Operating Instructions
Operating Instructions
-3-
English
The customer has to place a suitable room at disposal, as power cable. Make sure the system is adequately earthed.
shown in the figure: Check that the voltage and frequency of the power supply
correspond to the specifications on the unit’s data plate
and/or enclosed electrical plan.
-4-
English
Corrosion protection: Water quality A (No water treatment necessary):
PFANNENBERG recommends that Glycol is also used as a Fresh water from the tap, free of contamination
rust inhibitor. The minimum percentage of glycol (in a mixture Ph-level:7-9
with water) recommended by some important glycol supplier Hardness: <5 °dH
(Clariant, Total, Dowfrost, etc..) is between 20% and 30%. Conduction: <50µS/cm
Chloride: <20 mg/l
CAUTION!: Please contact the Glycol supplier to know
the minimum percentage needed in order to use the Glycol Water quality B (Water treatment is recomemended):
as rust inhibitor
Fresh water from tap, free of contamination
Ph-level:7-8, 5
CAUTION!: All the typelabel of the STD Pfannenberg Hardness: <10 °dH
unit are provided with a percentage of glycol of 20% Conduction: <300µS/cm
Chloride: <50 mg/l
The percentages of glycol into the mixture is related to the
minimum working temperature of the mixture (that must be in
line with the minimum working set point of the unit, please Water quality C (Water treatment manditory):
see the technical data of the unit): Fresh water from tap, free of contamination
Ph-level:7-8,5
percentage Water temperature up to : Hardness: <20 °dH
Conduction: <500µS/cm
10% + 3 °C Chloride: <100 mg/l
15% 0 °C
20% - 3 °C 10. Process Oil / Fluids
25% - 6 °C
PFANNENBERG chillers (in the std oil version) are designed
30% -10 °C to work with the following oil viscositys:
CAUTION!: The type of glycol (propylene or ethylene) CAUTION!: do not utilize oils with sulphur-base
must be in conformity with the Standard requested by the
application, please contact the Glycol supplier additives; the copper-made exchanger could be damaged (*)
• Do not allow mechanical contamination to get in the OIL CHILLER with pump
water. Use water filters if this could be a problem.
Usually, the CHILLERS with pump are utilized to cool an
• Water hardness should not be too high. (see below) hydraulic system provided with reservoir; therefore, the filling
is directly carried out on the machine. Refer to the
• Watch for chemical contamination. If this is to become a instructions provided by the system manufacturer
problem, treat the water with passivators and/or
inhibitors.
11. Ambient temperature
• Do not allow biological, slime bacteria, and algae
When ambient temperatures are above 35 degrees C. (95
contamination. If this does happen, treat the water with
degrees F.) or below 10 degrees C. (50 degrees F.),
biocides.
PFANNENBERG should be consulted. High ambient
PFANNENBERG recommends that the properties of the temperatures reduce chiller capacity. Low ambient
water has to be checked in order to identify the quality temperatures require special controls. Special conditions
apply when temperatures drop below 0 degrees C. (32
degrees F.). Fluid heaters may be required to prevent
-5-
English
freezing and to hold the fluid in the chiller reservoir at a Switch all circuit breakers to the “on” position. At this time the
constant temperature in order to reduce start-up delays while chiller should operate automatically according to the
the fluid warms up to operating temperature. controllers “set point values”. If necessary, set controller
according to customers temperature requirements. (Please
refer to the manual of the thermostat delivered with the unit)
12. Start up of the chiller
CAUTION!: WORK ON THE ELECTRICAL AND After installation, the REFRIGERATOR does not need
REFRIGERANT CIRCUITS MAY ONLY BE PERFORMED intervention by the Qualified Operator.
BY QUALIFIED PERSONEL.!!!!!!! Every calibration operation on thermostats, pressure switch
and whatever component of the refrigerating circuit, the
personnel of the Technical Servicing or the Refrigerator
• Turn main switch, control switch, all circuit breakers to Technician only is competent.
switches to the - 0 - (off) position.
