LRXD01 User Manual
LRXD01 User Manual
Contents
Summary of changes 4
Chapter 2: Installation 11
General Specifications 11
Product Specifications 12
Mounting 13
WIRING 14
1
LRX D01
Counter Instructions 47
Common Counter 47
Counter Mode 0 (Internal coil) 48
Counter Mode 1 (Fixed Count, Non-Retentive) 49
Counter Mode 2 (Continuous Count, Non-Retentive) 50
Counter Mode 3 (Fixed Count, Retentive) 51
Counter Mode 4 (Continuous Count, Retentive) 51
Counter Mode 5 (Continuous Count, Up-Down Count, Non-Retentive) 52
Counter Mode 6 (Continuous Count, Up-Down Count, Retentive) 53
High Speed Counters (DC Version Only) 54
High Speed Counter Mode 7 (DC powered versions only) 54
I185 GB 06 10
2
LRX D01
3
LRX D01
SUMMARY OF CHANGES
This user manual is modified by firmware V3.0 and LRXSW programming software ver. 3. LRD V3.0 adds some new functions with firmware
version V3.0 to strong LRD function. The upgrade content is shown as the 2 tables below simply. More information about idiographic function to
see function instruction.
4
LRX D01
The LRD Relay is an electronic device. For safety reasons, please carefully read and follow the paragraphs with "WARNING" or "CAUTION"
symbols. They are important safety precautions to be aware of while transporting, installing, operating, or examining the LRD Controller.
Compliance with the installation instructions and the user manual is absolutely necessary. Failure to comply could lead to improper
operation, equipment damage or in extreme cases even death, serious bodily injury or considerable damage to property.
When installing the open-board models, insure that no wiring or foreign materials can fall into the exposed circuits and components.
Damage to equipment, fire, or considerable damage to property could result.
Always switch off power before you wire, connect, install, or remove any module.
The wiring for the LRD relay is open and exposed. For the open-board models, all electrical components are exposed. For this reason, it
is recommended the LRD relay be installed in an enclosure or cabinet to prevent accidental contact or exposure to the electrical circuits
and components.
Never install the product in an environment beyond the limits specified in this user manual such as high temperature, humidity, dust,
corrosive gas, vibration, etc.
Improper wiring and installation could lead to death, serious bodily injury or considerable damage to property.
The LRD relay should only be installed and wired by properly experienced and certified personnel.
Make sure the wiring of the LRD relay meets all applicable regulations and codes including local and national standards and codes.
Always separate AC wiring, DC wiring with high-frequency switching cycles, and low-voltage signal wiring.
To insure safety with the application of the LRD relay, complete functional and safety testing must be conducted. Only run the LRD after
all testing and confirming safe and proper operation is complete. Any potential faults in the application should be included in
the testing. Failure to do so could lead to improper operation, equipment damage or in extreme cases even Death, serious bodily injury or
considerable damage to property.
When the power is on, never contact the terminals, exposed conductors or electrical components. Failure to comply could lead to
improper operation, equipment damage or in extreme cases even death, serious bodily injury or considerable damage to property.
It is strongly recommended to add safety protection such as an emergency stop and external interlock circuit in case the LRD relay
operation must be shut down immediately.
ENVIRONMENTAL PRECAUTIONS
The installation site of the LRD relay is very important. It relates directly to the functionality and the life span of your LRD. Please carefully
choose an installation site that meets the following requirements:
– Mount the unit vertically
– Environment temperature: -20°C...55°C (-4°F...131°F)
– Avoid placing LRD close to any heating equipment
– Avoid dripping water, condensation, or humid environment
– Avoid direct sunlight
– Avoid oil, grease, and gas
– Avoid contact with corrosive gases and liquids
– Prevent foreign dust, flecks, or metal scraps from contacting the LRD relay
– Avoid electric-magnetic interference (soldering or power machinery)
– Avoid excessive vibration; if vibration cannot be avoided, an anti-rattle mounting device should be installed to reduce vibration.
DISCLAIM OF LIABILITY
We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be
precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary
corrections are included in subsequent editions.
5
LRX D01
a b c d e
❶ The D024 version is equipped with 2 digital inputs that can be used as 0…10VDC analog type.
❷ The D024 version is equipped with 4 digital inputs that can be used as 0….10VDC analog type.
a b
This section is a simple 5-steps guide to connecting, programming and operating your new LRD relay. This is not intended to be the complete
instructions for programming and installation of your system. Many steps refer to other sections in the manual for more detailed information.
6
LRX D01
24VDC
24VAC
100...240VAC
50/60Hz
I185 GB 06 10
VAC VDC
ESTABLISH COMMUNICATION
a. Open the LRXSW software and select “New Ladder Document” as shown below.
7
LRX D01
c. Select the correct Com Port number where the programming cable is connected to the computer then press the “Link” button.
I185 GB 06 10
d. The LRXSW will then begin to detect the connected LRD relay to complete its connection.
Note: If the ladder toolbar is not visible at the bottom of the screen, select View>>Ladder Toolbar from the menu to enable.
8
LRX D01
b. Use the “A” key on your keyboard (or the “A” icon on the ladder toolbar) to draw the horizontal circuit line from the M contact to the right
most cell, as shown below.
I185 GB 06 10
c. Select the “Q” coil icon from the ladder toolbar and drop it on the right most cells. Select Q01 from the dialog and press OK as shown below.
See Chapter 4: Ladder Programming instructions for complete instruction set definitions.
d. Test the simple program. From the Operation menu, select the Write function and write the program to the connected LRD relay as shown
below.
9
LRX D01
e. Select the RUN icon from the toolbar, and select “No” when the pop-up message asks “Do you want to read program from module?”, as
shown below.
I185 GB 06 10
f. On the Input Status dialog, click on M01 to activate the contact M01 which will turn ON the Output Q01 as shown below. The highlighted
circuit will show active and the first Output (Q01) on the connected LRD relay will be ON. See Chapter 3: Programming Tools for more
detailed software information.
10
LRX D01
CHAPTER 2: INSTALLATION
GENERAL SPECIFICATIONS
LRD is a miniature Relay with a maximum of 44 I/O points and can be programmed in Relay Ladder Logic or FBD (Function Block Diagram)
program. The LRD can expand to its maximum I/O count by adding 3 groups of 4-input and 4-output modules.
POWER SUPPLY
Input Power Voltage Range 24V DC Models: 20.4-28.8V
12V DC Models: 10.4~14.4V
AC Models: 85-265V
I185 GB 06 10
11
LRX D01
ANALOG INPUTS
Resolution Basic unit: 12 bit
Expansion unit: 12bit
Voltage Range acceptable Basic unit: Analog input: 0-10VDC voltage,
24VDC when used as discrete input;
Expansion unit: Analog input: 0-10VDC voltage or 0-20mA current
Input Signal ”OFF” Threshold < 5VDC (as 24VDC discreet input)
Input Signal ”ON” Threshold > 9.8VDC (as 24VDC discreet input)
Isolation None
I185 GB 06 10
PRODUCT SPECIFICATIONS
Moduli base
Order code Input Power Inputs Outputs Display & Keypad Max I/O
LRD12RD024 24VDC 6 DC, 2 Analog 4 Relay 3, Z01-Z04 36 + 4 *1
*1 If module with keypad and display, Max IO can be added keypad input Z01-Z04.
2 More information about Product Specifications to see “chapter 6: Product Specifications”.
12
LRX D01
MOUNTING
35mm DIN-rail Mounting
The LRD relay must always be mounted vertically.
Place the upper end of the LRD relay inserting the slot on the DIN rail. Slightly press the relay downwards and fasten its lower end on the rail.
Check that the LRD is firmly fitted.
Insert the connector in the expansion module and fit the module on the DIN rail as previously described.
Slide the module on the rail toward the LRD relay, press the Press-button and connect them together.
I185 GB 06 10
Connector
+ - I1 I2 I3 I4 I5 I6 A1 A2 Input X1 X2 X3 X4
4¡ ÀC Press-button
L N AC 100~240V
DC 24V Input 8 x DC(A1,A2 0~10V)
Run
Output 4 x Relay / 8A
+ - I1 I2 I3 I4 I5 I6 A1 A2 Input X1 X2 X3 X4
4¡ ÀC End clamp
DC 24V Input 8 x DC(A1,A2 0~10V) L N AC 100~240V
Run
Output 4 x Relay / 8A
Q1 Q2 Q3 Q4 Y3 Y4
13
LRX D01
Screw Fixing
Use M4x20 screws to directly mount the LRD as shown. For direct installation of the expansion module, slide the expansion module and connect
with the Master after the Master is fixed.
M4x20 (#8x32)
I185 GB 06 10
+ - I1 I2 I3 I4 I5 I6 A1 A2 Input X1 X2 X3 X4
4¡ ÀC
Run
Output 4 x Relay / 8A
Q1 Q2 Q3 Q4 Y3 Y4
WIRING
WARNING: The I/O signal cables must be routed parallel to the power cable, or in the same cable trays to avoid the signal interference.
To avoid a short circuit on the load side, it is recommended to connect a fuse between each output terminals and loads.
