Revised Phed BSR 2023
Revised Phed BSR 2023
Government of Rajasthan
APPLICABLE FOR
Issued by:-
Chief Engineer (Tech) & TM.
RWSSMB, PHED, Jaipur
PUBLIC HEALTH ENGINEERING DEPARTMENT
Government of Rajasthan
CONTENTS
Chapter No. Chapter P. No.
1 Pipe Line Works. 1-18
2 Construction and Commissioning of Tube Wells, Open Wells
19-28
and Hand Pumps.
3 RCC Reservoirs. 29-44
4 Earth Work, Road cutting, Repairing & Trenchless Laying. 45-48
5 Pump Sets. 49-54
6 Valves and Appurtenance. 55-66
7 DOL/Star Delta Starter type LT Panels. 67-69
8 Construction of Pump House and Boundary Wall. 70-71
9 Valve Chambers 72-74
10 Solar based water supply schemes. 75-78
11 Instrumentation. 79-81
12 Earth Work & Civil Works related to Storage Tank, Filter
82-84
media work
13 Construction and Commissioning of water treatment plants
85
(WTP)
14 Miscellaneous. 86-87
Chapter 1
Pipe line work
S. No. Description Unit Rate (Rs.)
DI PIPES
1.1 Providing, lowering, laying in trenches, aligning, fixing in position
and jointing Ductile Iron (DI) ISI marked K-7 grade S&S pipes as
per IS:8329-2000 (amended up to date), with internal cement
mortar lining suitable for potable water with rubber ring (EPDM)
joints as per IS: 5382-1985 including all taxes (Central and local),
transportation and freight charges, inspection charges, loading/
unloading charges, including cost of labour and material, specials
(Tee, bend etc.) satisfactory hydraulic testing, disinfection,
commissioning etc. complete as per technical specifications and
direction of Engineer-in-charge. (excluding earth work)
Note : Providing and fixing of all requisite specials as per drawing,
design and layout are inclusive in RM measurement of the item and
shall not be paid separately.
Providing and applying Solvent free, two pack liquid epoxy lining to
internal surface of M.S. Pipe as per BS 6920:2000 and AWWA C210
standard including preparation of internal surface of pipe by
cleaning and abrasive blasting including field joints coating at site
1.12 SQM 409.00
complete as per technical specification and direction of Engineer in
In charge. Liquid Epoxy shall be NSF/WARS approved for drinking
water and minimum thickness of lining shall be 406 microns.
Notes
1) Class mentioned below represents the Factory Test pressure of pipe.
Plain ended CI specials including tail piece, spigot end and socket
1.24.1
end.
1.24.1.1 Up to 300 mm dia Kg 111.00
1.24.1.2 Above 300 mm and up to 600 mm dia Kg 129.00
1.24.2 Double flanged CI pipe fittings.
1.24.2.1 Up to 300 mm dia Kg 128.00
1.24.2.2 Above 300 mm and up to 600 mm dia Kg 143.00
House hold tap connections
1.25 Providing Household Tap Connection as per technical specification and
approved drawing as per relevant IS code (amended up to date) from
uPVC/DI/AC/MS/GI pipe line up to consumer meter/premises by using
PP/MS saddle piece (Complete job).This job includes digging out
suitable size of pits and trench for laying service line in all kinds of soil
(excluding road); depositing and refilling of pit & jhiri with watering &
ramming /compacting in layers and disposal of surplus excavated soil as
directed with in a lead of 100 meter ; providing & fixing of all fitting
duly approved in accordance with specification for potable water
including MS/PP saddle piece, gunmetal ferrule 4.0 mm , GM Full-way
Valve (IS:778 Mark) or ball valve (min. weight 165 gm) and specials,
below ground level 20 mm nominal dia MDPE pipe PE 80 PN 16 as per
ISO 4427 / 20 mm nominal dia PPR-C (Three layered) pipe PN16 SDR
7.4 (IS:15801:2008) (ISI mark) and above ground level using 20 mm dia
PPR-C pipe with standard PPR fittings/ 15 mm dia GI pipe with fittings
in the premises for fixing a tap / meter box (excluding) , inc
accessories with flushing, cleaning, disinfecting and testing of pipe line
complete required for making of service connection complete in all
respect including labour charges . The service line should be laid at
least 45 cm below ground level.
Note: Road cut and restoration is not part of this item and paid
separately.
1.25.1 For connection with 20 mm dia MDPE/PPR-C pipe length up to 05 Each 1658.00
mtr.
1.26.1 For connection with 20 mm dia MDPE/PPR-C pipe length up to 05 Each 1986.00
mtr.
1.27 Providing Household Tap Connection as per technical specification and
approved drawing as per relevant IS code (amended up to date) from
HDPE/uPVC/DI/AC/MS/GI pipe line up to consumer meter/premises
by using PP mechanical Integrated saddle with inbuilt flow control
valve made out of SS316 designed for 5 LPM discharge at 0.5 bar
pressure , not exceeding the flow of 7 LPM at 2 bar and a
compression elbow, moulded in single piece/ fusion welded
(Complete job) including digging out suitable size of pits and trench for
laying service line in all kinds of soil; depositing and refilling of pit &
jhiri with watering & ramming /compacting in layers and disposal of
surplus excavated soil as directed with in a lead of 100 meter ;
providing & fixing of all fitting duly approved in accordance with
specification for potable water including GM Full-way Valve (IS:778
Mark) or wheel valve and specials with 20 mm nominal dia MDPE pipe
PE 80 PN 16 as per ISO 4427 / 20 mm nominal dia PPR-C (Three
layered) pipe PN16 SDR 7.4 (IS:15801:2008) (ISI mark) and above
ground level using PPR-C pipe with standard PPR fittings/ GI pipes in
the premises for fixing a tap / meter box (excluding) ,including
accessories with flushing, cleaning, disinfecting and testing of pipe line
complete required for making of service connection complete in all
respect including labour charges . The service line should be laid at
least 45 cm below ground level.
Note: Road cut and restoration is not part of this item and paid
separately.
P & F Bib cock (IS : 8931 mark), superior quality of approved make, Each 311.00
1.29 chrome plated with complete brass body including brass handle
with wt. 300 to 325 gm.15 mm nominal bore.
Road cutting for house hold service connection in minimum trench Mtr 200.00
width wherever road crossing is required. Road cutting of cement
concrete,WBM, Black top etc. of all thickness shall be done by using
1.30 a concrete cutter machine keeping minimum trench width and
restoration of the road with Cement concrete with PCC M-10 and CC
M-30 grade as per specification and direction of Engineer in charge..
Add extra over item no 1.21, 1.22 & 1.23 for providing 20 mm PE Mtr 44.00
1.31 80 PN 16 as per ISO 4427 MDPE pipe including excavation,
providing, laying & jointing of service line above 5.00 mtr.
Add extra over item no 1.21, 1.22 & 1.23 for providing 20 mm ISI Mtr 57.00
marked PN16 SDR 7.4 (IS:15801:2008) PPR-C (Three layered) pipe
1.32
including excavation, providing, laying & jointing of service line
above 5.00 mtr.
