APACS+ Advanced Control Module Plus (ACM+)
APACS+ Advanced Control Module Plus (ACM+)
SD39ACM-3
Rev: 4
September 2005
APACS+™
Advanced Control Module Plus (ACM+)
Trademarks
ProcessSuite, QUADLOG, 4-mation, and APACS+ are trademarks of Siemens Energy & Automation, Inc.
Other names in this publication might be trademarks, the use of which by third parties for their own purposes may
violate the rights of the registered holder.
Table of Contents
Section Title Page
1 Introduction....................................................................................................................1-1
1.1 Product Description ......................................................................................................1-1
1.1.1 LED Indicators.......................................................................................................1-3
1.1.2 Configuration .........................................................................................................1-3
1.1.3 Software Functions ................................................................................................1-4
1.1.4 Control Strategies...................................................................................................1-4
1.2 Product Support ............................................................................................................1-4
1.3 Related Literature .........................................................................................................1-6
2 Installation......................................................................................................................2-1
2.1 Hardware Identification................................................................................................2-1
2.1.1 ACM Transition Board ..........................................................................................2-2
2.2 Considerations and Preparations ..................................................................................2-2
2.2.1 EMC Directive Installation Considerations ...........................................................2-2
2.2.2 Preparations............................................................................................................2-3
2.3 Environmental Considerations .....................................................................................2-3
2.4 Equipment Delivery and Handling ...............................................................................2-5
2.4.1 Predelivery Test .....................................................................................................2-5
2.4.2 Factory Shipment ...................................................................................................2-5
2.4.3 Receipt of Shipment...............................................................................................2-5
2.4.4 Equipment Handling ..............................................................................................2-6
2.4.5 Equipment Storage.................................................................................................2-6
2.5 Mechanical Installation.................................................................................................2-6
2.5.1 ACM Transition Board Installation .......................................................................2-7
2.5.2 ACM+ Installation .................................................................................................2-8
2.5.2.1 Module Rack Mechanical Keying................................................................2-8
2.5.2.2 Module Installation ......................................................................................2-9
2.6 ELECTRICAL INSTALLATION..............................................................................2-11
2.6.1 Cable Connections ...............................................................................................2-12
2.6.1.1 Redundancy Cable......................................................................................2-12
2.6.1.2 Serial Port Cables .......................................................................................2-13
2.6.2 Switches ...............................................................................................................2-14
2.6.2.1 SECURITY ENABLE Switch Setting .......................................................2-14
2.6.2.2 NODE Switch Setting ................................................................................2-17
2.6.3 RAM Battery........................................................................................................2-19
3 Maintenance ...................................................................................................................3-1
3.1 Tool and Equipment Requirements ..............................................................................3-1
3.2 Preventive Maintenance ...............................................................................................3-1
3.2.1 Visual Inspection....................................................................................................3-1
3.2.2 Cleaning .................................................................................................................3-2
3.3 Troubleshooting............................................................................................................3-2
3.3.1 Typical ACM+ Error Codes...................................................................................3-2
3.3.2 Bezel LEDs ............................................................................................................3-6
September 2005 i
Contents SD39ACM-3
6 Specifications..................................................................................................................6-1
6.1 Module Specifications ..................................................................................................6-1
6.2 Environmental Specifications.......................................................................................6-2
6.3 Electrical Classification ................................................................................................6-3
6.3.1 Approvals ...............................................................................................................6-3
6.3.2 CSA Hazardous Locations Precautions .................................................................6-3
6.4 Electromagnetic Compatibility (EMC).........................................................................6-5
ii September 2005
SD39ACM-3 Contents
List of Tables
Table Title Page
List of Illustrations
Figure Title Page
iv September 2005
SD39ACM-3 Contents
PREFACE
The following symbols may appear in this manual and may be applied to the equipment. The reader
should become familiar with the symbols and their meaning. Symbols are provided to quickly alert the
user to safety related situations, issues, and text.
Symbol Meaning
Indicates an immediate hazardous situation which, if not avoided, will result in
DANGER death or serious injury.
Important Identifies an action that should be taken to avoid an undesirable result or state.
Note Identifies additional information that should be read.
Electrical shock hazard. The included Warning text states that the danger of
electrical shock is present.
Electrical shock hazard. Indicated that the danger of electrical shock is
present.
September 2005 v
Contents SD39ACM-3
Qualified Persons
The described equipment should be installed, configured, operated, and serviced only by qualified persons
thoroughly familiar with this publication. The current version, in Portable Document Format (PDF), is
available at http://sitescape.sea.siemens.com/.
For the purpose of this publication and product labels, a qualified person is one who is familiar with the
installation, construction, and operation of the equipment, and the involved hazards. In addition, he or she
has the following qualifications:
• Is trained and authorized to energize, de-energize, clear, ground and tag circuits and equipment in
accordance with established safety practices.
• Is trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety
glasses or face shields, flash clothing, etc., in accordance with established safety practices.
Scope
This publication does not purport to cover all details or variations in equipment, nor to provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should further
information be desired or should particular problems arise which are not covered sufficiently for the
purchaser’s purposes, the matter should be referred to one of the support groups listed in the Product
Support section of this manual.
The contents of this manual shall not become part of or modify any prior or existing agreement,
commitment or relationship. The sales contract contains the entire obligation of Siemens. The warranty
contained in the contract between the parties is the sole warranty of Siemens. Any statements continued
herein do not create new warranties or modify the existing warranty.
WARNING
This equipment contains hazardous voltages, and it has been certified for use in the hazardous locations
specified on the product nameplate and in the Model Designation and Specifications section. Death,
serious personal injury, or property damage can result if safety instructions are not followed. Only
qualified personnel should work on or around this equipment after becoming thoroughly familiar with all
warning, safety notices, and maintenance procedures contained herein. The successful and safe operation
of this equipment is dependent upon proper handling, installation, operation, and maintenance.
