30300mmm
DD Fig.15
45° Room-sealed system Gas 620 Ace
45°bend
bend 2.0
2.0mm 2.4
2.4mm
90°
90°bend
bend 3.5
3.5mm 4.2
4.2mm
L= +
AD-3001609-01
AD-3001609-01
29
44
.5.5
.5.5 AA
ddd
itio nn
tio aa
lguu
lg idid
eelinlin
eess
Tab.14 Maximum length (L) D
Diameter (1)
G
Fig.13
L Length of the Room-ventilated
flue to roof terminal system Gas 620 L Length of the flue to roof terminal
Gas 620 Ace Ace
Flue gas outlet connection Gas
Flue gas outlet320 Ace 285
connection G
Gaslength
320(L)
Ace 355
flue
Diameter data.
Tab.13 Maximum length (L) Tab.13 Maximum
G
(1) 250 mm 300 mm 350 mm Diameter (1) 250 mm 300 mm 350 mm
L= Gas 320 Ace 430 G
Gas 620 Ace 570 50 m(1) 50 m(1) 50 m(1) Gas 620 Ace 570 50 m(1) 50 m(1) 50 m(1)
Gas 620 Ace 710 31 m 50 m 50 m Gas 620 Ace Gas
710 320 Ace 500 31 m 50 m 50 m
G
(1) (1)
AD-3001562-01 (1) (1)
Room
Gas sealed
620 Ace 860 system 20 m 50 m (1) Different pressure
50 m (1) Gas 620 Ace 860
Gas 320 zones
Ace 575
20 m 50 m (1)
50 m (1)AD-3001563-01
AD-3001563-01
Gas 620 Ace 1000 11 m 39 m 50 m(1) Gas 620 Ace 1000 11 m 39 m 50 m(1) G
If using a room-sealed version, it is necessary to connect Combustion air supply and combustion gas discharge are
Gas 620 Ace 1150 5m 26 m 50 m Gas 620 Ace Gas 1150 320 Ace 650 5 m 26 m 50 m
both the combustion gas exhaust and the air supply possible in various pressure zones, semi-CLV systems, with
Gas 620 Ace 1300 3 m 19 m 50 m Gas 620 Ace 1300 3 m 19 m 50 m
opening separately. the exception of (1)coastal
While maintaining
areas. The maximum maximum length, addition
permissible
(1) While maintaining maximum length, additional 5 times 90º or 10 times 45º difference
(1) While maintaining maximum
in height betweencan length, additional
the combustion 5 times
air supply and 45º
90º or 10 times
bends can be used (indicated for each boiler type and diameter). bends can be usedbends be boiler
(indicated for each used type(indicated
and diameter).for each boile
01564-01 AD-3001564-01 the combustion gas discharge is 36m.
Room-sealed system (C33 , C63 , C93 ) Fig.17
Fig.17
Room-sDifferent
ealeDifferent
d systepressure
m (Cpressure zones
33 , C63 , C93 )
zones GasGas 620620
Fig.15 Room-sealed system Gas 620 Ace AceAce L Combined length of the flue and air su
With a room-sealed system, both the flue and the air supply are With a room-sealed system, both the flue and the air supply are
connected. connected. terminal
Flue gas outlet connection
e L Combined length
Fig.14of the
Room-sealed systemchannel
flue and air supply Gas 320toAce
the roof L Combined length of the flue and air supply channel to the roof
Ta
terminal
L= + L =terminal
L= + +Air supply connection
Flue gas outlet connection Flue gas outlet connection
D
Air supply connection
L= + Tab.15
Air supply connectionMaximum length (L)
Tab.14 Maximum length (L) Tab.14 Maximum length (L)(1)
G
Diameter 300 m
Diameter (1)
250 mm 300 mm Diameter (1)
250 mm 300 mm G
Gas 320 Ace 285 100 m(1) 100 m(1) Gas 320 Ace Gas 285 620 Ace 570 100 m(1) 100 m(1) 100 m
Gas 320 Ace 355 100 m(1) 100 m(1) Gas 320 Ace 355 100 m(1) 100 m(1)
G
Gas 620 Ace 710 86 m
Gas 320 Ace 430 100 m 100 m(1) Gas 320 Ace 430 100 m 100 m(1) G
Gas 320 Ace 500 100 m 100 m(1) Gas 320 Ace Gas 500 620 Ace 860 100 m 100 m(1) 52 m
G
01562-01 AD-3001562-01
30
Technical support and
declaration of compliance.
> B
rochures
> E
C Type Examination Certificate (BED/R813) 92/42/
> C
ase studies
And complies with the following requirements:
> I nstallation manuals
> 7
3/23/EEC Electrical Low Voltage Directive
> B
IM files
> 9
7/23/EEC Pressure Equipment Directive
> C
AD files
> C
E Certification
> E
nergy-related products directive data
> N
O 2 Class Declaration EN15502-1:2012 + A1:2016 Gas Fired
> C
ommissioning
Heating Boilers – Part 1: General requirements and tests
> T
echnical information
> T
he unit has been inspected for compliance with the
> B
oiler Efficiency Declaration Issue date 14-10-2020
to EN15502-1:2012+A1:2015
Content provided within this document is correct as of publication, subject to change without notice.
Please refer to the Installation, Operation and Maintenance Manual which can be found at remeha.co.uk
31
Brooks House
Coventry Road
Warwick CV34 4LL
T 0345 070 1055
E [email protected]
W remeha.co.uk
Registered address:
Baxi Heating UK Ltd
Brooks House Coventry Road
Warwick CV34 4LL
Gas 320/620 Ace Specification Guide August 2022