100% found this document useful (1 vote)
84 views

S DDR

The document lists 48 digital input signals that are monitored by a disturbance fault recorder at the Biyagama Grid Substation STATCOM control building. The signals include protections operated, controller operations, transformer alarms and trips, and spare signals. They are divided into three categories: 27.7kV STATCOM bay signals, 27.7/0.4kV auxiliary transformer bay signals, and common alarm signals. The digital inputs will be connected via armored, flexible 1.5mm2 cables according to drawing B6-T297-304.

Uploaded by

Edciel Ebuen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
84 views

S DDR

The document lists 48 digital input signals that are monitored by a disturbance fault recorder at the Biyagama Grid Substation STATCOM control building. The signals include protections operated, controller operations, transformer alarms and trips, and spare signals. They are divided into three categories: 27.7kV STATCOM bay signals, 27.7/0.4kV auxiliary transformer bay signals, and common alarm signals. The digital inputs will be connected via armored, flexible 1.5mm2 cables according to drawing B6-T297-304.

Uploaded by

Edciel Ebuen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

BIYAGAMA GRID SUBSTATION - STATCOM CONTROL BUILDING

[[[
DISTURBANCE FAULT RECORDER - Digital Input List

A. 27.7kV STATCOM BAY


1. Isolator Close _27.7 kV 220 11D -1: 101

2. Pre Charging resistor Isolator Close - 27.7 kV 220 11D -2: 102

3. Lockout Relay Operated _27.7kV 220 11D -3: 103

4. Differential Protection Operated _27.7kV 220 11D -4: 104

5. Definite time over current protection Operated _ 27.7kV 220 11D -5: 105

6. Inverse Time over current protection Operated _ 27.7kV 220 11D -6: 106

7. Phase Balance protection Operated _ 27.7kV 220 11D -7: 107

8. Definite time over current protection Operated _ STATCOM 220 11D -8: 108

9. Inverse Time current protection Operated _ STATCOM 220 11D -9: 109

10. Thermal overload protection Operated 220 11D -10: 110

11. Zero sequence over voltage protection Operated 220 11D -11: 111

12. Protection panel DC MCB trip 220 11D -12: 112

13. Protection panel Relay Fail 220 11D -13: 113

14. STATCOM controller (A) Run 220 11D -14: 114

15. STATCOM controller (A) Stop 220 11D -15: 115

16. Trip operated by STATCOM Controller (A) 220 11D -16: 116

17. STATCOM controller (A) Block 220 12D -1: 101

18. STATCOM controller (B) Run 220 12D -2: 102

19. STATCOM controller (B) Stop 220 12D -3: 103

20. Trip operated by STATCOM Controller (B) 220 12D -4: 104

21. STATCOM controller (B) Block 220 12D -5: 105

22. SPARE 220 12D -6: 106

23. SPARE 220 12D -7: 107

24. SPARE 220 12D -8: 108

Physical Digital Input Signals List BIYAGAMA GRID SUBSTATION


BEN 6000 Disturbance Fault Recorder STATCOM CONTROL BUILDING

2
B6-T297-002D R0
4
BIYAGAMA GRID SUBSTATION - STATCOM CONTROL BUILDING
DISTURBANCE FAULT RECORDER - Digital Input List

B. 27.7/0.400kV AUXILIARY TRANSFORMER BAY

25. Circuit Breaker Trip_27.7kV 220 13D -1: 101

26. Isolator Close_27.7kV 220 13D -2: 102

27. Trip Circuit Supervision 1/2 Operated 220 13D -3: 103

28. Lockout relay Operated 220 13D -4: 104

29. Definite time over current protection Operated 220 13D -5: 105

30. Inverse Time over current protection Operated 220 13D -6: 106

31. zero sequence over voltage protection Operated 220 13D -7: 107

32. Breaker Failure protection Operated 220 13D -8: 108

33. Protection panel DC MCB trip 220 13D -9: 109

34. Protection Panel Relay Fail 220 13D -10: 110

35. Aux. Transformer Mechanical Protection alarm operated 220 13D -11: 111

36. Aux.Transformer Mechanical Protection Trip operated 220 13D -12: 112

37. Aux.Transformer Buchholz Relay operated 220 13D -13: 113

38. SPARE 220 13D -14: 114

39. SPARE 220 13D -15: 115

40. SPARE 220 13D -16: 116

Physical Digital Input Signals List BIYAGAMA GRID SUBSTATION


BEN 6000 Disturbance Fault Recorder STATCOM CONTROL BUILDING

3
B6-T297-002D R0
4
BIYAGAMA GRID SUBSTATION - STATCOM CONTROL BUILDING
DISTURBANCE FAULT RECORDER - Digital Input List

C. COMMON ALARM

41. DC Earth Fault 220 12D -16: 116

42. SPARE 220 12D -9: 109

43. SPARE 220 12D -10: 110

44. SPARE 220 12D -11: 111

45. SPARE 220 12D -12: 112

46. SPARE 220 12D -13: 113

47. SPARE 220 12D -14: 114

48. SPARE 220 12D -15: 115

Vide refer DWG, B6-T297-304

that require monitoring [armoured, Flexible,1.5mm2]

Physical Digital Input Signals List BIYAGAMA GRID SUBSTATION


BEN 6000 Disturbance Fault Recorder STATCOM CONTROL BUILDING

4
B6-T297-002D R0