Part-2 - Section 7 - Static Digital Excitation System - Particular Technical Specification
Part-2 - Section 7 - Static Digital Excitation System - Particular Technical Specification
Part-02
TABLE OF CONTENTS
7-01 SCOPE
A. This Section specifies the detailed requirements for the design, manufacture,
testing at works, delivery for project site, storage till handing over, erection, testing &
commissioning of Nine (9) Set of excitation systems and appurtenances to be furnished
complete in accordance with these Specifications.
B. The following paragraphs written in the singular form for one excitation system
shall apply equally to all excitation systems furnished, except where specifically
indicated otherwise.
C. The basic materials and methods shall be in accordance with Part-02, Section – 1-
07: Materials and Equipment’s. The generators shall be in accordance with Part-02,
Section – 6: Generators. Field-testing shall be in accordance with Part-02, Section – 08:
Installation and Field Testing of Major Equipment.
2. Be a high initial response type, as defined in IEEE Std. 421.1. The excitation
system voltage response time shall not exceed 0.08-s for positive field forcing
and 0.15-s for negative field forcing.
3. Have a positive ceiling voltage not less than 2 times the generator rated full-
load field voltage. The system shall be designed to attain full ceiling voltage
with generator terminal voltage at 80% of the rated value.
4. Capacity to supply continuously 1.1 times the excitation current and voltage
required by the generator at 100% rated kVA and 90% to 110% of rated
voltage. The rectifier shall be provided with 3 x 110% bridges, one operating in
standby mode. Transfer from one bridge to the other shall be bumpless.
Alternately, the rectifier shall have 3 x 55% bridges operating in parallel.
Page 2 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
6. During transients such as short circuits and load rejections, the excitation
system shall be able to operate with a supply voltage between 30%-130% of
rated generator voltage applied to the excitation transformer without an
excitation system trip.
7. The excitation system shall be capable of supplying its ceiling voltage and the
growing field current associated with the sudden application of ceiling voltage
to the generator field for at least 5 seconds. The ceiling current momentary
capability of the excitation system shall be at least 2 times the rated field
current, and the thermal capability for periods of more than 5 seconds shall be
higher than the short-time thermal capability of the generator field winding.
10. The DC output shall be provided with suitable filters to minimize harmonic
heating of the generator field, audible noise, and possible shaft voltages. Shaft
voltages produced by the excitation system ripple shall be limited to 5 V peak
or less.
Page 3 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
11. Adjustable and accurately set parameters such as gain, time constants,
feedback signals, reference signals, etc. The optimum settings shall be
recommended by the manufacturer and approved by the Purchaser.
13. Designed for local (at the excitation regulator cubicle) and remote control. The
Excitation Control System shall be equipped with necessary communication
interface equipment for direct digital communication with the Plant Control
System over fiber-optic cables.
14. The microprocessor shall include all software functions for protection and
excitation limiting needed to operate the generator within safe boundaries, as
well as a Power System Stabilizer (PSS) function.
F. Standards: Ratings, tests, and characteristics shall be in accordance with the latest
approved standards of IEC, IEEE, unless otherwise specified.
G. General: Controls shall be arranged for both local and remote operation of the
excitation system. Unless otherwise specified, all accessories required for remote
interface shall be provided whether or not such items are specifically mentioned in
these Specifications.
Page 4 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
H. Controls: The following controls shall be mounted on the front of the excitation
system enclosures. Similar functioning controls in a touch screen or soft touch
buttons mounted on the faceplate of the microprocessor-based excitation controller
can be provided instead of switches:
Page 5 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
or base excitation control. The balance position shall be provided for manual
adjustment, as necessary, of either the base excitation regulator or voltage
regulator prior to completing the transfer.
1. Status Signals
Page 6 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
be used instead of the switch contacts listed when the actions are
performed by the microprocessor control system:
Page 7 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
2. Alarms: Alarm and trip contacts shall be as specified in this Section under 7-08,
Protective Devices.
3. Controls: Provisions shall be made for interfacing with the remote control
circuits as follows:
c. PF Set point.