The perfect and safe operation of the equipment is conditional upon proper transport, proper storage,
installation and assembly, as well as, on careful operation and commissioning.
The equipment may be used only for the purposes specified in this publication.
vi September 2005
SD39ACM-3 Contents
CAUTION
Electrostatic discharge can damage or cause the failure of semiconductor devices such as
integrated circuits and transistors. The symbol at right may appear on a circuit board or other
electronic assembly to indicate that special handling precautions are needed.
• Electronic assemblies must be stored in anti-static protective bags when not installed in equipment.
DANGER
Explosion hazard
1 Introduction
This Instruction provides installation and service information for the following Advanced Control Module
Plus (ACM+) hardware:
• Section 1, Introduction – Contains product description, product support, and lists related literature.
• Section 4, Circuit Description – Contains a brief system level description of the ACM.
• Section 5, Model Designation – Provides model designation and lists of accessories and options.
The microprocessor-based Advanced Control Module Plus (ACM+) is a key element of the APACS+
Advanced Controller. An ACM+ can communicate with any APACS+ I/O modules via the IOBUS or
communicate with control, computer, and communication modules via the MODULBUS. Figure 1-1
illustrates the ACM+ and its associated transition boards.
The ACM+ occupies a single module rack slot. The top connector at the rear of the module mates with a
connector on the rack back plane. This connector provides power bus, IOBUS, and MODULBUS access.
The bottom connector mates with an ACM transition board to access the serial ports and redundancy
connector. Each installed ACM+ requires a transition board to operate, which includes two RS-232C
serial ports for serial communications applications. Also provided is a redundancy connector, which
permits two ACM+s to operate in a redundant configuration.
In comparison to the APACS+ ACM module, the ACM+ contains 1MB of FLASH EEPROM memory
for non-volatile storage of the operating system software, whereas the ACM stored the operating system
software in RAM. FLASH EEPROM storage protects the operating system software from accidental
modification and/or corruption. The ACM+ also frees approximately 500KB of RAM for the application
specific configuration.
The ACM+ runs operating system software from its Program flash, instead of from SRAM. However, the
configuration still resides in SRAM. As such, it is no longer possible to erase the ACM operating
software by pulling the module out of the rack and removing the battery. The module must be re-
initialized via 4-mation or cross-loaded to load new operating system software.
The ACM+’s LEDs support local troubleshooting without an operator interface. The module includes
three LEDs, which indicate the following module statuses:
See Table 3-2 in section 3.0, Maintenance, of this Guide for detailed description of the ACM+ status LED
indications.
1.1.2 Configuration
The ACM+ is configured using the ProcessSuite™ 4-mation™ Configuration software. 4-mation allows a
control strategy to be defined using any mix of four languages, which are based on the IEC specification
for programmable controllers (IEC 1131-3). These languages are function blocks, ladder logic, sequential
function charts, and structured text. These languages allow a configuration to be created using the tool(s)
most effective for each application.
4-mation is also used to configure an ACM+’s I/O, as well as modules within an APACS+ system. A
backup copy of the I/O module’s configuration is maintained by the ACM+ to allow automatic
configuration of an I/O module when it is inserted into a module rack.
An ACM+’s configuration can be created off-line and transferred to the module, or a configuration can be
created within an on-line ACM+ during the initial design phase. On-line configuration is possible because
all of the information needed to configure an ACM+ is stored in its database, thus eliminating the need to
have a disk-based master database for viewing or editing a configuration. Several different restriction
levels are available.
The ACM+’s security can be programmed so no unauthorized or inadvertent changes are made to a
configuration. When this security feature is activated, a configuration can be opened in read/write
mode only, ensuring that no further changes are made to the control strategy.
The ACM+ also includes features to simplify start-up should operation be disrupted. An ACM+ s
configuration is battery-backed so that the configuration for an ACM+ and its I/O is maintained when
power is lost. Also, variables within an ACM+ can be assigned warm start and cold start values. When
power is lost, the ACM+’s real-time clock continues to run so that warm start and cold start states can be
determined and acted upon once power is restored.
The ACM+ can be used in conjunction with APACS+ I/O modules to control either a continuous or batch
process. ACM+ software is able to execute Function Block Diagrams, Ladder Diagrams, Sequential
Function Charts, and Structured Text.
The ACM+ can be used in conjunction with APACS+ I/O modules to build DCS style and/or PLC style
systems. It can also be used by itself (or with I/O modules) to supervise the operation of other APACS+
control modules, as required by the process strategy.
Our Technical Support Centers (TSC) offer a variety of technical support services that are designed to
assist you with Siemens products and systems. Our support engineers have experience with
troubleshooting, development, system startup, and system test. They will help you to solve your issues in
an efficient and professional manner.
Customers in North America can contact Siemens Technical Support Center at 1-800-333-7421, on the
web at: http://support.automation.siemens.com, or by e-mail: [email protected]
Customers outside North America can contact their local Siemens subsidiary; addresses and telephone
numbers are listed on the Internet at the web site: http://support.automation.siemens.com.
When contacting Siemens, customers will be asked to provide site-contact information (name, address,
and phone number), the product involved and detailed information regarding the nature of the issue.
Product documentation is now located in the Library forum of the Process Automation User Connection
at: http://sitescape.sea.siemens.com/. The Process Automation User Connection is a secure site.
