Mcquay MDB
Mcquay MDB
REGISTERED
ISO 9002
MMC 075 - 150 D/DR
Contents
Note : Installation and maintenance are to be performed only by qualified personnel who are
familiar with local codes and regulations, and experienced with this type of equipment.
Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Warning : Moving machinery and electrical power hazard. May cause severe personal
injury or death. Disconnect and lock off power before servicing equipment.
"McQuay" is a registered trademark of McQuay International. All rights reserved throughout the world.
"Bulletin illustrations cover the general appearance of McQuay International products at the time of publication
and we reserve the right to make changes in design and construction at any time without notice."
1
Nomenclature System
M 4 DB 150 D R 2
Refrigerant Circuitry
e.g. 2 : 2 circuit
Omitted if single circuit
Model Type
R : heatpump
Omitted if Cooling
Series
D : D series
Capacity
e.g. 150 : 150,000 Btu/h
Model Name
DB : Ducted Static Blower
MC : Modular Condenser
Brand
M : McQuay
Features
Easy Maintenance
The simple design concept has provided the ease of maintenance and servicing. Access to the internal part
of the unit can be from the service panel or other side of the unit by loosening a few screws.
Only for model MDB075/100 D/DR with additional service panel from bottom
2
Air Discharge Orintation
MDB075-150 D/DR models come with standard horizontal air discharge. MDB200-500 D/DR models come
with standard vertical air discharge and they are convertible to horizontal air discharge. For outdoor unit,
M/M4MC75-150 D/DR models come with standard vertical air discharge.
Versatility
Multiple rooms can be cooled together at the same time by using just one unit of fan coil unit.
3
General Specifications
Unit Structure
The casing is constructed with electro-galvanised (EG) mild steel sheet which provide a rigid cabinet. The
thickness of the indoor casing is ranging from 1.0mm to 3.2mm whereas the outdoor casing thickness is
ranging from 1.0mm to 2.3mm. The finishing of the casing is a long-lasting epoxy polyester powder coating.
The indoor panel is using PE insulation with 10mm thickness. All outdoor units are classified under the IP55
Standard.
Coil
Each coil consists of staggered rows of 3/8” OD seamless copper tubes, mechanically expanded into die-
formed corrugated aluminum fins. All coils are using aluminum fin except heatpump models which are using
hydrophilic blue fin to have better deicing during defrost cycle.
Compressor
All outdoor units are using high efficiency, refrigerant-cooled, Copeland Scroll compressor. Compressor has
the internal overload protection and supplied with crank case heater to prevent liquid migration, which can
damage compressor scroll, during off-cycle and eases start-up.
Safety Controls
Outdoor units are equipped with auto reset high pressure and low pressure cut-out and discharge thermostat
to protect against compressor damage due to high head pressure and system leakage respectively. Phase
protector is used to detect for any wrong phase and phase loss during installation and operation.
4
Specifications
Cooling only 50Hz (R22)
INDOOR UNIT MDB075D MDB100D MDB125D MDB150D1
MODEL
OUTDOOR UNIT MMC075D MMC100D MMC125D MMC150D
TOTAL COOLING OUTDOOR Btu/h 75,000 100,000 125,000 150,000
35 °CDB kcal/h 18,900 25,200 31,500 37,800
CAPACITY
W 21,975 29,300 36,625 43,950
NOMINAL TOTAL POWER W 8,170 10,598 12,543 15,963
NOMINAL TOTAL CURRENT A 16.0 18.7 23.4 29.0
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 507 (19.96) 710 (27.95)
DIMENSION WIDTH (W) mm (in) 1507 (59.33) 1917 (75.47) 1794 (70.62) 2073 (81.61)
DEPTH (D) mm (in) 859 (33.81) 964 (37.95)
3
VOLUME M 1.112 1.395 1.875 2.192
NET WEIGHT kg (lb) 95 (209) 120 (264) 155 (341) 175 (385)
NOISE LEVEL dBA 64 64 77 79
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-0
FACE AREA m2 (ft2) 0.53 (5.73) 0.72 (7.75) 0.89 (9.66) 1.06 (11.50)
FACE VELOCITY m/min (FPM) 119.48 (392) 117.95 (387) 118.26 (388) 119.17 (391)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / DIRECT CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 2 1
INDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 1.2 1.2
RATED INPUT POWER W 550 923
MOTOR OUTPUT W 350 560
MOTOR POLES 10 12
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 380-415 / 3 / 50
RATED RUNNING CURRENT A 13.6 16.9 17.9 23.5
RATED INPUT POWER W 6810 9040 10200 13300
MAXIMUM STARTING CURRENT A 95.0 125.0 110.0 198.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 8940 11250
PROTECTION DEVICE CONTROL MODULE & AUTO
OVERLOAD PROTECTION AND AUTO RESET HIGH/LOW PRESSURE SWITCH
RESET H/L PRESS. SW
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE AUTO-TRANSFORMER
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
5
Cooling only 50Hz (R22)
INDOOR UNIT MDB150D2 MDB200D2 MDB250D2
MODEL
OUTDOOR UNIT MMC075D x2 MMC100D x2 MMC125D x2
TOTAL OUTDOOR Btu/h 150,000 200,000 250,000
COOLING 35 °CDB kcal/h 37,800 50,400 63,000
CAPACITY W 43,950 58,600 73,250
NOMINAL TOTAL POWER W 16,460 21,980 26,546
NOMINAL TOTAL CURRENT A 32.9 42.2 48.0
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 710 (27.95) 881 (34.68) 983 (38.70)
DIMENSION WIDTH (W) mm (in) 2073 (81.61) 1324 (52.12) 1486 (58.50)
DEPTH (D) mm (in) 964 (37.95) 1209 (47.59) 1298 (51.10)
VOLUME M3 2.192 2.056 2.675
NET WEIGHT kg (lb) 175 (385) 248 (546) 321 (707)
NOISE LEVEL dBA 78.6 85 87
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-50-0
FACE AREA m2 (ft2) 1.06 (11.50) 1.43 (15.41) 1.77 (19.12)
FACE VELOCITY m/min (FPM) 119.17 (391) 118.56 (389) 119.48 (392)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 1
INDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 1.2 1.2
RATED INPUT POWER W 550 923
MOTOR OUTPUT W 350 560
MOTOR POLES 10 10
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 380-415 / 3 / 50
RATED RUNNING CURRENT A 13.6 16.9 17.9
RATED INPUT POWER W 6810 9040 10200
MAXIMUM STARTING CURRENT A 95.0 125.0 110.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 8940
OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE AUTO-TRANSFORMER
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
6
Cooling only 50Hz (R22)
INDOOR UNIT MDB300D2 MDB400D4 MDB500D4
MODEL
OUTDOOR UNIT MMC150D x2 MMC100D x4 MMC125D x4
TOTAL OUTDOOR Btu/h 300,000 400,000 500,000
COOLING 35 °CDB kcal/h 75,600 100,800 126,000
CAPACITY W 87,900 117,200 146,500
NOMINAL TOTAL POWER W 33,446 44,260 55,592
NOMINAL TOTAL CURRENT A 62.1 86.6 100.7
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 983 (38.70) 1176 (46.29) 1176 (46.29)
DIMENSION WIDTH (W) mm (in) 1486 (58.50) 1722 (67.79) 1722 (67.79)
DEPTH (D) mm (in) 1501 (59.09) 1691 (66.57) 2047 (80.59)
VOLUME 3
M 3.047 4.552 5.427
NET WEIGHT kg (lb) 394 (868) 470 (1036) 567 (1250)
NOISE LEVEL dBA 89 90 96
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-50-0 100-75-50-25-0
FACE AREA m2 (ft2) 2.12 (22.90) 2.89 (31.11) 3.61 (38.88)
FACE VELOCITY m/min (FPM) 119.78 (393) 117.34 (385)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 1
INDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 914.40 (36) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 1.2 1.2 1.2
RATED INPUT POWER W 923 500 923
MOTOR OUTPUT W 560 350 560
MOTOR POLES 10 10 10
AIR FLOW L/s (CFM) 4720 (10000) 3304 (7000) 4720 (10000)
.