Page 8 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
j. Excitation "On"
k. Excitation "Off"
L. The excitation system shall be provided with one 3-phase power transformer with
the following characteristics:
Page 9 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
3. Temperature Rise °C 70
6. Connections:
N. The transformer shall be totally enclosed in a metal enclosure, with front and back
doors. All necessary equipment for making the secondary interconnections to the
excitation cubicles shall be provided, including suitable bus or cables, raceway and
supports, and barriers and connectors, as needed. Punched louvers with cleanable
and reusable filters shall be provided as necessary for adequate ventilation.
Louvers shall be designed to prevent the entrance of insects and rodents. All
Page 10 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
doors shall be equipped with a handle, a three-point latch, and flush lock. The
locks shall be keyed alike.
Page 11 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
5. Low voltage surge protection equipment as required for the protection of the
transformer and static excitation system.
Q. Except for the core, windings, and enclosure, all metal parts shall be hot-dip
galvanized steel.
7-05 RECTIFIER
1. The rectifier shall consist of 3 x 110%. Each bridge assembly shall include a 6-
element, two quadrants and three phase set of thyristors with complete draw-
out capability for ready servicing. The assembly shall include individual fuses
Page 12 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
for thyristors and other critical elements and indication/locaters for blown
fuses and/or bad thyristor elements.
6. The power rectifying unit shall be provided with monitoring circuits to detect
failure of the firing signal to the thyristor.
7. The excitation system shall meet all the specified requirements when individual
thyristors are replaced by others of the same type but with different forward
voltage drop characteristics. The thyristors shall be replaceable with
commercially available units.
Page 13 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
8. All the control wires in the rectifier cubicle shall be shielded and isolated from
the AC and DC power circuits in the cubicle.
T. Cooling: Two sets of redundant, full-capacity cooling fans shall be provided for
cooling the exciter. Each set of fans shall be capable of supplying the total required
cooling air with the other set out-of-service. Power to the fans shall be derived
from the auxiliary power transformers specified in this Section under 7-13,
Auxiliary Power Equipment. Controls shall be provided for selecting the lead and
standby set of fans with automatic switchover to the standby set if the lead set of
fans fails. Alarm contacts shall be provided to alarm for fan failure as specified in
this Section under 7-8, Protective Devices. The cooling system components shall be
of types which are easily replaceable without tools. Inlet air shall not be drawn
from near the floor to prevent rapid clogging of the air filters. Filters shall be
aluminum, electrostatic, cleanable and reusable. If aluminum filters are furnished,
they shall contain layers of expanded aluminum laid at right angles to one another
and inner layers of woven aluminum wire to achieve maximum filtering.
U. A 2-pole, generator field air circuit breaker, equipped with a trip coil and with a field
discharge contact mechanically interlocked to the circuit breaker contact and an
Page 14 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
auxiliary switch having not less than 6 normally-closed and 6 normally-open single-
pole contact circuits shall be furnished. The breaker shall be provided with arc
extinguishers, and the operating mechanism shall be electrically and mechanically
trip free. It shall be arranged for 110 V DC electrical operations. The circuit breaker
shall have a rated continuous current not less than the maximum continuous
current of the excitation circuit under any of the specified operating conditions of
the generator and shall be capable of interrupting the generator field current
successfully under maximum voltage and short-circuit conditions. The contacts
shall be readily accessible for inspection and replacement. A molded-case circuit
breaker will not be acceptable. The field breaker will not be used for normal
disconnection of the field, which shall be done by application of negative voltage
as indicated in this Section under 7-03 C, De-excitation; however, the field breaker
shall open under fault conditions to de-energize the generator more quickly.
V. Non-linear field discharge resistors made of zinc-oxide switched by the breaker field
discharge contacts shall be furnished. The non-linear resistors shall have
characteristics such that the voltage across the resistor varies in proportion to
approximately the one-eighth power of current and shall be rated so that the field
flux will be reduced to zero in the shortest possible time. The generator field
winding voltage withstand rating and field circuit-breaker voltage rating shall be as
high as is necessary to accomplish this rapid reduction of the flux.
7-07 TRANSDUCERS
The DC voltage and current transducers shall have an accuracy of at least 0.5%.