Registration is open to all verified users of Siemens process automation systems. If you are not already,
and would like to become a member, please visit our Process Automation User Connection web page at:
http://www.sea.siemens.com/process/support/papauc.html
Contained within the Process Automation User Connection is the APACS+/QUADLOG Secure Site at:
http://sitescape.sea.siemens.com/forum/aca-1/dispatch.cgi/f.apacsquadlo forum. This site is only open to
customers with an active service agreement. It contains all service manuals, service memos, service notes,
configuration manuals, etc. for the APACS+ and QUADLOG family of products. If you are experiencing
technical difficulties with the site, please contact SiteScape technical support at: toll free 1-877-234-1122
(US) or 1-513-336-1474.
Nürnberg
2 Installation
This section describes the installation of the ACM+ and the ACM Transition Board. Read this entire
section before starting an installation.
IMPORTANT NOTE
The Advanced Control Module Plus is identified by the letters “ACM+” on the bezel and by two
nameplate labels: a large label, shown below, located on the tracking plate (left side of ACM+ in Figure
1-1), and a small label inside the bezel battery compartment. Access to the battery compartment is by
loosening a captive screw in the hinged compartment cover. Both labels contain the module’s Model
Designation, Part Number, ROM Version, and Serial Number. The larger label also shows its current and
voltage requirements.
The Transition Board is identified by information silk screened on the component side of the board.
ACM
ADVANCED
CONTROL MODULE
SIEMENS ENERGY &
AUTOMATION, INC.
TRANSITION BOARD
P/N 16147-51
Read Sections 2.2.1 and 2.2.2 before continuing with ACM+ installation. Section 2.2.1 describes
considerations required to ensure that APACS+ modules are compliant with the European Union’s
Electromagnetic Compatibility (EMC) Directive.
Some installations of APACS+ modules may require adherence to the European Union’s Electromagnetic
Compatibility (EMC) Directive. Section 6 features the Declaration of Conformity statement showing the
certificate number of the Technical Construction File issued to the ACM+. EMC compliance requires the
following:
Consult the factory for additional information concerning EMC Directive installation and the availability
of enclosures and needed hardware.
2.2.2 Preparations
1. Install SIXRACs or MODULRACs with Local Termination Panels (for local termination only) in
MODULPACs or cabinets where ACM+s are to be installed. The ACM+s should not be installed in
their racks at this time. However, the rack slots numbers for ACM+s should be known.
• Only I/O modules installed in slots to the right of an ACM+ (higher slot numbers or in next
IOBUS-connected rack) are slaved to that ACM+.
• Only an empty slot, Bus Continuation Module (BCM), or Bus Diverter Module (BDM) may be
between an ACM+ and any of its slaved I/O modules. Empty slots are not permitted on the
IOBUS of rack-to-rack redundant systems.
• Terminate the IOBUS before assigning slot numbers for the next ACM+ and its I/O modules.
3. Determine whether redundant ACM+s will be installed. ACM+ hardware and software provides for
module-to-module and rack-to-rack redundancy as described as follows:
• Rack-to-Rack Redundancy – Two ACM+s are mounted in two module racks that are complete
duplicates. One rack is operating, the other is in standby and can instantly assume control should
a failure occur in the operating rack. They communicate over a dedicated redundancy cable.
A transition board NODE Switch provides for the setting of a node address for each ACM+ when the
controller’s MODULBUS is not connected via MBX module to MODULNET.
CAUTION
Many industrial environments create severe operating conditions. The conditions at each ACM+ location
must be within the specifications stated in Section 6.2, Environmental Specifications, of this Guide.
CAUTION
To ensure reliable data communications, it would be prudent to locate APACS+ module enclosures as far
as possible from sources of interference such as high current electrical equipment, which emit strong
electromagnetic fields and switching transients.
Industrial environments often contain particulate, liquid, and gaseous contaminants. Particulate matter,
usually dust and dirt, is abrasive and can cause intermittent contact in connectors associated with circuit
assemblies. A layer of dust on circuit boards will interfere with semiconductor heat dissipation. Liquid
and gaseous contaminants can have a corrosive effect on metal, rubber, plastic and circuit board
components. Extended exposure to this environment may result in equipment malfunction.
• When cleaning equipment and surrounding area, especially the floor, either vacuum away all dust and
dirt or use a dampened rag or mop.
• Clean or replace all air conditioning filters, room air filters, and equipment filters regularly.
• Inform personnel with access to APACS+ modules of the need for site cleanliness.
The following subsections provide information of interest to shipping, receiving, and warehouse
personnel.
An ACM+ that will be installed by the user is fully tested and inspected to ensure proper operation. If the
ACM+ is ordered factory installed in a MODULPAC or other enclosure, the ACM+ is tested as part of
the APACS+ system and inspected to ensure proper operation.
ACM+s to be installed by the user are placed in static shielding bags and packaged for shipment.
Accessories are packaged separately.
If the ACM+ is ordered factory installed in a MODULPAC or other enclosure, the enclosure is bolted to a
pallet and wrapped for protection during shipment.
All cartons should be inspected at the time of their delivery for possible external damage. Any visible
damage should be immediately recorded on the carrier’s copy of the delivery slip. Each carton should be
carefully unpacked and its contents checked against the enclosed packing list. At the same time, each item
should be inspected for hidden damage that may or may not have been accompanied by exterior carton
damage.
If it is found that some items have been damaged or are missing, notify Siemens immediately and provide
full details. In addition, damages must be reported to the carrier with a request for their on-site inspection
of the damaged item and its shipping carton.
The ACM+ is completely enclosed and may be safely handled without undertaking special ESD
(electrostatic discharge) handling procedures provided the battery compartment door is closed and
secured. DO NOT touch the connector pins on the back of the module. Handle the module carefully and
do not subject it to excessive shock or vibration.
