Specification For Instrumentation
Specification For Instrumentation
SECTION 01017
CONDITION SURVEY AND MONITORING
INDEX TO SPECIFICATION
CLAUSE PAGE
This specification section is the copyright of DPE Consultants Sdn Bhd. No reproduction either in part or
in whole in any manner whoever is allowed without written permission from DPE Consultants Sdn Bhd.
1.0 GENERAL
Read with the Particular Specification, and all other contract documents.
This technical specification shall form part of the Contract and the Contractor shall allow for all
obligations, requirements, considerations, etc. to comply with the specification. The Contractor is
also deemed to have visited the site and fully acquainted himself as to the nature and
practicability of the works. No claims will be entertained as a result of his failure to do all of the
above.
The Consulting Civil and Structural Engineer is DPE Consultants Sdn Bhd. The Contractor is to
note that when the term ‘Engineer’ in the following Specification means the representative of the
Consulting Engineer.
The Contractor is to note that when the term Client is referred to in the Specifications, such term
shall be deemed to mean the Employer/Developer unless the context otherwise requires.
The Contractor is to note that when the term Engineer is referred to in the following specification,
such term shall be deemed to mean The Architect as defined in the Articles of Agreement or any
other person designated in writing by the Architect from time to time to exercise the power of the
Architect as required.
The Works shall be carried out in accordance with the requirements of the Uniform Building By-
Laws of Malaysia, the Malaysian Standards and Codes of Practices, Malaysian Standards
Eurocodes current at the date of tender and to the satisfaction of the local Building Authorities
empowered to control the Works, the Specifications and drawings supplied to the Contractor and
any other instructions issued by the Engineer/Architect or their representative from time to time.
Any reference in the Specifications to a Malaysian Standard (MS), Eurocodes (EC) or Code of
Practices (CP) shall imply the latest version at the time of tender of the applicable Standards or
Code of Practices. Should there be any discrepancy between these Specifications and the MS,
EC or CP, the more onerous requirement/s shall be adopted. The Engineer has the sole
discretion to modify or upgrade the specifications, drawings and documents to comply fully with
MS, EC or CP requirements at no additional cost and time to the Contract.
1.1 Scope
This specification covers the requirements for the condition survey and monitoring of
buildings, services and other structures within the area of influence of other
construction works. The survey may be carried out prior to and / or after the execution
of the other construction works.
It applies generally to buildings and structures that could be affected by works such
as:
(a) Demolition
(b) Piling
(c) Earthworks
The requirements for instrumentation for monitoring are given in SECTION 01018
INSTRUMENTATION AND MONITORING.
Read this section in conjunction with the relevant requirements of the following work
sections:
Where the works are done as required by the authorities, comply with all standards
and regulation as directed by the authorities.
Submit and work to a quality control plan as agreed with the Engineer.
§ Inclinometers
§ Piezometers
§ Water Standpipes
§ Vibration Sensors
§ Settlement Markers
§ Load Cells
Take cognisance of and co-ordinate with other contractors on site who may
be carrying out instrumentation and monitoring works to avoid duplication of
installation and readings.
1.5 Definitions
Sections of the report relating to individual owners of the nearby and adjacent
buildings/properties must be distributed to the respective owners prior to commencing
any Works on Site.
Confirm in writing to Engineer and authorities (e.g. MRTC, SPAD, DBKL etc.) when
this requirement has been complied with.
Any delays in the issuance of the Permit to Commence Piling/Building Works due to
either an incomplete report, or a report unacceptable to the authorities remains the full
responsibility of the Contractor.
Provide adequate record to identify changes that occurred and to allow changes to
methods of the construction works such as to avoid or minimise damage to the
surveyed buildings.
When planning for suitable methods and instrumentation for the survey, take account
on the limits on movements and levels of vibration, refer to SECTION 01018
INSTRUMENTATION AND MONITORING, as well as in the respective specifications
relevant to the other construction works. Also take account of the frequency of
monitoring as indicated in the respective sections.
Take all necessary actions to ensure compliance with the environmental protection
and management regulations or the latest noise control regulations imposed by the
relevant authorities. In the absence of any guide, the noise level (maximum allowable
equivalent continuous noise level measured over a period of 5 minutes in dB) at the
nearest occupied building outside the site shall not exceed the following permissible
noise level. If there are specific guide published by the relevant authorities, the latest
applicable regulations shall apply.