The voltage transducer shall be connected to the generator field pilot brushes,
and the current transducer shall be connected in series with the generator field
leads.
X. Field Temperature: Field temperature transducers shall be furnished for use with
the field temperature indicator mounted on the excitation cubicle and with the
computer control system -Control, Measuring, Metering, and Protective System.
The field temperature transducer shall sense the variation in the field winding
resistance caused by temperature changes by integrating the values of field
voltage and field current to produce a single output rated 4-20 mA DC if connected
to a load of zero to 750 Ω. The transducer shall either be solid-state or digital,
integrated into the automatic voltage regulator specified in this Section under
7-12, Voltage Regulator. The accuracy shall be at least 0.5%. The temperature
indicator shall have a scale range of zero to 150°C.
Y. Output Ripple: Output ripple of transducers shall be less than 1.0% (peak-to-peak).
Z. Leads: All transducer input and output leads shall be shielded and isolated from AC
and DC power and control circuits.
Page 16 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
AA. The following solid state protective relays shall be furnished, mounted, and wired
on the front panels of the excitation system enclosures. Alternatively, these
protective functions may be performed by the microprocessor-based control
system:
2. One field voltage relay (59F) for detection of sustained field overvoltage.
3. One overcurrent relay (50/51 ET) for transformer primary winding overload
protection. Protection device shall consist both of definite time and inverse
time elements. Output contacts of definite time element shall be arranged to
alarm and reduce field current with auxiliary time delay relay. Output contacts
of inverse time element shall be arranged to trip the generator and field circuit
breaker.
BB. In addition to the above relays, sensing devices and/or functions shall be included
for detecting the following conditions:
Page 17 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
CC. Each of the protective relays and sensing devices shall be provided with a minimum
of 3 electrically independent contact circuits. One set of contacts shall be wired to
the annunciator. The other 2 contact circuits shall be wired to terminal blocks for
connection to remote devices.
NOTE - The offered system has no annunciator, All alarms are displayed in the local HMI.
All protection function in the excitation system are connected in parallel. This parallel
Page 18 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
connection has 2 contact circuit wired to terminal blocks for connection to remote
device.
7-09 ALARMS
DD. Alarms shall be displayed in the excitation control system touch-screen display or by
means of LED’s in the front plate of the microprocessor control system. One alarm
signal shall be provided for each condition listed in this Section under 11-08,
Protective Devices, plus a minimum of 8 additional unassigned signals. Each alarm
input circuit shall be powered from the internal power supply of the
microprocessor
EE. The alarm function shall have the following operating sequence for each alarm
signal:
Page 19 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
FF. Pushbuttons or touch screen functions shall be furnished to perform the following
functions:
1. Alarm Acknowledge.
2. Alarm Reset.
3. Lamp Test.
7-10 INSTRUMENTS
1. Field voltmeter
2. Field ammeter
Page 20 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
Equipment shall be furnished for a field build-up circuit for connection to the 400
V Unit Auxiliary Switchboard. The equipment shall include an AC contactor for switching,
rectifying diodes that also prevent feedback of current to the AC system, and control
devices. A backup system for field flashing from the station battery shall also be
provided. The backup system shall also be provided with a DC contactor and diodes to
prevent surge voltages into the batteries.
7-12 REGULATOR
HH. Type
3. The regulator system shall provide for local and remote adjustment.
Page 21 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
1. The automatic voltage regulator function shall have the following selectable
modes of operations:
3. The voltage set point shall be overruled when in VAR/PF control mode,
however, the system shall retain the limiting and protective functions, including
those related to the generator voltage
4. The voltage adjuster shall provide a range of voltage control of 80% to 110%
rated voltage. Local voltage set point adjustment shall be available from the
front of the excitation cubicle enclosure when the excitation system is under
local control only. Remote adjustment of the voltage set point shall be
available when control is set to other than local. The remote set point
adjustment shall be compatible with the Plant Control System and powerhouse
switchboard controls.