CAUTION
The storage temperature and humidity parameters of Section 6.2 must be met to properly store an ACM+.
When the ACM+ is not powered in storage, the backup battery must be disabled. An ACM+ removed
from storage for use must be prepared as described in Section 2.6.3.
IMPORTANT
This section provides detailed information on the installation of transition boards and the module.
Mount the ACM Transition Board (Figure 1-1) at the MODULRAC or SIXRAC slot location of its
companion ACM+.
1. Consult user documentation and note the slot location assigned to the ACM+(s).
• At the rear of the rack, locate and identify the extruded spacer to which the lower edge of the
backplane is mounted. Note that the bottom of the extruded spacer is grooved. The top edge of
the transition board will rest in this groove.
• Identify alignment pins located below the rack’s frame that span the width of the rack. The left-
most pin corresponds to rack slot #1. One of these pins will engage a hole located on the
termination board above the SIEMENS logo.
• A transition board’s captive mounting screws can be seen projecting from the bottom of the
plastic extrusion panel.
a) Angle the top edge of the board toward the back plane’s extruded spacer and insert the tip of the
board in the spacer’s groove.
b) Slide the board in the groove until it is vertically and horizontally aligned with the appropriate
pin.
c) Carefully lower the transition board and engage the alignment pin with the extrusion and board
pin mounting holes. Firmly push down to seat the board on the pin. When the board is properly
seated, the pin will be flush with, or project slightly above the board’s surface.
d) Tighten the captive mounting screws, which are automatically aligned with their respective panel
mounting holes.
Modules are shipped individually packaged in protective, sealed, static shielding bags. Refer to Section
2.4.4 for module handling considerations. Each MODULRAC/SIXRAC slot and each module must be
keyed to prevent accidental installation of a module into an incompatible slot. Keying is highly
recommended. A unique keying pattern is assigned to each module type. See Figure 2-2 for ACM+
keying patterns.
A factory-assembled rack is keyed at the factory. A user-assembled rack must be keyed by the user
according to the module types assigned each slot. Slot keying patterns must complement those of each
module. MODULRACs/SIXRACs are supplied with stop plugs.
2. Refer to Figure 2-2 and note the MODULRAC keying pattern. Also, locate the MODULRAC top and
bottom rails.
3. Press the stop plugs into the holes identified by the solid dots.
Use the following instructions to install the ACM+. Refer to Figure 2-2.
1. Refer to user documentation for the correct module slot number and proper placement of the ACM
transition board. For module-to-module redundancy, ACM+s are adjacently mounted in odd-even (1-
2, 3-4, 7-8) slots.
2. Remove the ACM+ from its static shielding bag and ensure that the module is keyed. Also, check the
rack slot to be sure it is keyed.
3. Insert the module in the assigned rack slot. Firmly seat the module in the back plane and transition
board connectors. A properly seated module will have the rear of its bezel flush against the rack’s
front rails. A keyed module that is not matched to a keyed slot will not engage the back plane or
transition board connectors or seat flush against the rack’s front rails.
4. Pull open the bezel’s pivoting top and bottom handles to expose the slotted captive mounting screws
and secure the module to the top and bottom rails. Close the bezel’s handles when finished.
CAUTION
Do not use the captive mounting screws to seat the module. Doing this
may damage the ACM+’s bezel.
DANGER
• Remove power from all wires and terminals and verify that there
are no hazardous voltages before working on equipment.
• In potentially hazardous atmosphere, remove power from
equipment before connecting or disconnecting power, signal, or
other circuit, or extracting/inserting module.
• Observe all pertinent regulations regarding installation in
hazardous area.
• Ensure all devices are rated for hazardous (classified) locations.
The following subsections provide details for the connection of redundancy and serial port cables.
Redundancy is discussed in Section 2.2.2. Refer to Figure 2-3 and connect the cable as follows:
1. Consult user documentation and identify the module rack(s) and ACM+ slots for each redundant pair.
2. Install one of the following redundancy cables between the transition boards of each redundant
ACM+ pair. Mate the cable connectors with the J2 Redundancy Connectors on the ACM transition
boards.
NOTE
Serial Ports 1 and 2 are RS-232 industrial (isolated) serial communication ports with a software selected
communications rate of between 300 and 38400 Baud. They provide an interface to the ACM+ for serial
communications applications and are located on the transition board.
Serial ports can be connected to foreign devices non-redundantly or redundantly. For non-redundant
installations, use the ACM Serial Port Cable to Converter, P/N 16137-191. For redundant installations,
use the Redundant ACM Serial Port Cable to Converter, P/N 16137-221. For users wishing to fabricate a
serial cable, Table 2-1 lists serial pin designations.
2.6.2 Switches
The following subsections provide details for the setting of the Security Enable and Node switches.
The ACM+’s SECURITY ENABLE Switch and the 4-mation Security function block can be configured
to either:
• Protect the data and/or configuration database stored in the ACM+ from being changed by any
MODULBUS station (i.e. ACM+, CCM, or PC running 4-mation software).
or
When the SECURITY ENABLE Switch is set to ENABLE and the EN input to the Security function
block is true, a level of security will be established. The LED on the ACM+ bezel indicates as follows.
Note that the level of security is determined by the inputs to the Security function block. Refer to the
Using ProcessSuite™ 4-mation Configuration Guide (CG39-20) to determine the actual protection and
LED operation. Set the Security Enable Switch, shown in Figure 2-4, as follows:
1. Place wrist strap on and connect its ground lead to module rack ground stud.
2. Loosen the battery compartment cover screw and open the pivoting cover. The SECURITY ENABLE
Switch is located above the DIAG PORT connector.
