0% found this document useful (0 votes)
46 views

RTM Load Sched

1. The document appears to be a panel schedule listing load descriptions, voltages, circuit breaker sizes, wire sizes, and conduit sizes for various circuits. 2. Key information includes a main circuit breaker, bus riser circuit breaker, and five listed circuits covering utility room loads. 3. Computations are shown calculating full load current, circuit breaker ampacity, and wire ampacity for the panel. A transformer computation is also included.

Uploaded by

Alvin Pangilinan
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
46 views

RTM Load Sched

1. The document appears to be a panel schedule listing load descriptions, voltages, circuit breaker sizes, wire sizes, and conduit sizes for various circuits. 2. Key information includes a main circuit breaker, bus riser circuit breaker, and five listed circuits covering utility room loads. 3. Computations are shown calculating full load current, circuit breaker ampacity, and wire ampacity for the panel. A transformer computation is also included.

Uploaded by

Alvin Pangilinan
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 5

PANEL NAME MAIN MCCB CABLE SIZED AND CONDUIT SIZE KAIC ENCLOSURE LOCA

PHASE VOLTS
DP-2A POLE AT AF 3 - #REF! + #REF! MAIN: 10 NEMA-1 UTILI
3 230 3 #REF! #REF! AT #REF! IMC BRS: 10 WALL MTD (PLAT
CKT. BRS MCCB LOAD DISTRIBUTION CABLE/GROUNDING CONDU
LOAD DESCRIPTION PHASE VOLTS KVA BREAKER WIRE
NO POLE AT AF RN SN TN 3Ø AMP TYPE & SIZE TYPE
1 PP-UTIY-1 3 230 3 #REF! #REF! #REF! #REF! #REF! #REF! #REF! 1.732 #REF! #REF! #REF! 3 - #REF! + #REF! IMC
2 PP-UTIY-2 3 230 3 #REF! #REF! #REF! #REF! #REF! #REF! #REF! 1.732 #REF! #REF! #REF! 3 - #REF! + #REF! IMC
3 PP-UTIY-3 3 230 3 #REF! #REF! #REF! #REF! #REF! #REF! #REF! 1.732 #REF! #REF! #REF! 3 - #REF! + #REF! IMC
4 PP-PROD-230V 3 230 3 #REF! #REF! #REF! #REF! #REF! #REF! #REF! 1.732 #REF! #REF! #REF! 3 - #REF! + #REF! IMC
5 PP-CT 3 230 3 #REF! #REF! #REF! #REF! #REF! #REF! #REF! 1.732 #REF! #REF! #REF! 3 - #REF! + #REF! IMC

TOTAL #REF! #REF! #REF! #REF! #REF!


COMPUTATION: Demand Factor : 80% Correction Factor: 94% HMR: 80.30 A

Full Load Current L-L (A): Circuit Breaker Ampacity (A):

I_FL (= I_3Ø + √3 x I_1Ø + 25% HMR ) x DF I_CB = ( I_FL x 125%)


= ( #REF! + √3 x #REF! + 25% x 80.3 ) x 80% = ( #REF! x 125%)
I_FL = #REF! A I_CB ###
= #REF! A

Wire Ampacity (A): USE : #REF! / #REF! , 3 - #REF! + #REF!


I_WA =( I_FL x 125%) / 𝐂𝐅 AT #REF!
= ( #REF! x 125%)/0.94
I_WA = #REF! A
LOCATION
UTILITY RM
(PLATFORM)
CONDUIT SIZE
SIZE
#REF!
#REF!
#REF!
#REF!
#REF!
PANEL NAME MAIN MCCB CABLE SIZED AND CONDUIT SIZE KAIC ENCLOSURE LOCATION
PHASE VOLTS
MDP-230A POLE AT AF 3 - #REF! + #REF! MAIN: 10 NEMA-1
UTILITY RM
3 230 3 #REF! #REF! AT #REF! IMC BRS: 10 WALL MTD
CKT. BRS MCCB LOAD DISTRIBUTION CABLE/GROUNDING CONDUIT SIZE
LOAD DESCRIPTION PHASE VOLTS KVA
NO POLE AT AF RN SN TN 3Ø TYPE & SIZE TYPE SIZE
1 DP - 1 3 230 3 #REF! #REF! #REF! #REF! #REF! #REF! #REF! 3 - #REF! + #REF! IMC #REF!
2 DP - 2A 3 230 3 #REF! #REF! #REF! #REF! #REF! #REF! #REF! 3 - #REF! + #REF! IMC #REF!
3 DP - 3 3 230 3 #REF! #REF! #REF! - - - #REF! 3 - #REF! + #REF! IMC #REF!
4 100 KVA DT TRANSFORMER 230V/200V 3 230 3 300 350 100.00 - - - 251.0 3 - 150mm² THHN + 22mm²(E) IMC 75mmØ
5 CAPACITOR BANK ( 150KVAR - 6 STEPS) 3 230 3 20 63 3 - 3.5mm² THHN + 3.5mm²(E) IMC 15mmØ