C
Ø3.5
Nm 0.6
(0.14in) C
lbin 5.4
Input 24VDC
+- A1 A2
A3
1 1 +- A1
A2 A4
24VDC 2 2
+ - I1 I2 I3 I4 I5 I6 A1 A2 + - I1 I2 I3 I4 I5 I6 I7 I8 A1 A2 A3 A4
DC V Input DC V INPU T
14
LRX D01
Sensor Connection
24VDC
I185 GB 06 10
Input 100~240VAC/24VAC
1 1
24VAC
100...240VAC 3 3
50/60Hz
+ - I3 I4 I5 I6 A1 A2 + - I1 I2 I3 I4 I5 I6 I7 I8 A1 A2 A3 A4
AC V Input AC V INPU T
Output (Relay)
Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8
5 5
4
12...240VAC
50/60Hz
or 12...125VDC
Output (Transistor)
+Q1 - +Q2 - +Q3 - +Q4 - +Q1 - +Q2 - +Q3 - +Q4 - +Q5 - +Q6 - +Q7 - +Q8 -
5
4
24VDC
or
24VDC
12VDC
15
LRX D01
Insert the plastic connector end of the programming cable into the LRD relay as shown in the figure below.
Connect the opposite end of the cable to an RS232 serial port on the computer. In case the computer does not have one, connect the LRX C00
cable to a RS232-USB converter, compatible with USB2.0 or higher.
16
LRX D01
START SCREEN
Run the LRXSW software and the below Start screen will be displayed. From this screen, you can perform the following functions
I185 GB 06 10
17
LRX D01
PROGRAMMING
The LRXSW software can be programmed by either position of instructions or by using keyboard entry commands. Below is an example of
some common methods of entering programming instructions.
18
LRX D01
The “A” and “L” keys or icons are used to complete parallel and serial circuits. The right column is for output coils.
I185 GB 06 10
SIMULATION MODE
The LRXSW software includes a built-in simulator to test and debug programs easily without the need for downloading to a controller. To
activate simulation mode, simply press the red RUN icon. The program below is shown in simulation mode, identifying the significant available
features.
19
LRX D01
ESTABLISH COMMUNICATION
The following is the simple procedure for establishing communication between PC and the LRD relay.
a. Select “Operation/Link Com Port…” as shown below.
I185 GB 06 10
b. Select the correct Com Port number where the programming cable is connected to the computer then press the “Link” button.
c. The LRXSW software will then begin to detect the connected LRD relay to complete its connection.
20
LRX D01
OPERATION MENU
The Operation menu, includes several system configuration functions for both online and offline setup. The following explains the details of each
function.
Monitor - Online function for runtime monitor and editing when connected to a controller
Simulator - Offline function for testing and debugging a program.
Simulator Control - Self-motion simulator control
Run-Stop-Quit - Mode change selections for both runtime editing and simulation mode.
Read-Write - Reading and writing programs to and from a connected LRD relay.
RTC Set - Online function for setup of the Real-time clock/calendar (see dialog below left)
I185 GB 06 10
Analog Set - setup analog input A01-A08 gain and offset (see dialog below right)
Password - Set a password for accessing the current program after upload to the LRD relay
Language - Change LRD relay menu language
Module System Set - Dialog for changing important system setup functions including Module ID, Remote I/O preferences, Expansion I/O
settings, and Retentive memory preferences (Keeping) for (C) Counters, (M) Auxiliary Coils, and (Z) keypad input set and the LCD Backlight.
Link Com Port - Select the port communication with LRD relay.
21
LRX D01
ONLINE MONITORING/EDITING
The LRXSW software allows for online monitoring of the currently running program during runtime. Additional online functions include, I/O
forcing, and Mode changes (Run/Stop/Quit).
I185 GB 06 10
– The LRXSW software does not support runtime logic editing changes. All logic edits to contacts, coils, Timers/Counters, and circuit
connecting lines must be written to the connected LRD relay while in Stop mode.
HMI/TEXT
This function block can display information on 16_4 LCD screen. Information displaying can be present value or target value of Counter, Timer,
RTC and Analog comparator etc. Under running mode, to modify the target value of timer, counter and analog comparator via HMI is available.
HMI can display the status of input terminal (I, Z, X) and Auxiliary terminal M, N (only FBD).
22
LRX D01
HMI/TEXT setting:
I185 GB 06 10
The user can modify T01 preset value when H coil enable and display on LCD.
Download to LRD, and I01 turn ON, or press “SEL” if the H coil is set to mode 1, then the LRD LCD will display the first H text as shown below.
23
LRX D01
HMI/TEXT Example:
I185 GB 06 10
Power ON and RUN (initial display) Press “” (Z01) and display H03 coil
24
LRX D01
Press “” to disable H03 coil, and the LCD display changes to initial frame.
Press “” to reset Timer (T01°¢T02°¢T03) as program designed.
I185 GB 06 10
PROGRAM DOCUMENTATION
The LRD Client software includes the ability to document a program using Symbols and Line Comments. Symbols are used to label each I/O
address up to a length of 12 characters. Line Comments are used to document sections of a program. Each Line Comment can have up to 4
lines with each line containing up to 50 characters in length. Below are examples of entering Symbols and Line Comments.
SYMBOL...
The Symbol editing environment can be access through the menu using the Edit>>symbol… selection or using the symbol icon on the main
toolbar shown below.
The Symbol editing environment allows for documenting all the contact and coil memory types, and selecting display modes as shown below.
LINE COMMENTS
The Line Comment editor is accessed by clicking the “N” icon on the Ladder Toolbar. After clicking on the “N” icon, to drag the line
number you want to comment and release, and then type the desired comments and press OK.
25
LRX D01
AQ SET…
The AQ editing environment can be access through the menu using the Edit>> AQ Set… selection shown below. The range of AQ is 0~1000 if
the output mode of AQ is voltage mode. And the range is 0~500 if the output mode is current mode. The preset value of AQ can be set as either
a constant or a code of other data. The output mode of AQ and preset value are set as below. More information about output mode and
displaying to see: Chapter 4: Relay Ladder Logic Programming
I185 GB 06 10
After the operating above, the Data Register editing environment can be access through the menu using the Edit>> Data Register Set…
selection shown below. The preset value of DR can be set as either a constant or a code of other data type.
26
LRX D01
About to use PM05 and PM05 (3rd) with LRDV2/3, see next figure:
The optional LRXM00 memory is used to easily transfer programs from one LRD relay to another.
The LRXM00 memory plugs into the same connector as the programming cable (see procedure below).
1. Remove the plastic connector cover from LRD using a flathead screwdriver as shown in the figure below left.
2. Insert the LRXM00 memory onto the connector as shown below right.
3. From the display keypad on the face of the LRD relay, select either WRITE or READ to transfer the program to LRXM00 or from the LRXM00
memory to the LRD relay.
4. Program in different types are not compatible, here are the regulations:
A-1: 10/12 point type program —— available in 20 point type
A-2: 20 point type program —— unavailable in 10/12 point type
B-1: AC type program —— available in DC type
B-2: DC type program —— unavailable in AC type
C-1: Relay type program —— available in Transistor type
C-2: Transistor type program —— unavailable in Relay type
D-1: LRD V2.0 program —— available LRD V3.0 type
D-2: LRD V3.0 program —— unavailable LRD V2.0 type
27
LRX D01
KEYPAD
Most LRD CPU units include the built-in LCD Display and Keypad. The keypad and display are most often used for changing timer/counter set
points, controller mode changes (Run/Stop), uploading/downloading to the PM05 memory cartridge, and updating the RTC (Real Time
Clock/Calendar). Although, logic programming can be performed from the keypad and display, it is highly recommended to only perform logic
changes using the LRDSW software. Below is an overview of the basic keypad and display functions.
I185 GB 06 10
Select (SEL) - Used to select the available memory and instruction types for editing. Holding the Select button will display all “H” HMI/Text
messages on the LCD.
OK - Used to accept the selection displayed of an instruction or function. It is also used to select any of the Main Menu options on the LCD.
Note: Press the “SEL” and “OK” simultaneously to insert a rung above the current active cursor position.
Escape - Used to exit a selected display screen and go to the previous screen. When in a ladder display screen, press the ESC to display the
main menu.
Delete - Used to delete an instruction or rung from the ladder program.
The 4 navigation buttons () are used to move the cursor throughout the functions of the LRD display or active program. The 4 buttons
also can be set programmable input coils Z01-Z04 (‘’= Z01, ‘’=Z02, ‘’=Z03, ‘’ =Z04).
ORIGINAL SCREEN
LCD displays 4-line state
– Original screen as power on
28
LRX D01
WRITE
RTC SET
PASSWORD
> LANGUAGE
29
LRX D01
– LRD can be modified, edited, cleared and read user program only when it is under STOP Mode.
– As the program is modified, LRD will automatically backup it to FLASH.
30
LRX D01
– PARAMETER
Under Ladder mode, press “SEL” key, function block display in sequence:
TCRGASMDPIMXARMUT...
I185 GB 06 10
– RUN or STOP
– DATA REGISTER
Displaying preset value when the LRD is STOP status and displaying current value when the LRD is RUN status.
(1) CLEAR PROGRAM (Clear RAM, EEPROM and Password at the same time)
(2) WRITE: save the program (RAM) to PM05 (3rd) program spare cartridge
(3) READ: read the program from the PM05 or PM05 (3rd) program spare cartridge to LRD (RAM)
31
LRX D01
– M KEEP function is available for keeping M status and current value of T0E/T0F when power is re-supplied after loss.
Now press
Move the cursor
SEL Begin to edit.