PVC-O Pipe
Providing, lowering, laying and jointing in trenches, standard
lengths ISI marked Rigid PVC-O S/S Pipes (push on joints) as per IS-
16647: 2017 (amended up to date) with EPDM Gasket seals on
joints including all taxes , transportation and freight charges,
inspection charges, loading/ unloading charges, stacking of pipes,
laying of pipes, including cost of labour and material, specials (Tee,
1.33
bend etc.), satisfactory hydraulic testing, disinfection etc. complete
as per technical specifications and direction of Engineer-in-charge of
following class and diameter.
Note : Providing and fixing of all requisite specials as per drawing,
design and layout are inclusive in RM measurement of the item and
shall not be paid separately.
1.33.1 PVC-O pipe Class 500 PN-16
1.33.1.1 110 mm dia RMT 874.00
1.33.1.2 160 mm dia RMT 1480.00
1.33.1.3 200 mm dia RMT 1701.00
1.33.1.4 250 mm dia RMT 2280.00
1.33.1.5 315 mm dia RMT 2780.00
1.33.2 PVC-O pipe Class 500 PN-12.5
1.33.2.1 110 mm dia RMT 757.00
1.33.2.2 160 mm dia RMT 1281.00
1.33.2.3 200 mm dia RMT 1462.00
PTMT Bib Cock
Providing and fixing ISI mark (IS 9763: 2000 or amended up to date) Each 196.00
PTMT bib cock 15 mm nominal bore, minimum weight 92 gms and
1.34 length 100 mm as per technical specification, approved make and
direction of Engineer in charge.
Construction and Commissioning of Tube wells, Open Wells & Hand Pumps.
2.1.5 Add 40% extra on above item (Item no 2.1.1 to 2.1.3) for drilling depth beyond
200 mtr, rate shall be applicable for only extra depth beyond 200 mtr .
2.2 Construction of Tube Well from ground level and up to 100 mtr. depth to
accommodate housing and assembly pipe in all type of alluvium strata,
unconsolidated formation such as pebbles, boulders etc. by percussion/ rotary
drilling method as per IS:2800 Part 1: 1991 and IS:2800 Part II: 1979 (both
amended up to date) and technical specifications for removal of overburden.
The work includes the cost of lowering of casing pipe, but excludes the cost of
casing pipe.
2.2.1 Nominal bore 200 mm dia. Mtr 1227.00
2.2.2 Nominal bore 250 mm dia. Mtr 1384.00
2.2.3 Add 15% extra on above item (Item No 2.2.1 to 2.2.2) for drilling depth beyond
100 mtr, rate shall be applicable for only extra depth beyond 100 mtr .
2.7 Deepening of existing tube well by DTH system beyond existing depth up to 100
mtr. and above in all type of rocks including flushing of tube well and obtaining
sand free water.
2.7.1 Nominal bore 150 mm dia. Mtr 927.00
2.7.2 Nominal bore 200 mm dia. Mtr 1344.00
2.8 Testing verticality of tube well by plumbing system and yield test and draw
down test by pumping system as per IS : 2800 (Part – II) – 1979 or as per Each 8178.00
amended up to date.
2.9 Supplying & Packing P-gravel suitable for slot size/mesh size as suggested in IS
2800 (Part-1) 1991 or as per amended up to date. Cum. 4109.00
2.10 Development of tube well having depth up to 250 mtr as per IS: 11189- 1985
and IS: 2800 (Part- I)- 1991 (both amended up to date) using suitable methods
Hr. 1456.00
to give sand free water for required yield of the gravel packed tube well.
2.11 Supply of ERW M.S. black casing pipe ISI marked (IS: 4270/2001) or amended
up to date of following sizes
2.11.1 150 mm dia NB(Thickness of pipe 5.0 mm & mass of tube 20.13 Kg/m) Mtr 1933.00
2.11.2 200 mm dia NB (Thickness of pipe 5.4mm & mass of tube 28.46 Kg/m) Mtr 2734.00
2.11.3 250 mm dia NB (Thickness of pipe 7.1 mm & mass of tube 46.57 Kg/m) Mtr 4473.00
2.12 Labour charges for making slots on blank pipes made of ERW MS black pipe ISI
marked of following sizes, the slotting should be as per IS:8110-1985.
2.17 Supply and Fixing of electric control feeder panel comprising of suitable rating
MCCB, DOL starter, overload relay, ampere meter, volt meter, phase preventer,
phase indicators, lighting arrangement etc. complete suitable for three phase
pump set. The panel should have space for energy meter ( supplied by
DISCOM). All these equipments shall be housed by panel box made out from 18
gauge M.S. Sheet with powder coating. Panel should be of minimum size 900 x
600 x 300mm with Stand ( made of angle iron of size 35x35x5mm) duly
bolted/screwed with enclosure box having 4 legs, each leg’s length 18" and
double door including in built locking system. The legs should be embedded in
M-15 cement concrete platform. The size of CC platform should be equal or
bigger than the base size of panel having height of at least 200 mm from
ground level. The panel should have opening of suitable size in front of space
for energy meter with glass for meter reading. The operation of panel should
be suitable for on 440 Volt AC Supply.
2.23 Supply & Fixing tube well cover of MS sheet 8mm thick at top & 5mm thick
100mm wide shroud around the edge so as to form a cap on the top end of
casing pipe with GI Nipple 45cm long & two GI flanges at both ends in 80mm
sizes passing through a hole in the centre of MS sheet. A 25 mm socket with
end plug shall also be welded over top plate. A GI nipple having outside thread
of size 1/2" (for installation pressure gauge) shall be provided & welded with
80mm GI nipple near top plate nipple shall be provided with end plug.
2.32 Supplying & Installing 100 mm diameter sealed diaphragm bourdon type
pressure gauge of range 0 to 10 kg. including all jointing material as per Each 1243.00
specification with safety cover.
2.33 Construction of bore hole for shallow depth tube well from ground level to
required depth for following size for all type of relevant strata by percussion/
rotary drilling/ hand boring method excluding cost of casing pipe. The bore
hole should be as per nominal bore of PVC casing pipe. The work will be
complete after obtaining sand free water.
2.33.1 125 mm dia nominal bore Mtr. 347.00
2.33.2 150 mm dia nominal bore Mtr. 387.00
2.33.3 200 mm dia nominal bore Mtr. 551.00
2.33.4 250 mm dia nominal bore Mtr. 775.00
2.34.1 Shallow well casing pipe (CS) suitable for depth up to 80 mtr.
2.34.1.1 150 mm nominal dia ( internal dia ). Mtr 475.00
2.34.1.2 200 mm nominal dia ( internal dia ). Mtr 872.00
2.34.1.3 250 mm nominal dia ( internal dia ). Mtr. 1362.00
2.34.2 Medium well casing pipe (CM) suitable for depth above 80 mtr and up to 250
mtr.
2.34.2.1 100 mm nominal dia ( internal dia ) Mtr. 282.00
2.34.2.2 125 mm nominal dia ( internal dia ) Mtr. 450.00
2.34.2.3 150 mm nominal dia ( internal dia ) Mtr 616.00
2.34.2.4 200 mm nominal dia ( internal dia ) Mtr 1114.00
2.34.2.5 250 mm nominal dia ( internal dia ) Mtr. 1733.00
2.35 Supply of ISI mark AC pressure pipe class 15 manufactured by MAZZA process
as per IS:1592-2003 or amended up to date, for casing of tube well for
following dia nominal bore, with jointing material PVC coupler as per technical
specification and direction of Engineer In charge.