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 380-415 / 3 / 50
RATED RUNNING CURRENT A 23.5 16.9 17.9
RATED INPUT POWER W 13300 9040 10200
MAXIMUM STARTING CURRENT A 198.0 125.0 110.0
COMPRESSOR MOTOR OUTPUT W 11250 7500 8940
CONTROL MODULE AND OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET H/L PRESS. SW. AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE AUTO-TRANSFORMER
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
7
Heatpump 50Hz (R22)
INDOOR UNIT MDB075DR MDB100DR MDB125DR MDB150DR1
MODEL
OUTDOOR UNIT MMC075DR MMC100DR MMC125DR MMC150DR
TOTAL OUTDOOR Btu/h 77,000 96,000 116,000 150,000
COOLING 35 °CDB kcal/h 19,404 24,192 29,232 37,800
CAPACITY W 22,567 28,140 34,000 43,960
TOTAL OUTDOOR Btu/h 85,000 106,000 130,000 160,000
HEATING 8.3°CDB / 6.1°CWB kcal/h 21,420 26,712 32,760 40,320
CAPACITY W 24,912 31,070 38,100 46,890
NOMINAL TOTAL POWER (COOLING) W 7,765 9,580 11,413 15,244
NOMINAL TOTAL POWER (HEATING) W 8,184 10,390 10,674 13,470
NOMINAL TOTAL CURRENT (COOLING) A 14.8 17.9 20.5 27.5
NOMINAL TOTAL CURRENT (HEATING) A 15.3 18.6 19.5 25.6
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 507 (19.96) 710 (27.95)
DIMENSION WIDTH (W) mm (in) 1507 (59.33) 1917 (75.47) 1794 (70.62) 2073 (81.61)
DEPTH (D) mm (in) 859 (33.81) 964 (37.95)
VOLUME M3 1.112 1.395 1.875 2.192
NET WEIGHT kg (lb) 95 (209) 120 (264) 155 (341) 175 (385)
NOISE LEVEL dBA 64 64 77 79
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-0
FACE AREA m2 (ft2) 0.53 (5.73) 0.72 (7.75) 0.89 (9.66) 1.06 (11.50)
FACE VELOCITY m/min (FPM) 119.48 (392) 117.95 (387) 118.26 (388) 119.17 (391)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / DIRECT CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 2 1
INDOOR UNIT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO 26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO 26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB OUTDOOR
8
Heatpump 50Hz (R22)
MODEL INDOOR UNIT MDB150DR2 MDB200DR2 MDB250DR2
OUTDOOR UNIT MMC075DR x2 MMC100DR x2 MMC125DR x2
TOTAL OUTDOOR Btu/h 154,000 192,000 232,000
COOLING 35 °CDB kcal/h 38,808 48,384 58,464
CAPACITY W 45,135 56,272 67,995
TOTAL OUTDOOR Btu/h 170,000 212,000 260,000
HEATING 8.3°CDB / 6.1°CWB kcal/h 42,840 53,424 65,520
CAPACITY W 49,824 62,134 76,200
NOMINAL TOTAL POWER (COOLING) W 15,794 19,940 24,286
NOMINAL TOTAL POWER (HEATING) W 16,632 21,560 22,808
NOMINAL TOTAL CURRENT (COOLING) A 30.5 37.8 43.0
NOMINAL TOTAL CURRENT (HEATING) A 31.5 39.2 41.0
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 710 (27.95) 881 (34.68) 983 (38.70)
DIMENSION WIDTH (W) mm (in) 2073 (81.61) 1324 (52.12) 1486 (58.50)
DEPTH (D) mm (in) 964 (37.95) 1209 (47.59) 1298 (51.10)
VOLUME M3 2.192 2.056 2.675
NET WEIGHT kg (lb) 175 (385) 248 (546) 321 (707)
NOISE LEVEL dBA 79 85 87
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-50-0 100-50-0
FACE AREA m2 (ft2) 1.06 (11.50) 1.43 (15.41) 1.77 (19.12)
FACE VELOCITY m/min (FPM) 119.17 (391) 118.56 (389) 119.48 (392)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 1
INDOOR UNIT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO 26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO 26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB OUTDOOR
9
Heatpump 50Hz (R22)
MODEL INDOOR UNIT MDB300DR2 MDB400DR4 MDB500DR4
OUTDOOR UNIT MMC150DR x2 MMC100DR x4 MMC125DR x4
TOTAL OUTDOOR Btu/h 300,000 384,000 464,000
COOLING 35 °CDB kcal/h 75,600 96,768 116,928
CAPACITY W 87,920 112,540 135,990
TOTAL OUTDOOR Btu/h 320,000 424,000 520,000
HEATING 8.3°CDB / 6.1°CWB kcal/h 80,640 106,848 131,040
CAPACITY W 83,780 124,267 152,400
NOMINAL TOTAL POWER (COOLING) W 32,008 40,180 51,072
NOMINAL TOTAL POWER (HEATING) W 28,320 43,420 48,116
NOMINAL TOTAL CURRENT (COOLING) A 56.6 75.8 88.7
NOMINAL TOTAL CURRENT (HEATING) A 51.7 78.6 84.7
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 983 (38.70) 1176 (46.29) 1176 (46.29)
DIMENSION WIDTH (W) mm (in) 1486 (58.50) 1722 (67.79) 1722 (67.79)
DEPTH (D) mm (in) 1501 (59.09) 1691 (66.57) 2047 (80.59)
VOLUME M3 3.047 4.552 5.427
NET WEIGHT kg (lb) 394 (868) 470 (1036) 567 (1250)
NOISE LEVEL dBA 89 90 96
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-50-0 100-75-50-25-0
FACE AREA m2 (ft2) 2.12 (22.90) 2.89 (31.11) 3.61 (38.88)
FACE VELOCITY m/min (FPM) 119.78 (393) 117.34 (385)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 1
INDOOR UNIT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO 26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO 26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB OUTDOOR
10
Cooling only 50Hz (R407C)
INDOOR UNIT MDB075D MDB100D MDB125D MDB150D1
MODEL
OUTDOOR UNIT M4MC075D M4MC100D M4MC125D M4MC150D
TOTAL COOLING OUTDOOR Btu/h 73,000 91,000 10,800 145,000
35 °CDB kcal/h 18,396 22,932 27,216 36,540
CAPACITY
W 21,395 26,670 31,653 42,497
NOMINAL TOTAL POWER W 8,080 9,150 12,100 16,239
NOMINAL TOTAL CURRENT A 15.1 18.3 21.6 28.4
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 507 (19.96) 710 (27.95)
DIMENSION WIDTH (W) mm (in) 1507 (59.33) 1917 (75.47) 1794 (70.62) 2073 (81.61)
DEPTH (D) mm (in) 859 (33.81) 964 (37.95)
3
VOLUME M 1.112 1.395 1.875 2.192
NET WEIGHT kg (lb) 95 (209) 120 (264) 155 (341) 175 (385)
NOISE LEVEL dBA 64 64 77 79
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-0
FACE AREA m2 (ft2) 0.53 (5.73) 0.72 (7.75) 0.89 (9.66) 1.06 (11.50)
FACE VELOCITY m/min (FPM) 119.48 (392) 117.95 (387) 118.26 (388) 119.17 (391)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / DIRECT CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 2 1
INDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 1.2 1.2
RATED INPUT POWER W 570 600 820
MOTOR OUTPUT W 350 560
MOTOR POLES 10 10
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 380-415 / 3 / 50
RATED RUNNING CURRENT A 12.7 15.9 17.5 23.9
RATED INPUT POWER W 6772 8550 9860 13679
MAXIMUM STARTING CURRENT A 95.0 125.0 110.0 198.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 8940 11250
CONTROL MODULE & AUTO
PROTECTION DEVICE OVERLOAD PROTECTION AND AUTO RESET HIGH/LOW PRESSURE SWITCH
RESET H/L PRESS. SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE AUTO-TRANSFORMER
REFRIGERANT
TYPE R407C
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
11
Cooling only 50Hz (R407C)
INDOOR UNIT MDB150D2 MDB200D2 MDB250D2
MODEL
OUTDOOR UNIT M4MC075D x2 M4MC100D x2 M4MC125D x2
TOTAL OUTDOOR Btu/h 146,000 182,000 216,000
COOLING 35 °CDB kcal/h 36,792 45,864 54,432
CAPACITY W 42,790 53,500 63,306
NOMINAL TOTAL POWER W 15,854 11,950 24,840
NOMINAL TOTAL CURRENT A 17.2 38.4 45.2
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 710 (27.95) 881 (34.68) 983 (38.70)
DIMENSION WIDTH (W) mm (in) 2073 (81.61) 1324 (52.12) 1486 (58.50)
DEPTH (D) mm (in) 964 (37.95) 1209 (47.59) 1298 (51.10)
3
VOLUME M 2.192 2.056 2.675
NET WEIGHT kg (lb) 175 (385) 248 (546) 321 (707)
NOISE LEVEL dBA 79 85 87
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-50-0
FACE AREA m2 (ft2) 1.06 (11.50) 1.43 (15.41) 1.77 (19.12)
FACE VELOCITY m/min (FPM) 119.17 (391) 118.56 (389) 119.48 (392)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 1
INDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 1.2 1.2
RATED INPUT POWER W 600 820
MOTOR OUTPUT W 350 560
MOTOR POLES 10 10
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 380-415 / 3 / 50
RATED RUNNING CURRENT A 12.7 15.9 17.5
RATED INPUT POWER W 6772 8550 9860
MAXIMUM STARTING CURRENT A 95.0 125.0 110.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 8940
OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE AUTO-TRANSFORMER
REFRIGERANT
TYPE R407C
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
12
Cooling only 50Hz (R407C)
INDOOR UNIT MDB300D2 MDB400D4 MDB500D4
MODEL
OUTDOOR UNIT M4MC150D x2 M4MC100D x4 M4MC125D x4
TOTAL OUTDOOR Btu/h 290,000 364,000 432,000
COOLING 35 °CDB kcal/h 73,080 91,728 108,864
CAPACITY W 84,990 105,510 126,612
NOMINAL TOTAL POWER W 33,178 42,500 53,820
NOMINAL TOTAL CURRENT A 59.2 79.4 93.1
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 983 (38.70) 1176 (46.29) 1176 (46.29)
DIMENSION WIDTH (W) mm (in) 1486 (58.50) 1722 (67.79) 1722 (67.79)
DEPTH (D) mm (in) 1501 (59.09) 1691 (66.57) 2047 (80.59)
3
VOLUME M 3.047 4.552 5.427
NET WEIGHT kg (lb) 394 (868) 470 (1036) 567 (1250)
NOISE LEVEL dBA 89 90 96
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-50-0 100-75-50-25-0
FACE AREA m2 (ft2) 2.12 (22.90) 2.89 (31.11) 3.61 (38.88)
FACE VELOCITY m/min (FPM) 119.78 (393) 117.34 (385)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 1
INDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 914.40 (36) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 1.2 1.2 1.2
RATED INPUT POWER W 820 600 820
MOTOR OUTPUT W 560 350 560
MOTOR POLES 10 10 10
AIR FLOW L/s (CFM) 4720 (10000) 3304 (7000) 4720 (10000)
.
