RigidBusbarDesign Paper vsIEEE
RigidBusbarDesign Paper vsIEEE
net/publication/268585429
Static Analysis of Substation Rigid Bus Using the Finite Element Program
CITATION READS
1 1,270
1 author:
Prapon Somboonyanon
AEC Lionstech
13 PUBLICATIONS 14 CITATIONS
SEE PROFILE
All content following this page was uploaded by Prapon Somboonyanon on 13 May 2020.
Prapon Somboonyanon1
1
P.E., Senior Civil/Structural Engineer, Burns & McDonnell Engineering Company
Inc., 9400 Ward Parkway, Kansas City, MO 64114; PH (816) 822-3953; FAX (816)
822-3296; email: [email protected]
ABSTRACT
To design a rigid bus system, several design methods are available. The IEEE
Std. 605-2008 design method is widely used but is conservative and has several
limitations. A dynamic analysis approach offers more accurate results but is more
complex and time consuming. The static analysis using a finite element program
design approach was proposed and described in this paper. The IEEE Std. 605-2008
design limitations were first identified followed by design advantages from the
proposed method. Proper design considerations should be accounted for when using
the program to obtain meaningful results. Results were compared between the IEEE
Std. 605-2008 and the proposed design methods using the same applied loads derived
from IEEE Std. 605-2008 design guidelines and the same set of design inputs. Three
case studies were performed, and the results from Case 1 and Case 2 showed the
conservatism in the IEEE Std. 605-2008 design method. Results from Case 3 showed
the impact from overload factors on the same bus arrangement. It was then
concluded that the static analysis using finite element program design approach
offered more accurate results than the IEEE Std. 605-2008. In addition, results
showed that insulator internal forces and bus conductor fiber stresses analyzed by the
proposed method were reduced comparing to the IEEE 605 Std. 605-2008 design
method, which could result in overall construction cost savings due to less insulators,
less bus structures, or less foundations needed.
INTRODUCTION
The design procedure based on IEEE Std. 605-2008 “IEEE Guide for Bus
Design in Air Insulated Substations” for designing a rigid bus system is widely used
by utility companies. This standard provides design guidelines in great detail using a
simplified static analysis approach providing closed-form equations. Although this
design method is simple and easy to implement, it has several limitations and, in
some cases, is too conservative. The primary source that makes the IEEE Std. 605-
2008 design method conservative is short-circuit load. Several papers have been
published to address the conservatism in short-circuit load applied to rigid bus system
using a dynamic analysis approach. For example, Amundsen, Oster, and Malten
(2009) proposed a design method considering rigid bus dynamic response in order to
reduce short-circuit load applied to rigid bus span. Pinkham and Killeen (1971)
provided a design method and simplified formulas to determine dynamic response of
insulators supporting rigid bus. In addition, Iordanescu, Hardy, and Nourry (1987)
presented a dynamic design approach with a finite element technique to determine
stresses and displacements of rigid bus conductors and bus structures. Although the
dynamic analysis design method provides more accurate results that better agree with
experimental data as shown in IEEE Std. 605-2008 Annex F, it is more complex and
time consuming compared to the static design approach. A simplified dynamic
design method may be less complex, but it may not be applicable for all rigid bus
arrangements. Because of the conservatism and limitations in static design approach
based on IEEE Std. 605-2008, and the complexity of dynamic design approach, a
static design approach using finite element program is proposed as an alternative.
The finite element software program used for analysis in this paper is RISA-3D
developed by RISA Technologies, LLC. The main focus of this paper is to address
the design limitations of IEEE Std. 605-2008 and to compare results between the two
design methods.
Rigid bus systems are generally used to connect electrical equipment, as well
as transmission structures, in a substation or switchyard. Regardless of bus
arrangements, the system typically consists of rigid bus conductors, insulators, and
bus structures. With an increase of fault currents in substations resulting in higher
short circuit loading, different insulator configurations have been used to support bus
conductors and to transfer loads to bus structures, as shown in Figure 1. Closed-form
equations provided in IEEE Std. 605-2008 are valid only for single insulator
configurations. For double insulator configurations, some designers may use IEEE
Std. 605-2008 assuming that insulators have the twice cantilever strengths. With the
conservatism in the design method, this assumption may still be valid. However, it is
obvious that the design method is not applicable for delta configurations.