• SECURITY ENABLE – Move the switch to the right, as indicated by the label
• SECURITY DISABLE – Move the switch to the left
1. Secure the battery compartment cover and disconnect the wrist strap.
2. For redundant ACM+s, follow the above procedure and set the SECURITY ENABLE Switch on the
redundant module.
Every MODULBUS device, such as an ACM+, RIC/ICM, PC with MBI or MNI, RNI/NIM and MBX
has an address associated with it. This address consists of the Node, Rack, and Slot identifiers. However,
the ACM+ is different in that its Node identifier (also called number or address) is determined by one of
the other M-BUS devices. The following subsections describe the procedures used to establish the
operational Node number under which an ACM+ in a particular local area system will appear.
Proceed to the subsection that describes your specific local area system to determine the correct Node
switch setting (0 or 1) on a particular ACM transition board.
If the local area system (LAS) contains an MBX, the Node selector switch on the ACM transition board is
ignored (leave it in 0 or 1 position). The ACM+ will appear with the same Node address as the MBX.
• The MBX Node address can be set to any number from 1 to 63. Each RNI/NIM, RIC/ICM, and PC
with MBI should have its Node set to the same number as that of the MBX in that cluster. A PC with
MNI can have the same Node number as the MBX or its own unique Node number, which is
recommended.
• When using MBXs in Rack-to-Rack redundant systems, the first MBX is set to N and the second
MBX is set to N+1, where N is an even number. (e.g. 2/3, 4/5, 6/7). Do not use 00 and 01.
• Do not change the Node address (SNA-System Node Address) when the MBX is powered (ACM+s
will not pick up a change in Node address until the ACM+ is fully reinitialized (power down, remove
battery).
If the local area system (LAS) does not have an MBX, the ACM+ s Node address will be determined by
the Node address of the first client that communicates to it and by the Node selector switch setting on its
transition board. This client could be an RIC (or an ICM), PC with MBI, or an RNI (or NIM). Each of
these devices has a Node number in the APACS.INI file ( Node= ). The ACM+ s ultimate Node
address will depend on the Node address of one of these clients and on the setting of the Node selector
switch on the ACM’s transition board (see Table 2-2).
• When an application is started on a client machine that then communicates with the ACM+, the
ACM+ will use the Node address of the client and its selector switch to determine its operational
Node address. Running 4-mation on-line and just opening the module tree is enough to start this
process.
• If the application is run from a PC over Ethernet, the Node address of the RNI/NIM is actually used;
not that of the PC. However, when setting up the architecture, the PC and RNI/NIM would typically
have the same node number; if only for system documentation reasons.
IMPORTANT
The Node switch setting on the ACM transition board determines the
ultimate Node address used by the ACM+ (with no MBX present). See
Table 2-2 to determine an ACM+’s Node address.
EFFECT OF
CLIENT’S NODE ACM+ NODE SWITCH EXAMPLES
ADDRESS (WHEN NO MBX IS PRESENT)
EVEN (including 0) Add the Switch setting to determine 1. Client=4, ACM+ Node Switch=0
the ACM+ s final Node address yields ACM+ Node=4
• An ACM transition board must always be installed for each ACM+, even when redundancy and serial
ports are not being used.
• An older ACM transition board without the Node selector switch will operate as if the switch is set to
0.
• For Module-to-Module redundant ACM+s, the switches should be equal (both 0 or both 1). The
criteria in Table 2-2 will still apply in determining the operational Node address of the ACM+.
IMPORTANT
If you need to change the Node number of an ACM+, the ACM+ must be
fully reinitialized to take on the new Node number. To fully reinitialize
the ACM+, pull the ACM+, remove the battery, wait about 1 minute,
reinstall the battery, then reinsert the ACM+.
The purpose of the RAM battery is to retain memory contents and real-time clock operation during power
interruptions. The battery MUST be connected just prior to applying power to the ACM+. See Section 6
for battery life data.
IMPORTANT
• It is recommended that the battery be disconnected to preserve battery life when the module is
placed in storage or stock.
To check the status of the battery, and connect the battery if it is disconnected, perform the following
steps:
1. Place wrist strap on wrist and connect ground lead to module rack’s ground stud. ESD protection is
required when the battery compartment is opened.
2. Loosen the battery compartment cover screw and open the pivoting cover.
3. Refer to Figure 2-4 and note the location of the battery and its plug.
4. If the module’s battery is not connected, orient the keyed plug and push it onto the circuit board
connector pins. If the module’s battery is connected, proceed to step 5.
5. Proceed to Section 2.6.2.1 to set the SECURITY ENABLE Switch and close the battery compartment
door.
3 Maintenance
The APACS+ Advanced Control Module Plus (ACM+) and its associated transition board require
minimal maintenance. Some routine maintenance is recommended in the form of a visual inspection and a
possible cleaning.
DANGER
• Remove power from all wires and terminals and verify that there
are no hazardous voltages before working on equipment.
• In potentially hazardous atmosphere, remove power from
equipment before connecting or disconnecting power, signal, or
other circuit, or extracting/inserting module.
• Observe all pertinent regulations regarding installation in
hazardous area.
• Ensure all devices are rated for hazardous (classified) locations.
The ACM+ and its transition board should be inspected periodically. The frequency of inspection will
depend on the severity of the operating environment. The primary aim of the inspection is to watch for
excessive accumulations of dust, dirt, or other foreign material on the ACM+’s transition board and
protective covers. Excessive accumulations impede heat dissipation and may eventually cause module or
system failure. The ACM+ will alarm on an over-temperature condition long before over-temperature
failure can cause permanent damage. If the ACM+ is installed in a NEMA 12/IP55 compliant cabinet, the
ACM+ does not require cleanliness inspections. Refer to Section 3.2.2 for cleaning instructions.