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 380-415 / 3 / 50
RATED RUNNING CURRENT A 23.9 15.9 17.5
RATED INPUT POWER W 13679 8550 9860
MAXIMUM STARTING CURRENT A 198.0 125.0 110.0
COMPRESSOR MOTOR OUTPUT W 11250 7500 8940
CONTROL MODULE AND OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET H/L PRESS. SW. AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE AUTO-TRANSFORMER
REFRIGERANT
TYPE R407C
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
13
Heatpump 50Hz (R407C)
INDOOR UNIT MDB075DR MDB100DR MDB125DR MDB150DR1
MODEL
OUTDOOR UNIT M4MC075DR M4MC100DR M4MC125DR M4MC150DR
TOTAL OUTDOOR Btu/h 73,000 91,000 108,000 145,000
COOLING 35 °CDB kcal/h 18,396 22,932 27,216 36,540
CAPACITY W 21,395 26,670 31,653 42,497
TOTAL OUTDOOR Btu/h 81,000 109,000 124,000 150,000
HEATING 8.3°CDB / 6.1°CWB kcal/h 20,412 27,468 31,248 37,800
CAPACITY W 23,740 31,946 36,342 43,962
NOMINAL TOTAL POWER (COOLING) W 8,080 10,160 12,100 16,239
NOMINAL TOTAL POWER (HEATING) W 8,305 10,670 11,100 14,110
NOMINAL TOTAL CURRENT (COOLING) A 15.1 18.8 21.6 28.4
NOMINAL TOTAL CURRENT (HEATING) A 15.1 19.3 20.3 25.8
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 507 (19.96) 710 (27.95)
DIMENSION WIDTH (W) mm (in) 1507 (59.33) 1917 (75.47) 1794 (70.62) 2073 (81.61)
DEPTH (D) mm (in) 859 (33.81) 964 (37.95)
VOLUME M3 1.112 1.395 1.875 2.192
NET WEIGHT kg (lb) 95 (209) 120 (264) 155 (341) 175 (385)
NOISE LEVEL dBA 64 64 77 79
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-0
FACE AREA m2 (ft2) 0.53 (5.73) 0.72 (7.75) 0.89 (9.66) 1.06 (11.50)
FACE VELOCITY m/min (FPM) 119.48 (392) 117.95 (387) 118.26 (388) 119.17 (391)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / DIRECT CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 2 1
INDOOR UNIT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO 26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO 26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB OUTDOOR
14
Heatpump 50Hz (R407C)
MODEL INDOOR UNIT MDB150DR2 MDB200DR2 MDB250DR2
OUTDOOR UNIT M4MC075DR x2 M4MC100DR x2 M4MC125DR x2
TOTAL OUTDOOR Btu/h 146,000 182,000 216,000
COOLING 35 °CDB kcal/h 36,792 45,864 54,432
CAPACITY W 42,790 53,500 63,306
TOTAL OUTDOOR Btu/h 162,000 218,000 248,000
HEATING 8.3°CDB / 6.1°CWB kcal/h 40,824 54,936 62,496
CAPACITY W 47,479 63,892 72,685
NOMINAL TOTAL POWER (COOLING) W 16,424 21,100 25,660
NOMINAL TOTAL POWER (HEATING) W 16,874 22,120 23,660
NOMINAL TOTAL CURRENT (COOLING) A 31.1 39.6 45.2
NOMINAL TOTAL CURRENT (HEATING) A 31.1 40.6 42.6
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 710 (27.95) 881 (34.68) 983 (38.70)
DIMENSION WIDTH (W) mm (in) 2073 (81.61) 1324 (52.12) 1486 (58.50)
DEPTH (D) mm (in) 964 (37.95) 1209 (47.59) 1298 (51.10)
VOLUME M3 2.192 2.056 2.675
NET WEIGHT kg (lb) 175 (385) 248 (546) 321 (707)
NOISE LEVEL dBA 79 85 87
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-50-0 100-50-0
FACE AREA m2 (ft2) 1.06 (11.50) 1.43 (15.41) 1.77 (19.12)
FACE VELOCITY m/min (FPM) 119.17 (391) 118.56 (389) 119.48 (392)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 1
INDOOR UNIT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO 26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO 26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB OUTDOOR
15
Heatpump 50Hz (R407C)
MODEL INDOOR UNIT MDB300DR2 MDB400DR4 MDB500DR4
OUTDOOR UNIT M4MC150DR x2 M4MC100DR x4 M4MC125DR x4
TOTAL OUTDOOR Btu/h 290,000 364,000 432,000
COOLING 35 °CDB kcal/h 73,080 91,728 108,864
CAPACITY W 84,990 105,510 126,612
TOTAL OUTDOOR Btu/h 300,000 436,000 496,000
HEATING 8.3°CDB / 6.1°CWB kcal/h 75,600 109,872 124,992
CAPACITY W 87,925 127,784 145,369
NOMINAL TOTAL POWER (COOLING) W 33,998 42,500 53,820
NOMINAL TOTAL POWER (HEATING) W 29,740 44,540 49,820
NOMINAL TOTAL CURRENT (COOLING) A 59.2 79.4 93.1
NOMINAL TOTAL CURRENT (HEATING) A 54.0 81.4 87.9
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 983 (38.70) 1176 (46.29) 1176 (46.29)
DIMENSION WIDTH (W) mm (in) 1486 (58.50) 1722 (67.79) 1722 (67.79)
DEPTH (D) mm (in) 1501 (59.09) 1691 (66.57) 2047 (80.59)
VOLUME M3 3.047 4.552 5.427
NET WEIGHT kg (lb) 394 (868) 470 (1036) 567 (1250)
NOISE LEVEL dBA 89 90 96
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-50-0 100-75-50-25-0
FACE AREA m2 (ft2) 2.12 (22.90) 2.89 (31.11) 3.61 (38.88)
FACE VELOCITY m/min (FPM) 119.78 (393) 117.34 (385)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 1
INDOOR UNIT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO 26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO 26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB OUTDOOR
16
Cooling only 220V – 60Hz (R22)
INDOOR UNIT MDB075D MDB100D MDB125D MDB150D1
MODEL
OUTDOOR UNIT MMC075D MMC100D MMC125D MMC150D
TOTAL COOLING OUTDOOR Btu/h 75,000 100,000 125,000 150,000
35 °CDB kcal/h 18,900 25,200 31,500 37,800
CAPACITY
W 21,975 29,300 36,625 43,950
NOMINAL TOTAL POWER W 7,846 10,005 12,970 14,829
NOMINAL TOTAL CURRENT A 25.4 37.2 49.4 55.1
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 507 (19.96) 710 (27.95)
DIMENSION WIDTH (W) mm (in) 1507 (59.33) 1917 (75.47) 1794 (70.62) 2073 (81.61)
DEPTH (D) mm (in) 859 (33.81) 964 (37.95)
3
VOLUME M 1.112 1.395 1.875 2.192
NET WEIGHT kg (lb) 95 (209) 120 (264) 155 (341) 175 (385)
NOISE LEVEL dBA 64 64 77 79
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-0
2 2
FACE AREA m (ft ) 0.53 (5.73) 0.72 (7.75) 0.89 (9.66) 1.06 (11.50)
FACE VELOCITY m/min (FPM) 119.48 (392) 117.95 (387) 118.26 (388) 119.17 (391)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / DIRECT CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
INDOOR UNIT
QUANTITY 2 1
BLOWER DIAMETER mm (in) 282.70 (11.13) 394.97 (15.55)
BLOWER LENGTH mm (in) 203.20 (8.00) 381.00 (15.00)
AIR FLOW L/s (CFM) 1062 (2250) 1416 (3000) 1770 (3750) 2124 (4500)
EXTERNAL STATIC PRESSURE mmWG(inWG) 10.2 (0.40) 15.2 (0.6)
BLOWER PULLEY DIAMETER mm - - 1 SPZ 160
MOTOR PULLEY DIAMETER mm - - 1 SPZ 85
PULLEY TYPE - - 1 SPZ
V-BELT TYPE - - SPZ 760
EVAPORATOR BLOWER MOTOR
TYPE PERMANENT SPLIT CAPACITOR SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 220 / 1 / 60 220 / 3 / 60
NUMBER x RATED RUNNING CURRENT A 2 x 2.4 2 x 3.0 5.2 5.9
NUMBER x RATED INPUT POWER W 2 x 486 2 x 605 1372 1681
NUMBER x MOTOR OUTPUT W 2 x 236 2 x 378 1500
MOTOR POLES 6 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 12.70 (1/2) 15.88 (5/8) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 28.57 (1-1/8) 34.92 (1-3/8) 34.92 (1-3/8) 41.28 (1-5/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 399 x 385 536 x 385 508 x 581 601 x 581
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 3
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1041 (40.98) 1142 (44.96)
DIMENSION WIDTH (W) mm (in) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 981 (38.62) 1083 (42.63)
3
VOLUME M 1.654 1.654 1.957 2.12
NET WEIGHT kg (lb) 170 (374) 184 (405) 197 (434) 268 (590)
NOISE LEVEL dBA 64 64 66 67
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER INNER GROOVED
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x1 2x2
FIN PER INCH 20 16
2 2
FACE AREA m (ft ) 2.29 (24.72) 2.26 (24.38) 2.54 (27.38) 2.82 (30.40)
FACE VELOCITY m/min (FPM) 86.25 (283) 87.47 (287) 111.25 (365) 100.27 (329)
OUTDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
RATED RUNNING CURRENT A 3.1 3.1 2.2
RATED INPUT POWER W 594 625 728
MOTOR OUTPUT W 350 350 450
MOTOR POLES 12
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
RATED RUNNING CURRENT A 20.7 32.1 42.0 47.0
RATED INPUT POWER W 6280 8170 10870 12420
MAXIMUM STARTING CURRENT A 95.0 203.0 247.0 245.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 9750 8940
CONTROL MODULE & AUTO
PROTECTION DEVICE OVERLOAD PROTECTION AND AUTO RESET HIGH/LOW PRESSURE SWITCH
RESET H/L PRESS. SW
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE AUTO-TRANSFORMER
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
17
Cooling only 220V – 60Hz (R22)
INDOOR UNIT MDB150D2 MDB200D2 MDB250D2
MODEL
OUTDOOR UNIT MMC075D x2 MMC100D x2 MMC125D x2
TOTAL OUTDOOR Btu/h 150,000 200,000 250,000
COOLING 35 °CDB kcal/h 37,800 50,400 63,000
CAPACITY W 43,950 58,600 73,250
NOMINAL TOTAL POWER W 15,429 20,334 27,499
NOMINAL TOTAL CURRENT A 53.5 80.1 102.4
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 710 (27.95) 881 (34.68) 983 (38.70)
DIMENSION WIDTH (W) mm (in) 2073 (81.61) 1324 (52.12) 1486 (58.50)
DEPTH (D) mm (in) 964 (37.95) 1209 (47.59) 1298 (51.10)
3
VOLUME M 2.192 2.056 2.675
NET WEIGHT kg (lb) 175 (385) 248 (546) 321 (707)
NOISE LEVEL dBA 78.6 85 87
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-50-0
FACE AREA m2 (ft2) 1.06 (11.50) 1.43 (15.41) 1.77 (19.12)
FACE VELOCITY m/min (FPM) 119.17 (391) 118.56 (389) 119.48 (392)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
INDOOR UNIT
QUANTITY 1
BLOWER DIAMETER mm (in) 394.97 (15.55) 469.90 (18.50)
BLOWER LENGTH mm (in) 381.00 (15.00) 459.99 (18.11)
AIR FLOW L/s (CFM) 2124 (4500) 2832 (6000) 3540 (7500)
EXTERNAL STATIC PRESSURE mmWG(inWG) 15.2 (0.6) 20.3 (0.8)
BLOWER PULLEY DIAMETER mm 1 SPZ 160 2 SPZ125 2 SPZ180
MOTOR PULLEY DIAMETER mm 1 SPZ 85 2 SPZ 75 2 SPZ95
PULLEY TYPE 1 SPZ 2 SPZ
V-BELT TYPE SPZ 760 SPZ 1150 SPZ 1400
EVAPORATOR BLOWER MOTOR
TYPE SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
NUMBER x RATED RUNNING CURRENT A 5.9 9.7 14.0
NUMBER x RATED INPUT POWER W 1681 2744 4303
NUMBER x MOTOR OUTPUT W 1500 3000 4000
MOTOR POLES 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 12.70 (1/2) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 28.57 (1 1/8) 34.92 (1 3/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 601 x 581 470 x 346 514 x 397
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 3 8
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1041 (40.98) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 981 (38.62) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 981 (38.62) 981 (38.62) 1083 (42.63)
3
VOLUME M 1.654 2.056 2.675
NET WEIGHT kg (lb) 170 (374) 184 (405) 197 (434)
NOISE LEVEL dBA 64 64 66
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER INNER GROOVED
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x1 2x2
FIN PER INCH 20 16
2 2
FACE AREA m (ft ) 2.29 (24.72) 2.26 (24.38) 2.54 (27.38)
FACE VELOCITY m/min (FPM) 86.25 (283) 87.47 (287) 111.25 (365)
OUTDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
RATED RUNNING CURRENT A 3.1 3.1 2.2
RATED INPUT POWER W 594 625 728
MOTOR OUTPUT W 350 350 450
MOTOR POLES 12
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
RATED RUNNING CURRENT A 20.7 32.1 42.0
RATED INPUT POWER W 6280 8170 10870
MAXIMUM STARTING CURRENT A 95.0 203.0 247.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 9750
OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE AUTO-TRANSFORMER
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
18
Cooling only 220V – 60Hz (R22)
INDOOR UNIT MDB300D2 MDB400D4 MDB500D4
MODEL
OUTDOOR UNIT MMC150D x2 MMC100D x4 MMC125D x4
TOTAL OUTDOOR Btu/h 300,000 400,000 500,000
COOLING 35 °CDB kcal/h 75,600 100,800 126,000
CAPACITY W 87,900 117,200 146,500
W 31,038 41,344 57,441
NOMINAL TOTAL CURRENT A 116.2 161.7 209.6
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 983 (38.70) 1176 (46.29) 1176 (46.29)
DIMENSION WIDTH (W) mm (in) 1486 (58.50) 1722 (67.79) 1722 (67.79)
DEPTH (D) mm (in) 1501 (59.09) 1691 (66.57) 2047 (80.59)
3
VOLUME M 3.047 4.552 5.427
NET WEIGHT kg (lb) 394 (868) 470 (1036) 567 (1250)
NOISE LEVEL dBA 89 90 96
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-50-0 100-75-50-25-0
2 2
FACE AREA m (ft ) 2.12 (22.90) 2.89 (31.11) 3.61 (38.88)
FACE VELOCITY m/min (FPM) 119.78 (393) 117.34 (385)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 1
INDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 914.40 (36) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
RATED RUNNING CURRENT A 3.1 3.1 2.2
RATED INPUT POWER W 625 625 728
MOTOR OUTPUT W 350 350 450
MOTOR POLES 12
AIR FLOW L/s (CFM) 4720 (10000) 3304 (7000) 4720 (10000)
.