2.35.1 125 mm nominal dia Mtr 328.00
2.35.2 150 mm nominal dia Mtr 581.00
2.35.3 200 mm nominal dia Mtr 955.00
2.35.4 250 mm nominal dia Mtr 1279.00
2.35.5 300 mm nominal dia Mtr 1855.00
2.36 Making slots of hole size and Nos. as directed by EIC in AC pressure pipe Class
15 as per technical specification for using slotted pipe in TW casing. Per 100 no. 98.00
RCC Reservoirs
Sr. No. Description Unit Rate (Rs.)
3.1 Construction and commissioning of RCC flat slab Over Head Service Reservoir of
following capacity and staging including all material and labour charges as per the Scope
of work and Technical Specification, consisting of the following main activities: -
a) Topographic survey, preparation of site contour plan, conducting SBC test and its
approval from department before construction. Submission and approval of concrete mix
design and water quality test report for water to be used in construction.
b) Excavation in all types of soil, PCC below foundation, all RCC Work, Plinth protection all
around the structure including all material, labour, shuttering, scaffolding etc.
c) OHSR shall be provided with adequate plinth protection all around the structure in a
width starting from edge of structure at GL and extending at least up to 1.0m beyond the
edge of outer most projection of OHSR. The plinth protection shall consist of 150mm thick
PCC in M-15 grade concrete laid over 150mm thick layer of compacted soil.
d) Providing and applying two coats of food grade epoxy paint on the inside surface roof
slab, and 600 mm height of the vertical wall.
e) Successfully hydro test and water tightness test as per I.S. code.
f) Providing and applying three coats of anti-carbonation paint on the top surface of the roof
slab.
g) Providing and applying three coats of cement-based paint on the external surface of the
container, balcony, cone wall, columns & beams etc.
h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS-304 ladder
from top Slab to bottom Slab inside container.
i) Providing and fixing of MS section ladder from the last landing to balcony and MS ladder
with safety cage from balcony to top slab.
3.1.1 Rates for RCC OHSR,SBC 7 T/sqm, SEISMIC ZONE-II & STAGING 15 M
3.1.1.1 50 KL capacity Litre 41.69
3.1.1.2 75 KL capacity Litre 34.38
3.1.2 Rates for RCC OHSR,SBC 7 T/sqm, SEISMIC ZONE-III & STAGING 15 M
3.1.2.1 50 KL capacity Litre 43.28
3.1.2.2 75 KL capacity Litre 35.28
3.1.3 Rates for RCC OHSR,SBC 7 T/sqm, SEISMIC ZONE-IV & STAGING 15 M
3.1.3.1 50 KL capacity Litre 45.96
3.1.3.2 75 KL capacity Litre 37.82
3.1.4 Rates for RCC OHSR,SBC 10 T/sqm, SEISMIC ZONE-II & STAGING 15 M
3.1.4.1 50 KL capacity Litre 38.16
3.1.4.2 75 KL capacity Litre 29.85
3.1.5 Rates for RCC OHSR,SBC 10 T/sqm, SEISMIC ZONE-III & STAGING 15 M
3.1.5.1 50 KL capacity Litre 38.95
3.1.5.2 75 KL capacity Litre 30.60
3.1.6 Rates for RCC OHSR,SBC 10 T/sqm, SEISMIC ZONE-IV & STAGING 15 M
3.1.6.1 50 KL capacity Litre 39.72
3.1.6.2 75 KL capacity Litre 31.10
3.1.7 Rates for RCC OHSR,SBC 18 T/sqm, SEISMIC ZONE-II & STAGING 15 M
3.1.7.1 50 KL capacity Litre 36.69
3.1.7.2 75 KL capacity Litre 28.70
3.1.8 Rates for RCC OHSR,SBC 18 T/sqm, SEISMIC ZONE-III & STAGING 15 M
3.1.8.1 50 KL capacity Litre 37.81
3.1.8.2 75 KL capacity Litre 29.55
3.1.9 Rates for RCC OHSR,SBC 18 T/sqm, SEISMIC ZONE-IV & STAGING 15 M
3.1.9.1 50 KL capacity Litre 38.51
3.1.9.2 75 KL capacity Litre 30.17
3.2 Construction and commissioning of RCC INTZE type Over Head Service Reservoir of
following capacity and staging as per the Scope of work and Technical specifications,
consisting of the following main activities: -
a) Topographic survey, preparation of site contour plan, conducting SBC test and its
approval from department before construction. Submission and approval of concrete mix
design and water quality test report for water to be used in construction.
b) Excavation in all types of soil, PCC below foundation, all RCC Work, Plinth protection all
around the structure including all material, labour, shuttering, scaffolding etc.
c) OHSR shall be provided with adequate plinth protection all around the structure in a
width starting from edge of structure at GL and extending at least up to 1.0m beyond the
edge of outer most projection of OHSR. The plinth protection shall consist of 150mm thick
PCC in M-15 grade concrete laid over 150mm thick layer of compacted soil.
d) Providing and applying two coats of food grade epoxy paint on the inside surface on the
top dome, edge beam and 600 mm height of the vertical wall.
e) Conducting successfully hydro test and water tightness test as per I.S. code.
f) Providing and applying three coats of anti-carbonation paint on the top surface of the Top
Dome.
g) Providing and applying three coats of cement-based paint on the external surface of the
container, balcony, cone wall, columns & beams etc..
h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS-304 ladder
from top dome/Slab to bottom dome/Slab inside container.
i) Providing and fixing of MS section ladder from the last landing to balcony having railing all
around it and MS ladder with safety cage from balcony to top dome/slab.
j) Providing and fixing water level indicator (float type).
k) Providing and fixing of hand railing all around the balcony, top dome and staircase
consisting of 25mm diameter Class-B GI pipe in two rows and 1000 mm high, 50X50X6mm
angle iron vertical post at a maximum spacing of 1500mm centres.
l) All MS parts to be painted with two coats of the enamel paint over the primer coat of red
oxide.
m) Providing and fixing of 150mm wide PVC water bar for the construction joints in the
container (vertical wall & cone wall).
n) Providing one Aluminium portable ladder of appropriate length to access first landing (3.5
to 4.5m above GL) from ground.
o) Lighting arrestor consisting of providing and fixing of 2 Nos. of chemical earthing and
connecting it to the conical cover of SS ventilator with two separate GI strips of
50mmX3mm.
p) CI/DI puddle collar shall be fixed in the bottom dome/ slab for connecting inlet, outlet,
overflow and washout pipe of the reservoir.
q) Painting the name of the scheme and other details on the reservoir, and any other work
related to structure as per the directions of Engineer-in- Charge, Technical Specification and
Scope of Work.
r) Inlet, outlet, overflow, washout pipes and valves are not included in this work,
provision for the same shall be taken separately.