The ACM+ status is indicated by LEDs located on its bezel. Refer to Section 3.3.2 for LED indications.
3.2.2 Cleaning
Cleaning a module involves brushing or vacuuming the protective covers to restore cooling efficiency that
may have been degraded by accumulated dust.
Cleaning a transition board involves careful brushing and vacuuming to remove accumulated dust and dirt
harboring chemical particulate that may accelerate terminal, switch, or connector contact corrosion.
3.3 Troubleshooting
Fault analysis focuses on identifying a failure annunciated by the operator interface, or by status LEDs
located on the ACM+’s bezel. If the operator interface alarm blocks have been configured, module errors
will be reported. The operator can access error code descriptions and recommended corrective actions.
Failure annunciation and fault analysis is also available within 4-mation software (refer to Using the
ProcessSuite 4-mation Configuration Software, CG39-20, located in binder UM39-11). The on-line
display of the Module Tree in 4-mation graphically represents both the hardware modules that comprise a
system and the function that hardware performs. There is an entry in the Tree for each module including
its node, rack, and slot address.
In the Module Tree, ACM+ symbols are displayed to the left of the address. When 4-mation is running in
the on-line mode, these symbols are displayed in one of three colors, depending upon a module’s state of
operation:
The ACM+ address text (e.g. [R01,S02] ) is displayed in one of four colors, based on error status:
• White – Indicates that error information could not be obtained from the module
• Red – Indicates the module has errors
• Green – Indicates the module has no errors
• Yellow – Indicates the resource module has no errors but its I/O module(s) do
Once a fault is identified, correct the fault by replacing the failed ACM+ with a known good module and
return the failed ACM+ to one of the addresses in the warranty statement for repair.
Table 3-1 lists typical error codes associated with ACM+s. For a detailed description of all module error
codes, refer to ProcessSuite Module Diagnostic Error Codes (CG39-19) located in binder UM39-14.
System
Service Error Code ERROR DESCRIPTION USER ACTION
Code
System
Service Error Code ERROR DESCRIPTION USER ACTION
Code
Specific Task
Timeout Manual Clear Allowed
System
Service Error Code ERROR DESCRIPTION USER ACTION
Code
System
Service Error Code ERROR DESCRIPTION USER ACTION
Code
replace module.
Three LEDs on the ACM+ bezel show module status as indicated in Table 3-2.
LED
LED LABEL ACM+ STATUS
INDICATION
Steady GREEN ACM+ OK
A diagnostic port is located in the bezel battery compartment. It is an engineering and manufacturing port.
It is not a field troubleshooting port.
A module can be removed from or installed in the rack without removing power from the module slot,
from I/O circuits, or from the rack.
1. As shown in Figure 2-2, pull open bezel’s pivoted top and bottom handles to expose the module s
slotted captive mounting screws. Loosen the screws.
2. Grasp the top and bottom handles and pull the module from the card cage.
3. Place the module in a static shielding bag and package for return (see Section 3.8).
1. Remove the replacement ACM+ from its protective bag. Its protective covers permit the ACM+ to be
handled without a grounded wrist strap.
2. Insert the module in its MODULRAC slot. Firmly seat the module in the back plane and termination
board connectors. A properly seated module will have the rear of its bezel flush against the
MODULRAC housing rails.
NOTE
A keyed module that is not matched to a slot will not engage the back
plane or termination board connectors or seat flush against the
MODULRAC housing’s front rails.
3. As shown in Figure 2-2, pull open bezel s pivoted top and bottom handles to expose the module s
slotted captive mounting screws and secure the module to the top and bottom rails. Close the bezel’
handles when finished.
CAUTION
Do not use the captive mounting screws to seat the module. Doing this
may damage the bezel..
4. Ensure the battery is enabled (see Section 2.6.3) and set the Security Enable switch as described in
Section 2.6.2.1.
2. Remove the old cable from the primary (calculate) termination strip.
3. Remove the old cable from the backup (verify) termination strip.
4. Insert and screw down the new cable to the backup (verify) termination strip.
5. Insert and screw down the new cable to the primary (calculate) termination strip.
3.5.1 Removal
1. As necessary, take appropriate steps to shutdown the processes monitored or controlled by the field
devices controlled by the ACM+.
2. Remove the associated ACM+ from its slot in the module rack; see Section 3.4.1. Place the module in
a static shielding bag for protection.
3. Remove redundancy and serial port cables from the transition board.
IMPORTANT
4. Loosen the transition board s captive mounting screws. Gently lift the bottom of the board in an arc
until the board is free of its alignment pin located immediately above the Siemens logo. Pull the top
of the transition board from the grooved back plane spacer and lift it from the module rack.
3.5.2 Replacement
IMPORTANT
Be sure that the battery is connected. Refer to Section 3.6.1 for the
connection procedure.
A 3.6V lithium battery is housed in the module s bezel battery compartment. When power is removed
from the ACM+, the battery maintains ACM+ memory (RAM) to retain the configuration and executable
code.
Batter condition is monitored by software. System Service Code (SSC) 28 and Error Code (EC) 01 will
indicate a weak battery. SSC 28, EC 19 will indicate a disconnected battery. The error code and message
will be displayed on a system computer running 4-mation Release 2 or higher software.
If the battery is weak and a configuration is stored in the ACM+, replace the battery with power applied
to the ACM+. If the configuration is lost, it can be quickly downloaded using 4-mation software.
1. To protect the ACM+ from electrostatic discharge, snap on a wrist strap and connect its ground lead
to the ground stud on the module rack panel.