Page 22 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
6. After abrupt rejection of 100% rated active and reactive load, the regulator
shall restore the generator armature voltage to within 5% of the voltage before
the load rejection, in less than 1 second
8. When the generator is not connected to the system and under the control of
the automatic voltage regulator (AVR), if the set value of the generator
terminal voltage is step-changed from 95% to 105% or vice versa, the response
measured at the generator terminal voltage shall be non-oscillating and the
overshoot of the voltage response shall be less than 15% of the change.
current to the generator field. The manual voltage regulator function will be
used during testing and/or maintenance of the generator and excitation
system, and in case of a loss of voltage sensing or unbalance of the voltage
from the generator potential transformers.
2. When the excitation transformer is fed from the generator terminals the
Manual regulator adjustment shall permit adjustment of excitation current
required from 30% voltage and no load to 110% of generator voltage at full
load and rated power factor. Adjustment shall be available from the front of
the excitation cubicle enclosure.
3. During the generator short circuit tests, with the excitation system auxiliaries
and rectifier fed from a separate source the Manual regulator shall allow an
adjustment of the excitation current from 5% of the no-load current to 110% of
the rated full load current
LL. Automatic Failover Control: The regulator shall be provided with the capability to
continuously monitor its own function. Whenever AVR or VAR/PF function or
processor failure is detected, the control shall automatically transfer to the Backup
processor without causing a generator shutdown. Auxiliary contacts shall be
provided for indication and annunciation of these failures.
Page 24 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
1. The rate-of-change of the voltage and current set points shall be software
adjustable and, as a minimum, shall include a range of variation between 1%
and 0.3% of the rated no-load values per second.
2. A voltage follower unit shall be furnished for rapidly matching the generator
terminal voltage to the grid voltage to facilitate synchronizing.
3. The automatic voltage regulator shall include a power system stabilizer (PSS)
function to provide a supplementary control signal to the voltage regulator for
the purpose of improving dynamic stability of the generator. The PSS may
derive its signal from the change in unit speed, frequency, or power. A
complete PSS shall be furnished, including the speed, frequency, or power
transducer with adjustable gain and phase elements; damping elements; on-off
switch; and an adjustable limiter element to limit the voltage excursions of the
generator to 0-10% due to PSS control signals. The limiter shall have an alarm
contact circuit which closes for sustained operation at the limit after a time
delay which can be adjusted to prevent nuisance alarms. The optimal PSS
parameters shall be determined on the basis of system parameters supplied by
the Purchaser. As an alternative, a separate microprocessor-based self-
adaptive unit to respond to variation in the system load and impedance and to
automatically adjust the setting of the PSS may be provided. The design shall
include a self-test scheme to determine when a malfunction occurs and then
remove itself from control by automatically transferring control to the
automatic voltage regulator.
NN. Hardware
4. The microprocessor and each I/O module shall have LED type indicating lights
for trouble-shooting purposes. Photoelectric isolation shall be provided for all
I/O signals.
5. The I/O chassis shall be securely mounted in the rear of the control cabinet. All
I/O slots shall be keyed to prevent insertion of modules in the improper slot
location.
Page 26 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
6. A minimum of 20% full wired spare slots shall be provided for future expansion.
7. The microprocessor shall continuously set and reset a watchdog timer. Time
out of this device shall indicate failure of the microprocessor.
OO. Software: Software shall be provided to implement the requirements for the
voltage and base excitation regulation specified. Software shall be designed to
permit revisions to the program, such as changes in the operational sequences or
regulator parameters, from the program interface equipment specified.
PP. Auxiliary power transformers as needed shall be furnished to supply all required
auxiliary power in the excitation system, including power for fans, transducers,
display devices, and any other devices requiring low voltage AC power. The
primary of each such transformer shall be connected through a circuit breaker to
the excitation power transformer secondary.
Page 27 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
QQ. Control power for relays, air circuit breakers, field flashing circuits, and other
excitation system components will be 110 V DC from a station battery .
RR. Dual, regulated, fully-redundant, DC-DC power supply (or supplies) shall be
provided for the digital voltage regulator and for all low-voltage DC instrument
circuits. Power supplies shall be designed for 110 V DC from the station batteries
Equipment shall operate normally with the input power supply voltage at 80-110%
of rated.