3.2.1 Rates for RCC OHSR,SBC 7 T/sqm, SEISMIC ZONE-II & STAGING 18 M
3.2.1.1 100 KL capacity Litre 30.79
3.2.1.2 150KL capacity Litre 24.05
3.2.1.3 200KL capacity Litre 21.01
3.2.1.4 250KL capacity Litre 20.45
3.2.1.5 300KL capacity Litre 21.07
3.2.1.6 400KL capacity Litre 19.15
3.2.1.7 500KL capacity Litre 18.28
3.2.1.8 600 KL capacity Litre 16.20
3.2.1.9 700 KL capacity Litre 15.51
3.2.1.10 800 KL capacity Litre 14.94
3.2.1.11 900 KL capacity Litre 14.45
3.2.1.12 1000 KL capacity Litre 14.03
3.2.1.13 1250 KL capacity Litre 13.17
3.2.1.14 1500 KL capacity Litre 12.46
3.2.1.15 1750 KL capacity Litre 11.86
3.2.1.16 2000 KL capacity Litre 11.36
3.2.2 Rates for RCC OHSR,SBC 7 T/sqm, SEISMIC ZONE-III & STAGING 18 M
3.2.2.1 100 KL capacity Litre 31.38
3.2.2.2 150KL capacity Litre 24.80
3.2.2.3 200KL capacity Litre 21.62
3.2.2.4 250KL capacity Litre 21.27
3.2.2.5 300KL capacity Litre 21.60
3.2.2.6 400KL capacity Litre 19.70
3.2.2.7 500KL capacity Litre 18.80
3.2.2.8 600 KL capacity Litre 16.56
3.2.2.9 700 KL capacity Litre 15.85
3.2.2.10 800 KL capacity Litre 15.27
3.2.2.11 900 KL capacity Litre 14.76
3.2.2.12 1000 KL capacity Litre 14.33
3.2.2.13 1250 KL capacity Litre 13.46
3.2.2.14 1500 KL capacity Litre 12.77
3.2.2.15 1750 KL capacity Litre 12.23
3.2.6 Rates for RCC OHSR,SBC 10 T/sqm, SEISMIC ZONE-IV & STAGING 18 M
3.2.6.1 100 KL capacity Litre 31.74
3.2.6.2 150KL capacity Litre 24.98
3.2.6.3 200KL capacity Litre 21.66
3.2.6.4 250KL capacity Litre 21.72
3.2.6.5 300KL capacity Litre 21.29
3.2.6.6 400KL capacity Litre 17.58
3.2.6.7 500KL capacity Litre 17.04
3.2.6.8 600 KL capacity Litre 15.10
3.2.6.9 700 KL capacity Litre 14.26
3.2.6.10 800 KL capacity Litre 13.57
3.2.6.11 900 KL capacity Litre 12.99
3.2.6.12 1000 KL capacity Litre 12.50
3.2.6.13 1250 KL capacity Litre 11.50
3.2.6.14 1500 KL capacity Litre 10.75
3.2.6.15 1750 KL capacity Litre 10.16
3.2.6.16 2000 KL capacity Litre 9.67
3.2.7 Rates for RCC OHSR,SBC 18 T/sqm, SEISMIC ZONE-II & STAGING 18 M
3.2.7.1 100 KL capacity Litre 24.90
3.2.7.2 150KL capacity Litre 19.44
3.2.7.3 200KL capacity Litre 17.25
3.2.7.4 250KL capacity Litre 15.99
3.2.7.5 300KL capacity Litre 15.75
3.2.7.6 400KL capacity Litre 13.93
3.2.7.7 500KL capacity Litre 12.86
3.2.7.8 600 KL capacity Litre 12.10
3.2.7.9 700 KL capacity Litre 11.42
3.2.7.10 800 KL capacity Litre 10.87
3.2.7.11 900 KL capacity Litre 10.40
3.2.7.12 1000 KL capacity Litre 10.01
3.2.7.13 1250 KL capacity Litre 9.21
3.2.7.14 1500 KL capacity Litre 8.61
3.2.7.15 1750 KL capacity Litre 8.13
3.2.7.16 2000 KL capacity Litre 7.74
3.2.8 Rates for RCC OHSR,SBC 18 T/sqm, SEISMIC ZONE-III & STAGING 18 M
3.2.8.1 100 KL capacity Litre 25.42
3.2.8.2 150KL capacity Litre 20.02
3.2.8.3 200KL capacity Litre 17.66
3.2.8.4 250KL capacity Litre 16.68
3.2.8.5 300KL capacity Litre 16.18
3.2.8.6 400KL capacity Litre 14.44
3.2.8.7 500KL capacity Litre 13.35
3.2.8.8 600 KL capacity Litre 12.62
3.2.8.9 700 KL capacity Litre 11.93
3.2.8.10 800 KL capacity Litre 11.36
3.2.8.11 900 KL capacity Litre 10.88
3.2.8.12 1000 KL capacity Litre 10.47
3.2.8.13 1250 KL capacity Litre 9.65
3.2.8.14 1500 KL capacity Litre 9.03
3.2.8.15 1750 KL capacity Litre 8.53
3.2.8.16 2000 KL capacity Litre 8.13
3.2.9 Rates for RCC OHSR,SBC 18 T/sqm, SEISMIC ZONE-IV & STAGING 18 M
a) Topographic survey, preparation of site contour plan, conducting SBC test and its
approval from department before construction. Submission and approval of concrete mix
design and water quality test report for water to be used in construction.
b) Excavation in all types of soil, PCC below foundation & all RCC Work including all labour
and material charges including providing and fixing of accessories such as SS ladder, SS
manhole frame and covers, water level indicator (float type), SS ventilator with SS screen,
float valve, puddle collars, G.I. pipe railing around walk way, Top Dome/Slab, Staircase.
c) CWR shall be provided with adequate plinth protection all around the structure in a width
starting from edge of structure at GL and extending at least up to 1.0m beyond the vertical
wall of CWR. The plinth protection shall consist of 150mm thick PCC in M-15 concrete over
150mm thick compacted soil fill.
d) Providing and applying two coats of food grade epoxy paint on the inside surface of the
roof slab, and 600 mm height of the vertical wall.
e) Successful hydro test and water tightness test as per I.S. code.
f) Providing and applying three coats of anti-carbonation paint on the roof Slab.
g) Providing and applying three coats of cement-based paint on the remaining external
surface area of the structure.
h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS 304 ladder
from roof slab to bottom Slab, inside container. Providing and fixing water level indicator
(Float type).
i) Providing and fixing MS ladder from ground to top slab.
j) All MS parts to be painted with two coats of the enamelled paint over the primer coat of
red oxide.
k) Providing and fixing of 150mm wide water bar for the construction joints in the container.
l) Providing and fixing CI/DI puddle collars the vertical wall for connecting inlet, outlet,
overflow and washout pipes of the reservoir.
m) Inlet, outlet, overflow, washout pipes and valves are not included in this work,
provision for the same shall be taken separately.