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
RATED RUNNING CURRENT A 47.0 32.1 42.0
RATED INPUT POWER W 12420 8170 10870
MAXIMUM STARTING CURRENT A 245.0 203.0 247.0
COMPRESSOR MOTOR OUTPUT W 8940 7500 9750
CONTROL MODULE AND OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET H/L PRESS. SW. AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE AUTO-TRANSFORMER
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
19
Cooling only 460V – 60Hz (R22)
INDOOR UNIT MDB075D MDB100D MDB125D MDB150D1
MODEL
OUTDOOR UNIT MMC075D MMC100D MMC125D MMC150D
TOTAL COOLING OUTDOOR Btu/h 75,000 100,000 125,000 150,000
35 °CDB kcal/h 18,900 25,200 31,500 37,800
CAPACITY
W 21,975 29,300 36,625 43,950
NOMINAL TOTAL POWER W 7,858 10,018 13,043 14,908
NOMINAL TOTAL CURRENT A 13.2 20.0 22.8 23.6
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 507 (19.96) 710 (27.95)
DIMENSION WIDTH (W) mm (in) 1507 (59.33) 1917 (75.47) 1794 (70.62) 2073 (81.61)
DEPTH (D) mm (in) 859 (33.81) 964 (37.95)
3
VOLUME M 1.112 1.395 1.875 2.192
NET WEIGHT kg (lb) 95 (209) 120 (264) 155 (341) 175 (385)
NOISE LEVEL dBA 64 64 77 79
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-0
FACE AREA m2 (ft2) 0.53 (5.73) 0.72 (7.75) 0.89 (9.66) 1.06 (11.50)
FACE VELOCITY m/min (FPM) 119.48 (392) 117.95 (387) 118.26 (388) 119.17 (391)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / DIRECT CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
INDOOR UNIT
QUANTITY 2 1
BLOWER DIAMETER mm (in) 282.70 (11.13) 394.97 (15.55)
BLOWER LENGTH mm (in) 203.20 (8.00) 381.00 (15.00)
AIR FLOW L/s (CFM) 1062 (2250) 1416 (3000) 1770 (3750) 2124 (4500)
EXTERNAL STATIC PRESSURE mmWG(inWG) 10.2 (0.40) 15.2 (0.6)
BLOWER PULLEY DIAMETER mm - - 1 SPZ 160
MOTOR PULLEY DIAMETER mm - - 1 SPZ 85
PULLEY TYPE - - 1 SPZ
V-BELT TYPE - - SPZ 760
EVAPORATOR BLOWER MOTOR
TYPE PERMANENT SPLIT CAPACITOR SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 220 / 1 / 60 460 / 3 / 60
NUMBER x RATED RUNNING CURRENT A 2 x 2.4 2 x 3.0 2.5 2.9
NUMBER x RATED INPUT POWER W 2 x 486 2 x 605 1396 1711
NUMBER x MOTOR OUTPUT W 2 x 236 2 x 378 1500
MOTOR POLES 6 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 12.70 (1/2) 15.88 (5/8) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 28.57 (1-1/8) 34.92 (1-3/8) 34.92 (1-3/8) 41.28 (1-5/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 399 x 385 536 x 385 508 x 581 601 x 581
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 3
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1041 (40.98) 1142 (44.96)
DIMENSION WIDTH (W) mm (in) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 981 (38.62) 1083 (42.63)
3
VOLUME M 1.654 1.654 1.957 2.12
NET WEIGHT kg (lb) 170 (374) 184 (405) 197 (434) 268 (590)
NOISE LEVEL dBA 64 64 66 67
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER INNER GROOVED
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x1 2x2
FIN PER INCH 20 16
2 2
FACE AREA m (ft ) 2.29 (24.72) 2.26 (24.38) 2.54 (27.38) 2.82 (30.40)
FACE VELOCITY m/min (FPM) 86.25 (283) 87.47 (287) 111.25 (365) 100.27 (329)
OUTDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 460 / 3 / 60
RATED RUNNING CURRENT A 1.6 1.6 1.1
RATED INPUT POWER W 606 638 777
MOTOR OUTPUT W 360 360 460
MOTOR POLES 12
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 460 / 3 / 60
RATED RUNNING CURRENT A 10.0 16.4 19.2 19.6
RATED INPUT POWER W 6280 8170 10870 12420
MAXIMUM STARTING CURRENT A 74.0 95.0 125.0 125.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 9750 8940
CONTROL MODULE & AUTO
PROTECTION DEVICE OVERLOAD PROTECTION AND AUTO RESET HIGH/LOW PRESSURE SWITCH
RESET H/L PRESS. SW
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE AUTO-TRANSFORMER
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
20
Cooling only 460V – 60Hz (R22)
INDOOR UNIT MDB150D2 MDB200D2 MDB250D2
MODEL
OUTDOOR UNIT MMC075D x2 MMC100D x2 MMC125D x2
TOTAL OUTDOOR Btu/h 150,000 200,000 250,000
COOLING 35 °CDB kcal/h 37,800 50,400 63,000
CAPACITY W 43,950 58,600 73,250
NOMINAL TOTAL POWER W 15,483 20,387 27,599
NOMINAL TOTAL CURRENT A 26.1 40.7 47.3
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 710 (27.95) 881 (34.68) 983 (38.70)
DIMENSION WIDTH (W) mm (in) 2073 (81.61) 1324 (52.12) 1486 (58.50)
DEPTH (D) mm (in) 964 (37.95) 1209 (47.59) 1298 (51.10)
3
VOLUME M 2.192 2.056 2.675
NET WEIGHT kg (lb) 175 (385) 248 (546) 321 (707)
NOISE LEVEL dBA 78.6 85 87
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-50-0
FACE AREA m2 (ft2) 1.06 (11.50) 1.43 (15.41) 1.77 (19.12)
FACE VELOCITY m/min (FPM) 119.17 (391) 118.56 (389) 119.48 (392)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
INDOOR UNIT
QUANTITY 1
BLOWER DIAMETER mm (in) 394.97 (15.55) 469.90 (18.50)
BLOWER LENGTH mm (in) 381.00 (15.00) 459.99 (18.11)
AIR FLOW L/s (CFM) 2124 (4500) 2832 (6000) 3540 (7500)
EXTERNAL STATIC PRESSURE mmWG(inWG) 15.2 (0.6) 20.3 (0.8)
BLOWER PULLEY DIAMETER mm 1 SPZ 160 2 SPZ125 2 SPZ180
MOTOR PULLEY DIAMETER mm 1 SPZ 85 2 SPZ 75 2 SPZ95
PULLEY TYPE 1 SPZ 2 SPZ
V-BELT TYPE SPZ 760 SPZ 1150 SPZ 1400
EVAPORATOR BLOWER MOTOR
TYPE SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 460 / 3 / 60
NUMBER x RATED RUNNING CURRENT A 2.9 4.7 6.7
NUMBER x RATED INPUT POWER W 1711 2771 4305
NUMBER x MOTOR OUTPUT W 1500 3000 4000
MOTOR POLES 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 12.70 (1/2) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 28.57 (1 1/8) 34.92 (1 3/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 601 x 581 470 x 346 514 x 397
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 3 8
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1041 (40.98) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 981 (38.62) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 981 (38.62) 981 (38.62) 1083 (42.63)
VOLUME M3 1.654 2.056 2.675
NET WEIGHT kg (lb) 170 (374) 184 (405) 197 (434)
NOISE LEVEL dBA 64 64 66
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER INNER GROOVED
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x1 2x2
FIN PER INCH 20 16
2 2
FACE AREA m (ft ) 2.29 (24.72) 2.26 (24.38) 2.54 (27.38)
FACE VELOCITY m/min (FPM) 86.25 (283) 87.47 (287) 111.25 (365)
OUTDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 460 / 3 / 60
RATED RUNNING CURRENT A 1.6 1.6 1.1
RATED INPUT POWER W 606 638 777
MOTOR OUTPUT W 360 360 460
MOTOR POLES 12
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 460 / 3 / 60
RATED RUNNING CURRENT A 10.0 16.4 19.2
RATED INPUT POWER W 6280 8170 10870
MAXIMUM STARTING CURRENT A 74.0 95.0 125.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 9750
OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE AUTO-TRANSFORMER
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
21
Cooling only 460V – 60Hz (R22)
INDOOR UNIT MDB300D2 MDB400D4 MDB500D4
MODEL
OUTDOOR UNIT MMC150D x2 MMC100D x4 MMC125D x4
TOTAL OUTDOOR Btu/h 300,000 400,000 500,000
COOLING 35 °CDB kcal/h 75,600 100,800 126,000
CAPACITY W 87,900 117,200 146,500
W 22,565 41,394 57,665
NOMINAL TOTAL CURRENT A 43.7 82.0 96.9
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING FINISHING EPOXY POLYESTER POWDER COATING
INSULATION PE FOAM -- 10MM THICKNESS
HEIGHT (H) mm (in) 983 (38.70) 1176 (46.29) 1176 (46.29)
DIMENSION WIDTH (W) mm (in) 1486 (58.50) 1722 (67.79) 1722 (67.79)
DEPTH (D) mm (in) 1501 (59.09) 1691 (66.57) 2047 (80.59)
3
VOLUME M 3.047 4.552 5.427
NET WEIGHT kg (lb) 394 (868) 470 (1036) 567 (1250)
NOISE LEVEL dBA 89 90 96
EVAPORATOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
FIN THICKNESS mm (in) 0.127 (0.005)
ROWS / FIN PER INCH(FPI) 3 / 14
CAPACITY STEP % 100-50-0 100-75-50-25-0
FACE AREA m2 (ft2) 2.12 (22.90) 2.89 (31.11) 3.61 (38.88)
FACE VELOCITY m/min (FPM) 119.78 (393) 117.34 (385)
EVAPORATOR BLOWER
TYPE / DRIVE CENTRIFUGAL / BELT DRIVEN
BLOWER MATERIAL ZINC COATED STEEL
QUANTITY 1
INDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 914.40 (36) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 460 / 3 / 60
RATED RUNNING CURRENT A 1.6 1.6 1.1
RATED INPUT POWER W 638 638 777
MOTOR OUTPUT W 360 360 460
MOTOR POLES 12
AIR FLOW L/s (CFM) 4720 (10000) 3304 (7000) 4720 (10000)
.