7-14 DIAGNOSTICS
Page 28 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
signal and for measuring the resulting output. A provision shall be included for
complete operational testing of the voltage regulator, without energizing the
generator. Field repairable functional units shall be provided to the extent that
replacement of a failed subassembly or module shall restore the unit to normal
operating condition.
UU. Totally-enclosed metal enclosures shall be furnished to house the excitation and
voltage regulator equipment. The enclosures shall be provided in accordance with
the requirements. They shall be bolted together to make one uniform assembly.
Resistance elements may be enclosed in expanded metal or wire mesh enclosures.
All buses and wiring inside and between enclosures and from the excitation
transformer shall be furnished and installed. All outgoing wiring shall be
terminated on terminal blocks located in only one enclosure of the excitation
system. The generator field leads and the AC bus or cables from the excitation
transformer shall enter the excitation equipment enclosures from the bottom.
VV. All finished painted surfaces and metal work shall be protected from damage during
shipment. Major components in the excitation cubicles shall be identified with
painted letters or numbers or suitable labels, corresponding to the identifications
shown on approved shop drawings.
All enclosures and devices shall be completely wired to designated terminal blocks for
connection to external devices. Standard cables and methods of cable terminations
between standard modules within the cubicles shall be used. Wiring shall be formed,
Page 29 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
where not installed in channels or ducts, into compact wire bundles suitably bound
together and properly supported. Wire loops shall be formed, which will provide
rotation around the longitudinal axis of the conductors. Any wiring extending beyond
the equipment cubicles shall be terminated at 600 V terminal blocks, except excitation
system power leads such as generator field leads, etc. All individual conductors,
including spares, of each external cable shall be terminated on adjacent terminal points.
The wire (terminal point) designations used on the Supplier’s wiring diagrams may be
according to the Supplier’s standard practice; however, additional wire and cable
designations for identification of external circuits may be required. Wiring diagrams
shall be prepared such that they reflect the actual equipment arrangement, as seen by
an observer. All wiring of current transformer secondary circuits shall use ring-tongue
type terminations and short-circuiting type terminal blocks.
WW. Metal-enclosed bus or cables in trays shall be furnished for the connections from
the excitation cubicles to the field bushing assembly terminals at the generator air
housing, including all bus supports, hangers, barriers, equipment flanges, and
connectors.
XX. The bus conductors or cables shall be made of insulated copper having a total
capacity adequate to carry the maximum continuous excitation current without
exceeding the rated temperature of the insulation at the ambient air temperature
of the powerhouse.
YY. The bus or cables voltage rating and insulation level shall be at least as high as that
of the generator field.
Page 30 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
ZZ. The buses or cable connections shall be designed to withstand the maximum forces
produced by currents due to short-circuits in the excitation system.
Tools and equipment required for the installation and maintenance of the turbine, as
listed in Annexure –2B “List of Special Tools and Maintenance Equipment’s”, shall be
furnished. All tools and devices shall be properly stamped for identification and use.
AAA. General
BBB. Excitation Systems: The following tests shall be performed on each excitation
system:
2. Operational checks shall be made of all cooling fans, breakers, and other
devices such as sensors, transducers, alarms, and protective devices.
Page 31 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
3. The main power circuits of the assembled cubicles shall be given a one-minute
dielectric test to ground at an AC rms voltage of 10 times the field voltage
corresponding to the rated generator load.
4. All other electrical parts, such as regulators, rheostats, and similar devices, shall
be tested individually in accordance with applicable ANSI/IEC or IEEE Standards,
except that where the parts are in quantity production and routine tests are
made, and such routine tests are in accordance with the ANSI or IEEE
Standards, individual tests of such parts shall not be required; however, in
either event, certified test data covering each parts shall be submitted.
CCC. Rectifier: The following tests shall be performed on one completely assembled
rectifier:
1. Tests to demonstrate that, with one thyristor fuse removed, the temperature
rise of the component parts will not exceed that which would be suitable for
continuous operation of the elements of the rectifier at maximum rated
output.
2. Tests to demonstrate that the thyristors and thyristor fuses, with one thyristor
fuse removed, can withstand without injury an output current corresponding to
the field current at excitation ceiling voltage for duration of one minute.
4. Tests to demonstrate the capability of the exciter to reach the positive and
negative ceiling voltages corresponding to the specified excitation system
voltage response ratio.