3.3.1 Rates for RCC Partially Underground type clear water reservoir SBC 7 T/sqm, SEISMIC
ZONE-2,3 & 4
3.3.1.1 50 KL capacity Litre 8.61
3.3.1.2 75 KL capacity Litre 7.99
3.3.1.3 100 KL capacity Litre 7.95
3.3.1.4 150KL capacity Litre 7.14
3.3.1.5 200KL capacity Litre 6.58
3.3.1.6 250KL capacity Litre 6.26
a) Topographic survey, preparation of site contour plan, conducting SBC test and its
approval from department before construction. Submission and approval of concrete mix
design and water quality test report for water to be used in construction. .
b) Excavation in all types of soil, PCC below foundation & all RCC Work including all labour
and material charges including providing and fixing of accessories such as SS ladder, SS
manhole frame and covers, water level indicator (float type), SS ventilator with SS screen,
float valve, puddle collars, G.I. pipe railing around walk way, Top Dome/Slab, Staircase.
c) CWR shall be provided with adequate plinth protection all around the structure in a width
starting from edge of structure at GL and extending at least up to 1.0m beyond the vertical
wall of CWR. The plinth protection shall consist of 150mm thick PCC in M-15 concrete over
150mm thick compacted soil fill.
d) Providing and applying two coats of food grade epoxy paint on the inside surface of the
roof slab, and 600 mm height of the vertical wall.
e) Successful hydro test and water tightness test as per I.S. code.
f) Providing and applying three coats of anti-carbonation paint on the roof Slab.
g) Providing and applying three coats of cement-based paint on the remaining external
surface area of the structure.
h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS 304 ladder
from roof slab to bottom Slab, inside container. Providing and fixing water level indicator
(Float type).
i) Providing and fixing MS ladder from ground to top slab.
j) All MS parts to be painted with two coats of the enamelled paint over the primer coat of
red oxide.
k) Providing and fixing of 150mm wide water bar for the construction joints in the
container.
l) Providing and fixing CI/DI puddle collars the vertical wall for connecting inlet, outlet,
overflow and washout pipes of the reservoir.
m) Inlet, outlet, overflow, washout pipes and valves are not included in this work,
provision for the same shall be taken separately.
3.4.1 Rates for RCC Partially Underground type clear water reservoir SBC 7 T/sqm, SEISMIC
ZONE2,3 & 4
3.4.1.1 400 KL capacity Litre 6.51
3.4.2 Rates for RCC Underground type clear water reservoir SBC 7 T/sqm, SEISMIC ZONE-2,3 & 4
3.5.1 Rates for RCC GROUND LEVEL SERVICE RESERVOIR SEISMIC ZONE-II & III and SBC18T/sqm
3.6 Providing and fixing double flanged ISI marked GI pipes medium duty (class B ) Steel tube as
per IS:1239 or amended up to date and zinc coating as per IS 4736 with GI fittings excluding
valves as vertical pipes for RCC Reservoirs including specials required such as bend, tee etc.
providing and fixing with MS clamps at every 3 mtr, jointing materials such as nuts, bolt,
rubber packing, hydraulic testing etc. complete in all respect up to and from valve chamber
as per direction of EIC, Technical Specification and Scope of work.
PHED REVISED BSR 2023 Earth work, Road cutting, restoration trenchless laying 45
RajKaj Ref No. : 4242943
S. No. Description Unit Rate (Rs.)
4.6 Dismantling of flexible pavement for pipe line and chambers by mechanical
means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in
volume and stock piling at designated locations and disposal of dismantled
materials up to a lead of 1000 meters. Measurement for dismantled trench to
be made as per standard trench width specified in tender document and no
extra payment shall be made be made for trench width more than specified, re-
handling of material/earth to complete the tasks per technical specification and
scope of work.
4.8 Providing and laying in position cement concrete in specified grade over
prepared base course complete including finishing, curing, all material, labour,
machinery, lighting, guarding for road restoration work in trenches of pipe line
and chamber work. Measurement for CC work to be made as per standard
trench width specified in tender document and no extra payment shall be made
be made for trench width more than specified, complete work as per technical
specification and scope of work.
PHED REVISED BSR 2023 Earth work, Road cutting, restoration trenchless laying 46
RajKaj Ref No. : 4242943
S. No. Description Unit Rate (Rs.)
4.9 Removing & Re-fixing of Precast concrete interlocking blocks for laying of pipe
line by manual method, stacking of serviceable & non serviceable material
separately, disposal of dismantled material lead up to 50 mtr. The C.C.
interlocking paving blocks be laid on average 25 mm thick bed of coarse sand
and the joints to be filled with fine sand. Laying procedure on compacted sub
base as defined. Complete job is to be executed as per the directions of
Engineer in charge. The rates to be inclusive of fixing of 70 percent reusable
precast concrete interlocking block and cost of required new precast concrete
interlocking block against damaged, including all lead and lift as per Technical
specifications. (Interlocking block manufactured by fully computerized
automatic stationery hydraulic vibro pressed machine & full computerized
automatic batching plant of class A-1 as per BS:6717-2001. Tensile splitting
strength and breaking load as per BS: 6717-2001 Colour: Grey cement natural
colour. Variation in Dimension : Less than 1.6 mm Variation in thickness: Less
than 3.2 mm)
Note: If existing precast block used more than 70%, than for every 1% use
above 70%, deduction of 1% in cost shall be done for every 1% use above 70%.
4.11 Supply laying and pushing of MS casing pipe of specified thickness approved by
concerned department authority by trenchless method adopting any suitable
technology below ground at required depth under running traffic condition as
per Highway/ Railway standard including carrying out survey work at the job
site for determining underground cable trenches like telephone, cable, water &
sanitary lines and resistivity test for finding the soil strata using necessary
equipments for completion of works, mobilizing of machineries and specialized
crew at the job site complete in all respect, including excavation of driven pit
and exit pit (up to 3 meter depth) with proper protection at these sites with
shoring sheets and ISMB. Providing MS cutting edges for front shield and
constructing thrust bed at designated level. Necessary dewatering and
providing concrete foundation at the base of the driven pit, PVC/Rubber saddle
as per the requirement of Highway/Railway authority, crane for handing of pipe
and any other machinery, tools, and tackles required, construction of
temporary works as per design, drawing and method as per approved by
authority specification and the direction of the Engineer.
Apply corrosion, resistant, protection on inside and outside of casing pipe as
per technical specification.
PHED REVISED BSR 2023 Earth work, Road cutting, restoration trenchless laying 47
RajKaj Ref No. : 4242943
S. No. Description Unit Rate (Rs.)
PHED REVISED BSR 2023 Earth work, Road cutting, restoration trenchless laying 48
RajKaj Ref No. : 4242943
Chapter 5
Pump sets
Sr. No. Description Unit Rate (Rs.)
5.1 Providing, installation, testing and commissioning of Centrifugal Monoblock
pump set conforming to IS 9079 , 2 pole motor operating at synchronised
speed of 3000 RPM with requisite MOC impeller, priming funnel, cock,
suitable flanges at suction and delivery side. Pump shall have common shaft
for pump and motor. Motor shall be suitable for working on 415 V ± 10%, 3
Ph, 50 Hz A.C. Supply. Motor shall be TEFC type and Pump set shall be
suitable for working at various discharge and head requirements as per
scope of work. Pump shall be erected on C.C. foundation / cross channels /
RSJ frame block with suitable foundation bolts grouted in C.C. foundation
block etc. complete in all respect as per specification, scope of work and
direction of Engineer in Charge of following power rating, suitable for
prescribed duty conditions mentioned in TD.