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 460 / 3 / 60
RATED RUNNING CURRENT A 16.4 16.4 19.2
RATED INPUT POWER W 8170 8170 10870
MAXIMUM STARTING CURRENT A 95.0 95.0 125.0
COMPRESSOR MOTOR OUTPUT W 7500 7500 9750
CONTROL MODULE AND OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET H/L PRESS. SW. AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE AUTO-TRANSFORMER
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
22
Performance Table
50Hz R22 Specifications
Cooling Model
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
23
Model : MDB150D vs. MMC150D (cooling capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
°C °C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC 43.523 40.931 38.617 36.304 33.990 31.213 29.362 28.437 27.511
SC 43.523 40.931 38.617 36.304 33.990 31.213 29.362 28.437 27.511
15 TC 46.487 43.381 40.608 37.835 35.063 31.735 29.517 28.408 27.298
SC 42.652 40.197 38.005 35.813 33.621 30.991 29.237 28.361 27.484
18 TC 54.571 50.063 46.038 42.013 37.988 33.158 29.938 28.328 26.718
SC 40.277 38.194 36.335 34.475 32.616 30.384 28.897 28.153 27.409
19.4 TC 58.344 53.181 48.572 43.962 39.353 33.822 30.134 28.291 26.447
SC 39.169 37.260 35.556 33.851 32.147 30.101 28.738 28.056 27.374
20 TC 59.961 54.708 50.019 45.329 40.640 35.013 31.261 29.385 27.509
SC 38.694 36.687 34.895 33.103 31.310 29.160 27.726 27.009 26.293
22 TC 65.350 59.799 54.843 49.886 44.930 38.982 35.017 33.034 31.052
SC 37.111 34.776 32.692 30.607 28.523 26.022 24.354 23.520 22.687
24 TC 70.740 64.890 59.666 54.443 49.219 42.951 38.773 36.683 34.594
SC 35.528 32.866 30.489 28.112 25.735 22.883 20.982 20.031 19.081
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
24
Model : MDB250D vs. MMC125D x 2 (cooling capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
°C °C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC 69.216 65.596 62.364 59.132 55.901 52.022 49.437 48.144 46.851
SC 69.216 65.596 62.364 59.132 55.901 52.022 49.437 48.144 46.851
15 TC 74.732 70.147 66.054 61.960 57.867 52.954 49.679 48.042 46.405
SC 68.252 64.625 61.388 58.150 54.912 51.027 48.437 47.142 45.847
18 TC 89.776 82.559 76.116 69.672 63.228 55.496 50.341 47.764 45.186
SC 65.622 61.978 58.724 55.471 52.217 48.313 45.710 44.409 43.107
19.4 TC 96.796 88.351 80.811 73.271 65.731 56.682 50.650 47.634 44.618
SC 64.395 60.742 57.481 54.220 50.959 47.046 44.438 43.133 41.829
20 TC 99.805 91.136 83.395 75.655 67.915 58.626 52.434 49.338 46.242
SC 63.869 60.042 56.625 53.208 49.791 45.691 42.957 41.590 40.224
22 TC 109.834 100.418 92.010 83.603 75.195 65.106 58.380 55.017 51.654
SC 62.115 57.706 53.769 49.833 45.896 41.172 38.022 36.448 34.873
24 TC 119.864 109.700 100.625 91.550 82.475 71.586 64.326 60.696 57.066
SC 60.362 55.371 50.914 46.458 42.001 36.653 33.088 31.305 29.522
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
25
Model : MDB500D4 vs. MMC125D x 4 (cooling capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
°C °C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC 138.432 131.192 124.729 118.265 111.801 104.045 98.874 96.288 93.703
SC 138.432 131.192 124.729 118.265 111.801 104.045 98.874 96.288 93.703
15 TC 149.464 140.294 132.107 123.920 115.733 105.909 99.359 96.084 92.809
SC 136.503 129.251 122.775 116.300 109.825 102.054 96.874 94.284 91.694
18 TC 179.552 165.118 152.231 139.344 126.457 110.992 100.683 95.528 90.373
SC 131.244 123.956 117.449 110.941 104.434 96.626 91.420 88.817 86.214
19.4 TC 193.593 176.703 161.622 146.542 131.461 113.365 101.300 95.268 89.236
SC 128.789 121.485 114.963 108.441 101.919 94.093 88.875 86.266 83.658
20 TC 199.610 182.272 166.791 151.310 135.829 117.252 104.868 98.675 92.483
SC 127.737 120.083 113.250 106.416 99.582 91.381 85.914 83.181 80.447
22 TC 219.669 200.836 184.020 167.205 150.390 130.212 116.760 110.034 103.307
SC 124.231 115.412 107.539 99.665 91.792 82.344 76.045 72.895 69.746
24 TC 239.727 219.400 201.250 183.100 164.951 143.171 128.651 121.392 114.132
SC 120.724 110.742 101.828 92.915 84.002 73.306 66.175 62.610 59.045
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Heatpump Model
Model : MDB075DR vs. MMC075DR (cooling capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
°C °C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC 21.490 20.339 19.311 18.284 17.256 16.023 15.201 14.790 14.379
SC 21.490 20.339 19.311 18.284 17.256 16.023 15.201 14.790 14.379
15 TC 22.869 21.531 20.335 19.140 17.945 16.511 15.555 15.077 14.599
SC 21.131 19.995 18.981 17.967 16.953 15.736 14.924 14.519 14.113
18 TC 26.631 24.781 23.129 21.477 19.825 17.843 16.521 15.861 15.200
SC 20.153 19.058 18.081 17.103 16.125 14.952 14.170 13.779 13.388
19.4 TC 28.386 26.298 24.432 22.567 20.702 18.464 16.972 16.226 15.480
SC 19.697 18.621 17.660 16.700 15.739 14.587 13.818 13.434 13.050
20 TC 29.139 26.990 25.071 23.153 21.234 18.932 17.397 16.629 15.862
SC 19.501 18.376 17.371 16.367 15.362 14.157 13.353 12.951 12.549
22 TC 31.647 29.298 27.201 25.104 23.007 20.490 18.812 17.974 17.135
SC 18.849 17.559 16.408 15.256 14.105 12.723 11.802 11.341 10.880
24 TC 34.155 31.606 29.330 27.055 24.779 22.048 20.228 19.318 18.407
SC 18.197 16.743 15.444 14.146 12.847 11.289 10.250 9.731 9.212
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
26
Model : MDB125DR vs. MMC125DR (cooling capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
°C °C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC 32.960 31.103 29.445 27.786 26.128 24.138 22.812 22.148 21.485
SC 32.960 31.103 29.445 27.786 26.128 24.138 22.812 22.148 21.485
15 TC 34.622 32.614 30.822 29.029 27.236 25.084 23.650 22.933 22.216
SC 32.232 30.496 28.947 27.397 25.847 23.987 22.748 22.128 21.508
18 TC 39.156 36.737 34.577 32.417 30.257 27.665 25.937 25.073 24.209
SC 30.246 28.842 27.588 26.334 25.080 23.576 22.573 22.071 21.570
19.4 TC 41.271 38.660 36.329 33.998 31.666 28.869 27.004 26.071 25.139
SC 29.319 28.070 26.954 25.838 24.723 23.384 22.491 22.045 21.599
20 TC 42.178 39.496 37.100 34.705 32.310 29.436 27.520 26.561 25.603
SC 28.922 27.594 26.407 25.221 24.035 22.612 21.663 21.189 20.714
22 TC 45.200 42.279 39.671 37.063 34.455 31.326 29.239 28.196 27.153
SC 27.598 26.007 24.586 23.165 21.744 20.039 18.903 18.334 17.766
24 TC 48.223 45.063 42.242 39.422 36.601 33.216 30.959 29.831 28.702
SC 26.274 24.420 22.764 21.109 19.453 17.467 16.142 15.480 14.818
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
27
Model : MDB200DR2 vs. MMC100DR x 2 (cooling capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
°C °C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC 50.117 47.977 46.067 44.156 42.246 39.953 38.425 37.660 36.896
SC 50.117 47.977 46.067 44.156 42.246 39.953 38.425 37.660 36.896
15 TC 54.258 51.501 49.040 46.579 44.118 41.165 39.197 38.212 37.228
SC 50.336 48.018 45.948 43.878 41.809 39.325 37.669 36.841 36.013
18 TC 65.550 61.112 57.150 53.188 49.226 44.471 41.302 39.717 38.132
SC 50.934 48.129 45.625 43.120 40.616 37.611 35.608 34.606 33.604
19.4 TC 70.820 65.597 60.935 56.272 51.609 46.014 42.284 40.419 38.554
SC 51.213 48.181 45.474 42.767 40.060 36.811 34.646 33.563 32.480
20 TC 73.078 67.626 62.759 57.892 53.024 47.183 43.289 41.342 39.395
SC 51.332 48.058 45.135 42.212 39.289 35.781 33.442 32.273 31.104
22 TC 80.606 74.390 68.840 63.290 57.740 51.080 46.641 44.421 42.201
SC 51.730 47.649 44.006 40.362 36.718 32.345 29.430 27.973 26.515