‘ SEL’ quindi ‘/‘ Move the cursor for 'ID SET' item and 'V COMM SET' item
‘SEL’ quindi ‘/‘ 1. ID SET = 00~99 ; I/O NUMBER = 0~3
2. REMOTE I/O = NMSN
3. BACK LIGHT ; C KEEP ; Z SET = x3
4. M KEEP; I/O ALARM = 3x
5. V COMM SET = (0~3)(0~5)
6. DATA REG. = US
OK Confirm the Edition Data
ESC 1. Cancel the setting when pressed 'SEL'
2. Back to Main Menu(save edit data)
– When REMOTE I/O is selected, the distribution of the remote I/O is as follows:
Master Slave
Remote Input X01~X0C I01~I0C
Remote Output Y01~Y08 Q01~Q08
– The high bit of V COMM SET detects the form of RS-485, and the low bit detects the baud rate of RS-485.
More detailed to see chapter 4: Relay Logic Programming: Data Link/Remote IO Instruction
Now press
Enter RTC setting or Summer/Winter setting
SEL Begin to input parameters
‘SEL’ then ‘/‘ Move the Cursor
‘SEL’ then ‘/‘ 1. year=00~99, month=01~12, day=01~31
2. week: MOTUWETHFRSASU‘MO
3. hour = 00~23 , minutes = 00~59
‘SEL’ then ‘SEL’ Summer/Winter setting: NO - EUROPE - USA - OTHER - NO …
OK Save the Input Data
ESC 1. Cancel the Input Data when press 'SEL'.
2. Back to Main Menu.
– RTC precision
Temperature Error
+25° ±3 s/day
-20°C/+50°C ±6 s/day
32
LRX D01
1) PC Client
I185 GB 06 10
2) Keypad
Then pressing “” selects edit location, pressing “”, “” edit content.
Example:
Year 2009, SUM M: 05 D: 01 32009-5-3; M: 10 D: 00 2009-10-25.
6. ANALOG SET
Now press
1. Move the Cursor downward
2. Switch the setting screen from A01/A02í A03/A04í A50/A06 í A07/A08
SEL Begin to input parameters
‘SEL’ then ‘/‘ Move the Cursor
‘SEL’ then ‘/‘ 1. GAIN =000 ~ 999
2. OFFSET=(-50 ~ +50)
OK Save the Input Data
ESC 1. Cancel the Input Data when press 'SEL'.
2. Back to Main Menu (save edit data).
33
LRX D01
Now press
I185 GB 06 10
ITALIANO
DEUTSCH German
PORTOGUES Portuguese
Now press
Vertically move the Cursor
OK Select the language the cursor located
ESC Back to Main Menu
INITIAL
> LADDER 3
FBD
Now press
Vertically move the Cursor
OK Select the mode the cursor located
ESC Back to Main Menu
34
LRX D01
➣
➣
Symbol [ P (NO/NC)
35
LRX D01
– The state of auxiliary relays “M01~M3F” will be kept when the LRD powers down if “M Keep” is active. “M Keep” can be set by the two ways
below.
I185 GB 06 10
36
LRX D01
➣
➣
Symbol [ P (NO/NC)
Lo Hi Used in function
block
Expansion input coil X x 12 (X01-X0C / x01-x0C)
Expansion output coil Y Y Y Y Y y 12 (Y01-Y0C / y01-y0C)
Differential (one shot) D d
RTC R R r 31 (R01-R1F / r01-r1F)
Analog comparator G G g 31 (G01-G1F / g01-g1F)
HMI H 31 (H01-H1F)
PWM P 2 (P01-P02)
DATA LINK L 8 (L01-L08)
SHIFT S 1 (S01)
37
LRX D01
OUTPUT INSTRUCTIONS
➣
SET OUTPUT INSTRUCTION (LATCH) ( )
A set output instruction, or Latch, turns ON an output coil (Q) or an auxiliary contact (M) when the preceding input contact transitions from OFF
to ON. Once the output is ON or set, it will remain ON until it is reset using the Reset output instruction. It is not necessary for the preceding
input contact controlling the Set output instruction to remain ON.
I185 GB 06 10
➣
RESET OUTPUT INSTRUCTION (UNLATCH) ( )
A reset output instruction, or Unlatch, turns OFF a previous set output coil (Q) or an auxiliary contact (M) when the preceding input contact
transitions from OFF to ON. Once the output is OFF or reset, it will remain OFF until it if reset using another output instruction. It is not
necessary for the preceding input contact controlling the Reset output instruction to remain ON.
Analog value (A01~A08, V01~V08, AT01~AT04, AQ01~AQ04) and current value of functions (T01~T1F, C01~C1F, AS01~AS1F, MD01~MD1F,
PI01~PI0F, MX01~MX0F, AR01~AR0F, and DR01~DRF0) can be used as other function's preset value. And the parameter preset value is its limit
value when the current value of those functions is bigger or less than parameter limit value.
38
LRX D01
TIMER INSTRUCTION
The LRD includes a total of 31 separate Timers that can be used throughout a program. T0E and T0F keep their current value after a loss of
power to the LRD relay if “M Keep” is active, but the other Timers' current value is non-retentive. Each Timer has a choice of 8 operation modes,
1 for a pulse Timer and 7 for general purpose Timer. Additionally, each Timer has 6 parameters for proper configuration. The table below
describes each configuration parameter and lists each compatible memory type for configuring Timers.
1 Symbol Description
2 1 Timer Mode (0-7)
I185 GB 06 10
– The preset value of Timer could be a constant or other function current value.
– The current value of T0E and T0F will be kept when LRD on a loss of power if the “M-Keep” is active.
39
LRX D01
1
2
4
I185 GB 06 10
6
5
3
– T0E and T0F keep their current value after a loss of power to the LRD relay if “M Keep” is active, but the others' reset to 0.
40
LRX D01
1
2
4
I185 GB 06 10
6
5
3
– T0E and T0F keep their current value after a loss of power to the LRD relay if “M Keep” is active, but the others' reset to 0.
41
LRX D01
1
2
4
I185 GB 06 10
6
5
3
– T0E and T0F keep their current value after a loss of power to the LRD relay if “M Keep” is active, but the others' reset to 0.
42
LRX D01
1
2
4
I185 GB 06 10
6
5
3
– T0E and T0F keep their current value after a loss of power to the LRD relay if “M Keep” is active, but the others' reset to 0.
43
LRX D01
1
2
4
I185 GB 06 10
6
5
3
44
LRX D01
1
2
4
I185 GB 06 10
6
5
3
45
LRX D01
1
I185 GB 06 10
2
4
6
5
3
46
LRX D01
COUNTER INSTRUCTIONS
The LRD includes a total 31 separate counters that can be used throughout a program. Each counter has a choice of 9 operation modes, 1 for
pulse counter, 6 for general purpose counting and 2 for high speed counting. Additionally, each counter has 6 parameters for proper
configuration. The tables below describe each configuration parameter and lists each compatible memory type for configuring counters.
COMMON COUNTER
1 Symbol Description
2 1 Counting Mode (0-6)
I185 GB 06 10
– The preset value of Counter could be a constant or other function current value.
The figure below shows the relationship among the numbered block diagram for a Counter, the ladder diagram view, and the software Edit
Contact/Coil dialog box.
1
2
4
6
5
3
47
LRX D01
6
I185 GB 06 10
48
LRX D01
1
2
4
I185 GB 06 10
6
5
3
Mode = 1
Set value 20
Current value 0 0 0 1 1 2 2 1 1 0 19 19 20 20 20 0 20 20 20
Input pulse
– Under this mode, the counter current value will be init value when the LRD is power up or switching between RUN and STOP. The init value is
0 if the counter is configured as counting up or else the preset value.
49
LRX D01
1
2
4
I185 GB 06 10
6
5
3
Mode = 2
Set value 20
Current value 0 19 19 20 20 21 21 20 20 19 19 18 18 0 0 19 19 20 0 20
Input pulse
– Under this mode, Counter will continue counting after reaching preset value if it's configured as counter up. But it stops counting when its
current value is 0 if it is configured as counter down.
– The counter current value will be init value when the LRD status switches between RUN and STOP or the LRD is power up. If the counter is
configured as counting up, the init value is 0 or else, it is the preset value.
50
LRX D01
1
2
I185 GB 06 10
4
6
5
3
1
2
4
6
5
3
51
LRX D01
1
I185 GB 06 10
2
4
6
5
3
Mode = 5
Set value 20
Current value 0 19 19 20 20 21 21 20 20 19 19 18 18 19 19 20 0 0 0 0
Input pulse
– Under this mode, the count will continue after reaching its preset value;
– The current value is always 0 regardless of the state of its direction bit when the reset is availability;
– The current value is always 0 regardless of the state of its direction bit when the LRD switches between RUN and STOP.