7.1.1 DOL STARTER 2.2 KW (3 HP)- : For 2 motors (1 W+ 1S) Each 49356.00
I/C - MCB 25A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0-
500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A )
(1), Amp. Selector Switch (1), C. T. 30/5A CL 1.0 5VA (3) , Indicating Lights
( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP
10 KA C Curve (3) and
O/G- MCB 16A ,TP, 10 KA, C Curve (2), Power Cont 9A TP AC3 Duty(2), 2
NO+2 NC Aux. Block(2), Thermal Overload Relay (4-6A )(2), Control MCB
6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights
(Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1
)(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty
MPP Type 2 Kvar (2)
7.1.2 DOL STARTER 3.7KW (5 HP ) - : For 2 motors (1 W+ 1S) Each 50413.00
I/C - MCB 32A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0-
500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A )
(1), Amp. Selector Switch (1), C. T. 30/5A CL 1.0 5VA (3) , Indicating Lights
( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP
10 KA C Curve (3) and
O/G- MCB 25A ,TP, 10 KA, C Curve (2), Power Cont 12A TP AC3 Duty(2),
2 NO+2 NC Aux. Block(2), Thermal Overload Relay (7-10A )(2), Control
MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating
Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green -
1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty
MPP Type 2 Kvar (2)
7.1.3 DOL STARTER 5.5 KW (7.5HP) - : For 2 motors (1 W+ 1S) Each 51448.00
I/C - MCB 40A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0-
500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A )
(1), Amp. Selector Switch (1), C. T. 30/5A CL 1.0 5VA (3) , Indicating Lights
( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP
10 KA C Curve (3) and
O/G- MCB 25A ,TP, 10 KA, C Curve (2), Power Cont 12A TP AC3 Duty(2),
2 NO+2 NC Aux. Block(2), Thermal Overload Relay (7-10A )(2), Control
MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating
Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green -
1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty
MPP Type 2 Kvar (2)
PHED REVISED BSR 2023 DOL Star delta starter type LT panels 67
RajKaj Ref No. : 4242943
S. No. Description Unit Rate (Rs.)
7.2 SITC STAR DELTA Starter type LT Panel of following rating: all
switchgears are of PHED approved makes, CRCA sheet of Panel enclosure
is of TATA/ Essar 1.6mm/ 2.0mm thick duly Electrostatic Powder Coated
with angle frame including other ancillaries ( Insulators, Acrylic Sheet ,
Backlight Sheet, Hardware, Wire, Name Plates, Lugs, Pvc Channel , Mcb
Chanel , Lock, Hing , Bidding , Connectors, Neutral Links , Spiral , Saddle
& Packing Material ) etc. and 100A/ 125A ,TPN, Aluminium Bus Bar with
Colour coated heat shrinkage sleeves complete as per Technical
Specifications and as per direction of Engineer-In-Charge.
7.2.1 STAR DELTA STARTER 7.5 KW (10.0 HP) - : For 2 motors (1 W+ Each 65077.00
1S)
I/C - MCB 63A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0-
500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A )
(1), Amp. Selector Switch (1), C. T. 60/5A CL 1.0 5VA (3) , Indicating Lights
( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP
10 KA C Curve (3) and
O/G- MCB 32A ,TP, 10 KA, C Curve (2), Power Cont 18A TP AC3 Duty(2),
2 NO+2 NC Aux. Block(2), Thermal Overload Relay (7-10A )(2), Control
MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating
Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green -
1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty
MPP Type 5Kvar (2), S/D Timer(2)
7.2.2 STAR DELTA STARTER 9.3 KW (12.5 HP) - : For 2 motors (1 W+ Each 66938.00
1S)
I/C - MCB 63A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0-
500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A )
(1), Amp. Selector Switch (1), C. T. 60/5A CL 1.0 5VA (3) , Indicating Lights
( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP
10 KA C Curve (3) and
O/G- MCB 40A ,TP, 10 KA, C Curve (2), Power Cont 18A TP AC3 Duty(2),
2 NO+2 NC Aux. Block(2), Thermal Overload Relay (7-10A )(2), Control
MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating
Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green -
1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty
MPP Type 5Kvar (2), S/D Timer(2)
7.2.3 STAR DELTA STARTER 11.0 KW (15.0 HP) - : For 2 motors (1 W+ Each 70561.00
1S)
I/C - MCB 63A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0-
500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A )
(1), Amp. Selector Switch (1), C. T. 60/5A CL 1.0 5VA (3) , Indicating Lights
( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP
10 KA C Curve (3) and
O/G- MCB 40A ,TP, 10 KA, C Curve (2), Power Cont 25A TP AC3 Duty(2),
2 NO+2 NC Aux. Block(2), Thermal Overload Relay (9-13A )(2), Control
MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating
Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green -
1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty
MPP Type 7.5Kvar (2), S/D Timer(2)
PHED REVISED BSR 2023 DOL Star delta starter type LT panels 68
RajKaj Ref No. : 4242943
S. No. Description Unit Rate (Rs.)
7.2.4 STAR DELTA STARTER 15.0 KW (20.0 HP) : For 2 motors (1 W+ Each 99226.00
1S)
I/C- MCCB 100A TPN 25 KA With T/M Based Over Current & Short Circuit
Protection (1),Spreaders (2),Extended Rotary Handle (1) , Analog
Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog
Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 100/5A
CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights (
Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve (3)
and
O/G- MCCB 63A TPN 25 KA With T/M Based Over Current & Short Circuit
Protection (2), Power Cont 32A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2),
Thermal Overload Relay (12-18A )(2), Control MCB 6A SP 10 KA C Curve
(2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1,
Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1
Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 7.5Kvar (2), S/D
Timer(2)
7.2.5 STAR DELTA STARTER 18.5 KW (25.0 HP) - : For 2 motors (1 W+ Each 108534.00
1S)
I/C- MCCB 125A TPN 25 KA With T/M Based Over Current & Short Circuit
Protection (1),Spreaders (2),Extended Rotary Handle (1) , Analog
Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog
Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 125/5A
CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights (
Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve (3) and
O/G- MCCB 100A TPN 25 KA With T/M Based Over Current & Short
Circuit Protection (2), Power Cont 32A TP AC3 Duty(2), 2 NO+2 NC Aux.
Block(2), Thermal Overload Relay (16-24A )(2), Control MCB 6A SP 10 KA
C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green -
1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1 )(4), Selector Switch
1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 10 Kvar (2),
S/D Timer(2)
7.2.6 STAR DELTA STARTER 22.0 KW (30.0 HP) - : For 2 motors (1 W+ Each 122057.00
1S)
I/C- MCCB 125A TPN 25 KA With T/M Based Over Current & Short Circuit
Protection (1),Spreaders (2),Extended Rotary Handle (1) , Analog
Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog
Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 125/5A
CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights (
Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve (3)
and
O/G- MCCB 100A TPN 25 KA With T/M Based Over Current & Short
Circuit Protection (2), Power Cont 40A TP AC3 Duty(2), 2 NO+2 NC Aux.
