Piping Support Types Purpose Design Codes Optimization Rules PDF
Piping Support Types Purpose Design Codes Optimization Rules PDF
Piping support plays a very crucial role in the proper functioning of the piping
systems. Pipe support carries the pipe weight with contents. To maintain the integrity
of the piping system, A pipe must be supported following a proper span. Pipe support
engineering is very critical for the success of any project as an accurate and judicious
selection of piping support is required. Pipes as irregular space frames are not self-
supporting so must be supported. Piping Loads are transmitted from pipe to supporting
structures with the help of pipe supports. Proper pipe support knowledge during the layout
stage is advantageous.
The piping system is a major part of any hydrocarbon industry. Proper pipe support
knowledge during the layout stage is advantageous. Piping Loads generated due to Weight,
Pressure, Temperature, or Occasional Event has to be transmitted from pipe to supporting
structures with the help of appropriate pipe supports.
1/16
To eliminate exposure of elements to temperature extremes, outside their design limit.
To limit undesirable line movements to protect sensitive equipment against overloading.
To redirect pipe thermal movements to the favourable direction.
to reduce excessive loading in support itself
For the proper working of the piping system, it has to be supported properly. The major
purpose of pipe supports can be elaborated as follows:
Pipe Supports are required to support the line during all conditions i.e. during operation as
well as during testing. In the case of the vapor line, this difference will be very large due to
hydro testing. Supports should be designed for this load (unless otherwise decided in the
project). Sometimes the line is capable of having a longer span but the load coming on the
support may be very large (especially with large diameter pipelines). Then to distribute the
load uniformly, the number of supports should be provided with a smaller span. Note: 1. it
may be noted that during testing conditions there is no thermal load. 2. All spring supports
are locked during testing.
Advertisements
The hydraulic thrust (Fig. 1) in the pipeline is present at certain points such as pressure-
reducing valve, relief valve, bellows, etc.
If the control valve has a large pressure differential and the line size is more, then this force
can be very high.
2/16
Fig. 1: Figure showing thrust force
The support should be provided and designed to take this load, otherwise, this will load the
piping system and may cause failure.
When the pipe is subjected to moving machinery or pulsating flow or very high-velocity flow,
the pipe may start vibrating vigorously and ultimately may fail, particularly if the span is large.
To avoid this it may be required to introduce additional supports at a smaller span apart from
other requirements. It may not take axial load but must control lateral movements.
Wind introduces lateral load on the line. This load is considerable especially on large
diameter pipes and increases as line size is increased. This load tends to sway the line from
its normal position and the line must be guided properly against it to avoid any kind of
malfunction. In the case of large diameter overhead lines, supported by tall support extended
from the floor, wind load introduces large bending moments and should be considered
critically.
3/16
nullified and exert a thermal load on supports.
The standby condition is also similar. If there are two pumps, one being standby and both
connected in parallel (as shown), the design and operating temperature of both the
connections will be the same. But the expansion of two parallel legs will not be nullified
because at a time only one leg will be hot and another being cold.
In most plants, noise is resulting from vibration and if such vibrations are controlled, noise is
reduced to a great extent. In such lines, between clamp (i.e. support) and pipe, the asbestos
cloth is put to absorb vibration and avoid noise.
Noise due to pulsating flow can be reduced by using a silencer in the line. Still, if it is not
below an acceptable level acoustic enclosure may be used. Insulation over line also helps in
reducing the noise.
4/16
When for maintenance certain equipment or component like the valve is taken out, the
remaining system should not be left out unsupported.
Referring to the FIG-3, support ‘S1’ will be sufficient but when valve ‘V1’ is taken out for
maintenance there will not be any support for the vertical leg. Therefore second support ‘S2’
may be required to take care of such conditions.
In shutdown conditions, all equipment may not be in the same condition as in operating
conditions. For example, refer to the pump discharge line in FIG-4, Point A is resting, Point B
& C are spring supports and Point D is the pump discharge nozzle. The springs are,
designed based on weights considering the weight of fluid as well as pipeline and thermal
movements. But during shutdown conditions, the fluid may be drained and the pipe becomes
lighter. Hence the spring will give an upward reaction and shall load the nozzle ‘D’ beyond
the permissible limit.
5/16
Fig. 4: Use of Limit elements in spring during shut down
In this case, a limit stop is used which will not allow Point C to move up above the horizontal
level. (However, it will allow downward movement during operating conditions).
Erection conditions can be different than the operating condition which should be considered
while designing supports.
For example, for normal operation, a long vessel supported by three supports, S1, S2 & S3
is shown in FIG-5. If support S2 is higher then all load will act at S2 only. During an erection,
if the level of S2 is lower than the entire load will be divided into two supports S1, S2 only.
Therefore the foundation of S1, S2 & S3 should be capable of taking such conditions.
6/16
Fig. 5: Vessel supported at three supports.
A pipeline supported by S1, S2 & S3 taken from the vessel is shown in above FIG – 6.