52
LRX D01
1
2
I185 GB 06 10
5
3
6
Mode = 6
Set value 20
Current value
Mode 1&2&5 0 1 1 2 2 3 0 1 1 2 2 3
Current value
Mode 3&4&6 0 1 1 2 2 3 3 4 4 5 5 6
Input pulse
Reset input
Counter coil
53
LRX D01
1 Symbol Description
2 1 Counting Mode (7) high speed counting
2 High speed counting input terminal: I01 or I02 only
4
3 Use (I01~g1F) to Reset the counting value
ON: the counter reset to 0
5 OFF: the counter continues to count
3 4 Current Count Value, range: 0~999999
6
5 Preset Value, range: 0~999999
6 Counter Coil Number (C01~C1F total: 31 counters)
Mode = 7
Set value 20
54
LRX D01
I185 GB 06 10
Symbol Description
1 Counting Mode (8) high speed counting
2 High speed counting input terminal: I01 or I02 only
3 Counting interval time: 0~99.99 sec
4 Counter 'on' preset Value, range: 0~999999
5 Counter 'off' preset Value, range: 0~999999
6 Counter Coil Number (C01~C1F total: 31 counters)
1
2
4
5
3
6
Mode = 8
Current value = 5 3 5 4 3 4
Reset input = 3
Input pulse
55
LRX D01
Symbol Description
1 Input the first week to RTC
2 Input the second week to RTC
3 RTC mode 0~2, 0: internal coil 1:daily, 2:consecutive days
4 RTC displays the hour of present time.
I185 GB 06 10
8 9
10
ON
ON
56
LRX D01
1 2
3
I185 GB 06 10
4 5
10
6 7
8 9
ENABLE
Rn Output
Example 2
➂ 1
➀:➁ TU-FR
➅:➆ 17:00
➇:➈ 8:00
ENABLE
Rn Output
Example 3:
➂ 1
➀:➁ FR-TU
➅:➆ 8:00
➇:➈ 17:00
ENABLE
Rn Output
57
LRX D01
Example 4:
➂ 1
➀:➁ FR-MO
➅:➆ 17:00
➇:➈ 8:00
Time 8:00 17:00 8:00 17:00 8:00 17:00 8:00 17:00 8:00 17:00
ENABLE
Rn Output
Example 5:
➂ 1
➀:➁ SU-SU
➅:➆ 08:00
➇:➈ 17:00
ENABLE
Rn Output
Example 6:
➂ 1
➀:➁ SU-SU
➅:➆ 17:00
➇:➈ 8:00
ENABLE
Rn Output
58
LRX D01
1 2
3
4 5
I185 GB 06 10
10
6 7
8 9
ENABLE
Rn Output
Example 2
➂ 2
➀:➁ SA-TU
➅:➆ 17:00
➇:➈ 08:00
Enable
Rn Output
Example 3
➂ 2
➀:➁ WE-WE
➅:➆ 17:00
➇:➈ 08:00
ENABLE
Rn Output
59
LRX D01
Example 4
➂ 2
➀:➁ WE-WE
➅:➆ 08:00
➇:➈ 17:00
ENABLE
Rn Output
Symbol Description
1 RTC Year ON
1 2
2 RTC Year OFF
3 3 RTC Mode 3, Year-Month-Day
4
4 Display RTC present time, Year-Month-Day
9 5 RTC month ON
5 6 6 RTC day ON
7 RTC month OFF
7 8 8 RTC day OFF
9 RTC code (R01~R1F, total 31 group)
1 2
3
4
9
5 6
7 8
ENABLE
ON
RTC Output OFF OFF
60
LRX D01
Example 2:
➂ 3
➀/➄/➅ 2010/11/11
➁/➆/➇ 2009/02/17
ENABLE
RTC Output
Example 3:
➂ 3
➀/➄/➅ 2010/11/11
➁/➆/➇ 2010/11/11
Year-Month-Day 2010/11/11
Time 0:00
ENABLE
RTC Output
Symbol Description
1 RTC adjustment week
1
2 RTC mode 4
2 3 RTC present hour
3 4
4 RTC present minute
8 5 RTC adjustment hour
5 6 6 RTC adjustment minute
7 RTC adjustment second
7 8 RTC code (R01~R1F, total 31 group)
61
LRX D01
1
2
3 4
8
5 6
I185 GB 06 10
Week SA
Time 8:00 8:00:20
ENABLE
ON
RTC Output OFF OFF
The present time will be 8:00:00 when it achieves 8:00:20 at first time, and RTC status bit R01 will be ON. RTC status bit R01 will be OFF when
the present time achieves 8:00:20 at second time. Then time continuous going. So, this means that RTC status bit is ON for 21 seconds.
1
2
3 4
8
5 6
Week SA
Time 8:00 8:00:40
ENABLE
Rn Output
The present time will change to be 8:01:00 when it achieves 8:00:40, and RTC status bit R01 turns ON. Then time is onging on and R01 turns
OFF. This means that the RTC status bit will be ON for one pulse.
62
LRX D01
COMPARATOR INSTRUCTIONS
The LRD relay includes a total of 31 separate comparator instructions that can be used throughout a program. Each comparator has a choice of
8 operation modes. Additionally, each comparator has 5 parameters for proper configuration. The table below describes each configuration
parameter, and lists each compatible memory type for configuring Comparators.
Symbol Description
1
1 Comparison Mode (0~7)
2 Ax analog input value (0.00~99.99)
2
3 Ay analog input value (0.00~99.99)
I185 GB 06 10
The preset value ➁, ➂ and ➃ can be a constant or other function current value.
ON
ON
63
LRX D01
In the example below, Mode 4 is the selected function that compares the value of analog input A01 to a constant value (N) of 2.50. Status coil
G01 turns ON when A01 is not less than constant 2.50.
2
5
3
64
LRX D01
The Comparator instruction can be used to compare Timer, Counter, or other function values to a constant value or each other. In this example
below, Mode 5 is the selected function that compares the value of Counter (C01) with the value of Timer (T01). Status coil G01 turns ON if
present value of C01 is not less than present value of T01.
2
I185 GB 06 10
5
3
A phone number can be displayed on the screen to alert an operator to call for help. But the phone number field does not dial a modem or allow
for a modem connection.
Each HMI instruction has a choice of 2 operation modes. The table below describes each configuration parameter.
Symbol Description
1 Display mode (1-2)
2 HMI character output terminal (H01~H1F)
65
LRX D01
2
I185 GB 06 10
The Chinese (fixed) and Chinese (edit) are shown below. The total number of Chinese (edit) is 60.
66
LRX D01
HMI STATUS
1. HMI scanning state, press SEL into at IO interface
I185 GB 06 10
3. HMI edit preparing state, press SEL when HMI is scanning or running state, flicker cursor will show if there is edited content.
KEYPAD INSTRUCTION
Mode Output
P01 PWM, PLSY Q01
P02 PWM Q02
67
LRX D01
PWM MODE
P01 and P02 both can work under this mode. Each PWM has 8 group preset stages which contents Width and Period. The 8 group preset
values can be constant or other function current value. Each PWM has 10 parameters for proper configuration. The table below describes each
configuration parameter, and lists each compatible memory type for configuring PWM.
Example:
1 2
3 9
6
4 10
7
5
8
The state of M01, M02 and M03 are 010, so PWM output pulse is like this as setting above:
EN
t=5s
Output
T=10s
The state of M01, M02 and M03 decide PWM output. PWM stages can be changed by the status of M01, M02 and M03 when P01 is running. _
displays the number of pulse when P01 is running, but _ equals 0 when P01 is disabled.
PLSY MODE
Only P01 can work under this mode, and the output is Q01. PLSY has 6 parameters for proper configuration. The table below describes the
information of PLSY parameters.
Symbol Description
1 PLSY mode (2)
2 Total number of pulse (storing in DRC9)
3 Preset frequency of PLSY (1~1000Hz)
4 Preset pulse number of PLSY(0~32767)
5 Output port (Q01)
6 PWM code (P01)
68
LRX D01
The preset frequency and pulse number could be constant or other function current value. They are variable if the preset are other data code.
The PLSY will stop output if it has outputted the number of ➃. pulse. PLSY will run again if it is enabled for a second time.
Example:
Parameter setting: ➂ = 500Hz ➃ = 5, output as shown below:
EN
1ms
I185 GB 06 10
Output
2ms
In the example below, the frequency is other data code (C01). So the wave's frequency will change following the current value of C01.
2 5
3 10
– In the example above, frequency is 1000 if the current value of C01 is bigger than 1000.
– PLSY stops outputting pulse after it has output 100 pulses.
– PLSY will be going on as long as it is enabled if ➃ is 0.
69
LRX D01
Symbol Description
1 Preset number of output pulse (1~8)
1 2 SHIFT input coil (I01~g1F)
3 SHIFT output coils (Q, Y, M, N)
4
I185 GB 06 10
3 4
Enable
I01
Q03
Q04
Q05
Q06
Q07
Q03 is ON, and from Q04 TO Q07 are OFF when ENABLE is active. Q04 turns ON when I01's rising edge coming on, and others points turn OFF.
The next coil turns ON at each rising edge of SHIFT input, and others turn OFF.
70
LRX D01
AQ (ANALOG OUTPUT)
The default output mode of AQ is 0-10V voltage, the corresponding value of AQ is 0~1000. It also can be set as 0-20mA current, the
corresponding value of AQ is 0~500. The output mode of AQ is set by the current value of DRD0~DRD3 as shown below.
It will be considered as 0 if the value of DR is not in the range of 0~3. That means the output mode of AQ is mode 1. AQ displays preset value
(constant of code of other data) under STOP mode, displays current value under RUN mode. AQ preset value can be a constant or other function
current value.
AQ DISPLAY
AQ displays the preset value under STOP mode, and displays the current value under RUN mode.
A Q 0 1 = 0 1 . 2 3 V
A Q 0 2 = 0 8 . 9 2 m A 0 ~ 10VDC voltage mode (AQ value: 0_1000), depending on DRD0
A Q 0 3 = A 0 1 V 0 ~ 20mA current mode (AQ value: 0_500), depending on DRD1
A Q 0 4 = D R 3 F m A
The value will be considered if in over-flow when writing AQ preset value or current value through PC communication. So, output mode
information should have been written before preset value.