Page 32 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
The Supplier shall furnish in his Bid a list of recommended additional spare parts,
including prices, and shall indicate the time required for delivery of each item to the
Site, after receipt of purchase order from the Purchaser.
Annexure-2B
The Supplier shall supply as a minimum the following spare parts for the excitation
system
equipment:
a) Rectifier
Twelve (12) sets of power fuses for one bridge and lamps;
Page 33 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
b) Voltage regulator
c) Auxiliary relaying
d) Field breaker
Six (6) sets of main and arcing contacts, stationary and moving;
Page 34 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
e) Field flashing
f) Excitation transformer
All spare parts shall be electrically and mechanically identical to the corresponding
parts in the equipment, shall be adjusted and calibrated where necessary and
shall be suitably packed and clearly marked ready for long-term storage indoors. A
list of all spare parts with their specifications shall be provided.
Page 35 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
1.0 General
1.1 Manufacturer -
Place of -
1.2
manufacture
System -
2
Requirement
Regulation 1 No-Independ
1 No-Independ
panel- Control double chanel
double chanel
panel ( eacha with
( eacha with
AVR+FCR),AQR
AVR+FCR),AQR
2.1 and AFR, V/F
and AFR, V/F
Limiter,OEL,UEL
Limiter,OEL,UEL;
; Residual
Residual voltage
voltage flashing
flashing and PSS
and PSS
Ventilation fans
( two No ), Field
( two No ), Field
Bus
Bus
Page 37 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
Applicable - IEC/IEEE
2.5 IEC/IEEE
standards
Thickness of Mm
enclosure
2.6 2
frame , roof
and rear panel.
Mounting plate Mm
2.7 4
thickness
Thickness of Mm
2.8 2
doors
Power cable
exit from the
2.9 Bottom
cubicle
top/bottom
Control cable
exit from the
2.10 Bottom
cubicle
top/bottom
2.11 2
Material and Mm
thickness of
Page 38 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
gland plate
Following
3 accessories to
be provided
7 Main data
7.1 Data of
Page 39 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
excitation
system at
rated
generator
output, rated
generator
terminal
voltage and
rated power
factor (hot
rotor winding)
Field V 251
362
voltage
Field A 2229
2102
current
Field current at A
7.2 129
no load
Field Voltage V
7.3 1089
at no load
8 Ceiling voltage
in per units of
Page 40 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
rated field
voltage
Field current at
8.1 rated ceiling A 6306
voltage
Excitation
8.2 system voltage 1/s <0.1 <0.1
response ratio
Maximum time
period for
operation at s 10
8.3
ceiling voltage
10
without
damage
Page 41 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
Data of
excitation
system at
continuous
overload
generator
9 output, 110%
generator
terminal
voltage and
rated power
factor (hot
rotor winding)
Field V
398.2
voltage
Field A
2312.2
current
Maximum
continuous
output
10
capability of
excitation
system
Page 42 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
Maximum A
field 6306
current
Maximum V
field 1086
voltage
Maximum
duration of s
over 10
excitation
period
Range of %
automatic
10.1 10-110
voltage level
setting
Range for
manual control %
10.2 of excitation, 20-130
normal
operation
10.3 20-130
Range for
manual control %
Page 43 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
of excitation,
test purposes
Voltage
11 Regulating
System
Voltage -
11.1 regulator,
make
Voltage - 1 No-Independ
1 No-Independ
regulator, type double chanel
double chanel
( eacha with
( eacha with
AVR+FCR),AQR
AVR+FCR),AQR
11.2 and AFR, V/F
and AFR, V/F
Limiter,OEL,UEL
Limiter,OEL,UEL;
; Residual
Residual voltage
voltage flashing
flashing and PSS
and PSS
EXCITER
13 THYRISTOR
CONVERTOR
Page 44 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
Rated DC A 2229
13.3 2102
output current
Maximum A -
13.4 continuous DC 2312
output rating
Short time s 10
13.5 rating in Amps 10
(specify time)
Page 45 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
No. of 3
13.10 3
converters
Rating of each A
13.11 converter 2000
bridge
Rated Hz 50
13.15 50
frequency
Page 46 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
