Cable Failure Modes
Cable Failure Modes
com
Failures of cable systems are disruptive, expensive and hazardous and results in loss of
vital evidence.
Cables, jointing, terminations and connectors properly installed and not subjected to
mechanical forces, moisture, or extreme temperatures have a predictable long service
lifetime.
Cable faults, very random in nature, normally only affect a short length of a specific cable
and are cleared by the protective relaying.
In conduits and cable trays, cables seldom can directly affect others through mechanical
motion or by heating (fire).
Protective relays properly designed, installed and kept calibrated, should clear cable
faults in a short time and thus restrict the damage to the faulting cable.
The cables can fail from any combination of electrical, mechanical, and thermal factors.
The service environments in which power cables operate are varied and may include mild
environments, as well as harsh environments with high temperature levels. Power cables
used to energize medium and high voltage equipment, such as pump motors and switchgear,
must operate at voltages and currents that are significantly higher than cables for control
and instrumentation.
Because medium and high voltage power cables operate at higher voltages, there is an
increased stress on the cables, which could accelerate aging degradation due to internal
ohmic heating and partial discharges (corona).
In addition, medium and high voltage cables are susceptible to unique aging mechanisms,
such as water treeing, that low voltage cables (up to 1 kV) do not experience.
Placement in conduit, raceways, underground ducts, and cable trays affects service
conditions under which the cables must operate.
Routing in densely filled cable trays, enclosed ducts, or fire-wrapped cable trays, together
with other continuous duty power cables, will result in elevated operating temperatures.
Exposure to elevated temperatures can also be caused by the location of cables installed in
close proximity to high temperature steam lines and other high temperature sources.
Aging due to elevated temperatures will cause the various polymers used to insulate the
cables to degrade, resulting in loss of elongation, embrittlement, and eventual cracking over
long exposure periods.
This can occur for cables installed below grade in ducts or conduits that are susceptible to
water intrusion, or for cables buried directly in the ground. Cables exposed to water while
energized are susceptible to a phenomenon called water treeing in which tree-like micro
cracks are formed in the insulation due to electrochemical reactions.
Reactions are caused by the presence of water and the relatively high electrical stress on
the insulation at local imperfections within the insulating material, such as voids and
contaminant sites that effectively increase the voltage stress at that point in the insulation.
Moisture can also cause corrosion of the various metallic components of the cable, such as
metallic shields or the conductor.
In general, aging degradation of the insulating material is of the most concern for high and
medium voltage power cables.
Other subcomponents are also susceptible to aging degradation due to various stressors to
which they are exposed; however, their degradation rate is usually minimal.
• Short-circuit to ground
• Conductor-to-conductor short-circuit
• Reduced insulation resistance
• Reduced dielectric strength
• Excessive partial discharge
Cable can also be damaged during construction when earth moving equipment can dig into
the cable or cable duct banks.
Repeated bending and twisting during installation or in service can result in irreversible
straining of conductor wires.
Thermal degradation causes the insulation of the cable to lose its physical properties.
Thermally induced failures are due to overloading beyond its design capability for extended
periods and/or excessive ambient temperature conditions.
This failure mode describes where the shield ceases to perform its function. In order for the
shield to perform its function, its volume resistivity must always remain sufficiently low.
However, when metallic shield is damaged or corroded its volume resistivity is impacted
by temperature.
This is the case where metallic shield is insulated from the semiconducting tape shield due to
poor contact.
This can be caused by a layer of corrosion or scale buildup on the metallic shield.
Such a condition will give rise to a potential difference between the semiconducting shield
and the metallic shield that will cause arcing between the two shields.
This will lead to arcing damage from the outside into semiconducting shield and insulation
and eventual cable failure, being more severe if there are multiple areas of poor contact or
breaks between the two shield systems.
Failures in most cases occur at the end-terminations or joints (where the factory-
manufactured insulation gets disturbed).
• Ageing
• Wrong selection or application
• Mechanical failures
• Corrosion of sheath
• Moisture in the insulation
• Heating of cable
• Fire and lightning surges
• Electrical puncture
Mechanical failures
Mechanical failures can be due to breaks and defects of sheath material, mechanical
punctures by people or machines, or cracks due to sharp bending or vibration.