Boundary conditions are critical and could have significant impacts on the
results. Without bus structures in a bus model, fixed support can be used
at the base of the insulators. At the top of insulators, where the bus
conductor is supported, this boundary condition varies depending on bus
fitting types. Three common bus fittings used in most substations include
1) fixed fitting, 2) slip fitting, and 3) expansion fitting. Expansion fitting
allows bus conductors to move horizontally parallel to the conductor to
accommodate thermal expansion, but unlike slip fitting, horizontal
movement is limited, approximately two inches. The actual value varies
from one manufacture to another. Defining boundary conditions for fixed
and slip fittings are straightforward, but care should be taken for
expansion fitting.
As also recommended in IEEE Std. 605-2008, allowable stress of bus
conductors with welded connections are reduced by 50%, therefore
locations of welded connections should be considered in the model.
When applying short-circuit load in the model without bus structures or
with one-phase bus structures, the direction of short-circuit load on each
conductor phase does not matter as each phase is independent. However,
direction of short circuit load in the model with three-phase bus structures
becomes important as each phase is connected by three-phase bus
structures. Proper direction of load will provide more accurate results to
all components of the system.
According to ANSI C37.32-2002 standard, Table 4 provides the preferred
mechanical loadings for high-voltage switches. The loads transferring to
switches should be accounted for in the model and should be kept within
the limit.
Selected load combinations used in a bus model analysis will also have
impacts to results. The impact was investigated and is described in the
case study section.
DESIGN INPUTS
All rigid bus conductors are made of “Aluminum 6063-T6.” Rigid bus is
5” Schedule 80, and A-frame is 2-1/2” Schedule 80.
Damping wire is used and weighs 1.094 lbf/ft in addition to rigid bus
weight.
Phase spacing, D, is equal to 12 feet, and the system fault current, Isc, is
50,000 A with assumed X/R value of 20. System frequency, f, is taken as
60 Hz. Support flexibility factor, Kf, is equal to 1.0, assuming the system
includes three-phase bus structures.
Wind speed is 100 mph for extreme wind load case. Ice with concurrent
wind load case is also analyzed with 40 mph wind speed and 0.75” radial
ice. Exposure category is C, and the effective height at which the wind is
being evaluated, z, is 25 feet.
CASE STUDIES
Using design inputs defined in the previous section and additional design
inputs shown below, results from Case 1 showed the conservatism in the IEEE Std.
605-2008 design method. Additional design inputs are as follows:
Figure 3. Rigid bus model of two equal spans with 21.74 feet in span length
without a bus structure.
Next, another bus model was created and analyzed using the same bus
arrangement as shown in Figure 3 with the addition of a three-phase bus structure in
the middle, as shown in Figure 4. All steel members supporting the bus arrangement
used in this model are wide flange W8x31 Gr. 36. Results from Phase C insulator at
the middle support for all three configurations were compared and summarized
subsequently in Table 1.
Figure 4. Rigid bus model of two equal spans with 21.74 feet in span length
including a three-phase bus structure.
Table 1 clearly shows the conservatism of the IEEE Std. 605-2008 design
method. Even with the same design inputs, a 13% reduction in insulator capacity
usage was provided from the model without a bus structure. This means designers
could lengthen a span, possibly resulting in a construction cost savings as fewer
insulators would be needed. This reduction in insulator capacity usage is likely from
more accurate calculations in the program accounting for rigidity of the insulator as
well as defined bus fitting conditions. Results from the model using the three-phase
bus structure show a 23% reduction resulting in an even longer span because of bus
structure rigidity consideration in the model. It should be noted that higher
reductions are normally expected from a model with bus structures compared to a
model without bus structures. These results, however, could vary due to several
factors, such as bus arrangements, bus structure configurations and materials, and bus
fittings. Also, results from both models, in Figure 3 and Figure 4, show the insulators
at both ends experienced high torsional stresses. Although stresses were within the
limit, at some point torsional strength could govern the design rather than cantilever
strength for this bus arrangement. As expected, tensile and compression loads in a
single-insulator configuration were relatively low compared to cantilever and
torsional loads.
For Case 2, the study was similar to Case 1, which was to observe the design
conservatism, but the focus was on the bus conductor fiber stress rather than insulator
strengths. An allowable span was first computed using formulas provided in IEEE
Std. 605-2008 Clause 12.2. The computed span is equal to 43.35 feet based on
pinned-fixed end conditions, which represents bus conductor stress at 100% capacity
usage. The spans in the two models shown in Figure 3 and Figure 4 were then
modified to 43.35 feet, matching the value from the IEEE Std. 605-2008 design
method. Both bus spans experienced the same maximum bus stress for all three
configurations. Results are summarized and shown below in Table 2.