Rated PIV of V 1
13.17 1
Thyristor
Rated current A -
13.18 2000
of thyristor
Maximum A -
current rating Forced Cooling
of thyristor
element
cooling
method
Total no. of
13.20 Thyristors 3
Cubucle
No. of bridges
13.21 1
per cubicle
No. of No
thyristors per
13.22 6
converter
bridge
13.23 ℃ 55
Thyristor
Page 47 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
junction
temperature at
rated current
Thyristor fuse -
RSM2000A/
13.4 rating: type &
2000V
make
Maximum % <5%*
ripple content
13.25 <5%
at rated
current
AC / DC bus Copper
13.27 Copper
bar material
Whether Yes
13.28 Yes
insulated
Location in Yes
13.29 Yes
cubicles
Electrical fan
13.30
motor ratings
Page 48 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
Rated kW _____________
13.30. power
3.9
2 consumptio
n
Field circuit
14
breaker
Rated kA
maximum
14.4 75
breaking
current
Page 49 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
Field discharge
resistor rating (
14.9 Kw, amps, 6MJ
ohms to be
specified )
14.9.1 Rating Kw NA
14.9.2 Amps A NA
AC - field
15 flashing
equipment
Duration of S 10
15.1 10
flashing
Power rating of
15.2 field flashing kVA 3
transformer
Rated voltages
15.3
of transformer
Page 50 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
Primary V
15.4 400
side
Secondary V
15.5 20
side
DC - field
16 flashing
equipment
Power
requirements, Kw
16.1 if such 10
equipment is
provided
Page 51 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
1 Introduction
Rufiji Hydroelectric project is a Surface Power Station comprising of nine generating units
of 235 MW capacities each. The station will generate power at 15.75 kV and it will be
stepped up to 420 kV through single phase generator transformers located in transformer
cavern. The single phase transformer 420/√3/16.0 kV shall be connected to generator
through Generator Circuit Breaker and Isolated phase bus duct. The terminals of HV side
of transformer shall be connected to 420 kV Short Transmission line.
2 Purpose
3 General Information
Page 52 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
The Static Excitation Transformers shall comply with the latest edition of the following
standards and other relevant standards.
S. No. Description Reference
1 Acoustic Pressure Level DIN 45635
2 Design and Construction IEC60076-1,
IEC60076- 11, IEC60071,
IEC61378, EN50178,
IEC61800, IEC60146,
Page 53 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
DIN 61378-1
5 Equipment Description
5.1 Scope
The scope of work shall be a comprehensive functional system covering all supply and
services including the following:
1. *Nine (27) Nos. – 15.75/0.690 kV, three phase 1250VA, 1Ph cast resin dry type Static
Excitation Transformer Transformer (SET) complete with necessary accessories such as
bushings, off-circuit tap changer, CT’s, instrumentation, fittings etc. or
2. *Nine (9) No. – 15.75/0.69 kV, three phase 4000 kVA, cast resin dry type Static Excitation
Transformer (SET) complete with necessary accessories such as bushings, off-circuit tap
changer, CT’s, instrumentation, fittings etc.
The basic technical Particulars of the Static Excitation Transformers are as follows:
I. SET*
Type - Indoor, dry type cast resin
Page 54 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
5.3.2 Core
The core shall be constructed from high grade, non-aging, low loss, high permeability, cold
rolled grain oriented silicon steel laminations.
Page 55 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
5.3.3 Windings
The high and low voltage windings of the transformer shall be of electrolytic grade copper,
free from scales and burns. All windings of the transformer shall be fully insulated for the
rated voltage. The winding insulation shall be class F & temperature rise shall be limited to
class F.
5.3.7 Fittings
The following fittings shall be provided with the dry type transformers:
a. Inspection covers.
b. Off circuit links on HV side.
Page 56 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
6.1 Layout
1 <100.0m
Excitation Transformer
6.2 Cabling
The HV side of Excitation Transformer shall be connected to Isolated bus duct and LV
side shall be connected to Static Excitation System through suitable size Cu cables.