7pm to 10pm
10pm to 7am
7pm to 10pm
10pm to 7am
10pm to 7am
7pm to 10pm
7am to 7pm
7am to 7pm
7am to 7pm
Types of
affected
buildings
(a) Hospital,
school,
No
home for 75 55 75 55 No Work
Work
the aged,
sick etc
(b) Residential
Buildings
located less
than 150m 90 70 55 90 70
from the
construction
site
(c) Buildings
other than
those in (a) 90 70 90 70 90 70
and (b)
above
Note: Noise levels in dBA (Leq 5mins)
3.1 Instrumentation
3.2 Camera
Use camera capable of producing digital records of the survey unless otherwise
agreed with the Engineer.
Plan to carry out the Works in a manner that the Works do not cause any damage to
the buildings or properties. Submit a workable and reliable working method to the
Engineer for acceptance. If damage is inevitable provide a solution to rectify the
damage to the Engineer for acceptance prior to commencement of any work.
Submit colour photographs, their negatives and *.jpg or *.bmp format files to the
Engineer for record. Comply with size and other requirements as described in the
contract. Where a digital camera is used, submit an electronic copy of the
photographs in either *.jpg or *.bmp format in place of the photograph negatives.
The photographs shall show clearly all required details and shall contain a graduated
scale and colour chart for reference. These shall be taken under natural light
condition and the intensity of light shall be uniform to reflect the natural colour of the
intended objects. Use flashlight only as agreed.
Ensure that all labels and markers are clearly identified within the photograph.
Give at least 48 hours notice of the intention to install any instrument unless otherwise
agreed by the Engineer. Install all instruments and establish initial readings prior to
the construction activity or area of works to which they relate unless otherwise agreed
by the Engineer.
Carry out a visual survey of all structural elements in the adjacent properties for
cracks in excess of 0.1mm. Notify the Engineer if there are signs of structural
damages. Mark the location of cracks thus identified on plans and elevations as
appropriate.
The survey shall include at least the cracks previously identified and agreed in the
report as described in the contract.
Establish the initial (datum) reading of each survey point and submit records to the
Engineer. Protect the datum during monitoring period.
Carry out a plumb survey to establish the verticality of the members where necessary.
Typical details of acceptable installations for ground and building settlement points
are shown in the drawings.
Monitor and record the levels of ground survey and building settlement points
throughout the duration of the Works to the accuracy of 0.5mm.
Review the monitoring records on receipt. Notify the Engineer immediately if the alert
or work suspension levels are reached and agree any action proposed.
4.12 Reinstatement
5.1 Submissions
Submit survey records within 1 week after completion of the survey. Provide each
neighbouring owner a copy of relevant portion of the survey as directed by the
Engineer.
5.3.1 General
Submit final records for each instrument incorporating any comments from
the Engineer within seven days of completion of installation of each
instrument.
(a) Instrument number and location (in eastern and northern co-ordinates
and level).
(b) Names of personnel responsible for installation.
(c) Time and date for commencement and completion of instrument.
(d) Plant and labour used.
(e) Ground conditions encountered (if applicable).
(f) Details of instrument installation (grout, fixings etc).
(g) Instrument readings during installation, calibration and immediately
after installation are completed.
(h) Location of instrument terminals, housings and any leads or cabling.
(i) Details of any splices, numbers of casings or joins.
(j) Details of any breakdowns or delays.
5.3.4.1 Frequency
5.4.1 Frequency
Submit the post-completion survey for the Engineer for record. Follow the same
procedures as for the pre-condition survey unless otherwise required by the Engineer.
SECTION 01018
INSTRUMENTATION AND MONITORING
INDEX TO SPECIFICATION
CLAUSE PAGE
This specification section is the copyright of DPE Consultants Sdn Bhd. No reproduction either in part or
in whole in any manner whoever is allowed without written permission from DPE Consultants Sdn Bhd.
1.0 GENERAL
Read with the Particular Specification, and all other contract documents.
This technical specification shall form part of the Contract and the Contractor shall allow for all
obligations, requirements, considerations, etc. to comply with the specification. The Contractor is
also deemed to have visited the site and fully acquainted himself as to the nature and
practicability of the works. No claims will be entertained as a result of his failure to do all of the
above.