Block(2), Thermal Overload Relay (23-32A )(2), Control MCB 6A SP 10 KA
C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green -
1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1 )(4), Selector Switch
1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 12.5 Kvar (2),
S/D Timer(2)
PHED REVISED BSR 2023 DOL Star delta starter type LT panels 69
RajKaj Ref No. : 4242943
Chapter 8
8.3 Providing and fixing steel, gate, grating and grills made of angles, tees,
square bars, flats or black pipe with hold fast and fitting complete as per
design and drawing including cutting welding and fabrication with priming Kg 121.00
coat of red oxide and two coat of enamel paints.
10.1 Supply, installation, testing and commissioning of MNRE approved Grid tied
Solar Panels with inverter, meter, cable etc. suitable for Rooftop installation
as well as Utility Scale Solar Power Projects with 25 years of Linear
Generation warranty. Work includes designing of solar panel area and MS
frame and foundation on ground/roof of Pump house or CWR, showing
arrangement of panel in available space, installation of PV module on MS
frame as per approved design and drawings. Mounting structure shall be
suitably designed to withstand wind velocity up to 150km/hr.
Grid Tie Transformer less inverters, Multiple independent MPPTs, Peak
efficiency of >98%. Connect up to multiple strings PV arrays, Easy & fast
connection, Built-in string-level monitoring, IP65 protection level, Wi-Fi /
internet based remote monitoring with 5 years warranty.
All cabling up to panel and metre, earthing etc. required accessories and
taxes are inclusive. The work shall be executed as per detailed technical
specifications, approved drawing and direction of Engineer in Charge.
Note: There shall be 5 year service warranty for panel, inverter, meter, cable
etc. and suitable provision shall be included in tender document.
10.3 Supply, installation, testing and commissioning of MNRE approved off Grid
Solar Panels for running of motor pumps with 25 years of Linear Generation
warranty, Work includes designing of solar panel area and MS fabricated
structure 120 micron hot dip galvanized iron , showing arrangement of panel
in available space and installation of PV module on frame structure such
that minimum height of lower edge of panel shall be 4.0 mtr from ground
level to safeguard against damage and theft as per indicative drawing
enclosed with the bid document. The foundation of structure shall be in RCC. Watt 60.00
Mounting structure shall be suitably designed to withstand wind velocity up
to 150km/hr. The work shall be executed as per detailed technical
specifications, approved drawing and direction of Engineer in Charge.
Note: There shall be 5 year service warranty for solar panel and mounting
structure and suitable provision shall be included in tender document.
10.4 Supply, installation, testing and commissioning of MNRE approved off Grid
Solar Panels for running of motor pumps with 25 years of Linear Generation
warranty, Work includes designing of solar panel area and structure,
showing arrangement of panel on rectangular OHSR with flat roof/ MS
fabricated structure with polyethylene tank and installation of PV module
on above structure as per approved design and drawings. Mounting
structure shall be suitably design to withstand wind velocity up to 150km/hr.
The work shall be as per detailed technical specifications, approved drawing Watt 51.00
and direction of Engineer in Charge.
This item does not include cost of OHSR/ MS fabricated structure with tank
but includes cost of items required for installation of solar panels on top of
the tank.
Note: There shall be 5 year service warranty for solar panel and mounting
structure and suitable provision shall be included in tender document.
(other than rocky strata). The work includes P&F of Polyethylene Water
Storage Tank(IS: 12701, ISI marked, indicating the BIS license No.) of
approved make with cover. Providing & fixing 50 mm dia ISI marked G.I. class
B pipe for inlet, outlet and over flow pipe and 32 mm GI class B pipe for wash
out with GM gate valves at inlet and outlet pipe Including making connection
etc. complete as per drawing, technical specification and direction of
Engineer in In charge. The scope includes inlet GI pipe from ground level to
water tank and outlet pipe from water tank to ground and up to 2.0 mtr
away from foundation and overflow pipe is to be interconnected in
distribution pipe line. Wash out pipe shall be taken up to a suitable point
minimum 5.0 mtr away from tank. Water level controller shall installed to
monitor level in tank and shall automatically shut off motor when tank is
filled .
Note: There shall be 5 year service warranty for structure, tank, fittings etc.
and suitable provision shall be included in tender document.
10.8.1 5000 Litre X 2 Nos. PE water tank, staging 10 meter. Each 665565.00
10.8.2 7500 Litre X 2 Nos. PE water tank, staging 10 meter. Each 731261.00
10.8.3 5000 Litre X 2 Nos. PE water tank , staging 12 meter. Each 754589.00
10.8.4 7500 Litre X 2 Nos. PE water tank, staging 12 meter. Each 816729.00
Instrumentation
S. No. Description Unit Rate (Rs.)
STORAGE TANKS
12.1 Earth work in excavation over area ( for Sedimentation cum storage tank) Cum 93.00
Exceeding 30 cm in depth 1.5 Mtrs in width as well as 10 Sqm on plan)
including disposal of excavated earth lead up to 50 M and all lift.
Disposed earth to be levelled and neatly dressed including stacking of
useful material if any available during excavation for all kind of soil. Earth
work to be carried out by means of mechanical system i.e. Tractor craw or
any other mechanical system. No extra payment shall be done for lift of
any limit. This work also involves dressing of sides & bottom for lining
purpose which is to be done manually, slope of sides to be maintained as
per specification. Work is to be done as per direction of Engineer In
Charge and technical specifications.
12.2 Silt clearance from Sedimentation cum storage tank with all lift and lead Cum 117.00
up to 50 Mtr. Silt to be disposed outside the Headworks boundaries.
Disposed silt to be levelled and neatly dressed including stacking of useful
material if any available during excavation for all kind of soil. Silt
clearance is to be carried out by means of mechanical system i.e. Tractor
craw/Trolley or any other mechanical system. No extra payment shall be
done for lift . This work also involves dressing of bottom which is to be
done manually and there shall be no damage to lining and LDPE film of
tank. Work is to be done as per direction of Engineer In Charge and
technical specifications.
NOTE :- For additional lead, beyond 50M, every additional lead will be
paid as per PWD BSR. But for lead of 500M, 1 km. and onward; initial rate
of 50M will be deducted from concern rates of above said leads
12.3 SINGLE FLAT BRICK LINING WITH 250 MICRON LDPE FILM:- Preparing Sqm 589.00
surface levelled & dressed to proper slope & laying over it on sand
properly rammed and watered in 2 Layers of 5 cm each. Providing and
laying 250 micron LDPE film as per ISS:2506-1984 including overlapping
on the finished surface of compacted sand. Over LDPE film 15 mm thick
cement sand mortar 1:3 shall be provided and laid which shall be cured
properly. Over the base mortar single layer Ist class brick lining in cement
sand mortar 1:3 shall be provided with joints not more than 8 mm wide
and curing shall be done for 14 days. This also includes providing
weedicides & anti-termite treatment, complete work as per technical
specifications.