24 TC 88.134 81.154 74.921 68.689 62.457 54.978 49.992 47.499 45.006
SC 52.129 47.241 42.876 38.512 34.148 28.910 25.419 23.673 21.927
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
28
Model : MDB400DR4 vs. MMC100DR x 4 (cooling capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
°C °C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC 100.234 95.955 92.134 88.313 84.492 79.906 76.849 75.321 73.792
SC 100.234 95.955 92.134 88.313 84.492 79.906 76.849 75.321 73.792
15 TC 108.599 103.056 98.107 93.159 88.210 82.272 78.313 76.334 74.354
SC 100.739 96.079 91.918 87.757 83.596 78.603 75.274 73.609 71.945
18 TC 131.410 122.423 114.400 106.376 98.352 88.724 82.305 79.096 75.886
SC 102.115 96.417 91.329 86.241 81.153 75.047 70.977 68.942 66.906
19.4 TC 142.055 131.461 122.003 112.544 103.085 91.735 84.168 80.385 76.601
SC 102.758 96.575 91.054 85.533 80.013 73.388 68.972 66.763 64.555
20 TC 146.617 135.563 125.694 115.824 105.955 94.112 86.216 82.268 78.321
SC 103.033 96.364 90.410 84.456 78.502 71.358 66.594 64.213 61.831
22 TC 161.824 149.237 137.998 126.759 115.520 102.034 93.042 88.547 84.051
SC 103.951 95.664 88.265 80.866 73.468 64.589 58.670 55.711 52.751
24 TC 177.032 162.910 150.302 137.694 125.085 109.955 99.869 94.825 89.782
SC 104.868 94.963 86.120 77.276 68.433 57.821 50.746 47.208 43.671
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
29
Heatpump Model
Model : MDB075DR vs. MMC075DR (HEATING CAPACITY)
Indoor DB°C
Outdoor WB°C kW 15.0 17.0 19.0 21.0 24.0 26.7
FROST REGION
-9.0 TC 14.825 14.719 14.614 14.508 14.265 14.046
SC 14.825 14.719 14.614 14.508 14.265 14.046
-5.0 TC 16.912 16.760 16.609 16.457 16.229 16.025
SC 16.912 16.760 16.609 16.457 16.229 16.025
6.0 TC 22.649 23.404 24.158 24.912 23.098 21.466
SC 22.649 23.404 24.158 24.912 23.098 21.466
12.0 TC 25.779 25.549 25.319 25.089 24.744 24.434
SC 25.779 25.549 25.319 25.089 24.744 24.434
15.0 TC 27.344 27.100 26.856 26.612 26.247 25.918
SC 27.344 27.100 26.856 26.612 26.247 25.918
18.3 TC 29.065 28.806 28.547 28.288 27.899 27.550 ###
SC 29.065 28.806 28.547 28.288 27.899 27.550 ###
FROST REGION
-9.0 TC 20.265 20.105 19.944 19.783 19.476 19.200
SC 20.265 20.105 19.944 19.783 19.476 19.200
-5.0 TC 23.208 23.000 22.792 22.584 22.272 21.991
SC 23.208 23.000 22.792 22.584 22.272 21.991
6.0 TC 31.301 31.223 31.145 31.067 30.329 29.666
SC 31.301 31.223 31.145 31.067 30.329 29.666
12.0 TC 35.716 35.397 35.079 34.760 34.282 33.852
SC 35.716 35.397 35.079 34.760 34.282 33.852
15.0 TC 37.923 37.585 37.247 36.909 36.401 35.945
SC 37.923 37.585 37.247 36.909 36.401 35.945
18.3 TC 40.351 39.991 39.632 39.272 38.733 38.247 ###
SC 40.351 39.991 39.632 39.272 38.733 38.247 ###
30
Model : MDB150DR vs. MMC150DR (HEATING CAPACITY)
Indoor DB°C
Outdoor WB°C kW 15.0 17.0 19.0 21.0 24.0 26.7
FROST REGION
-9.0 TC 29.415 28.891 28.367 27.843 27.857 27.869
SC 29.415 28.891 28.367 27.843 27.857 27.869
-5.0 TC 35.344 35.027 34.711 34.394 33.919 33.491
SC 35.344 35.027 34.711 34.394 33.919 33.491
6.0 TC 51.649 50.063 48.478 46.893 47.976 48.950
SC 51.649 50.063 48.478 46.893 47.976 48.950
12.0 TC 60.542 60.002 59.462 58.922 58.112 57.383
SC 60.542 60.002 59.462 58.922 58.112 57.383
15.0 TC 64.989 64.409 63.830 63.250 62.381 61.599
SC 64.989 64.409 63.830 63.250 62.381 61.599
18.3 TC 69.880 69.257 68.634 68.012 67.078 66.237 ###
SC 69.880 69.257 68.634 68.012 67.078 66.237 ###
FROST REGION
-9.0 TC 29.651 29.439 29.227 29.015 28.529 28.092
SC 29.651 29.439 29.227 29.015 28.529 28.092
-5.0 TC 33.824 33.520 33.217 32.914 32.459 32.049
SC 33.824 33.520 33.217 32.914 32.459 32.049
6.0 TC 45.299 46.807 48.316 49.824 46.196 42.931
SC 45.299 46.807 48.316 49.824 46.196 42.931
12.0 TC 51.558 51.098 50.638 50.178 49.488 48.867
SC 51.558 51.098 50.638 50.178 49.488 48.867
15.0 TC 54.688 54.200 53.712 53.225 52.493 51.835
SC 54.688 54.200 53.712 53.225 52.493 51.835
18.3 TC 58.130 57.612 57.094 56.576 55.799 55.100 ###
SC 58.130 57.612 57.094 56.576 55.799 55.100 ###
31
Model : MDB250DR2 vs. MMC125DR x 2 (HEATING CAPACITY)
Indoor DB°C
Outdoor WB°C kW 15.0 17.0 19.0 21.0 24.0 26.7
FROST REGION
-9.0 TC 46.138 45.510 44.883 44.256 43.970 43.713
SC 46.138 45.510 44.883 44.256 43.970 43.713
-5.0 TC 54.328 53.841 53.354 52.867 52.137 51.479
SC 54.328 53.841 53.354 52.867 52.137 51.479
6.0 TC 76.852 76.635 76.418 76.202 74.430 72.836
SC 76.852 76.635 76.418 76.202 74.430 72.836
12.0 TC 89.137 88.342 87.547 86.752 85.559 84.486
SC 89.137 88.342 87.547 86.752 85.559 84.486
15.0 TC 95.280 94.430 93.581 92.731 91.457 90.310
SC 95.280 94.430 93.581 92.731 91.457 90.310
18.3 TC 102.037 101.128 100.218 99.309 97.945 96.717 ###
SC 102.037 101.128 100.218 99.309 97.945 96.717 ###
FROST REGION
-9.0 TC 58.830 57.782 56.734 55.686 55.714 55.739
SC 58.830 57.782 56.734 55.686 55.714 55.739
-5.0 TC 70.688 70.055 69.421 68.788 67.837 66.982
SC 70.688 70.055 69.421 68.788 67.837 66.982
6.0 TC 103.297 100.127 96.957 93.787 95.952 97.901
SC 103.297 100.127 96.957 93.787 95.952 97.901
12.0 TC 121.084 120.004 118.924 117.844 116.224 114.766
SC 121.084 120.004 118.924 117.844 116.224 114.766
15.0 TC 129.977 128.818 127.659 126.501 124.762 123.198
SC 129.977 128.818 127.659 126.501 124.762 123.198
18.3 TC 139.760 138.514 137.269 136.023 134.155 132.474 ###
SC 139.760 138.514 137.269 136.023 134.155 132.474 ###
32
Model : MDB500DR4 vs. M4MC125DR x 4 (HEATING CAPACITY)
Indoor DB°C
Outdoor WB°C kW 15.0 17.0 19.0 21.0 24.0 26.7
FROST REGION
-9.0 TC 80.802 80.148 79.494 78.839 77.637 76.555
SC 80.802 80.148 79.494 78.839 77.637 76.555
-5.0 TC 92.612 91.782 90.951 90.121 88.875 87.754
SC 92.612 91.782 90.951 90.121 88.875 87.754
6.0 TC 125.089 134.194 143.298 152.403 134.587 118.552
SC 125.089 134.194 143.298 152.403 134.587 118.552
12.0 TC 142.804 141.530 140.256 138.982 137.071 135.351
SC 142.804 141.530 140.256 138.982 137.071 135.351
15.0 TC 151.661 150.309 148.956 147.604 145.576 143.750
SC 151.661 150.309 148.956 147.604 145.576 143.750
18.3 TC 161.404 159.966 158.527 157.089 154.931 152.989 ###
SC 161.404 159.966 158.527 157.089 154.931 152.989 ###
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
33
Model : MDB125DR vs. M4MC125DR (cooling capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
°C °C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC 31.619 29.694 27.975 26.256 24.537 22.474 21.098 20.411 19.723
SC 31.619 29.694 27.975 26.256 24.537 22.474 21.098 20.411 19.723
15 TC 33.122 31.045 29.190 27.335 25.480 23.254 21.771 21.029 20.287
SC 31.108 29.299 27.684 26.069 24.454 22.516 21.224 20.578 19.932
18 TC 37.222 34.729 32.504 30.279 28.054 25.384 23.604 22.714 21.824
SC 29.714 28.223 26.891 25.560 24.229 22.631 21.566 21.033 20.501
19.4 TC 39.135 36.449 34.051 31.653 29.255 26.377 24.459 23.500 22.541
SC 29.063 27.720 26.521 25.322 24.123 22.685 21.725 21.246 20.766
20 TC 39.954 37.221 34.780 32.340 29.899 26.971 25.018 24.042 23.066
SC 28.784 27.347 26.064 24.781 23.498 21.959 20.932 20.419 19.906
22 TC 42.687 39.795 37.212 34.630 32.047 28.948 26.882 25.849 24.816
SC 27.855 26.104 24.541 22.977 21.414 19.538 18.288 17.662 17.037
24 TC 45.420 42.369 39.644 36.919 34.195 30.925 28.745 27.655 26.565
SC 26.925 24.861 23.017 21.174 19.330 17.118 15.643 14.906 14.168
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
34
Model : MDB200DR2 vs. M4MC100DR x 2 (cooling capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
°C °C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC 50.510 47.849 45.474 43.098 40.723 37.872 35.972 35.022 34.071