The Consulting Civil and Structural Engineer is DPE Consultants Sdn Bhd. The Contractor is to
note that when the term ‘Engineer’ in the following Specification means the representative of the
Consulting Engineer.
The Contractor is to note that when the term Client is referred to in the Specifications, such term
shall be deemed to mean the Employer/Developer unless the context otherwise requires.
The Contractor is to note that when the term Engineer is referred to in the following specification,
such term shall be deemed to mean The Architect as defined in the Articles of Agreement or any
other person designated in writing by the Architect from time to time to exercise the power of the
Architect as required.
The Works shall be carried out in accordance with the requirements of the Uniform Building By-
Laws of Malaysia, the Malaysian Standards and Codes of Practices, Malaysian Standards
Eurocodes current at the date of tender and to the satisfaction of the local Building Authorities
empowered to control the Works, the Specifications and drawings supplied to the Contractor and
any other instructions issued by the Engineer/Architect or their representative from time to time.
Any reference in the Specifications to a Malaysian Standard (MS), Eurocodes (EC) or Code of
Practices (CP) shall imply the latest version at the time of tender of the applicable Standards or
Code of Practices. Should there be any discrepancy between these Specifications and the MS,
EC or CP, the more onerous requirement/s shall be adopted. The Engineer has the sole
discretion to modify or upgrade the specifications, drawings and documents to comply fully with
MS, EC or CP requirements at no additional cost and time to the Contract.
1.1 Scope
Read this work section in conjunction with the relevant requirements of the other work
sections as follows:
Unless otherwise agreed by the Engineer, ensure all of the Works comply with the
relevant requirements of the Authorities, Regulations, Standards and Codes listed
below or referenced in the body of the Specification. Alternative Standards and Codes
may be proposed for approval by the Engineer, provided it can be demonstrated that
the alternative Standards and Codes comply with the requirements of the standards
specified. All Standards and Codes quoted are the current version, unless specific
year references are noted.
In the event that the standards or codes are revised or superseded, refer to the latest
edition or the appropriate substitution for the relevant subjects.
Based on the information issue, propose and submit the following to the
Engineer for acceptance:
1.1.1.1. Select suitable make and model of the instrumentation for the
project.
1.1.1.3. Propose suitable schedule for the monitoring reading and records.
Co-ordinate with other contractors who may carry out other works at the
same time at the site. Take into account of site access, space occupation,
safety and safeguarding of adjoining properties and each other’s works.
Submit and work to a quality control plan as agreed with the Engineer.
Engage qualified crew of not less than two men to the Engineer’s
acceptance for the operation of each boring or drilling rig.
1.4.5.3 Installer
1.4.6 Safety
For works within Railway Protection Zone, ensure the works comply fully
with Railways (Railway Protection Zone) Regulations 1998.
3.0 MATERIAL/EQUIPMENT
Refer to Section 01016 Particular Specification and Drawings for the schedule of
instrumentation including the minimum frequency of reading to be implemented for
the works.
Provide data acquisition set up as per requirement in the contract. Provide remote
data acquisition in compliance with the following:
3.2.2.1 General
Use reliable and safe remote data collection systems with back-up
facilities in the event of mains power failure. Prove the reliability of
the logger prior installation by demonstration and records of
previous works.
Use a flex outlet without switches for all loggers when connected
to the mains electrical supply. Do not use plug sockets.
Logger stations are to collect the cabling from the various remotely
read instruments and from local terminal boxes, so that monitoring
can be conveniently carried out from a single position close to any
instrumented section.
Use cabling and connectors that are robust, water resistant and corrosion
resistant for instrumentation. Use only low smoke zero halon cabling for all
cables, which is durable and suitable for the proposed locations in the
works.
Use items that are extinguishable non-metallic and emit no toxic fumes in
the event of fire.
3.3.1 General
Inclinometers are to take the form of an access tube with four keyways (in
pairs at right angles), which shall be grouted in to a borehole.
The orientation of the keyways to be such that they are parallel to and
perpendicular to the orientation of any tunnel, excavation or wall or
otherwise as accepted by the Engineer.
3.3.3 Probe
Signal shall be emitted to confirm power failure and confirm that the battery
pack is operative.
When taking readings, insert the inclinometer probe in the tube. The
inclinometer shall travel along the whole length of the tube with its wheels
engaged in each pair of the keyways in turn to obtain deformation
measurements in both directions. A force balance accelerometer within the
probe shall respond to changes in alignment, which shall be displayed on a
portable readout unit.