AQ current value is different from display value, and current value is used in operation and storage. AQ display is shown below.
71
LRX D01
AS (ADD-SUBTRACT)
The LRD relay includes a total of 31AS instructions that can be used throughout a program. The ADD-SUB Addition and/or Subtraction function
enables simple operations to be carried out on integers. There are 6 parameters for proper configuration. The table below describes each
configuration parameter, and lists each compatible memory type for configuring AS.
1 Symbol Description
1 AS current value ( -32768~32767)
2 5 2 V1 parameter ( -32768~32767)
I185 GB 06 10
3 V2 parameter ( -32768~32767)
3 6 4 V3 parameter ( -32768~32767)
5 Error output coil (M, N, NOP)
4 6 AS code (AS01~AS1F)
Compute formula: AS = V1 + V2 – V3
AS current value is the result of compute. Parameters V1, V2, and V3 can be a constant or other function current value. The output coil will be
set to 1 when the result is overflow. And the current value is no meaning at this time. But it will do nothing if the output coil is NOP. The output
coil will turns OFF when the result is right or the function is disabled.
2 5
3 6
Error output coil N01 will turn ON when the compute result is overflow.
72
LRX D01
MD (MUL-DIV)
The LRD relay includes a total of 31MD instructions that can be used throughout a program. The MUL-DIV Multiplication and Division function
enables simple operations to be carried out on integers. There are 6 parameters for proper configuration. The table below describes each
configuration parameter, and lists each compatible memory type for configuring MD.
1 Symbol Description
1 MD current value ( -32768~32767)
2 5 2 V1 parameter ( -32768~32767)
I185 GB 06 10
3 V2 parameter ( -32768~32767)
3 6 4 V3 parameter ( -32768~32767)
5 Error output coil (M, N, NOP)
4 6 MD code (MD01~MD1F)
Compute formula: MD = V1 * V2 / V3
MD current value is the result of compute. Parameters V1, V2, and V3 can be a constant or other function current value. The output coil will be
set to 1 when the result is overflow. And the current value is no meaning at this time. But it will do nothing if the output coil is NOP. The output
coil will turns OFF when the result is right or the function is disabled.
2 5
3 6
Error output coil M01 will turn ON when the compute result is overflow.
1 Symbol Description
1 PI: PID current value (-32768~32767)
2 8 5 8 2 SV: target value (-32768~32767)
3 PV: measure value (-32768~32767)
3 9 6 9 4 TS: sampling time (1~32767 * 0.01s)
5 KP: Proportion (1~32767 %)
4 7 6 TI: Integral time (1~32767 * 0.1s)
7 TD: Differential time (1~32767 * 0.01s)
8 Error output coil (M, N, NOP)
9 PID code (PI01~PI0F)
The parameters ➀ and ➁ can be constant or other function current value. The error coil will turn ON when either TS or KP is 0. But it will do
nothing if the output coil is NOP. The output coil will turns OFF when the result is right or the function is disabled.
PID computes formula:
EVn = SV PVn
Ts
PI = K P (EVn EVn )+ EVn + Dn
TI
1
TD
Dn = (2 PVn PVn PVn )
TS
1 2
PI = - PI
73
LRX D01
2 8 5 8
3 9 6 9
I185 GB 06 10
4 7
MX (MULTIPLEXER)
The LRD relay includes a total of 15 MX instructions that can be used throughout a program. This special function transmits 0 or one of 4 preset
values to MX current value memory. The MX function enables simple operations to be carried out on integers. There are 7 parameters for proper
configuration. The table below describes each configuration parameter, and lists each compatible memory type for configuring MX.
1 Symbol Description
1 V1 parameter ( -32768~32767)
5
2 2 V2 parameter ( -32768~32767)
3 V3 parameter ( -32768~32767)
7
3 4 V4 parameter ( -32768~32767)
5 Selection bit 1: S1
6 4 6 Selection bit 2: S2
7 MX code (MX01~MX0F)
The parameters from ➀ to ➃ can be constant or other function current value. The table below describes the relationship between parameter and
MX current value.
disable MX = 0;
enable S1=0,S2=0: MX = V1;
S1=0,S2=1: MX = V2;
S1=1,S2=0: MX = V3;
S1=1,S2=1: MX = V4;
1
5
2
7
3
6 4
74
LRX D01
AR (ANALOG-RAMP)
The LRD includes a total of 15 AR instructions that can be used throughout a program. The AR function enables simple operations to be carried
out on integers. Analog Ramp instruction allows AR current level to be changed by step from starting level to target level at a specified rate.
There are 12 parameters for proper configuration. The table below describes each configuration parameter, and lists each compatible memory
type for configuring AR.
Symbol Description
1 5
1 AR current value: 0~32767
9 11 9 11 2 Level 1:-10000~20000
2 6
3 Level 2:-10000~20000
I185 GB 06 10
The parameters from ➁ to ➇ can be constant or other function current value. The table below describes detailed information of each parameter
of AR.
The output coil can be M, N or NOP. The output coil is set when errors happen, but it will do nothing if the output coil is NOP. And the current
value is no meaning at this time.
AR will keep the current level at “StSp + Offset "B"” for 100ms when it is enabled. Then the current level runs from StSp + Offset "B" to target
level at enactment Rate. If St is set, the current level decreases from current level to level StSp + B at enactment Rate. Then AR holds the level
StSp + Offset "B" for 100ms. After 100ms, AR current level is set to offset "B", which makes AR current value equal 0.
75
LRX D01
1 5
9 11 9 11
2 6
3 7
10 4 12 10 8 12
I185 GB 06 10
DR (DATA REGISTER)
The LRD includes a total of 240 DR instructions that can be used throughout a program. The DR function is transferring data. DR is a temp
register. DR sends data from prevention registers to current register when it is enabled. The data can be signed or unsigned by setting DR_SET
bit through operation>>module system set menu selection from the LRDSW. There are 2 parameters for proper configuration. The table below
describes each configuration parameter, and lists each compatible memory type for configuring DR.
Symbol Description
1 Preset value: DR_SET = 0, 0~65535
DR_SET = 1,-32768~32767
2 DR code (DR01~DRF0)
1 2
76
LRX D01
1 2
I185 GB 06 10
The data registers from DR65 to DRF0 will be kept when the LRD powers down. The last 40 DR that from DRC9 to DRF0 are special data
register as shown below. The content of DRC9 is PLSY total number of pulse, and DRD0~DRD3 are output mode registers of AQ01~AQ04, and
DRCA~ DRCF, DRD4~ DRF0 are reserved.
77
LRX D01
FBD INSTRUCTIONS
FBD program can only be edited and modified in the LRDSW software and write to LRD controlled equipment via communication cable. Via
controlled equipment, FBD program is available for querying or the parameter of the function block of the program for modifying. The preset
value of Block could be a constant or other block code. That means the preset value of this block is other block current value.
Each FBD block size is not restricted, it depends on its function.
HMI
M 0 1 H 0 1
78
LRX D01
PWM MODE
The PWM output terminal Q01 or Q02 can output 8 PWM waveforms.
I185 GB 06 10
M 0 1 PWM01 Mode: 1
N 0 1 SET 1 Out: 1
N 0 2 P 0 1 TP1=00000
N 0 3 TT1=00001
PLSY MODE
The PLSY output terminal Q01 can output preset number of pulse whose frequency is variable from 1 to 1000 Hz.
M 0 1 PWM01 Mode: 2
N o p
N o p P 0 1 PF=00100
N o p PN=00000
79
LRX D01
I/O Link01
Mode:1 Num:8
I01W09
I02W16
Shift01
Type:Q01–Q05
Num:5
Timing diagram
➁ Logic type
➀ Input B 0 0 1 ➂ Logic block number
terminal
N o p A N D
N o p B 0 0 2
N o p
80
LRX D01
block Number(byte)
Total block 260 6000
AND 1 8
AND(EDGE) 1 8
NAND 1 8
NAND(EDGE) 1 8
OR 1 8
I185 GB 06 10
NOR 1 8
XOR 1 6
SR 1 6
NOT 1 4
PLUSE 1 4
BOOLEAN 1 12
FBD LADDER
B 0 0 1
I 0 1 A N D
I01 I02 I03
I 0 2 B 0 0 2 =
I 0 3
FBD LADDER
B 0 0 3
I 0 1 A N D
I01 I02 I03
I 0 2 B 0 0 2 D =
I 0 3
FBD LADDER
i01
B 0 0 1
I 0 1 N A N D i02
I 0 2 B 0 0 2 =
i03
I 0 3
FBD LADDER
i01
B 0 0 1
d
I 0 1 N A N D i02
I 0 2 B 0 0 2 =
i03
I 0 3
81
LRX D01
OR Logic Diagram
FBD LADDER
I01
B 0 0 1
I 0 1 O R I02
I 0 2 B 0 0 2 =
I03
I185 GB 06 10
I 0 3
FBD LADDER
B 0 0 1
I 0 1 N O R
i01 i02 i03
I 0 2 B 0 0 2 =
I 0 3
FBD LADDER
B 0 0 1
I01 i02
I 0 1 X O R
I 0 2 B 0 0 2 i01 I02 =
SR Logic Diagram
FBD LADDER
B 0 0 1
I01 xx
I 0 1 S
I 0 2 R B 0 0 2 I02 xx =
FBD LADDER
B 0 0 1
I 0 1 N O T
i01 xx
Q 0 1 =
Not I01
Note: The input terminal is NOP which is equivalent to ''High'
82
LRX D01
FBD LADDER
P B 0 0 1
I 0 1
I01 xx
Q 0 1 P =
I185 GB 06 10
FBD LADDER
NO
M 0 5 B 0 0 2
I 0 1 B L
I01 xx
I 0 2 1 5 A 8 B 0 0 1 P =
B 0 0 3
Description:
Input 2 I 0 1 B L
Input 4 B 0 0 3
83
LRX D01
FUNCTION BLOCK
Function Block includes three types of function: special function, adjust-controlling function and communication function. Function type and
number are shown in the table below.