Page 57 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
6.5 Earthing
At least two (2) nos. bolted type ground pads complete with suitable tapped holes, bolts
and washers shall be provided in the transformers to connect the riser from the main
earth grid.
7 Painting procedure
Paint shade shall be RAL 7035 and painting procedure shall be as per manufacturer
standard.
Tests and inspection shall be as per IEC 60076-2 Standard for Excitation Transformer.
9 Mandatory spares
The following spares shall be supplied with each type of Auxiliary Transformer:
Page 58 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
11 Exclusions
12 Conclusion
Aforementioned points are the broad features of Excitation Transformers indicated for
Technical specification. The design requirements in general, shall be as per the technical
specifications of contract.
Data Sheet
Page 59 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
Selection
*Rating MVA 1250 KVA in
Calculation
case of 1ph
2 1250 KVA 1 Ph Required
and 4000 KVA
in case of 3 ph
Place of --------------
3 China
manufacture
Applicable IEC-60076
4 IEC60076
Standard
5 Yes
All the
equipment’s Yes
including
bought out
Page 60 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
items are
designed to
withstand for
Seismic forces
specified in the
specification
(Yes/No)
*Transformer
continuous kVA 1250 KVA for 1
1250KVA for 1
6 three-phase ph and 4000
Ph
power rating on KVA for 3 ph
any tapping
Design Ambient ℃ 40
7 40
Temperature
9 Rated frequency Hz 50 50
Number of 3
11 3
Phases
Page 61 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
15 Insulation Class F F
*Transformer
rated voltage at
16
rated frequency
and no-load
High- kV
voltage,
NA
principal
tapping
High-
voltage, kV
NA
extreme
plus tapping
Page 62 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
High-
voltage, kV
extreme NA
minus
tapping
Low voltage kV NA
*Impedance
voltage (75°C) at
18 rated frequency,
on 100 % rated
kVA and:
Principal ≤8
% ≤8 (±10 %
tapping Tolerances as
per IEC
standard )
Extreme ≤8
% ≤8 (±10 %
plus tapping Tolerances as
per IEC
standard )
Extreme ≤8
% ≤8 (±10 %
minus Tolerances as
tapping per IEC
Page 63 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
standard )
Rated short
duration power kVrms 50.0
frequency
19 50
withstand
voltage, 1 min.
HV side
voltage HV side
Rated short
duration power kVrms 3.0
frequency
21 3.0
withstand
voltage, 1 min.
LV side
Maximum pC <10
22 Partial <10
Discharge
Page 64 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
capacity @125%
of voltage
Conductor Copper
27 Copper
Materials
HV conductor mm2
28 Cross section ?
area
LV conductor mm2 To be
area
Page 65 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
Details of
34
enclosure
34.1 IP class 23 23
Temperature Digital
Digital
Indicator Temperature
Temperature
Scanner with
34.3 Scanner with
PT-100 as
PT-100 as
sensing
sensing element
element
*Transformer
no-load losses
(three-phase) at kW Approx. 8.26
35 rated voltage, Approx. 8.26
principal
tapping and
rated frequency
36 Approx. 43.0
*Transformer
total losses
(75°C three-
phase) at kW Approx. 43.0
nominal load,
rated voltage,
rated frequency
Page 66 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
and principal
tapping
*Efficiency at % ≥98.8
100% rated
37 ≥98.8
load, 75℃ and
0.85 pf
Transformer
temperature
rises after
continuous
operation with
rated kVA,
under rated
38
conditions and
on tapping
giving highest
losses from
ambient
temperature
( 40-50 ℃)
Page 67 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
Temperature
39 Type of Cooling AN or AF AN or AF
Installation m <100.0
40 <100.0
Height (EL)
41 Climatic Class C2 C2
Environmental E2
42 E2
Class
Fire Behavior F1
43 F1
Class
Page 68 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
Acoustic dB ≤60
46 ≤60
pressure level
52 Minimum 225/225
mm 225/225
Page 69 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02
Static Digital Excitation System /SECTION 7
External air
clearance as per
IEC code –Ph-
Ph/Ph-E
Page 70 of 23
Particular Technical Specification
RUFIJI HYDROPOWER PROJECT-E&M PACKAGE For Major Equipment / Part02