Provide a calibration device with the instrument, which calibrates both the
probe and the portable readout unit to the acceptance of the Engineer.
3.3.7 Tubing
At the final ground level fit the inclinometer tubing with a removable cap
within a lockable vandal-proof cover set in a concrete surround.
The protection, cover and surround details shall be to the acceptance of the
Engineer.
3.4.1 General
3.4.2 Sensor
3.5.1 General
Set a datum magnetic ring at the base of the inclinometer tubing and also
within the instrument chamber base, located at the top of the borehole.
Check that the reading system is reliable and require minimal maintenance
over the required monitoring period. Thermal or other influences shall be
negligible.
Measure relative movement between the magnetic ring and the reference
magnetic ring at the top of the holes by a reed switch attached to a stainless
steel tape. Raise and lower the steel tape and reed switch assembly from
the top of the borehole.
3.6.1 General
Use rod extensometers in the form of a rod anchored at the remote end of
the borehole passing into a plastic tube fixed in a reference collar at the
open end of the hole.
Install no more than six rods in a single hole with each rod of a different
length so that displacements at various borehole depths may be recorded.
Where more than six rods are required, prepare another borehole as close
as possible to the initial hole and rods set at alternate depths in each hole.
3.6.3 Materials
Rods to be fabricated from stainless steel. The grade of steel rod shall suit
the environment and duration of the project. Make provision for threading
the anchor points onto the rod.
Measure relative movement between the end anchor and the reference
collar by an automated measurement device (an electrical transducer)
registering on the free end of the rod and by manual means using a system
to the acceptance of the Engineer.
Use a tape extensometer that is capable of being read to ±0.15 mm, and have a
range of 20 m. Demonstrate a repeatability of reading to ±0.15 mm prior to use.
Deep Levelling Datum to comprise of a 25mm galvanised steel rod cast into a 250mm
diameter grout filled steel casing positioned within a 300mm diameter steel casing.
Fill the annulus between the two casings with grease. The top of the 25 mm steel rod
shall be domed and centre punched.
3.9 Levels
3.10 Piezometers
Piezometers shall be in place and calibrated two weeks before any excavation work
starts. They shall be installed at about 1m from the external temporary wall system face,
if any, as soon as practicable after the wall system has been installed.
The piezometer shall measure pore water pressure with an accuracy of not less than
0.5% full scale ±0.2m head of water and a resolution of 0.1m head of water.
3.10.1.1 Tube
3.10.1.2 Filter
3.10.1.3 Tip
Do not use.
A plan showing location of all vibration monitoring sensors must be prepared by the
Contractor’s PE. All buildings/structures likely to be affected by either the temporary
works, excavation or piling works must be included with sensors installed.
3.13 Tell-Tales
Tell tales to generally comprise of two clear plastic overlapping plates, one marked
with a millimetre scale the other with a cross-hair marking to allow reading on two
axis.
obstruction.
Install prism reflector targets at the locations shown in the drawings. Targets should
be durable, not damaged by rain and fixed so that they are not disturbed by vibration.
Ensure the working range of the sensors to be at least –40° Celsius to +60° Celsius
with an accuracy of ±1° Celsius. All sensors to be capable of being remotely
monitored and the data being downloaded to a computer in an ASCII file format.
3.16.1 General
The water level is measured normally by lowering a dipmeter probe from ground level.
The water standpipes shall be installed where possible, in sandy layers of high
permeability. Water standpipes shall be in place and calibrated two weeks before any
excavation work starts. They shall be installed at about 1m from the external
temporary wall system face, if any, as soon as practicable after the wall system has
been installed.
The water standpipe shall measure water level with an accuracy of not less than 0.01m
head of water.
The water table should not be reduced by more than 1m during excavation in any of the
water standpipes. Should the drop in water level approach this value, then the
Contractor shall immediately notify the Engineer and the Contractor must take
immediate action to prevent damage to relevant structures.
Load cells are to be used for measuring forces in the struts and braces of a strutted
excavation. It is very important to ensure that struts and bracing are accepting loads
and performing their tasks; also whether these members accept greater than designed
loads (indicating that additional struts/bracing may be required).
4.1 General
Maintain all instruments, including readout and data loggers, required for
monitoring in a satisfactory working order for the duration of the monitoring
programme.