12.4 Providing and fixing PVC float in Raw Water Storage tank with CI tail piece Job 15804.00
150mm dia-2 Nos, CI puddle collar-150mm dia- 1.20 M- 1 No. and PVC
hose pipe- 150mm dia -6 M & all accessories complete in all respect as
per Instructions of Engineer In Charge. Complete Job
82
PHED REVISED BSR 2023 EW Storage tank, Filter media
RajKaj Ref No. : 4242943
S. No. Description Unit Rate (Rs.)
FILTER MEDIA
12.5 Providing and placing of new graded gravel as (i) Size of Gravel vary from Cum 3926.00
50 mm at the bottom to 2. to 5 mm at the top as detailed: (a) Passing 80
mm screen but held on 10 mm- 150 mm layer (b) Passing 25 mm screen
but held on 10 mm- 50 mm layer (c) Passing 10 mm screen but held on 5
mm- 50 mm layer Passing (d) 5 mm screen but held on 2 mm- 50 mm
layer (ii) The filter gravel shall be as spherical as possible, hard, clean and
uniform in quality and also shall not contain such impurities as dirt and
clay as per IS: 8419 (Part-I) for filter gravel specifications. The work also
includes washing the gravel with required concentration of HCL acid and
finally with water and placing the same in filter beds as per direction of
Engineer- In- Charge and technical specification complete in all respect.
The gravel shall not contain more than 5% acid soluble matter as
determined by solubility test in Appendix B of IS: 8419 (Part-I) amended
up to date. (For RGF)
12.6 Supply and charging of filter media (Gravel) as per department Cum 2086.00
specification including screaming, washing with 5% HCL solution to make
Gravel (Size 4 to 6mm, 8 to 12mm, 10 to 20mm - Hard Coarse grit from
approved quarry) free from silt, clay and other all impurities work to be
executed as per scope of work fixed by the department at the time of
tendering (for SSF)
12.7 Providing and Placing of new filter media as (i) Sand shall be hard and Cum 4190.00
resistant quartz or quartzite and free of clay, fine particles, soft grains and
dirt of any description. (ii) Effective size shall be 0.45 to 0.70 mm. (iii)
Uniformity Coefficient not be more than 1.70 nor less than 1.30. (iv)
Ignition loss should not exceed 0.70% by weight. (v) Soluble fraction in
HCL acid shall not exceed 5.0% by weight, (vi) Silica content should not be
less than 95% (vii) Specific Gravity shall be in the range between 2.55 to
2.65 (viii) Wearing loss shall not exceed 3.0%. and as per specifications
given in IS: 8419 (Part-I). Filter media (fine sand and coarse sand) should
be processed through disintegrator and dust separator in automatic plant
including screening of sand to desired specification and washing and
cleaning of sand with water by aqua wash technology at quarry site. (For
RGF)
12.8 Providing and Placing of new filter media as (i) Sand shall be hard and Cum 4190.00
resistant quartz or quartzite and free of clay, fine particles, soft grains and
dirt of any description. (ii) Effective size shall be 0.20 to 0.30 mm. (iii)
Uniformity Coefficient not be more than 5.0 nor less than 3.0. (iv) Ignition
loss should not exceed 0.70% by weight. (v) Soluble fraction in HCL acid
shall not exceed 7.0% by weight, (vi) Silica content should not be less than
95% (vii) Specific Gravity shall be in the range between 2.55 to 2.65 (viii)
Wearing loss shall not exceed 3.0%. and as per specifications given in IS:
8419 (Part-I). (ix) The sand should not contain more than 2% of calcium
and manganese calculated as carbonate. Filter media (fine sand and
coarse sand) should be processed through. Disintegrator and dust
separator in automatic plant including screening of sand to desired.
Specification and washing and cleaning of sand with water by aqua wash
technology at quarry site. The sand shall not contain more than 5% acid
soluble matter as determined by solubility test in Appendix B of IS: 8419
(Part-I) (Fine sand 0.2 to 0.3mm and coarse sand 1.0 to 1.7mm) (For SSF)
83
PHED REVISED BSR 2023 EW Storage tank, Filter media
RajKaj Ref No. : 4242943
S. No. Description Unit Rate (Rs.)
12.9 Fixing of pipes for under drainage system including plugging pipes with RM 32.00
CM 1:4 on one end and fixing other end in collecting channel with CM 1:4
with all Material etc.(Excl.cost of pipes) This job, also, includes Making
4mm dia holes in pipes @15 cm c/c in zig-zag pattern and testing of
under drainage system as per instruction of Engineer-in-charge.
12.10 Removing & Re-fixing of pipes for under drainage system including RM 26.00
cleaning of one end plugged pipes and fixing /embedded in CM 1:4 on
one end and fixing other end in collecting channel with CM 1:4 with all
Material etc.(Excl.cost of pipes) This job, also, includes Making 4mm dia
holes if required in pipes @15 cm c/c in zig-zag pattern.
12.11 Making 4mm dia hole in pipes of under drainage system of filters duly Each 2.00
drilled. Carriage of pipe from stacks to filter site, making two per rows on
pipe and points of making holes in Zig-Zag pattern in two hold raw.
Making 4mm dia holes with drill machine @ 15cm c/c in zig-zag pattern.
12.12 Labour charges for screening of old sand (received from filter beds) Cum 915.00
through the standard sieves, washing the sand with HCL acid of required
concentration as directed by the Engineer- In- Charge, so as to remove all
the mud and other deposits from sand grains and then clean with water
till the sand is as neat and clean that it impart no colour to clean while
washing. It also includes placing this washed filter media (sand) in filter
beds in layer as instructed by the Engineer- In- Charge. (RGF, SSF)
12.13 Labour charges for screening of old gravel (received from filter beds) Cum 685.00
through the standard different sizes sieves for required sizes of gravel,
washing the gravel with HCL acid of required concentration as directed by
the Engineer- In- Charge, so as to remove all the mud and other deposits
from gravel grains and then clean with water till the gravel is as neat and
clean that it impart no colour to clean while washing. It also includes
placing this washed gravel in filter beds in layer as instructed by the
Engineer- In- Charge. (RGF, SSF)
84
PHED REVISED BSR 2023 EW Storage tank, Filter media
RajKaj Ref No. : 4242943
Chapter 13
14.3 Data entry of existing FHTCs in rural area under JJM on website
ejalshakti.gov.in; work includes visiting the village for collecting basic data
consumers like i.e. Aadhar no./ration card/voter ID/BPL card/ PAN
FHTC 30.00
card/driving license/passport/Antyodaya card/mobile no. etc. and entering
the details on the above website. The cost also includes computer and
operator.
14.4 Preparation of DPRs for single and small multi village rural water supply
schemes under JJM for Administrative & Financial Sanction and Technical
sanction, the work includes:
Survey by Electronic Total station/DGPS of villages with a view of preparing
village index plan, existing HW plan and survey for route of rising/ trunk
mains, indicating roads/ streets, surface and width of road/ streets along
with places of importance such as Panchayat Bhawan, Hospital, School, Post
office, Temple Water Supply structures (GLRs, PSPs, pumping station
physical boundary of village north etc. including levels and TBM at
important places as per instruction of engineer in charge.
Preparation of technical report, forecasting of population and design
demand, source design, techno-economic design of rising mains, selection
and design of pumps sets, capacities of CWR, OHSR etc. complete work as
per departmental prevailing guidelines and practice.
Hydraulic Design of Distribution network in Loop/Water Gem/EPANET or
any other compatible software. Preparation of Auto CAD Drawing (A-3/A-2)
with complete hydraulic design output details, such as pipe no, node no,
pipe length, pressure at node etc.