Bus Conductor
Description
Fiber Stress Usage
Results from IEEE Std. 605-2008 design method 100%
Results from the model (Figure 3 with 43.35-ft span) 70%
Results from the model with bus structure
68%
(Figure 4 with 43.35-ft span)
For Case 3, the intent of the study was to compare results of the same bus
arrangement based on different overload factors required per different standards. The
bus arrangement used in this study is shown in Figure 2, which includes single
insulators at end locations, double insulators at mid-locations, delta insulators at
bi-level locations, and bus conductor bents in one location. All fitting types were
used, including fixed, slip, and expansion. For all analysis in Case 3, deflections on
bus members were limited by L/200, both horizontally and vertically, and ice loads
were excluded when checking bus deflections. All analysis included wind loads
applied to the bus model in X- and Z-direction, as well as wind loads applied in a 45º
angle to the bus model. Additionally, the bus model was analyzed under thermal
loads to determine if proper bus fittings were provided. Seismic loads were excluded
from all analysis. Three sets of load factor (OLF) were analyzed, including:
Overload factors provided above were used in an extreme wind load case
only. In some cases, overload factors under ice with concurrent wind or seismic load
cases may be different. Designers should ensure that proper overload factors are
provided for all load combinations used for the analysis. Overload factors and results
for all Case 3 analysis were provided in Table 3 and Table 4, respectively.
From the results shown in Table 4, it is obvious that insulator cantilever
strength governed the design for this bus arrangement. Overload factors based on
ASCE 113, Set 2, yielded the maximum insulator usage. Overload factors based on
the IEEE Std. 605-2008, Set 1, provided an approximate 25% reduction in insulator
cantilever strength, and an approximate 40% reduction when using overload factors
from the utility standard practice, Set 3. Maximum insulator tensile and compression
usages occurred at bi-level locations. As expected for insulators in delta
configuration, tensile and compression usages were much higher compared to results
from single configuration, as shown in Table 1. Maximum fiber stress and bus
conductor deflection were the same for all three analyses as results were all obtained
using ASD methodology with no overload factors applied. Bus conductor stresses
and deflections under applied loads in this bus arrangement were within the limit. As
shown from results, it is important that proper overload factor values are used to
design rigid bus system as these values could significantly impact overall
construction costs.
CONCLUSION
Several design methods are available for designing a rigid bus system. The
IEEE Std. 605-2008 design method is widely used and easy to implement. However,
this design method has several limitations. A dynamic analysis approach is another
alternative providing more accurate results but it is more complex as well as time
consuming. Therefore, static analysis using a finite element program was proposed
as it is fairly simple and can address several limitations in the IEEE Std. 605-2008
design method. Three case studies were analyzed using the same design inputs to
compare results between the IEEE Std. 605-2008 design method and from the
proposed method. As shown from the results in Case 1 and Case 2, it is clear that the
IEEE Std. 605-2008 design method is more conservative. In Case 1, results from the
model showed a 13% reduction in cantilever strength on the same bus arrangement,
and a 23% reduction when including a bus structure. In Case 2, results from both
Overload Factors for Insulator Checks
REFERENCES
American Electric Power (AEP). Design Standard. Station Standards Bus Design
Guideline, Columbus, Ohio.
American Society of Civil Engineers (ASCE). (ASCE 113). ASCE Manuals and
Reports on Engineering Practice No. 113. Substation Structure Design Guide,
Reston, Virginia.
Amundsen, T.A., Oster, J.L., and Malten, K.C. (2009). “Analytical techniques to
reduce magnetic force from high fault current on rigid bus.” Proceedings of
the 2009 Electrical Transmission and Substation Structures Conference -
Electrical Transmission and Substation Structures 2009: Technology for the
Next Generation, v 363, p 173-183.
Iordanescu, M., Hardy C., and Nourry, J. (1987). “Structural analysis and testing of
HV busbar assemblies with rigid conductors under short-circuit conditions.”
IEEE Transactions on Power Delivery, v PWRD-2, n 4, p 1082-1089.
Pinkham, T.A. and Killeen, N.D. (1971). “Short circuit forces on station post
insulators.” IEEE Transactions on Power Apparatus Systems, v PAS-90, n 4,
p 1688-1697.
Thaik, A. (1995). “Beware of high stresses in 'A' frame supported two-level bus
structures.” Proceedings of the 57th Annual American Power Conference.
Part 1 (of 3), April 18, 1995 - April 20, 1995, v 57-2, p 864-869.