0% found this document useful (0 votes)
42 views

Datasheet MultiPlus II 120V EN

The MultiPlus-II is an inverter/charger that can boost the capacity of a grid or generator to prevent overloading. It can also provide backup power from batteries during grid failures. It has features like PowerControl, PowerAssist, and supports solar charging. It comes in several models with different voltage/power levels, and can operate in parallel or series configurations for greater output power or voltage. It can be monitored and controlled remotely through Victron products and software.

Uploaded by

Alamdar Hassnain
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
42 views

Datasheet MultiPlus II 120V EN

The MultiPlus-II is an inverter/charger that can boost the capacity of a grid or generator to prevent overloading. It can also provide backup power from batteries during grid failures. It has features like PowerControl, PowerAssist, and supports solar charging. It comes in several models with different voltage/power levels, and can operate in parallel or series configurations for greater output power or voltage. It can be monitored and controlled remotely through Victron products and software.

Uploaded by

Alamdar Hassnain
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

MultiPlus-II Inverter/Charger Victron online product page

120 V \ https://ve3.nl/6H

A MultiPlus with ESS (Energy Storage System) functionality


The MultiPlus-II is a multifunctional inverter/charger with all the features of the MultiPlus, plus an external
current sensor option which extends the PowerControl and PowerAssist function to 100A.
PowerControl and PowerAssist - Boosting the capacity of the grid or a generator
A maximum grid or generator current can be set. The MultiPlus-II will then take account of other AC loads and use
whatever is extra for battery charging, thus preventing the generator or grid from being overloaded (PowerControl
function).
PowerAssist takes the principle of PowerControl to a further dimension. Where peak power is so often required only for a
limited period, the MultiPlus-II will compensate insufficient generator, shore or grid power with power from the battery.
When the load reduces, the spare power is used to recharge the battery.
Solar energy: AC power available even during a grid failure
The MultiPlus-II can be used in off grid as well as grid connected PV and other alternative energy systems. It is
compatible with both solar charger controllers and grid-tie inverters.
Two AC Outputs
The main output has no break functionality. The MultiPlus-II takes over the supply to the connected loads in the event of
a grid failure or when shore/generator power is disconnected. This happens so fast (less than 20 milliseconds) that
computers and other electronic equipment will continue to operate without disruption.
The second output is live only when AC is available on the input of the MultiPlus-II. Loads that should not discharge the
battery, like a water heater for example, can be connected to this output.
Virtually unlimited power thanks to parallel, split phase and three phase operation
Up to 6 Multis can operate in parallel to achieve higher power output. Six 48/3000/35 units, for example, will provide
15 kW / 18 kVA output power with 210 Amps charging capacity.
In addition to parallel connection, two units of the same model can be connected for a 240V split phase output, and
three units of the same model can be configured for three phase output. But that’s not all: up to 6 sets of three units can
be parallel connected per phase.
On-site system configuring, monitoring and control
Settings can be changed in a matter of minutes with VEConfigure software (computer or laptop and MK3-USB interface
needed).
Several monitoring and control options are available: Color Control GX, Venus GX, Octo GX, CANvu GX, laptop,
computer, Bluetooth (with the optional VE.Bus Smart dongle), Battery Monitor, Digital Multi Control Panel.
Remote configuring and monitoring
Install a Color Control GX or other GX product to connect to the internet.
Operational data can be stored and displayed on our VRM (Victron Remote Management) website, free of charge.
When connected to the internet, systems can be accessed remotely, and settings can be changed.

