Sizing MV Cable
Sizing MV Cable
The values of R & X are respectively the net resistance and reactance of the cables.
The voltage drop allowable as per specification is 5% and hence within limits
Hence, the cable selected 2 Runs 3C x 300SQmm shall safely withstand the effects of short
circuit and shall carry the FLC within the permitted temperature limits and voltage drops.
LARSEN & TOUBRO LIMITED
ECC Division – EDRC
The values of R & X are respectively the net resistance and reactance of the cables.
Hence, the cable selected 2 Runs 3C x 300sqmm shall safely withstand the effects of short
circuit and shall carry the FLC within the permitted temperature limits and voltage drops.
LARSEN & TOUBRO LIMITED
ECC Division – EDRC
ROUTE LENGTH
VOLTAGE IN kV
MAX. DEMAND
TOTAL NO. OF
LOAD IN KVA
CONNECTED
CABLE SIZE
Remarks
(Mtrs.)
RUNS
(KVA)
SN
FROM TO
1 Main MV Board Raw Mill MV Board ( MV-11 ) 6.60 10489 9474 730 3 3C x 300
2 Main MV Board Kiln MV Board ( MV-12 ) 6.60 3519 3519 720 1 3C x 300
3 Main MV Board Clinker & Cooler -1 MV Board ( MV-13 ) 6.60 3309 3309 590 1 3C x 300
4 Main MV Board Cement Mill - 1 MV Board ( MV-14.1 ) 6.60 6709 6446 180 2 3C x 300
5 Main MV Board Distribution Transformer CCR& WS( 821TF05 ) 6.60 1600 1600 40 1 3C x 240
6 Main MV Board Emergency Transformer ( 828GN01TF10 ) 6.60 1250 1250 30 1 3C x 240