• Check the internal hydraulical connection (clamps and For further information on chiller installation, start-up or
fittings) that may get loose during transportation troubleshooting please contact PFANNENEBERG
• CHILLER without pump: check the fan direction of • Start the system in the same way like described above
rotation (see the arrow on the fan case). Reverse two for the Std units
phases R-S-T on the terminal board in case of incorrect
rotation • After the water circuit of the unit has run for approx. 5
minutes, switch off the main switch and check again the
pressure of the system
-6-
English
13. Maintanace / Check and Inspections
CAUTION! Before any maintenance intervention, not
needing the machine running, disconnect the supply voltage
and have a sign MAINTENANCE IN PROGRESS to be • Longer standstill of the chiller requires draining of the
posted to the general breaker tank and complete water circuit.
To carry out the tests and check program described here will • Check of the thermal charge of the chiller: the
extend the life of the equipment and avoid possible temperature and the delivery of the hydraulic circuit must
breakdowns. not exceed to the set limits of the unit
• The condenser must be cleaned in monthly intervals, or, Open loop applications
if required in shorter time intervals.
An open loop application is where there is some contact
• If the chiller is equipped with an air filter, the filter has to
between the air and the water. Our standard chillers, with
be changed/cleaned monthly, or, if required in a shorter
tanks, allow contact between air and water. Typically when
time interval
we cool a customer reservoir, the reservoir allows contact
between air and water.
In an open loop application, there is no problem placing the
chiller above the application.
There are some precautions we need to take when placing a
chiller below the application when we are in an open loop
application. There needs to be a check valve in the water
pipes on the outlet of the chiller. (A check valves allows
water to go out, but it does not allow it to come back.) There
also need to be an electrical solenoid valve placed on the
inlet of the water chiller. This valve needs to close when the
chiller is not running. These two valves will prevent water
from flowing back into the chiller, and overflowing out of the
tank
1. Air filter
-7-
English
15. Debug Table
The information shown in this table is designed for the service staff at the factory. The faults that require the intervention
of a refrigeration engineer must be carried out only by specialized staff. Follow all electrical legislation when working on
the unit basaed on valid laws of the countries were the unit is placed.
Chiller
Problem Cause Possible corrective Action
The unit does not start No supply voltage Check the supply main voltage line
up Not working thermostat Inspect the connection, check and correct the parameter settings and if there
is no fault, replace the thermostat,
The compressor protector (KLIXON) Important: After the shut down of the compressor, the resetting time will
has switched off depending on the environment of the compressor: In a hot closed
environment it will be 2 hours, in ventilated 1 hour.
Note: The compressors are protected against high temperatures and
currents, with of an internal or external device (Klixon). The internal/external
device protects the compressor against the following situations:
• overheating due to an inadequate cooling of the compressor motor.
• Blocked compressor due to a high temperature of the motor or a high
current.
• Loose connections which may cause high currents
It works, but does not There is not enough gas in the Service by a refrigeration engineer
cool equipment
Faulty thermostatic valve Service by a refrigeration engineer
Too high heat load Possible wrong application, to be checked with our staff
Refrigerant Cycle is not working
Problem Cause Possible corrective Action
Switching of the double The unit works for short periods, it Service by a refrigeration engineer
pressure switch (low stops and starts again after a while.
pressure side) The causes are:
• Low gas level in the equipment
• Outlet line of the compressor is
blocked and more in detail:
satured dehydrating filter,
blocked thermostatic valve.
Switching of the double The unit does not work.
pressure switch (high The causes are:
pressure side)
• Dirty condenser Clean the condenser with compressed air if it is full of dust, or use proper
solvents suitable to remove sludges.
• The fan is broken Replace the fan
• Too high ambient temperature Check that the chiller is located in a place that can guarantee suitable
ventilation of the refrigerating unit. Check also that the ambient temperature
does not exceed +40°C.
Note: after solving the cause of
the fault, start the chiller by
pressing the reset button (RESET)
located on the external body of the
pressure switch itself (see the
picture)
Compressor
Problem Cause Possible corrective Action
The compressor works continuously and the chiller can’t control the liquid temperature:
- too low temperature of the liquid
- too high temperature of the liquid
Too low temperature Broken thermostat (contact blocked) Replace the thermostat
Broken thermostat Replace the thermostat
Too high temperature Not enough Freon in the unit Please ask for the service by a refrigeration engineer
Too high heat load Possible wrong application, to be checked with our staff
-8-