SC 50.510 47.849 45.474 43.098 40.723 37.872 35.972 35.022 34.071
15 TC 53.985 50.813 47.980 45.147 42.314 38.914 36.648 35.515 34.382
SC 50.129 47.460 45.077 42.693 40.310 37.450 35.543 34.589 33.636
18 TC 63.465 58.895 54.814 50.734 46.653 41.757 38.492 36.860 35.228
SC 49.092 46.399 43.993 41.588 39.183 36.297 34.373 33.411 32.449
19.4 TC 67.889 62.667 58.004 53.341 48.678 43.083 39.353 37.488 35.623
SC 48.608 45.903 43.488 41.073 38.657 35.759 33.827 32.861 31.895
20 TC 69.785 64.411 59.614 54.816 50.018 44.261 40.423 38.504 36.585
SC 48.401 45.520 42.948 40.375 37.803 34.716 32.659 31.630 30.601
22 TC 76.104 70.227 64.980 59.732 54.485 48.188 43.990 41.891 39.792
SC 47.710 44.242 41.147 38.051 34.956 31.241 28.764 27.526 26.288
24 TC 82.424 76.043 70.346 64.648 58.951 52.114 47.556 45.278 42.999
SC 47.018 42.965 39.346 35.727 32.108 27.765 24.870 23.422 21.975
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
35
Model : MDB400DR4 vs. M4MC100DR x 4 (cooling capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
°C °C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC 101.019 95.698 90.947 86.196 81.446 75.744 71.944 70.043 68.143
SC 101.019 95.698 90.947 86.196 81.446 75.744 71.944 70.043 68.143
15 TC 107.971 101.625 95.959 90.294 84.628 77.829 73.296 71.030 68.764
SC 100.259 94.920 90.153 85.386 80.619 74.899 71.086 69.179 67.272
18 TC 126.930 117.790 109.629 101.468 93.307 83.514 76.985 73.720 70.456
SC 98.185 92.797 87.987 83.177 78.366 72.594 68.746 66.822 64.898
19.4 TC 135.777 125.333 116.008 106.682 97.357 86.166 78.706 74.976 71.246
SC 97.217 91.806 86.976 82.145 77.315 71.518 67.654 65.722 63.789
20 TC 139.569 128.823 119.227 109.632 100.037 88.522 80.846 77.008 73.170
SC 96.802 91.040 85.895 80.751 75.606 69.433 65.317 63.259 61.201
22 TC 152.209 140.454 129.959 119.464 108.969 96.376 87.980 83.782 79.584
SC 95.419 88.485 82.294 76.102 69.911 62.482 57.529 55.052 52.575
24 TC 164.848 152.086 140.691 129.297 117.902 104.229 95.113 90.555 85.997
SC 94.036 85.930 78.692 71.454 64.216 55.530 49.740 46.845 43.949
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
36
Heatpump Model
Model : MDB075DR vs. M4MC075DR (HEATING CAPACITY)
Indoor DB°C
Outdoor WB°C kW 15.0 17.0 19.0 21.0 24.0 26.7
FROST REGION
-9.0 TC 14.892 14.813 14.733 14.654 14.367 14.109
SC 14.892 14.813 14.733 14.654 14.367 14.109
-5.0 TC 16.833 16.682 16.531 16.380 16.153 15.950
SC 16.833 16.682 16.531 16.380 16.153 15.950
6.0 TC 22.170 22.693 23.216 23.740 22.304 21.011
SC 22.170 22.693 23.216 23.740 22.304 21.011
12.0 TC 25.081 24.857 24.633 24.409 24.074 23.772
SC 25.081 24.857 24.633 24.409 24.074 23.772
15.0 TC 26.536 26.300 26.063 25.826 25.472 25.152
SC 26.536 26.300 26.063 25.826 25.472 25.152
18.3 TC 28.137 27.887 27.636 27.385 27.009 26.671 ###
SC 28.137 27.887 27.636 27.385 27.009 26.671 ###
FROST REGION
-9.0 TC 18.978 18.904 18.831 18.757 18.348 17.980
SC 18.978 18.904 18.831 18.757 18.348 17.980
-5.0 TC 21.294 21.103 20.912 20.721 20.434 20.177
SC 21.294 21.103 20.912 20.721 20.434 20.177
6.0 TC 27.663 29.091 30.518 31.946 28.931 26.217
SC 27.663 29.091 30.518 31.946 28.931 26.217
12.0 TC 31.137 30.860 30.582 30.304 29.887 29.512
SC 31.137 30.860 30.582 30.304 29.887 29.512
15.0 TC 32.874 32.581 32.288 31.995 31.555 31.160
SC 32.874 32.581 32.288 31.995 31.555 31.160
18.3 TC 34.785 34.475 34.165 33.855 33.390 32.972 ###
SC 34.785 34.475 34.165 33.855 33.390 32.972 ###
37
Model : MDB150DR vs. M4MC150DR (HEATING CAPACITY)
Indoor DB°C
Outdoor WB°C kW 15.0 17.0 19.0 21.0 24.0 26.7
FROST REGION
-9.0 TC 30.139 29.814 29.488 29.162 28.843 28.555
SC 30.139 29.814 29.488 29.162 28.843 28.555
-5.0 TC 35.011 34.697 34.383 34.069 33.598 33.175
SC 35.011 34.697 34.383 34.069 33.598 33.175
6.0 TC 48.407 46.926 45.444 43.962 44.970 45.878
SC 48.407 46.926 45.444 43.962 44.970 45.878
12.0 TC 55.714 55.217 54.720 54.223 53.478 52.807
SC 55.714 55.217 54.720 54.223 53.478 52.807
15.0 TC 59.368 58.838 58.309 57.780 56.986 56.271
SC 59.368 58.838 58.309 57.780 56.986 56.271
18.3 TC 63.387 62.822 62.257 61.692 60.845 60.082 ###
SC 63.387 62.822 62.257 61.692 60.845 60.082 ###
FROST REGION
-9.0 TC 6.436 5.267 4.099 2.931 4.598 6.099
SC 6.436 5.267 4.099 2.931 4.598 6.099
-5.0 TC 13.738 13.615 13.493 13.370 13.186 13.021
SC 13.738 13.615 13.493 13.370 13.186 13.021
6.0 TC 33.820 38.373 42.926 47.479 39.362 32.056
SC 33.820 38.373 42.926 47.479 39.362 32.056
12.0 TC 44.774 44.374 43.975 43.576 42.978 42.439
SC 44.774 44.374 43.975 43.576 42.978 42.439
15.0 TC 50.250 49.803 49.355 48.907 48.235 47.631
SC 50.250 49.803 49.355 48.907 48.235 47.631
18.3 TC 56.275 55.773 55.272 54.770 54.018 53.341 ###
SC 56.275 55.773 55.272 54.770 54.018 53.341 ###
38
Model : MDB250DR2 vs. M4MC125DR x 2 (HEATING CAPACITY)
Indoor DB°C
Outdoor WB°C kW 15.0 17.0 19.0 21.0 24.0 26.7
FROST REGION
-9.0 TC 46.901 46.410 45.919 45.428 44.906 44.436
SC 46.901 46.410 45.919 45.428 44.906 44.436
-5.0 TC 54.391 53.903 53.416 52.928 52.196 51.538
SC 54.391 53.903 53.416 52.928 52.196 51.538
6.0 TC 74.987 74.220 73.452 72.685 71.834 71.069
SC 74.987 74.220 73.452 72.685 71.834 71.069
12.0 TC 86.221 85.452 84.683 83.914 82.760 81.722
SC 86.221 85.452 84.683 83.914 82.760 81.722
15.0 TC 91.838 91.020 90.201 89.382 88.154 87.048
SC 91.838 91.020 90.201 89.382 88.154 87.048
18.3 TC 98.017 97.144 96.270 95.397 94.087 92.907 ###
SC 98.017 97.144 96.270 95.397 94.087 92.907 ###
FROST REGION
-9.0 TC 60.279 59.627 58.975 58.324 57.685 57.111
SC 60.279 59.627 58.975 58.324 57.685 57.111
-5.0 TC 70.022 69.394 68.766 68.138 67.197 66.349
SC 70.022 69.394 68.766 68.138 67.197 66.349
6.0 TC 96.814 93.851 90.888 87.925 89.941 91.755
SC 96.814 93.851 90.888 87.925 89.941 91.755
12.0 TC 111.428 110.434 109.440 108.446 106.955 105.613
SC 111.428 110.434 109.440 108.446 106.955 105.613
15.0 TC 118.735 117.677 116.618 115.559 113.971 112.542
SC 118.735 117.677 116.618 115.559 113.971 112.542
18.3 TC 126.773 125.643 124.514 123.384 121.689 120.164 ###
SC 126.773 125.643 124.514 123.384 121.689 120.164 ###
39
Model : MDB500DR4 vs. M4MC125DR x 4 (HEATING CAPACITY)
Indoor DB°C
Outdoor WB°C kW 15.0 17.0 19.0 21.0 24.0 26.7
FROST REGION
-9.0 TC 93.803 92.820 91.838 90.856 89.812 88.872
SC 93.803 92.820 91.838 90.856 89.812 88.872
-5.0 TC 108.782 107.806 106.831 105.856 104.393 103.076
SC 108.782 107.806 106.831 105.856 104.393 103.076
6.0 TC 149.974 148.439 146.904 145.369 143.668 142.137
SC 149.974 148.439 146.904 145.369 143.668 142.137
12.0 TC 172.443 170.904 169.366 167.828 165.520 163.443
SC 172.443 170.904 169.366 167.828 165.520 163.443
15.0 TC 183.677 182.039 180.402 178.764 176.307 174.096
SC 183.677 182.039 180.402 178.764 176.307 174.096
18.3 TC 196.035 194.288 192.541 190.794 188.173 185.815 ###
SC 196.035 194.288 192.541 190.794 188.173 185.815 ###
MDB – D/DR Series Sound Power Level (Duct Discharge Sound Power Level)
1/1 Octave Sound Power (dB), ref 1pW
Model A (dBA) **
63 125 250 500 1k 2k 4k 8k
MDB075 D/DR 70 72 73 71 68 65 61 56 73
MDB100 D/DR 72 74 74 73 70 67 63 58 75
MDB125 D/DR 73 75 76 75 72 69 65 60 77
MDB150 D/DR 75 77 78 77 74 71 67 62 79
MDB200 D/DR 82 83 84 83 81 77 73 68 85
MDB250 D/DR 84 85 86 85 83 79 75 70 87
MDB300 /DRD 86 87 88 87 85 81 77 72 89
MDB400 D/DR 87 88 89 88 86 82 78 73 90
MDB500 D/DR 93 94 95 94 92 88 84 79 96
Remark
All sound power level are measured under ISO3741 Standard.
