Doughty2000 Top
Doughty2000 Top
Abstract—A test program has been completed to measure inci- to divert heat and explosive forces away from workers inter-
dent energy from 6-cycle arcs on 600 -V three-phase electric power acting with the switchgear. The utilization of current limiting
distribution systems. Testing was performed using an arc electrode protective devices not only limits damage to circuit parts, but
gap of 1.25 in that had previously produced maximum incident en-
ergy for a 600-V power system with a 36.25-kA prospective fault also significantly reduces duration of personnel exposure . The
current. The effect on incident energy of enclosing the arcs in a use of flame-resistant (FR) clothing has gained acceptance as an
cubic box was determined. Simple algorithms were developed to effective approach to personnel protection when other measures
allow estimation of incident energy at a specified distance from arc to prevent or limit arc exposure can not be employed.
electrodes as a function of the available bolted fault current on a These efforts have typically used theoretical models to quan-
600-V electric power distribution system. A comparison is made
with previously published methods for estimating incident energy tify arc exposure severity. While this approach has enabled sig-
and safe approach distances. The impact of the estimating algo- nificant progress in protecting people from injuries, improved
rithm on the management of the electric arc hazard is discussed. techniques for predicting arc energy and protective clothing per-
Index Terms—Arc burn, arc energy, arc protective clothing, in- formance offer more effective solutions. Even greater advance-
cident energy. ments could be achieved if hazard analysis tools and aids could
be easier to use by the electricians, operators, and technicians
most at risk, as well as engineers, supervisors and managers in-
I. INTRODUCTION
volved in equipment and protective clothing selection, system
TABLE I
THREE-PHASE ARC TEST RESULTS (600-V SYSTEM—1.25-IN ARC GAP)
measurements have determined that absorbed energy is equal to elevation of the electrode tips. The middle calorimeters in each
or greater than 90% of incident energy for copper calorimeters. set were aligned with the center electrode. A single calorimeter
Henceforth, incident and absorbed energy will be considered was located 6 in the above the center electrode tip.
as equivalent, and the term incident energy will be used.
The data acquisition system digitally sampled and recorded B. Test Sequence
arc voltage, arc current, time, and temperature rise from seven A series of three-phase arc tests was conducted during
copper calorimeters. An estimate of arc energy was calculated a one-week period. In order to reduce the impact of arc
by multiplying the phase-to-phase voltage/ by the phase cur- variability, four tests were run for each setup and the results
rent for each phase, summing the result for all three phases, and averaged. Since arc duration varies slightly from test to test, a
then multiplying the result by the arc duration. time-duration correction factor was applied to the temperature
Two different test setups were used for the three-phase arc rise data from the seven copper calorimeter sensors to insure
testing. Test Setup No. 1 was for a three-phase arc in open air, that each reported incident energy was based on an arc duration
as shown in Fig. 1. Test Setup No. 2 utilized electrodes mounted of 6 cycles. The mean incident energy for the seven sensors and
inside and 4 in from the back of a cubic metal box (20-in wide the maximum incident energy recorded by a single sensor were
× 20-in high × 20-in deep), as shown in Fig. 2. Tests were con- calculated for each test.
ducted with the box ungrounded, since earlier testing [4] indi- The first series of tests used the open-arc Test Setup No. 1
cated that the ungrounded box produced the maximum incident and measured the incident energy 24 in from the arc electrodes
energy. while the bolted fault current was adjusted in steps from 16 to 50
For each setup, an array of seven copper calorimeters was kA. At the conclusion of these tests, the bolted fault current was
located a specified distance from the centerline of the electrodes. set at 40.9 kA and the sensor distance was changed to 18 and 30
A set of three calorimeters was located in a horizontal row at in to determine the variation of incident energy with distance.
the same height as the tip of the electrodes. A second set of Thesecondseriesoftestsusedthearc-in-the-boxTestSetupNo.
three calorimeters was located in a horizontal row 6 in below the 2 and measured the incident energy 24 in from the arc electrodes
260 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 36, NO. 1, JANUARY/FEBRUARY 2000
(a)
TABLE II
MAXIMUM INCIDENT ENERGY—6-CYCLE ARC IN BOX AS A FUNCTION OF
BOLTED FAULT CURRENT AND DISTANCE FROM ARC ELECTRODES
(b)
Fig. 10. (a) Arc-in-box incident energy compared to calculated results . (b)
Open arc incident energy compared to calculated results.