TOTAL #REF! #REF! #REF! #REF! #REF!


COMPUTATION: Demand Factor : 80% Correction Factor: 94% HMR: - A

Full Load Current L-L (A): Circuit Breaker Ampacity (A): TRANSFORMER COMPUTATION: Use Diversity Factor of 1.3

I_FL (= I_3Ø + √3 x I_1Ø + 25% HMR ) x DF I_CB = ( I_FL x 125%) ((√3×𝐼_𝐹𝐿×𝑉))⁄1000


KVA_𝑇𝑅 =
= ( #REF! + √3 x #REF! + 25% x 0.0 ) x 80% = ( #REF! x 125%) =(√3× #REF! × ) / 1000
230
I_FL = #REF! A I_CB ###
= #REF! A = #REF! / 1.3
KVA_𝑇𝑅 = #REF!
Wire Ampacity (A): USE : #REF! / #REF! , 3 - #REF! + #REF! USE : #REF! DRY TYPE TRANSFORMER 230V/200V 3P 60HZ
I_WA =( I_FL x 125%) / 𝐂𝐅 AT #REF!
= ( #REF! x 125%)/0.94
I_WA = #REF! A
PANEL NAME MAIN MCCB CABLE SIZED AND CONDUIT SIZE KAIC ENCLOSURE LOCA
PHASE VOLTS
RC60 Panel POLE AT AF 3 - 125mm² THHN + 22mm² THHN (E) MAIN: 10 NEMA-1
UTILIT
3 230 3 40 63 65mmØ CONDUIT IMC BRS: 10 WALL MTD
CKT. BRS MCCB LOAD DISTRIBUTION CABLE/GROUNDING CONDU
LOAD DESCRIPTION PHASE VOLTS KVA WIRE BREAKER
NO POLE AT AF RS ST TR 3Ø AMP TYPE & SIZE TYPE
1 21 - Lightings (18W) 1 230 2 15 63 0.47 2.04 1 2.0 2.6 2.6 3.5mm² Royal Cord 3C EMT
2 4 - Blower Fan (200W) 1 230 2 20 63 1.00 4.35 1 4.3 5.4 5.4 3.5mm² Royal Cord 3C EMT
3 6 - C.O 1 230 2 20 63 1.50 6.52 1 6.5 8.2 8.2 3.5mm² Royal Cord 3C EMT
7 Welding Outlet 3 230 3 40 63 2.50 6.28 1.732 6.3 7.8 15.7 8.0mm² Royal Cord 4C EMT

TOTAL 5.6 2.04 4.35 6.52 6.28


COMPUTATION: Demand Factor : 80% Correction Factor: 94% HMR: A

Full Load Current L-L (A): Circuit Breaker Ampacity (A):

I_FL (= I_3Ø + √3 x I_1Ø + 25% HMR ) x DF I_CB = ( I_FL x 125%)


=( 6.3 + √3 x 6.5 + 25% x 0.0 ) x 80% = ( 14.1 x 125%)
I_FL = 14.06 A I_CB ###
= 17.6 A

Wire Ampacity (A): USE : 40AT/63AF, 3P


I_WA =( I_FL x 125%) / 𝐂𝐅 8.0mm² Royal Cord 4C
= ( 14.1 x 125%)/0.94
I_WA = 18.69 A
LOCATION

UTILITY RM

CONDUIT SIZE
SIZE
15mmØ
15mmØ
15mmØ
25mmØ