4.1.2 Storage
4.1.3.1 Grouting
Introduce the grout using a tremie pipe which is kept below the
surface of the grout as filling proceeds. Agree on methods to be
used where ground conditions make normal grouting
impracticable. Leave the area in a clean and tidy condition.
4.1.3.2 Testing
Fix the equipment such that it is capable of resisting vandalism and adverse
climatic conditions at surface locations. In addition, protect all instruments
by hoarding or barriers as directed.
Tag all external visible protective covers to equipment using aluminum rigid
nameplates of minimum size 2500 mm2, swg 24 or similar to the acceptance
of the Engineer, identifying the following:
Records of all readings have to be kept up to date on Site for inspection at any time.
Records shall be kept in the Contractor’s site office and at the office of the Resident
Engineer. All records/data must be certified by the Contractor’s PE and submitted to
the Engineer within one week. The Engineer shall be notified immediately in the event
an alert level is reached for any of the instruments.
Each instrument shall be assigned an identification number. This number shall also be
indicated on: -
Vary the frequency depending upon the stage of the works. In some cases
continuous logging will be required.
When planning for suitable methods and schedule for monitoring, take
account of the limits of movement and levels of vibration for the adjacent
buildings as set out in the Section 01016 Particular Specification and
Drawings.
Do not use any form of instrument which uses electrical resistance methods
for taking readings unless otherwise agreed.
Read all instruments as soon as possible after installation and at least once
per day for a period of two weeks thereafter. Where instruments appear not
to have stabilised, for example exhibiting a continued drift in the readings,
the cause shall be identified and the fault rectified and a new set of readings
provided. When all instruments are showing consistent results for a period
of 1 week, readings shall be averaged to provide a datum reading.
When recording instrumentation readings, record all site conditions that may
affect the results, including temperature and humidity readings.
Record also the instrument type, location reference, datum and time of
reading, personnel carrying out the readings and measuring instrument or
readout unit reference.
Take backup copies on a daily basis on two sets of disks; one set to be
stored remote from the site office.
Use the same recording devices, e.g. tape extensometers, level, EDM and
Theodolite, etc. at any given location throughout the monitoring programme.
4.3.1 General
4.3.2 Installation
4.3.3 Tubing
Provide the tubing with appropriate couplings for joining tube lengths to the
required borehole length. Cap the base of the tube.
Adequately fix and seal the cap and coupling joints so that the tube is grout-
and dirt-tight.
Lower the joined and sealed tubing into the borehole and grout the annulus
using a bentonite/cement grout tremied to the bottom of the hole. Fix the
tubing from rotation while being lowered.
Provide suitable means of measuring the position of the probe down the
borehole to an accuracy of ±10 mm from a reference point at the top of the
borehole.
Where inclinometers already exist and are to be extended, the new tubing
shall match the existing tubing.
Check stability and gain of the reading system at weekly intervals unless
otherwise agreed, and provide results to the Engineer.
Carry out spiral and inclination check prior to establishing the datum
reading.
4.4.1 General
4.4.2 Installation
4.4.3 Tubing
Provide the tubing with appropriate couplings for joining tube lengths to the
required borehole length.
Adequately fix and seal the cap and coupling joints so that the tube is grout-
and dirt-tight.
Lower the joined and sealed tubing into the borehole and grout the annulus
using a bentonite/cement grout tremied to the bottom of the hole. Fix the
tubing from rotation while being lowered.
4.4.4 Sensor
Check stability and gain of the reading system at weekly intervals by means
of three “dummy” electrolevels using precise resistors.
Carry out spiral and inclination checks prior to establishing the datum
reading.
4.5 Extensometers
(a) Fix a level survey point to the top of the reference head of the
extensometer to allow precise levelling back to a datum.
(b) Check the level survey point each time the instrument is read,
unless otherwise accepted by the Engineer.
Isolate each rod Individually by its own plastic sleeve and grout
the complete assembly in place, fixing the anchors to the ground
but allowing free movement of each rod within its sleeve.
Fix a level survey point to the top of the reference head of the
extensometer to allow precise levelling back to a datum.
Determine the lengths of rods using the level of the ground at the
hole location. For grout used for backfilling, use bentonite/cement
mix with just sufficient water to allow it to be tremied to the bottom
of the holes.
