Technical Specification VCB Panel
Technical Specification VCB Panel
INDEX
Clause No. Technical Particulars
1.0 Scope
2.0 System Specifications
3.0 Climate Endurance
4.0 Requirement of Auxiliary Power Supply
5.0 Key Technical Parameter
6.0 Compliance of applicable Standards & Safety Codes
7.0 General Requirement of 11kV HT PANEL
8.0 Requirement of Assorted Accessories & Equipment Guideline
9.0 Acceptance, Type and Routine Tests
10.0 Drawings
11.0 Packing & forwarding
12.0 Guaranteed Technical Particulars for 11kV HT VCB OUTDOOR IP54
PANEL
13.0 Typical SLD of System
1.0 SCOPE:
1.1. The section covers the specification of metal clad outdoor IP 54 vacuum type switchgear
unit with horizontal draw out circuit breaker as per IS 13118 [1991] / IS 62271-100/ IS 62271-
200 or latest amendment thereof. The equipment offered shall be of high quality, sturdy, robust
and of good design and workmanship complete in all respects and capable of performing
continuous and satisfactory operations in the actual service conditions at site and shall have
sufficiently long life in service as per statutory requirements.
1.2. All equipment shall be suitable for satisfactory operation in tropical climates and hot and
humid atmosphere prevailing in the location where it shall be used against the Contract. The
equipment shall be able to withstand a wide range of temperature variations in the required
location.
1.3. The equipment offered shall be complete with all parts necessary for their effective and
trouble-free operation. Such parts shall be deemed to be within the scope of the supply
irrespective of whether they are specifically indicated in the commercial order or not.
1.4. All the plant / apparatus / equipment supplied shall comply in all respect with the
requirement of Indian Electricity Act 2003 and Indian Electricity Rule 2003/IS and latest
amendment thereof during the execution of contract where-ever applicable.
1.5. Supplier shall bind himself to abide by these considerations to the entire satisfaction of the
purchaser and will be required to adjust such details at no extra cost to the purchaser over and
above the tendered rates and prices.
• Particulars of System:
a) Nominal system voltage: 11KV
b) Highest system voltage: 12KV
c) Number of phases: 3
d) Frequency: 50 Hz ± 3%.
e) System earthing: Solidly earthed neutral
f) Short Current Rating: 21.4 kA for 3sec
b) D.C. supply shall be provided for alarm, control, annunniciaton window and protective
device. The rating, quality and location of electrical supply system that will be made
available by the supplier for operation of the Ring Main units are described below:
6.1. The circuit breakers shall be suitable for outdoor IP54 type operation under the climatic
conditions, as specified under ‘Service Conditions’ for power transformers, without any protection
from sun and rain.
The above are minimum requirements. The manufacturers may offer their standard design, keeping
in view our minimum requirements.
The meters and relays shall be mounted in a convenient position so as these are readily accessible
for inspection or repair. The terminal board provided in the instrument panel of VCBs will be made
of moulded dielectric having brass studs, washers, holding nuts & locking nuts. All holding nuts shall
be secured by locking nuts. The connection studs shall project 6 mm from the lock nut surface. No
OTHTER TYPE OF TERMINAL BORAD IS ACCEPTABLE. The panels shall have a degree of protection of
IP - 4X. The leads from the metering CTs shall be directly terminated at MDM meter.. Similarly PT
leads from secondary box of the PT to & there from to MDM meter. The mode and extent of
concealing the metering leads of CTs & PTs, to prevent their tempering (by unscrupulous operating
personnel), will be discussed and mutually agreed upon with the successful bibber (s).
Earthing of current free metallic parts or metallic bodies of the relays switches mounted on the
instrument panel and metal enclosed switchgear shall be done by a suitable sized copper conductor.
Earth bus made of 25 X 6 mm bare copper flat will be extended through entire length of 11KV
switch-board with suitable provision to connect it to the sub-station earth at the extremities. The
earthing arrangement will meet with the requirements laid down in IS: 3427, read with its latest
amendments.
The secondary voltage & current rating of the instrument transformers shall match with the
metering and protective equipment. The CTs shall have ratio & accuracy class as mentioned in the
schedule of requirement. The CTs shall be wound/ring type in accordance with their ratings. The
terminal boards, associated with REF CTs & Over Current / Earth Fault Protection CTS will be of
disconnecting type, having short circuiting facility & thus facilitate secondary testing of concerned
protective relay without disturbing the associated small wiring. Interchangeability of housing of CTS,
from one panel to another, must be ensured. A resin cast potential transformer of ratio
(11000√3)/(110√3) volts, having 50VA output per phase with accuracy class 0.5S as per ISS: 3156
(Part-II) – 1965, shall be provided on the incoming side of each panel set and shall be star / star
connected. It shall be provided with HT Fuse and LT TP MCB. The neutral point, of star connected
secondary windings of instrument transformers, shall be earthed to the main earth bus. Multiple
earthing of any instrument transformers shall be avoided.