AS 250
MD 250
PID 30
adjust-controlling function
MX 250
AR 30
DR 240
The capability of each block is alterable; it depends on the type of function. There are a total of 260 blocks, and the total capability of block area
is 6000 bytes. For example, the block is Timer mode 7, the block size is 12 bytes.
Source table:
Block Number Timer Counter RTC Analog AS MD PID MX AR DR
(byte) comparator
Total source 260 6000 250 250 250 250 250 250 30 250 30 240
Timer mode 0 1 5 1
Timer mode 1~6 1 10 1
Timer mode 7 1 12 2
Counter mode 0 1 5 1
Counter mode 1~7 1 14 1
Counter mode 8 1 16 1
RTC mode 0 1 5 1
RTC mode 1~4 1 11 1
Analog mode 0 1 5 1
Analog mode 1~7 1 12 1
AS 1 11 1
MD 1 11 1
PID 1 17 1
MX 1 17 1
AR 1 23 1
DR 1 6 1
Function display:
Function type
t Q 0 3
Set P a r
Parameter
84
LRX D01
T0E and T0F keep their current value after a loss of power to the LRD relay if “M Keep” is active. But the other Timers current value is 0.
B 0 0 5
Enable Input I 0 4
I185 GB 06 10
Q 0 4
Program display
B 0 0 5 B005 T03
Enable Input I 0 4
t Q 0 4 T = 01.00Sec
Timing Parameter P a r
Program display
B 0 0 5 B005 T03
Enable Input I 0 4
Reset N o p Q 0 4 T = 01.00Sec
Timing Parameter P a r
Program display
85
LRX D01
B 0 0 1 B001 T01
Enable Input I 0 4
Reset N 0 1 M 0 1 T = 01.00Sec
I185 GB 06 10
Timing Parameter P a r t
Program display
B 0 0 1 B001 T01
Enable Input I 0 4
Reset N 0 1 M 0 1 T = 01.00Sec
Timing Parameter P a r t
Program display
B 0 0 1 B001 T01
Enable Input I 0 4
M 0 1 T = 01.00Sec
Timing Parameter P a r
Program display
86
LRX D01
B 0 0 1 B001 T01
Enable Input I 0 1
Reset N o p M 0 1 T = 01.00Sec
I185 GB 06 10
Timing Parameter P a r
Program display
B 0 0 1 B001 T01T02
Enable Input I 0 1
M 0 1 t = 05.00Sec
Program display
M 0 1
Program display
87
LRX D01
Up/Down Counting N 0 1
Reset I 0 2 M 0 1 C = 555555
I185 GB 06 10
Counting Parameter P a r
Program display
Up/Down Counting N 0 1
Reset I 0 2 M 0 1 C = 555555
Note: The “>”means the current value appeared will be greater than present value.
Program display
Up/Down Counting N 0 1
Reset I 0 2 M 0 1 C = 555555
Counting Parameter P a r PD
Note: The “PD” means the current value will be retain until the power recovers; Counter keeps current value when the LRD switches between
RUN and STOP when C KEEP enable
Program display
88
LRX D01
Up/Down Counting N 0 1
Reset I 0 2 M 0 1 C = 555555
I185 GB 06 10
Nota: The “>”means the current value appeared will be greater than present value;
The “PD” means the current value will be retain until the power recovers; Counter keeps current value when the LRD switches between
RUN and STOP when C KEEP enable.
Program display
Up/Down Counting N 0 1
Reset I 0 2 M 0 1 C = 555555
Note: The “>”means the current value appeared will be greater than present value.
Program display
Up/Down Counting N 0 1
Reset I 0 2 M 0 1 C = 555555
Note: The “>”means the current value appeared will be greater than present value;
The “PD” means the current value will be retain until the power recovers; Counter keeps current value when the LRD switches between
RUN and STOP when C KEEP enable.
Program display
Note: Only first 31 Counter functions can keep their current value after a loss of power to the LRD relay.
89
LRX D01
Enable Input N 0 1
Reset M 0
I185 GB 06 10
2 M 0 1 C = 555555
Program display
M 0 1 C = 000050
Program display
B 0 0 1
Enable Input I 0 1
Q 0 1
Program display
90
LRX D01
B 0 0 1 B001 R01
Enable Input I 0 1
Q 0 1 ON MO 08:00
I185 GB 06 10
Program display
B 0 0 1 B001 R01
Enable Input I 0 1
Q 0 1 ON MO 08:00
Program display
B 0 0 1 B001 R01
Enable Input I 0 1
Q 0 1 ON 09.02.17
Program display
91
LRX D01
B 0 0 1 B001 R01
Enable Input I 0 1
Q 0 1 ON
I185 GB 06 10
Program display
Q 0 1
Program display
Program display
92
LRX D01
Reference P a r G = B004 V
Program display
Reference P a r G = B004 V
Program display
Ref Ax = B002 V
Reference P a r G = B003 V
Program display
93
LRX D01
Ref Ax = B002 V
Reference P a r G = B003 V
Program display
Ref Ax = B002 V
Reference P a r G = B003 V
Program display
Ref Ax = B002 V
Reference P a r G = B003 V
Program display
94
LRX D01
B 0 0 1 B001 AS01
A M 0 1 V2 = B003
Reference P
I185 GB 06 10
a r AS V2 = B003
Program display
B 0 0 1 B001 MD01
A M 0 1 V2 = 00001
Reference P a r MD V2 = 00001
Program display
B 0 0 1 B001 PI01
A N 0 1 PV = 00100
Reference P a r MD Ts = 002.00Sec 1
Kp = 00100%
Ti = 0010.0Sec
Td = 001.00Sec 2
95
LRX D01
Reference P a r MX 1
V3 = 04565
V4 = 05846
Reference P a r AR ML = 01000 1
R = 00010
A = 01.00
B = 00000 2
96
LRX D01
INSTALLATION SPECIFICATION
PRODUCT SPECIFICATIONS
Input power Input Output Analog RTC LCD Expans. 1 KHz I/O
point point input keypad High LINK
MODE 100-240 24VDC 24VAC speed
VAC input
LRD10R ■ 6 4 Relay 0 ■ ■ ■
A240
10/12 points
LRD12R ■ 8* 4 Relay 2 ■ ■ ■ ■
D024
LRD12T ■ 8* 4 Transistor 2 ■ ■ ■ ■ ■
D024
LRD12R ■ 8 4 Relay 0 ■ ■ ■
A024
LRD20R ■ 12 8 Relay 0 ■ ■ ■
A240
LRD20R ■ 12* 8 Relay 4 ■ ■ ■ ■
20 points
024
LRD20T ■ 12* 8 Transistor 4 ■ ■ ■ ■ ■
D024
LRD20R ■ 12 8 Relay 0 ■ ■ ■
A024
LRE08R ■ 4 4 Relay 0
A240
LRE08R ■ 4 4 Relay 0
Expansion
D024
LRE08T ■ 4 4 Transistor 0
D024
LRE08R ■ 4 4 Relay 0
A024
97
LRX D01
POWER SPECIFICATIONS
Instantaneous power 10ms (half cycle) / 10ms (half cycle) / 1ms/10 times 1ms/10 times
down time allowable 20 times (IEC/EN 61131-2) 20 times (IEC/EN 61131-2) (IEC/EN 61131-2) (IEC/EN 61131-2)
Fuse Need connect a fuse Need connect a fuse Need connect a fuse Need connect a fuse
or breaker of 1A current or breaker of 1A current or breaker of 1A current or breaker of 1A current
Isolation None None None None
Current average 85..90mA 160..290mA 90..150mA 75..125mA
Power dissipation 7.5W 7W 5W 4.5W
Conductor section 24...14AWG 24...14AWG 24...14AWG 24...14AWG
min...max 0.14...2.5mm2 0.14...2.5mm2 0.14...2.5mm2 0.14...2.5mm2
Weight LRD10: 230g LRD12: 230g 345g 230g
LRD20: 345g LRD20: 345g
Reference standards IEC/EN 61131-2, UL508, CSA C22.2 N° 14-95, CE
INPUT SPECIFICATIONS
LRD...A240 MODEL
Content LRD10RA240 LRD20RA240
Input circuitry
LRD...A024 MODEL
Content LRD12RA024 LRD20RA024
Input circuitry
98
LRX D01
LRD12..D024 MODEL
Content LRD12RD024 - LRD12TD024
Normal digital input High speed input Analog input used as Analog input
normal digital input
Used as Used as
digital analog
LRD12: I7, I8 LRD12: A1, A2
LRD20: I9, IA, IB, IC LRD20: A1, A2, A3, A4
Input circuitry I03~I06 I01,I02 I07,I08
I185 GB 06 10
Number 4 2 2 2
Signal current input 3.2 mA/24 VDC 3.2 mA/24 VDC 0.63 mA/24 VDC < 0.17 mA/10 VDC
ON current input >1.875 mA/15 VDC >1.875 mA/15 VDC >0.161 mA/9.8 VDC ––
OFF current input < 0.625 mA/5 VDC < 0.625 mA/5 VDC < 0.085 mA/5 VDC ––
Wire length ) 100 m ) 100 m ) 100 m ) 30 m (shielded wire)
Response time of input On=>Off On=>Off On=>Off ––
3 ms 0.3 ms Typical: 5 ms ––
Off=>On Off=>On Off=>On ––
5 ms 0.5 ms Typical: 3 ms ––
Input voltage –– –– –– 0~10 VDC
Precision class –– –– –– 0.01 VDC
Bit of conversion –– –– –– 10
Error –– –– –– ±2%±0.12 VDC
Conversion time –– –– –– 1 cycle
Sensor resistance –– –– –– <1 kohm
LRD20..D024 MODEL
Content LRD20RD024 - LRD20TD024
Normal digital input High speed input Analog input used as Analog input
normal digital input
Used as Used as
digital analog
LRD12: I7, I8 LRD12: A1, A2
LRD20: I9, IA, IB, IC LRD20: A1, A2, A3, A4
Input circuitry I03~I08 I01,I02 I09,I0A,I0B,I0C
Number 6 2 4 4
Signal current input 3.1 mA/24 VDC 3.1 mA/24 VDC 0.63 mA/24 VDC < 0.17 mA/10 VDC
ON current input >1.875 mA/15 VDC >1.875 mA/15 VDC >0.163 mA/9.8 VDC ––
OFF current input < 0.625 mA/5 VDC < 0.625 mA/5 VDC < 0.083 mA/5 VDC ––
Wire length ) 100 m ) 100 m ) 100 m ) 30 m (shielded wire)
Response time of input On=>Off On=>Off On=>Off ––
5 ms 0.5 ms Typical: 5 ms ––
Off=>On Off=>On Off=>On ––
3 ms 0.3 ms Typical: 3 ms ––
Input voltage –– –– –– 0~10 VDC
Precision class –– –– –– 0.01 VDC
Bit of conversion –– –– –– 8
Error –– –– –– ±2%±0.12 VDC
Conversion time –– –– –– 1 cycle
Sensor resistance –– –– –– <1 kohm
99
LRX D01
OUTPUT SPECIFICATIONS
Content Relay Transistor
Output circuitry
I185 GB 06 10
LIGHT LOAD
The current value will be 10~20 times of normal value for several 10ms when filament is turning-on. A distributaries resistance or restricted
current resistance is added at output port to reduce the concussion current value.