Adjust the tension of the tape and take the tape and calliper readings.
Use the same extensometer for each set of readings to maintain
consistency.
4.6.1 Installation
Install a 300mm diameter casing not less than 300 mm into firm ground.
Install the 250 mm diameter casing not less than 1500mm beneath the
300mm casing and fill with water cement grout that is just pumpable. Ensure
the founding depth of deep levelling datum to be such that the founding
strata is not affected by the construction activity.
4.6.2 Protection
Protect the top of the Deep Levelling Datum by a manhole cover and by a
surface protection barrier to the acceptance of the Engineer.
4.7 Piezometers
In placing the sand, ensure that no sand adheres to the soil in the sides of
an unlined hole. Where there is water in a hole, allow sufficient time for all
the sand to settle, and take measurements of the upper surface of the sand
from time to time to ensure this. Record the final elevation of the top of the
sand.
Tamp the bentonite seal formed of either stiff hard rolled balls or pellets over
the sand to a thickness of approximately 1500 mm. Backfill the hole with
bentonite/cement grout mix to the acceptance of the Engineer. Terminate
grout backfill at the base of the instrumentation chamber.
Check that the tip of each piezometer is air free and the porous stone of the
tip is fully saturated by submergence in clean de-aired water for a period of
at least 24 hours prior to installation.
4.7.7 Records
Take samples of ground water of not less than one litre from the standpipes
and piezometer when required.
Store the water samples in clean sealed containers; clearly label and deliver
to the laboratory for chemical tests.
The tests for sulphate content (% SO3), chloride content, acidity (pH value)
and degree of salinity shall be determined from the same sample.
Ensure strain gauges and cabling are compatible for their intended location. Protect
them against any disturbance from the site activities.
Attach the bars at two locations only to limit the bending induced in the bars
changes by less than 50µε.
4.10 Tell-Tales
Fix the overlapping plates securely so that a gap of not greater than 1 mm separates
them at the start of monitoring and so that the cross-hairs are zeroed. Record the
location, orientation and plate separation for each telltale on the reading sheets.
Typical details of acceptable installations for ground and building settlement points
are shown in the drawings.
Monitor and record the levels of ground survey and building settlement
points throughout the duration of the Works, using a precise level and staff
accurate to 0.5mm or better.
Keep adjacent roads, neighbouring properties and structures clear of equipment and
spoils and regularly inspect the surface of the ground, properties and structures.
4.13 Completion
Remove all specialist monitoring and make good all installations to the satisfaction of
the Engineer upon completion of the monitoring, or at other such times if accepted by
the Engineer.
5.1 Submissions
Submit detailed method statements for the installation of all instruments for
the acceptance of the Engineer prior to installation.
5.1.2.1 Content
Submit detailed drawings showing the precise location and depth for
instrument installation for the acceptance of the Engineer prior to
commencement of installations.
Submit full details of the proposed data management system for the
acceptance of the Engineer. These shall include proposed formats for data
acquisition, checking, processing, and subsequent reporting to the Engineer
for all instruments.
5.1.6 Calculations
Carry out periodic checks at appropriate intervals to confirm the validity of calibration
of equipment in accordance with the manufacturer’s instructions and make any
necessary adjustments. Check instruments to have a validity of calibration at least 3
months after their last intended reading in the project.
Keep records of checks, errors recorded and whether any adjustment was
undertaken.
Retain copies of all certification and other records on site and make
available for the Engineer’s inspection when required.
5.3.1 General
Submit final records for each instrument incorporating any comments from
the Engineer within seven days of completion of installation of each
instrument.
(a) Instrument number and location (in eastern and northern co-ordinates
and level).
(b) Names of personnel responsible for installation.
(c) Time and date for commencement and completion of instrument.
(d) Details and records of boreholes.
(e) Plant and labour used.
(f) Ground conditions encountered (if applicable).
(g) Details of instrument installation (grout, fixings etc).
(h) Instrument readings during installation, calibration and immediately
after installation are completed.
(i) Location of instrument terminals, housings and any leads or cabling.
(j) Details of any splices, numbers of casings or joins.
(k) Details of any breakdowns or delays.
The registered surveyor shall establish the initial (datum) reading of each
survey point and submit records to the Engineer. Unless otherwise agreed,
submit the datum readings prior to any excavation and construction works.
5.3.6.1 Frequency