TABLE III
PROTECTIVE CLOTHING GUIDELINES FOR THE ELECTRIC ARC HAZARD
A. Arc Test Algorithms mated maximum incident energy for the 6-cycle arc-in-the-box,
Maximum incident energy from a three-phase 6-cycle arc , is calculated using
with 1.25-in electrode gap in open air on a 600-V system may
be estimated using the curve-fit equations derived in Figs. 3 and (2)
7. Multiplying the two equations, the estimated maximum inci-
dent energy for the 6-cycle arc in air, , is calculated using
where
distance from arc electrodes, in ( );
(1) maximum 20-in cubic box incident energy, cal/cm2;
bolted fault current, kA (16–50-kA range)
where Predicted values using(2) for distances greater than 60
distance from arc electrodes, in ( ); in (5 ft) are believed to be conservatively high. The authors hy-
maximum open-arc incident energy, cal/cm2; pothesize that the distance variation of incident energy for the
bolted fault current, kA (16–50-kA range). cubic box will tend to approach the open-air inverse distance
Maximum incident energy from a three-phase 6-cycle arc squared relationship as distances from the box increase above
with 1.25-in electrode gap contained in a 20-in cubic box on 60 in.
a 600-V system may be estimated using the curve-fit equations Estimated maximum incident energy levels for a three-phase
derived in Figs. 4 and 8. Multiplying the two equations, the esti- 6-cycle arc with a 1.25-in electrode gap in a 20-in cubic box
DOUGHTY et al.: PREDICTING INCIDENT ENERGY TO BETTER MANAGE THE ELECTRIC ARC HAZARD 263
Fig. 15. Second-degree burn boundary distances for 600-V three-phase 6-cycle electric arcs in open air.
Fig. 16. Second-degree burn boundary distances for 600-V three-phase 6-cycle electric arcs in 20-in cubic box.
bolted fault MVA at arc point; Table III and defines proposed clothing classes based upon the
duration of arc exposure, s. available incident energy. Clothing Class No. 2 has been split
Equation (7) was also included in [5, Pt. II, App. B] as a into two subcategories, Classes No. 2A and 2B, to reflect the
method of calculating flash protection boundaries. use of either cotton or FR underwear. Table III is based upon
A comparison is shown in Fig. 12 of Lee’s “curable burn” dis- FR clothing produced by a number of manufacturers and gives
tances with the second-degree burn distances determined using general guidance about how many layers of FR fabric should
(5) and (6) for a 6-cycle arc. The Lee “curable burn” distances be considered to use for a given incident energy exposure. The
coincide almost exactly with the second-degree burn distances terms ATPV and , used in Table III, are defined in ASTM
for the open three-phase arc. The second-degree burn distances PS58 Standard [5] and are explained as follows.
for the arc in the cubic box, however, are significantly higher. • ATPV is defined as the incident energy that would just cause
The difference is more pronounced at higher bolted fault levels. the onset of a second-degree burn.
• is defined as the average of the five highest incident
energy values which did not cause FR fabric break-open and
V. SELECTING FR CLOTHING
did not exceed the second-degree burn criteria. is re-
Once the incident energy exposure level for a particular situ- ported when ATPV cannot be measured due to FR fabric
ation has been determined, and the exposure level is sufficient break-open. Break-open is defined as any opening in the in-
to cause either a second-degree burn or ignition of clothing, the nermost (nearest the protected surface) layer of FR fabric of
user should select an appropriate FR clothing system to provide more than 0.5 in2 area or a slit or crack in the innermost FR
protection from the arc hazard. ASTM PS57 data in [4, Table I] fabric, 1 in or greater in length. In the event of FR fabric
indicates that an average incident energy level of 3.0 cal/cm2 break-open, a flammable fabric underlayer or human skin is
(L95%CL) is required for a 1% probability of ignition of a 5.2 directly exposed to incident energy.