Restricted
Distributaries resistance
resistance output output
There is a little current makes light shine faintness, so the value of The brightness will be described if the resistance value is too big.
resistance must be careful.
INDUCTANCE LOAD
There will be a concussion voltage (KV) when the inductance load switches between ON and OFF, especially relay model. The methods of
different power mode for absorbing the concussion voltage are shown below.
L load L load
Load Load
power power C
C
100
LRX D01
LIFE OF RELAY
I185 GB 06 10
– The data of picture above is standard, but the life of relay is influenced by the ambient operating temperature.
– The life is more than 100k times if the current is less than 2A.
ACCESSORY
MODE Description
LRXM00 Program backup memory
LRXSW LRD program software
DIMENSIONS LRD
10/12 points
54.6
72 5 44.3
106
90
98
45
68
Ø4.5
20 points
54.6
126 5 44.3
106
90
98
45
68
80 Ø4.5
101
LRX D01
– The method of all expansion modules connecting with LRD is the same as shown above.
I185 GB 06 10
DIGITAL IO MODULE
The LRD must set the number of expansion IO when connected together. The method of setting IO number is shown below.
1) Keypad
2) LRXSW software
102
LRX D01
– All the expansion modules have the same size as shown below.
103
LRX D01
INSTALLATION
– All the expansion modules' installation method is the same as shown below.
I185 GB 06 10
C
Ø3.5
Nm 0.6
(0.14in) C
lbin 5.4
104
LRX D01
WIRING
3) Relay output
4) Transistor output
– AC inductive load needs parallel connect Surge suppressor to dampen noise if the LRD output is relay. DC inductive load needs parallel
connect commute diode if the LRD output is relay. The commute diode inverted voltage should be more than 5~10 times the load voltage,
and the positive current should be more than load current. Inductive load needs parallel connect commute diode if the LRD output is
transistor.
105
LRX D01
Digital IO module and Analog module both have indicator light. The state of indicator light is the same.
The state of indicator light is shown below.
LED constantly on
LRE in Run mode
I185 GB 06 10
COMMUNICATION MODULE
106
LRX D01
COMMUNICATION SETTING
The LREP00 communication baud rate and format can be set by 8-bit switch (DIP) SW1.
Baud rate
SW1-3~SW1-1 set communication baud rate is 57.6K, 38.4K, 19.2K, 9.6K, 4.8K as shown below.
SW1-8 SW1-7 SW1-6 SW1-5 SW1-4 Stop bit, verifying bit, assembled set
* * OFF * OFF 2 stop bits, no verifying bit
* * OFF OFF ON 1 stop bit, 1 odd verifying bit
* * OFF ON ON 1 stop bit, 1 even verifying bit
* * ON * * SW1-1 - SW1-5 are inefficient, communication format is default
as 38.4Kbps, 2 stop bits, no verifying bit
* can be ON or OFF
107
LRX D01
Operation Sample:
1 2 3 4 5 6 7 8 Column
Line 1 > L A D D E R
2 B L O C C O F U N Z
I185 GB 06 10
3 P A R A M E T R I
4 R U N
Step 1: 1 2 3 4 5 6 7 8 Column
Press 'OK'.
Line 1
Enter LADDER edit.
2
Step 2 : 1 2 3 4 5 6 7 8 Column
Step 3 : 1 2 3 4 5 6 7 8 Column
Press '' 3 times.
Line 1 Q 0 1
Press '‘ or ‘' and the digit
where the cursor is located will 2
change from I to G.
3
Step 4 : 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 q 0 1
start /end modifying parameter:
contact stare from NO (Q) to 2
NC (q).
3
Step 5 : 1 2 3 4 5 6 7 8 Column
Press '' 2 times.
Line 1 q 0 1
Step 6 : 1 2 3 4 5 6 7 8 Column
Press '' for 3 times.
Line 1 q 0 4
Press '‘ or ‘';
the digit where the cursor is 2
located will change from 1 to 4.
3
Step 7 : 1 2 3 4 5 6 7 8 Column
Press '' 2 times to move the
Line 1 q 0 4
cursor to 1.
2
108
LRX D01
Automatically Link
Step 7 : 1 2 3 4 5 6 7 8 Column
Press 'OK'; the cursor moves to
Line 1 q 0 4 ––
character in column 3
automatically. 2
4
I185 GB 06 10
Automatically Link
or
Step 7 : 1 2 3 4 5 6 7 8 Column
Press ''; the cursor moves to
Line 1 q 0 4 ––
the link location in column 2
automatically. 2
Step 9 : 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 q 0 4 –– M 0 1 –– 1 0 3 –– ( Q 0 1
When the cursor is located at the
character and digit, press 'SEL' 2
again to show ' ( Q01'.
3
Step 10 : 1 2 3 4 5 6 7 8 Column
Press 'OK' to save the input
Line 1 q 0 4 –– M 0 1 –– 1 0 3 –– ( Q 0 1
program data; the position of the
cursor will not move. 2
Step 11 : 1 2 3 4 5 6 7 8 Column
Press '' 3 times to move the
Line 1 q 0 4 –– M 0 1 –– 1 0 3 –– ( Q 0 1
cursor to column 1 and Line 2.
2
Step 12 : 1 2 3 4 5 6 7 8 Column
Press '' 3 times to move the
Line 1 q 0 4 –– M 0 1 –– 1 0 3 –– ( Q 0 1
cursor to column 2.
Note: Never press 'SEL' before 2
completing all operations.
3
109
LRX D01
Step 13 : 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 q 0 4 M 0 1 –– 1 0 3 –– ( Q 0 1
(A vertical line emerges)
2
4
I185 GB 06 10
Step 14 : 1 2 3 4 5 6 7 8 Column
Press 'OK'. Move the cursor to
Line 1 q 0 4 M 0 1 –– 1 0 3 –– ( Q 0 1
character in column 3.
2
Repeat the step 1~7 and move the cursor to 'r0 3' , ' _' at Line 2 and column 3~6.
Step 15 : 1 2 3 4 5 6 7 8 Column
Press 'OK' and move the cursor
Line 1 q 0 4 M 0 1 –– 1 0 3 –– ( Q 0 1
to the character in Column 8.
2 r 0 3
Step 16 : 1 2 3 4 5 6 7 8 Column
Press 'SEL'.
Line 1 q 0 4 M 0 1 –– 1 0 3 –– ( Q 0 1
When the cursor is located at a
digit or character, press 'SEL' and 2 r 0 3 Q 0 1
'Q01' is viewed.
3
Step 17 : 1 2 3 4 5 6 7 8 Column
Press '' for 5 times.
Line 1 q 0 4 M 0 1 –– 1 0 3 –– ( Q 0 1
Press 'SEL' then '‘ or ‘'
to change character Q to C.) 2 r 0 3 C 0 1
Step 18 : 1 2 3 4 5 6 7 8 Column
Press '' 2 times.