2. Loosen the bezel compartment screw and open the door. See Figure 2-4.
4. Pull the battery from the compartment; a cloth hook and loop fastener secures the battery.
5. The replacement battery is supplied with a new hook and loop fastener. Separate the fastener halves.
6. If the compartment-mounted portion of the fastener is damaged, remove it and install the separated
fastener half.
8. Orient the keyed battery connector and plug it into the circuit board mounted connector.
9. Close and secure the battery compartment door. Remove the wrist strap.
WARNING
One spare ACM+ and battery should be stocked for every 1 to 10 in service. Spare and replacement parts
can be ordered from one of the addresses in the Warranty statement or through a local Siemens
representative.
Assembly part numbers are provided in Section 1 and printed on most modules and associated hardware.
The battery part number is listed as follows:
When ordering, provide the model number, part number, serial number, and software compatibility
identification code from the module to be replaced or spared. A purchase order number should also be
included.
WARNING
IMPORTANT
US Customers:
• Call the Repair Order PAS Inside Sales/Order Management Group at (215) 646-7400, ext 4RMA
(4762) weekdays between 8:00 a.m. and 4:45 p.m. eastern time to obtain an RMA number. Mark the
RMA number prominently on the outside of the shipment.
• When calling for an RMA number, provide the reason for the return. If returning equipment for
repair, a detailed description of failure symptoms and system behavior will be requested. Supply a
purchase order number for repairs. Follow the TSC specialist's recommendation for battery
connection, if applicable.
• If applicable, you must supply a Material Safety Data Sheet (MSDS) with each item being returned if
it was stored or used in a location where hazardous materials were present.
• Package items to be returned in their original shipping containers. Otherwise, package it for safe
shipment or contact the factory for shipping recommendations. A module must be placed inside a
static shielding bag to protect it from electrostatic discharge.
Canadian customers:
The Advanced Controller Module contains two nameplate labels: a large label, shown below, located on
the tracking plate (left side of ACM+ in Figure 1-1), and a small label inside the bezel battery
compartment. Both labels contain the module’s Software ROM Version as well as the Model
Designation, Part Number, and Serial Number.
The following guidelines should be observed to ensure software compatibility between ACM+s:
• Module-to-Module Redundancy: Both ACM+s should have the same software level installed
• Rack-to-Rack Redundancy: Both ACM+s should have the same software level installed
• Spare ACM+s: The software level of the spare module and module being replaced should agree.
Questions concerning the compatibility of different releases of software for the same type module
(ACM+) should be directed to the APACS+ Controller Product Specialist at Siemens.
An accurate record keeping system for tracking maintenance operations should be established and kept up
to date. Data extracted from the record may serve as a base for ordering maintenance supplies, including
spare parts. The record may also be useful as a troubleshooting tool. In addition, maintenance records
may be required to provide documentary information in association with a service contract. It is suggested
that the following information be recorded:
4 Circuit Description
This section provides a brief circuit description of the Advanced Control Module Plus (ACM+). See
Figure 4-1.
The 68040 CPU provides the computing power of a 32-bit architecture and instruction and data caches.
Internal operations in the 68040 CPU run at 66 MHz while its bus operations run at 33 MHz. The floating
point coprocessor performs floating point computations which allows the CPU to more quickly execute
its program tasks.
4.2 Watchdog/Reset
During an ACM+ power-up, the Watchdog generates a system reset while the IC supply voltage from the
on-board power supply is rising to its operating value. During ACM+ operation, if at any time the IC
supply voltage drops below 4.5V, the Watchdog will generate a reset to shut off RAM decode MOSFETS
to protect the RAM from invalid access during a power supply failure.
A bus timeout circuit generates an error signal input to the CPU which is used to terminate an
unsuccessful bus cycle. The ACM+ provides a maximum memory access time period. If a memory access
is attempted to a non-existing address or the RAM access circuitry is defective, and a failure to respond
within the time period occurs, a bus error signal is generated to terminate the bus cycle.
There are three bus masters. While the CPU is the initial arbitrator of the address, data, and control buses,
it will allow the peripheral controller and MODULBUS token bus controller to take control on demand.
Under the CPU’s direction, the Bus Request, Bus Grant, and Bus Grant Acknowledge signals handle bus
control transfer.
An ACM+ has 4 or 8 MB of battery-backed states static RAM, 512 KB of flash PROM, and 1 MB of
flash for operating system code. RAM is accessible by all three bus masters. Memory chip selection is
accomplished by a RAM bus decode circuit.
The ACM+’s application-specific configuration and operating system software is downloaded from a
workstation, or a personal computer connected to the APACS+ system. The application-specific
configuration is stored in ACM+ memory (RAM); whereas, the operating system is stored in the FLASH
EEPROM memory. A 3.6V lithium battery allows RAM contents to be retained when power is removed
from the ACM+. Software detects a weak or disconnected battery, and an error code displays on a
personal computer screen.
The serial ports available on the ACM Transition Board are wired for direct connection to the COM port
of a personal computer. Connection to a printer requires a null modem. The peripheral controller and a
RS-232 line driver/receiver control each port.
4.6 MODULBUS
The MODULBUS elements consist of a Token Bus Controller (TBC), M-BUS modem, and M-BUS line
drivers/receivers.
The TBC is an intelligent peripheral device to the peripheral controller. The peripheral controller
supervises the TBC, which implements the media access control portion of the IEEE 802.4 token passing
bus standard. The TBC communicates serially with the MODULBUS modem, which is interfaced to
MODULBUS through dual line drivers/receivers.
• Converts received MODULBUS data into a form compatible for data processing
• Converts serial data from the TBC into a form compatible for transmission over the MODULBUS
4.7 IOBUS
The IOBUS elements consist of an IOBUS modem and dual IOBUS line drivers/receivers. The 68302
Controller supervises IOBUS communications through handshaking operations with the IOBUS modem.