8.4 BUSBAR:
All the panels shall be provided with insulated COPPER bus bar of 800 Amps current rating for all
switch boards. These shall be connected in a separate moisture and vermin proof sheet metal
chamber. The bus - bar connection & insulator supports shall be mechanically strong & rigidly
supported so as to withstand the stresses, generated by vibrations, variation in temperature and
severe short circuits. The bus - bar should be in horizontal formations to connect with existing Circuit
Breaker Panel Board without any difficulty in matching.
The bus - bar shall be supported on insulator at short intervals, keeping adequate clearance between
the bus bar and earth. The bus - bar chamber shall be provided with inspection cover with gaskets &
bus bar shutters. Provision shall be made for future extension of bus bar & switch board.
8.6 CUBICLE:
a) The switchgear cubicle (panel) shall be free standing floor mounting indoor type.
There shall be sufficient reinforcement to have level surfaces resistance to vibration
and rigidity during transportation & installation.
b) Design & construction of the switchgear panel shall be of the highest order. All sheet
steel work shall be treated as per the seven tank process before applying primary
coating. For the final coat (stowed) epoxy paint color shade of light admiral grey to
shade No.697 as per IS:5 shall be used. Alternatively powder coating may also be
accepted. The panels after final painting shall present an aesthetically pleasing
appearance, free of any dent or uneven surface.
c) Power cable compartment shall be provided at the rear of the switchgear panels and
shall be suitable for cable entry from the bottom cable trenches. Rear bottom plates
of the cable compartment shall be fitted with removable gland plates of adequate
size for fixing the cable glands.
d) Cable compartments for the incomer shall be suitable for terminating 1nos. of 3Cx300
sq.mm XLPE cables and that for feeder shall be suitable to accommodate 2 nos. of
3Cx300 sq.mm. XLPE cables. Copper terminator strip of suitable size shall be
provided for termination of cables and shall have adequate height inside to
accommodate the heat shrinkable type indoor cable termination. Cable
compartment shall be robust enough & self-supporting. The design shall be such that
the weight of the power cable within the compartment shall not cause direct
pressure on the C.T. studs. Suitable clamping arrangement shall be provided at the
bottom of the cable compartment. Each power cable shall be terminated
independently.
• Outgoing 2 nos. of 400A VCB ((21.4kA for 3 Sec) shall be provided with IDMT non-
directional shunt trip & Electromechanical relay. Relay shall be microprocessor based
numerical type of preferred make as mentioned with adequate input and output suitable
for: The relay shall be complete with a wide range of standard communication protocols
(Modbus,RS-485, etc). Relay shall provide simple and powerful operator interface. The LEDs
and LCD display on the front panel shall be fully programmable to user requirements. The
relay shall be capable of control functions. Necessary displays shall be readable on the front
panel and available for local viewing and remote transmission. Each relay inputs and 4
outputs are to be freely assignable and combinations of any thresholds are independently
programmable for each output. Voltage input is to be derived from PT and current inputs are
to be derived from CTs mounted in the VCB panel.
Apart from the above, the outgoing feeder VCBs (2 Nos) shall be provided with required numbers of
distinct LED indication lamps for indicating Transformer Buchholz relay trip, Transformer high
temperature warning and Transformer high temperature trip for both oil & winding, Pressure
release valve Trip,Oil surge relay trip,Trip Circuit Synchronous Relay(95),Master trip relay (86).Each
lamp body shall be of moulded insulation and shall be able to withstand a high voltage test of
appropriate value. All LEDs shall be suitable for 240 V AC supply and shall have low power
consumption and shall provide a wide angle of illumination of sufficient intensity for comfortable
viewing. A glass of appropriate colour shall be screwed into the front of the LED. The design of LED
shall be such as to facilitate replacement of defective LEDs. An engraved label indicating the purpose
of the LED shall be provided with each LED.
b) All front mounted as well as internally mounted items including MCBs shall be
provided with individual identification labels. Labels shall be mounted directly below
the respective equipment and shall clearly indicate the equipment designation.