Line 1 q 0 4 M 0 1 –– 1 0 3 –– ( Q 0 1
2 r 0 3 C 0 1
110
LRX D01
Step 19 : 1 2 3 4 5 6 7 8 Column
Press '' for 6 times
Line 1 q 0 4 M 0 1 –– 1 0 3 –– ( Q 0 1
Digit 1 where the cursor is located
will change to 7. 2 r 0 3 C 0 1
4
I185 GB 06 10
Step 20 : 1 2 3 4 5 6 7 8 Column
Press 'OK'
Line 1 1
Automatic shift to FUNCTION
BLOCK to permit setting of the 2 L o w
counter input parameter.
3 0 0 0 0 0 0 C 0 7
4 L o w
Step 21 : 1 2 3 4 5 6 7 8 Column
Press 'ESC' back to
Line 1 q 0 4 M 0 1 –– 1 0 3 –– ( Q 0 1
LADDER edition screen.
2 r 0 3 –– –– –– –– –– ( C 0 7
1 2 3 4 5 6 7 8 Column
Line 1 q 0 4 M 0 1 –– 1 0 3 –– ( Q 0 1
2 r 0 3 –– –– –– –– –– ( C 0 7
Display the present Line the cursor locating and operation state of LRD
Step 23: 1 2 3 4 5 6 7 8 Column
Press 'SEL’ and ‘ESC'
Line 1 q 0 4 M 0 1 –– 1 0 3 –– ( Q 0 1
(simultaneously).
Line 4 displays where the cursor 2 r 0 3 –– –– –– –– –– ( C 0 7
is located and LRD operation
state. 3
4 S T O P L I N E 0 0 2
1 2 3 4 5 6 7 8 Column
Line 1 q 0 4 M 0 1 –– 1 0 3 –– ( Q 0 1
2 r 0 3 –– –– –– –– –– ( C 0 7
111
LRX D01
3 C L E A R L n 0 0 2
4 E S C ? O K ?
I185 GB 06 10
1 2 3 4 5 6 7 8 Column
Line 1 q 0 4 M 0 1 –– 1 0 3 –– ( Q 0 1
2 r 0 3 –– –– –– –– –– ( C 0 7
1 2 3 4 5 6 7 8 Column
Line 1 q 0 4 M 0 1 –– 1 0 3 –– ( Q 0 1
2 r 0 3 –– –– –– –– –– ( C 0 7
112
LRX D01
1 2 3 4 5 6 7 8 Column
Line 1 L A D D E R
2 > B L O C C O F U N Z
3 P A R A M E T R I
4 R U N
I185 GB 06 10
Step 1: 1 2 3 4 5 6 7 8 Column
Press 'OK'
Line 1 1
2 1
(Enter FUNCTION BLOCK edition)
3 0 0 . 0 0 S e c T 0 1
3 0 0 . 0 0 S e c T 0 1
3 0 0 . 0 0 S e c T 0 1
3 0 0 . 0 3 S e c T 0 1
3 0 0 . 0 3 S e c T 0 1
113
LRX D01
2 1
3 0 0 . 0 3 S e c T 0 1
4
I185 GB 06 10
Repeat Step 2-2 ~ step 2-4 for 3 times, to enter the following screen:
Step 2-6: 1 2 3 4 5 6 7 8 Column
Line 1 1
2 1
3 3 3 . 3 3 S e c T 0 1
As the present value of the timer, counter, analog input (A01-A08) and analog gain value (V01-V08) is set as the preset value of them. Next to
the Step 2-2, to execute the following operation:
Step 2-3A: 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 1
2 1
3 V 0 1 S e c T 0 1
Repeat the step 2-3A, the following screen will be shown in turn:
2 1
3 A 0 1 S e c T 0 1
2 1
3 T 0 1 S e c T 0 1
2 1
3 C 0 1 S e c T 0 1
2 1
3 A T 0 1 S e c T 0 1
2 1
3 A Q 0 1 S e c T 0 1
114
LRX D01
2 1
3 D R 0 1 S e c T 0 1
4
I185 GB 06 10
2 1
3 A S 0 1 S e c T 0 1
2 1
3 M D 0 1 S e c T 0 1
2 1
3 P I 0 1 S e c T 0 1
2 1
3 M X 0 1 S e c T 0 1
2 1
3 A R 0 1 S e c T 0 1
2 1
3 A 0 2 S e c T 0 1
Repeat Step 2-4B (key '' is also active), to change parameters and/or values of A01-A08, C01-C1F, T01-T1F and V01-V08.
After having made all the modifications, proceed with:
Step 2-5B: 1 2 3 4 5 6 7 8 Column
press 'OK'
Line 1 1
Save the present data.
2 1
3 A 0 2 S e c T 0 1
115
LRX D01
2 1
3 3 3 . 3 3 S e c T 0 1
4
I185 GB 06 10
3 3 3 . 3 3 S e c T 0 1
3 3 3 . 3 3 S e c T 0 1
3 3 3 . 3 3 S e c T 0 1
3 3 3 . 3 3 S e c T 0 1
3 3 3 . 3 3 S e c T 0 1
3 3 3 . 3 3 S e c T 0 1
4 L o w
3 3 3 . 3 3 S e c T 0 1
4 L o w
116
LRX D01
3 3 3 . 3 3 S e c T 0 1
4 L o w
I185 GB 06 10
3 3 3 . 3 3 S e c T 0 1
4 L o w
3 3 3 . 3 3 S e c T 0 1
4 I 0 1
Repeat the step 2-16A, the following screen will be shown in turn:
Step 2-16B: 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 4
2 2
3 3 3 . 3 3 S e c T 0 1
4 i 0 1
2 2
3 3 3 . 3 3 S e c T 0 1
4 L o w
Next to step 2-16A, then '', the following screen will be shown.
Step 2-17: 1 2 3 4 5 6 7 8 Column
Press '' for 5 times to change
Line 1 4
I to M.
2 2
3 3 3 . 3 3 S e c T 0 1
4 M 0 1
3 3 3 . 3 3 S e c T 0 1
4 M 0 1
117
LRX D01
3 3 3 . 3 3 S e c T 0 1
4 M 0 4
I185 GB 06 10
2 2
3 3 3 . 3 3 S e c T 0 1
4 M 0 4
3 3 3 . 3 3 S e c T 0 1
4 M 0 4
3 3 3 . 3 3 S e c T 0 1
4 M 0 4
3 A 0 2 V G 0 1
4 0 0 . 0 0 V
4 0 0 . 0 0 V
3 T 0 2 V G 0 1
4 0 0 . 0 0 V
3 T 0 2 V G 0 1
4 0 0 . 0 0 V
118
LRX D01
1 2 3 4 5 6 7 8 Column
Line 1 4
2 2
3 3 3 . 3 3 S e c T 0 1
4 M 0 4
I185 GB 06 10
Step 1: 1 2 3 4 5 6 7 8 Column
Press 'SEL’ and ‘'
Line 1 1
(Simultaneously)
2 1
3 0 0 . 0 0 S e c T 0 2
1 2 3 4 5 6 7 8 Column
Line 1 4
2 2
3 3 3 . 3 3 S e c T 0 1
4 M 0 4
3 0 0 . 0 0 S e c T 1 F
4 E S C ? O K ?
Line 1 L A D D E R
2 > B L O C C O F U N Z
3 P A R A M E T R I
4 R U N
1 2 3 4 5 6 7 8 Column
Line 1 4
2 2
3 3 3 . 3 3 S e c T 0 1
4 M 0 4
119
LRX D01
Step 1: 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 1
2 L o w
3 0 0 0 0 0 0 C 0 1
4 L o w
I185 GB 06 10
Step 2: 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 S u –– S u
2 1
3 0 0 : 0 0 R 0 1
4 0 0 : 0 0
Step 3: 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 1
2 A 0 1 V
3 A 0 2 V G 0 1
4 0 0 . 0 0 V
Step 4: 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 1
3 H 0 1
Step 5: 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 1
2 1 I 0 1 –– I 0 1
3 L 0 1
4 W 0 9 –– W 0 9
Step 6: 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 1
2 L o w Q 0 1
3 L o w 0 0 0 0 0 0 P 0 1
4 L o w 0 0 0 0 0 1
Step 7: 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 1
2 1
3 L o w Q 0 1 –– Q 0 1 S 0 1
Step 8: 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 1
2 0 0 0 0 0 N o p
3 0 0 0 0 0 A S 0 1
4 0 0 0 0 0
120
LRX D01
Step 9: 1 2 3 4 5 6 7 8 Column
Press 'SEL'
Line 1 1
2 0 0 0 0 1 N o p
3 0 0 0 0 1 M I 0 1
4 0 0 0 0 1
I185 GB 06 10
2 0 0 0 0 1 N o p
3 0 0 0 0 1 P I 0 1
4 0 0 0 . 0 1 1
2 0 0 0 0 1 N o p
3 0 0 0 0 . 1 P I 0 1
4 0 0 0 . 0 1 2
2 L o w 0 0 0 0 0
3 L o w 0 0 0 0 0 M X 0 1
4 0 0 0 0 0
2 L o w 0 0 0 0 0 N o p
3 L o w 0 0 0 0 0 A R 0 1
4 0 1 0 0 0 1
2 L o w 0 0 0 1 0 N o p
3 L o w 0 1 . 0 0 A R 0 1
4 0 0 0 0 0 2
2 0 1
3 0 0 0 1 M U 0 1
4 D R 0 1
121