Standard marine, mobile or off-grid application Grid parallel topology with MPPT solar charge controller
Loads that should shut down when AC input power is not available can The MultiPlus-II will use data from the external AC current sensor
be connected to a second output (not shown). These loads will be taken (must be ordered separately) or power meter to optimise self-
into account by the PowerControl and PowerAssist function in order to consumption and, if required, to prevent grid feed. In case of a power
limit AC input current to a safe value when AC power is available. outage, the MultiPlus-II will continue to supply the critical loads
MultiPlus-II 120V 12/3000/120-50 24/3000/70-50 48/3000/35-50 48/5000/70-95
PowerControl & PowerAssist Yes
Transfer switch 50A 50A 50A 95A
Maximum AC input current 50A 50A 50A 95A
INVERTER
DC Input voltage range 9,5–17 V 19–33 V 38 – 66 V 38 – 66 V
Output voltage: 120 VAC ± 2%
Output
Frequency: 60 Hz ± 0,1% (1)
Cont. output power at 25°C (3) 3000 VA 3000 VA 3000 VA 5000 VA
Cont. output power at 25°C 2400 W 2400 W 2400 W 4000 W
Cont. output power at 40°C 2200 W 2200 W 2200 W 3700 W
Cont. output power at 65°C 1700 W 1700 W 1700 W 3000 W
GX Touch 50 and Cerbo GX
Peak power 5500 W 5500 W 5500 W 9000 W
Provides intuitive system control and monitoring
Besides system monitoring and control the Cerbo GX Maximum efficiency 93% 94% 95% 96%
enables access to our free remote monitoring website: Zero load power 13 W 13 W 11 W 15 W
the VRM Online Portal. Zero load power in AES mode 9W 9W 7W 10 W
Zero load power in Search mode 3W 3W 2W 3W
CHARGER
Input voltage range: 90-140 VAC
AC Input
Input frequency: 45 – 65 Hz
Charge voltage 'absorption' 14,4 V 28,8 V 57,6 V 57,6 V
Charge voltage 'float' 13,8 V 27,6 V 55,2 V 55,2 V
Storage mode 13,2 V 26,4 V 52,8 V 52,8 V
Max. battery charge current 4) 120 A 70 A 35 A 70 A
Battery temperature sensor Yes
GENERAL
Auxiliary output (5) 32 A 32 A 32 A 48 A
External AC current sensor
100 A
(optional)
Programmable relay (6) Yes
VRM Portal Protection (2) a–g
Our free remote monitoring website (VRM) will For parallel, split phase and three phase operation,
display all your system data in a comprehensive VE.Bus communication port remote monitoring and system integration
graphical format. System settings can be changed General purpose com. port (7)
Yes, 2x
remotely via the portal. Alarms can be received by e- Remote on-off Yes
mail. Operating temperature range -40 to +60°C (-40 – 140 °F) (fan assisted cooling)
Humidity (non-condensing) max 95%
ENCLOSURE
Material & Colour Steel, blue RAL 5012
Protection category IP22
Battery-connection M8 bolts
13 mm² 13 mm² 13 mm² 35 mm²
120 V AC-connection
(6 AWG) (6 AWG) (6 AWG) (2 AWG)
Weight 19 kg / 42 lb 19 kg / 42 lb 19 kg / 42 lb 32 kg / 71 lb
578 x 277 x 148 536 x 277 x 147 572 x 277 x 147(8) 676 x 330 x 164
Dimensions (hxwxd) mm
22.8 x 10.9 x 5.8 21.1 x 10.9 x 5.8 22.5 x 10.9 x 5.8(8) 26.6 x 13.0 x 6.5
STANDARDS
Listings UL458 UL458 UL1741 UL1741 pending
Safety EN-IEC 60335-1, EN-IEC 60335-2-29, CSA 22.2 107.1-16
EN 55014-1, EN 55014-2
Emission, Immunity EN-IEC 61000-3-2, EN-IEC 61000-3-3
IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
1) Can be adjusted to 50 Hz 3) Non-linear load, crest factor 3:1
2) Protection key: 4) Up to 75°F / 25°C ambient
VRM app VE.Bus Smart Dongle a) output short circuit 5) Switches off when no external AC source available
Monitor and manage your Measures battery b) overload 6) Programmable relay which can be set for general alarm, DC under voltage or genset
Victron Energy system voltage and c) battery voltage too high start/stop function. AC rating: 120V / 4A, DC rating: 4A up to 35VDC and 1A up to 60VDC
d) battery voltage too low 7) A.o. to communicate with a Lithium-Ion battery
from your smart phone temperature and
e) temperature too high 8) Dimensions of the not UL1741 certified model:
and tablet. Available for allows monitoring and f) 120 VAC on inverter output 536 x 277 x 147 mm / 21.1 x 10.9 x 5.8 inch
both iOS and Android. control with a smart g) input voltage ripple too high
phone or other
Bluetooth enabled
device.

Current sensor 100A:50mA Digital Multi Control Panel


To implement PowerControl and PowerAssist A convenient and low-cost solution for remote
and to optimize self-consumption with monitoring, with a rotary knob to set
external current sensing. PowerControl and PowerAssist levels.
Maximum current: 100A.
Length of connection cable: 1 m. or 5m.
Connection Area 12/3000/120-50

Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands


E-mail: [email protected] | www.victronenergy.com

You might also like