c) Terminal blocks shall be of screw type design made out of non-trackable insulating
material of 1100 V grade. All terminals shall have all current carrying and live parts
made of tinned plated brass. The washers, nuts, etc. used for terminal connectors shall
also be of tinned plated brass.
d) At least 20% spare terminals shall be provided. All terminals shall be provided with
ferrules indelibly marked or numbered and identification shall correspond to the
designations on the relevant wiring diagrams. The terminals shall be rated for
adequate capacity which shall not be less than 10 Amps for control circuit. For power
circuit it shall not be less than 15 Amps.
e) All fuses used shall be of HRC type. The fuse base and carrier shall be plug-in type
moulded case kitkat of backelite/DMC. All current carrying and live parts shall be of
tinned/nickel plated copper. No fuse shall be provided on DC negatives and AC
neutrals. Tinned copper links shall, however, be provided on DC negatives and AC
neutrals.
f) All MCBs as per IS:8828/2006 (amended upto date) of adequate rating shall be used.
• Annunciator of Incoming system should have 4 window and 2 spare window provision
• Annunciator of outgoing system should have 12 window and 2 spare window provision
8.14 NAME PLATE AND DIAGRAM PLATES :
All equipment shall have weather proof and non corrosive metal plates fixed in suitable
position with full particulars engraved thereon with white letters against black background.
The firm shall affix a name plate on each Switchgear panel having following information:
1. Manufacturer’s name and trade mark.
2. Serial No.
3. Type of Panel.
4. CT Ratio.
5. Rated Voltage.
6. Rated Insulation Level
7. Rated Frequency
8. Rated Normal Current
9. Rated Short Circuit Breaking Current.
10. Weight
11. Specification No.
12. Order No. and Date
13. Year of supply.
14. Property of respective state DisCom.
8.15 PAINTING:
All metallic surface [except corrosion resistant aluminium-zinc material and enamelled and
bright parts] exposed to weather shall be given suitable primer coat and two coats of first
quality paint of approved colour. The supplier shall also supply adequate quantities of
paints, varnish etc. for use of finished cost and for use of patching up any scratches received
during transport, handling erection testing and commissioning.
Instead of above proper powder coating after proper pre-treatment is acceptable and in that
case earlier condition will not applicable.
9.4Switchgear Panel
a) IP 4X Test
b)Supplier shall furnish all above drawings and following additional drawings
for approval before commencement of supply.
i. Foundation details.
ii. Equipment door layout for incomer, bus coupler & feeder panels.
iii. Schematic Diagram for incomer bus coupler & feeder section of Switchgear
iv. Protection Circuit for incomer bus coupler & feeder section of Switchgear
v. DC control circuit for incomer, bus coupler & feeder section.
vi. Metering circuit for incomers, bus coupler & feeder section.
vii. Annunciator and Alarm scheme.
viii. P.T. supply change over scheme.
ix. Terminal block details for incomer, bus coupler & feeder section.
x. Cross section view for CTs.
xi. Name Plate & Connection diagram for CTs.
xii. Cross section view for PTs.
xiii. Name Plate & Connection diagram for PTs.
xiv Diagram for Control Desk.
xv. G. A. Drawing for Sliding Door Unit.
The manufacturing of the equipment shall be strictly in accordance with the approved
drawings and no deviation will be permitted without the written approval of the APDCL. All
manufacturing and fabrication work in connection with the equipment prior to the approval
of the drawings shall be at the suppliers risk.
• After approval of the drawings and bills of materials, the suppliers shall submit
detailed packing lists for approval. After approval, copies of these packing lists shall be
forwarded to the respective consignees.
• Six set of final drawings, bill of materials, wiring schedules, technical literature and
commissioning manuals shall invariably be forwarded to the consignee alongwith the each
panel consignment, and shall be listed out in the packing list when submitted for approval.
All drawings shall preferably be of A3 size. In case the supplier fails to furnish contractual
drawings and manuals even at the time of supply of equipment, the date of furnishing of
drawings/manuals will be considered as the date of supply of equipment for the purpose of
computing penalties for late delivery.
12.0 Guaranteed Technical Particulars for 11kV HT VCB OUTDOOR IP-54 PANEL
Excel Sheet of Technical parameters list which needs to be submitted by Vendor along with the offer
By evaluation of Techno - Commercial parameters order allotment will be done.
Note:
• The Manufacturer/Supplier has to full- fill the required technical specification mentioned as
mentioned Above.
• Manufacture to fill GTP along with offer.
13.0 Typical SLD of System