oz/yd2 blue cotton twill shirt material. Minimum incident en- Performance data about clothing systems utilizing specific
ergy required to produce a second-degree burn is 1.2 cal/cm2, fabrics is tabulated in [4]. A comparison of the performance of a
as discussed above. few selected FR fabric systems is illustrated in Fig. 13. Note that
The authors published a table of protective clothing guide- a dotted line at 3.0 cal/cm2 indicates incident energy required for
lines in [4] that was based on fabric testing utilizing the 1% probability of ignition for 5.2 oz/yd2 blue cotton twill shirt
ASTM PS58 test method [6]. This information is reproduced in material.
DOUGHTY et al.: PREDICTING INCIDENT ENERGY TO BETTER MANAGE THE ELECTRIC ARC HAZARD 265
TABLE IV
EVOLUTION IN KNOWLEDGE OF ARC FLASH PHENOMENA AND
IMPLEMENTATION OF HAZARD MANAGEMENT METHODS
ACKNOWLEDGMENT
VI. CONCLUSION
The authors wish to acknowledge the invaluable assistance
Significant progress has been made in the last 20 years in provided by C. Maurice and W. Dal Din of the Ontario Hydro
understanding the arc flash hazard and protecting people, as is Technologies High Current Laboratory.
266 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 36, NO. 1, JANUARY/FEBRUARY 2000
(a)
(b)
Fig. 18. (a) Second-degree burn boundary distances for 600-V three-phase 3-cycle electric arcs in open air . (b) Second-degree burn boundary distances for 600-V
three-phase 3-cycle electric arcs in 20-in cubic box. Data based on measured incident energy under specified test conditions. Real arc exposures may be more or
less than these simulated exposures.
(a)
(b)
Fig. 19. (a) Second-degree burn boundary distances for 600-V three-phase 9-cycle electric arcs in open air . (b) Second-degree burn boundary distances for 600-V
three-phase 9-cycle electric arcs in 20-in cubic box. Data based on measured incident energy under specified test conditions. Real arc exposures may be more or
less than these simulated exposures.
DOUGHTY et al.: PREDICTING INCIDENT ENERGY TO BETTER MANAGE THE ELECTRIC ARC HAZARD 267
(a)
(b)
Fig. 20. (a) Second-degree burn boundary distances for 600-V three-phase 12-cycle electric arcs in open air . (b) Second-degree burn boundary distances for
600-V three-phase 12-cycle electric arcs in 20-in cubic box. Data based on measured incident energy under specified test conditions. Real arc exposures may be
more or less than these simulated exposures.
(a)
(b)
Fig. 21. (a) Second-degree burn boundary distances for 600-V three-phase 18-cycle electric arcs in open air . (b) Second-degree burn boundary distances for
600-V three-phase 18-cycle electric arcs in 20-in cubic box. Data based on measured incident energy under specified test conditions. Real arc exposures may be
more or less than these simulated exposures.
268 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 36, NO. 1, JANUARY/FEBRUARY 2000
(a)
(b)
Fig. 22. (a) Second-degree burn boundary distances for 600-V three-phase 24-cycle electric arcs in open air . (b) Second-degree burn boundary distances for
600-V three-phase 24-cycle electric arcs in 20-in cubic box. Data based on measured incident energy under specified test conditions. Real arc exposures may be
more or less than these simulated exposures.
(a)
(b)
Fig. 23. (a) Second-degree burn boundary distances for 600-V three-phase 30-cycle electric arcs in open air . (b) Second-degree burn boundary distances for
600-V three-phase 30-cycle electric arcs in 20-in cubic box. Data based on measured incident energy under specified test conditions. Real arc exposures may be
more or less than these simulated exposures.
DOUGHTY et al.: PREDICTING INCIDENT ENERGY TO BETTER MANAGE THE ELECTRIC ARC HAZARD 269