Whenever mechanical damage occurs in cable sheath, the entrance of moisture will
produce slow deterioration of insulation material, resulting in eventual failure of the cable. It
is important therefore to take every precaution that either direct or indirect mechanical
damage be eliminated or minimized by correct selection, installation, and maintenance of
cable systems.
Corrosion of sheath
Corrosion of sheath will eventually allow moisture to penetrate into the insulation system
and cause an eventual failure. Sheath corrosion can be minimized by correct application of
cathodic protection, application of insulating paints, providing adequate drainage, and
removing the source of chemical contamination.
Because of mechanical damage or other reasons, entrance of moisture into the insulation
system will deteriorate the cable, and all precautions to prevent such entrance should be
taken. Damages due to moisture can be indicated by the following:
Heating of cable
An increased heat rise in the cable results in insulation degradation.
Heat can be due to overloading, high ambient temperatures, insufficient ventilation, manual
heating due to cables being installed too close to each other, or external sources of heat.
Care must be taken not to exceed the temperature rise of the cable insulation system.
This can be done by first identifying the various environmental and operating factors that
will determine the correct selection of the cable insulation and conductor size.
Once correct selection and installation are made, routine maintenance and inspection of
cable will ensure safe and long operating life of the cable.
Fire in conduit or manholes can cause cable failure in adjacent manholes and junction
boxes.
Barriers can be installed between large groups of conductors to prevent fire damage.
Surge arresters should be installed to protect the cable where it is connected to overhead
lines to minimize failures of cable due to lightning surges.
Electrical puncture
Once the insulation is weakened owing to any of the reasons already analyzed, it may fail
electrically.
That is to say that the insulation system cannot confine the flow of electrical current to the
conductor inside the insulation system.
• Inherent causes
• Non inherent causes
Inherent causes
Insulation defects
Conductor defects
• Irregular strands
• Sharp corners
• Missing strands
• Burrs on the strands
• Poor brazing
Corrosion of sheath:
Corrosion usually results either to complete penetration of the sheath or weakness of the
sheath, so that the sheath breaks open.
• Positive potential (anodic), indicated by rough, pitted surface and very thin deposits
of white crystals
• Negative potential (cathodic), indicated by heavy deposit of lead oxides colored red,
yellow, or orange
• Local galvanic action
• Chemical action
Galvanic corrosion may occur in the presence of an electrolyte and some other metal that is
connected electrically to the sheath elsewhere.
Such failures are indicated by corroded sheath, which may be identical with either type of
corrosion depending on whether the sheath is anode or cathode.
Chemical action
Chemicals such as alkali attack cable insulation, which comes about from incompletely
cured concrete; acetic acid, rotting wood, jute, and other materials.
Usually, these can be identified by the chemical known to be present for a particular
installation.
4. PARTIAL DISCHARGES
Partial discharges are among the principal causes of catastrophic failures in cable
terminations and joints.
Main causes of discharges are deterioration of the insulation wall and joint defects.
Acoustic Emission techniques can be used for the detection of partial discharges in cables
and a Partial Discharge Scanner (PDS) is used for monitoring.
This equipment provides easy access, may be handheld or manipulated and indicates the
intensity of the partial discharges.
There are various methods to locate a fault, such as “acoustic fault location”, “decay
method”, based on voltage decoupling by a capacitive voltage divider, “surge current
differential method” (DICM), “impulse current method” (ICM), “multiple impulse method”
(MIM/SIM), based on single high voltage impulse, “fault burn down technology”, that
forces an high current carbonizing the insulation material, used for paper-oil impregnated
cables and “time domain reflection method” (TDR).
MIM/SIM is the most recent method, and TDR is the most established and widely used.
In TDR method a low voltage impulse is sent into the cable under test. That low voltage
impulse (maximum 160V) travels through the cable and is reflected positively at the cable
end or at any cable interruption (cable cut). At a short-circuit point this low voltage impulse
is reflected negatively.