During operation, there will be no weight at S2 & S3 (as it is the only guide), but wind
conditions will be there. Loads due to such conditions must be considered while designing
the supports.
7/16
Fig. 6: Pipe supported from vessel cleats.
MSS-SP-58- Establishes the material, design, and inspection criteria to be used in the
manufacturing of standard pipe supports. (USA)
MSS-SP-69- Provides recommendations for the selection and application of pipe
supports. (USA)
MSS-SP-89- Provides recommendations for the fabrication and installation of pipe
supports. (USA)
BS-3974- Specification of pipe supports 1, 2, 3. (UK)
VGB-R-510 L- Standard supports guidelines. (Germany)
8/16
RCC-M- Specifications for pipe supports. (France)
MITI 501- Technical regulations (Japan)
Major Criteria (Parameter) governing the pipe support hardware selection are
9/16
5. Based on Pipe Support function
Resting Support
Guide Support
Axial Stop or Line Stop
Anchor Support
Pipe Supports that are directly attached to the pipe are called Primary pipe Supports. For
example, Shoe support, Clamp Support, Guide Support, Line Stop Support, Trunnion
Support, etc. The design and selection of primary pipe support (Fig. 1) is the responsibility of
the piping team.
10/16
Group pipelines so as to minimize the number of structures needed solely to pipe
supports.
Route lines close to the possible point of supports ( i.e. grade or structure which is
provided for other purposes.)
Supports or braces to be located at or near neutral pts. (thermal null pts)
Supports to be located as near as possible to concentrated loads such as valves,
flanges, heavy actuators, etc.
Piping susceptible to vibration such as compressor connected lines to be supported
independently. The use of hold down or similar supports offering resistance to motion
and providing some damping capacity to be used rather than hanging type supports.
Piping connected to the top of the vessel to be advantageously supported from the
vessel to minimize relative movement between supports and piping.
Always maintain the distance between supports as per project specification
recommended support span table. ( it is applicable to straight run pipe length only.)
When a change of direction in a horizontal plane occurs, it is suggested that the
spacing be limited to ¾ times the standard pipe span.
Sufficient space to be provided to facilitate support assembly installation, inspection,
and maintenance.
Anchor Support or Fixed Support- A rigid restraint providing substantially full fixation is
termed as an anchor. Anchor support restricts all six degrees of freedom and does not allow
the pipe to move in any direction. Normally Full Welded or Bolted supports are called anchor
supports. Full Anchor supports (Fig. 10) are rarely used in piping systems.
Stop- A device that permits rotation but prevents translatory movements of piping. A line
stop or axial stop (Fig. 9) prevents pipe movement in the axial direction of the pipe. It is also
known as a stopper.
Guide- A device that prevents the rotation of one or more axis is called a guide (Fig. 10).
Guide supports (Fig. 8) prevents Lateral pipe movements.
Hold Down Support- A device that holds the pipe in position disallowing vertical upwards
movement or allows decided upward movement. Hold down supports prevent pipe dis-
engagement from the Support structure.
Hanger- A support by which piping is suspended from a structure that functions by carrying
the piping load in tension.
Resilient support- A support that includes one or more largely elastic members to carry
pipe sustain + thermal loads at the same time allowing pipe thermal movement in the desired
direction.
Rest Support or Sliding support- A device that is provided below piping to take gravity
loads, offering no resistance other than frictional to horizontal motion. Rest supports (Fig. 8)
do not allow the pipe to sag or move downward.
Damping element- A device that increases damping of a system offering high resistance
against rapid displacement, caused by dynamic loading while permitting essentially free
movement.
Adjustable Support– An adjustable support (Fig. 9) can be adjusted at the site during plant
operation. These supports are normally provided for pipe and equipment alignment
purposes.
Dummy Leg – Basically an extension pipe welded to an elbow, to provide support either as
a resting, anchor, etc.
12/16
Fig. 9: Line Stop and Adjustable Trunnion Support
13/16
Fig. 10: Anchor Support and Shoe Support with Guide
1. Piping GAD
2. Electrical and Inst cable trench/trays layouts
3. Civil and Structural drawings
4. Piping spec and line list
5. Insulation spec
6. Valve’s weights
7. Equipment connection displacements
8. Stress recommendations (Stress isometrics) and Support loads.
14/16
Pipe Support Span
Typically piping is supported at regular intervals on steel supports embedded in concrete
foundation or directly on the steel structure. The distance between supports is the supporting
span.
There are three main factors that affect the support span.
Stress
Deflection/ sagging and
Frequency of piping system (for two-phase flow lines, reciprocating equipment
connected lines, vibrating lines, etc.). Click here to know more about pipe support
span
15/16
CS pipes with less than SCH 20
SS pipes with less than SCH 10S
The pipe that requires a slope
Dissimilar material to avoid galvanic corrosion
Pipe to be supported on pipe shoe to avoid damaging to the pipe wall
The drawing is normally prepared by the pipe stress or pipe support engineer and checked
by a civil engineer to ascertain the structural member load-carrying capability.
16/16