The modem and dual line drivers/receivers perform the same tasks as described for the M-BUS modem
and line drivers/receivers.
The SCSI redundancy port elements consist of a redundancy switchover circuit and an SCSI bus interface
controller. The peripheral controller supervises redundant switchover and the SCSI bus.
Redundant ACM+s (rack-to-rack) communicate with each other over the high-speed SCSI bus. The SCSI
bus controller interfaces the peripheral controller to the SCSI bus. SCSI bus communications are the
exchange of I/O and diagnostic data between the primary and backup ACM+s.
• An operator can initiate a switchover if the Redundancy Control Function Block is configured (see
the APACS+ 4-mation Configuration Guide).
• The standby ACM+ receives and stores all IOBUS data while in the standby mode. An exchange of
data is made over the SCSI bus so both ACM+s can confirm and compare the others received data. If
the data received by the backup from the active ACM+ contains any data-check error flags posted by
the active ACM+, a switchover is initiated by the standby.
• The active ACM+ sends an OK flag to the standby ACM+ as part of the exchange of diagnostic
information. The OK flag indicates the ACM+ is functioning normally as a controller. If the active
ACM+’s onboard diagnostics detects a fault affecting ACM+ control, a NOT-OK flag is posted and
the backup initiates a switchover.
5 Model Designation
Refer to Figure 5-1 to decode the model designation.
IMPORTANT
5.1 Accessories
Refer to Table 5-1 for the list of available ACM+ accessories. Redundancy is briefly discussed in section
2.2.2, Preparations. A typical redundancy cable is illustrated in Figure 2-3. RAM battery installation and
setup is described in section 2.6.3.
5.2 Options
The only available option for the ACM+ is the P/N 16147-51 Transition Board with NODE Switch. This
board is illustrated in Figure 1-1 and its installation is described in Section 2.5.1.
6 Specifications
This section lists specifications for Advanced Control Module Plus (ACM+) Models 39ACM24BEN and
39ACM28AEN.
SPECIFICATIONS DATA
Module Weight 4.5 Lbs (2.04 Kg)
Supply Voltage 24 Vdc ± 10% (from module rack backplane)
Supply Input Current 0.52 Amperes
Power Dissipation 12.5 Watts ± 10%
Computer Specifications:
Microprocessor (39ACM2x) 68040 with Internal Floating Point Coprocessor
Clock 33 MHz (bus operations)
Internal Caches Dual 4 KB (68040)
I/O Coprocessor 68302
Real Time Clock Battery-backed, typical error: 1 sec./day (6 min. /yr.)
worse-case error: 2 sec./day (12 min./yr.)
Memory 4 or 8 MB SRAM, battery-backed
1MB FLASH EEPROM
Battery Life Expectancy:
ACM+ in powered rack 10 Years
Storage with battery disconnected 10 Years @ 23 ˚C, 9.5 Year @ 71 ˚C, 8.5 Years @ 85 ˚C
Storage with battery connected 1 Month
Communication Buses:
Backplane Redundant APACS MODULBUS Interface
I/O Redundant APACS IOBUS Interface
ACM+ Redundancy SCSI Interface
Serial Ports 1 and 2 RS-232 Format; 300 to 38000 Baud
Software selected
Table 6-2 lists the ACM+ EMC specifications and Table 6-3 the temperature and humidity specifications.
SPECIFICATIONS DATA
Temperature and Humidity:
Cooling Convection only
IEC Class Bx
Operating Temperature -25 to 70 ˚C (-13 to 158 ˚F), measured 0.25"
below rack
Operating Humidity 5 to 95% non-condensing
Maximum Moisture Limits 0.028 lb water/lb air
Storage Temperature & Humidity:
Temperature -25 ˚C to 85˚C (-13 to 185 ˚F)
Humidity 0 to 100% condensing
Allowable Enclosure External
Temperature and Humidty:
External Temperature -25 to 50 ˚C (-13 to 122 ˚F)
External Humidity 0-100% condensing
Corrosive Atmosphere ISA-S71.04 Class G3
This section provides certification agency ratings and hazardous locations precautions.
6.3.1 Approvals
IMPORTANT
This section provides CSA hazardous location precautions that should be observed by the user when
installing or servicing the equipment described in this Instruction. These statements supplement those
given in the preceding section.
DANGER
Explosion hazard
Precautions - English
Use only factory-authorized replacement parts. Substitution of components can impair the suitability of
this equipment for hazardous locations.
When the equipment described in this Instruction in installed without safety barriers, the following
precautions should be observed. Switch off electrical power at its source (in non-hazardous location)
before:
Précautions - Français
Les pièces de rechange doivent être autorisées par l'usine. Les substitutions peuvent rendre cet appareil
impropre à l'utilisation dans les emplacements dangereux.
Lorsque l'appareil décrit dans la notice ci-jointe est installé sans barrières de sécurité, on doit couper
l'alimentation électrique a la source (hors de l'emplacement dangereux) avant d'effectuer les opérations
suivantes:
This product has been tested per the European Union’s EMC Directive. See the Declaration of
Conformity statement at the back of this Instruction. Refer to Section 2.1.2 for considerations affecting
EMC compliance.
39ACM14, 39ACM24, QLACM14, QLACM24 with any factory installed options and in any
configuration available from the factory to which this declaration relates is in conformity with the
following standards:
Electromagnetic Compatibility Technical Construction File for APACS+ and QUADLOG, Issue 1.0,
dated 11 January 1996 was issued certificate number RFI\CBCB1\32341A by:
Edward M. Coll
General Manager
Systems Division
Spring House, PA USA
3/12/96