** A is the overall sound power level in dBA
The spectrum data is non-A-weighted sound power level
40
Operating Range
Ensure the operating temperature is in allowable range.
Cooling only
Cooling
54
HIGH AMBIENT
Caution :
UNIT
46
Outdoor temp. (°CDB)
-5
15 24
Indoor temp. (°CWB)
Heat pump
Heating Cooling
54
18 HIGH AMBIENT
UNIT
46
Outdoor temp. (°CWB)
35
STD
6
STD
19
LOW AMBIENT
KIT
-9
-5
15 21 27 15 24
Indoor temp. (°CDB) Indoor temp. (°CWB)
41
Drive Package Selection Example
For MDB250D2, given conditions :
Supply Air Quantity = 8,000 CFM
External Static Pressure = 0.8 in. wg.
Step 1: Find the velocity pressure (Hd).
From blower performance curve of ADB250D2,
The velocity pressure at 8,000 CFM supply air = 0.55 in. wg.
Step 2: Find total external static pressure (Ht).
Total external static pressure
= External static pressure + Velocity pressure (Hd)
= 0.8 in. wg. + 0.55 in.wg.
= 1.35 in. wg.
Step 3: Find fan operating speed and brake kW
Read from blower performance curve of MDB250D2,
a) Fan speed = 725 RPM
b) Brake kW = 2.75 kW
c) Fan efficiency = 72.4 %
d) Motor kW = Brake kW x Safety factor (1.2)
= 2.75 kW x 1.2
= 3.3 kW
≅ 4.0 kW
Step 4: Assuming change motor pulley only. Calculate motor pulley diameter (X).
X = [ Blower speed (RPM) x Blower pulley diameter (in) ] / Motor speed (RPM)
Fix blower pulley diameter = 12 in
Read from Motor and Blower Specifications table,
a) Motor speed = 1440 RPM
b) X = [ 725 x 12 ] / 1440
= 6.04 in
∴Choose 6.5” ( the next pulley size which is bigger than 6.04”)
Step 5: Calculate V-belt size.
Read from Motor and Blower Specifications table,
A = Motor to blower centre point ( 623 mm ) x 2 = 1,246 mm
B = Motor pulley diameter ( 6.5” or 165.1 mm ) + Blower pulley diameter ( 12” or 304.8 mm)
= 469.9 mm
Belt size = A + B × pi / 2
= 1984.1 mm or 78.1 in
≅ 78 in
Summary
i) Fan Motor kW = 4kW
ii) Motor Pulley Diameter = 6.5 in
iii) V-Belt Size = 78 in
43
MOTOR AND BLOWER DESIGN SPECIFICATIONS FOR 50HZ MODELS
NO DESCRIPTION UNIT MDB125D/DR MDB150D/DR1/2 MDB200D/DR2 MDB250D/DR2 MDB300D/DR2 MDB400D/DR4 MDB500D/DR4
1 MOTOR
Output kW 1.5 1.5 3.0 4.0 5.5 7.5 11.0
HP 2.0 2.0 4.0 5.5 7.5 10.0 15.0
Rotation rpm 1425 1425 1430 1440 1445 1445 1450
Rated Current at 415V/3PH/50Hz A 3.39 3.39 6.15 8.00 10.90 14.40 20.70
Pulley Size mm 1SPZ85 1SPZ85 2SPZ75 2SPZ95 2SPZ132 2SPZ140 3SPA125
Shaft Size mm 24 24 28 28 38 38 42
2 Blower Pulley Size mm 1SPZ160 1SPZ160 2SPZ125 2SPZ180 2SPZ250 2SPZ315 3SPA250
Blower Shaft Size mm 25 25 25 25 25 35 35
3 Air Flow CFM 3,750 4,500 6,000 7,500 9,000 12,000 15,000
L/sec 1,770 2,124 2,832 3,540 4,248 5,664 7,080
4 Motor to Blower Centre Point mm 180 180 515 580 615 780 820
Horinzontal Air Discharge V-Belt Size mm SPZ760 SPZ760 SPZ1362 SPZ1600 SPZ1850 SPZ2287 SPA2240
5 Motor to Blower Centre Point mm NIL NIL 410 480 495 630 650
Vertical Air Discharge V-Belt Size mm NIL NIL SPZ1150 SPZ1400 SPZ1600 SPZ1987 SPA1900
6 V-Belt Brand mm BANDO BANDO BANDO BANDO BANDO BANDO BANDO
7 Design rpm 741 746 777 688 707 583 660
8 Selected rpm 757 757 858 760 762 642 725
9 Blower Wheel Model AT15-15S AT15-15S AT15-15S AT18-18S AT18-18S AT22-22TIC AT22-22TIC
10 Coil Velocity FPM 388 391 389 392 393 385 385
11 External Static inch 0.60 0.60 0.60 0.80 0.80 0.80 1.00
mm 15.24 15.24 15.24 20.32 20.32 20.32 25.40
Pa 150 150 150 200 200 200 250
44
Blower Performance Curves
45
BLOWER PERFORMANCE CURVE
MDB 100D
46
BLOWER PERFORMANCE CURVES
47
BLOWER PERFORMANCE CURVES
48
Outlines And Dimensions (Indoor)
Model: MDB 075D/DR
NOTE :
1) WITH TORIN BLOWER
2) WITH U1.4 CCT SLM EC CONTROLLER
3) FOR LOCAL AND EXPORT SPEC.
NOTE :
1) WITH TORIN BLOWER
2) WITH U1.4 CCT SLM EC CONTROLLER
3) FOR LOCAL AND EXPORT SPEC.
49
Model : MDB 125D/DR
NOTE :
1) WITH TORIN BLOWER
4) WITH C3.0B CC SLM EC CONTROLLER
5) FOR LOCAL AND EXPORT SPEC.
NOTE :
1) WITH TORIN BLOWER
2) WITH C3.0B CC SLM EC CONTROLLER
3) FOR LOCAL AND EXPORT SPEC.
50
Model : MDB 150D2/DR2
NOTE :
1) WITH TORIN BLOWER
2) WITH SEQUENTIAL CONTROLLER
3) FOR LOCAL AND EXPORT SPEC.
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL DISCHARGE
51
Model : MDB 250D2/DR2
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
52
Model : MDB 400D4/DR4
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
53
Outlines And Dimensions (Outdoor)
Model : MMC 075/100 D/DR
54
Model : MMC 150 D/DR
55
Wiring Diagrams (Cooling)
Cooling Unit
Model : MDB 075D vs MMC075D (WITH U1.4 MAINBOARD AND SLM3 HANDSET)
Model : MDB 100D vs MMC100D (WITH U1.4 MAINBOARD AND SLM3 HANDSET)
56
Model : MDB 125D vs. MMC 125D (WITH C3.0B MAINBOARD AND SLM HANDSET)
Model : MDB 150D vs. MMC 150D (WITH C3.0B MAINBOARD AND SLM HANDSET)
57
Model : MDB 150D2 vs. MMC 075D x 2
MDB 200D2 vs. MMC 100D x 2 WITH SEQUENTIAL CONTROLLER
MDB 250D2 vs. MMC 125D x 2
58
Model : MDB 400D4 vs. MMC 100D x 4
MDB 500D4 vs. MMC 125D x 4 WITH SEQUENTIAL CONTROLLER
59
Wiring Diagrams (Heatpump)
(Heatpump)
Model : MDB 075DR vs. MMC 075DR (WITH U1.4 / SLM3 HANDSET)
Model : MDB 100DR vs. MMC 100DR (WITH U1.4 / SLM3 HANDSET)
60
Model : MDB 125DR vs. MMC 125DR (WITH C3.0B / SLM)
61
Model : MDB 150DR2 vs. MMC 075DR x 2
MDB 200DR2 vs. MMC 100DR x 2 WITH SEQUENTIAL CONTROLLER
MDB 250DR2 vs. MMC 125DR x 2
62
Model : MDB 400DR4 vs. MMC 100DR x 4
MDB 500DR4 vs. MMC 125DR x 4 WITH SEQUENTIAL CONTROLLER
63
Refrigerant Circuit Diagram
Model : MMC 075DR/100DR/125DR/150DR (R22)
M4MC 075DR/100DR/125DR/150DR (R407C)
64
Installation (indoor)
Preliminary Site Survey
a) Electrical supply and installation is to confirm to local authority’s (e.g. National Electricity Board) codes
and regulations.
b) Voltage supply fluctuation must not exceed +/- 10% of rated voltage. Electricity supply line must be
independent of welding transformers which can cause supply fluctuation.
c) Ensure that the location is convenient for wiring and piping.
Mounting
a) For ceiling mounted models, locate a position where piping and ducting work can be kept to a minimum.
Ensure that overhead supports are strong enough to hold the unit’s weight. Position hanger rods and
check for alignment with the unit. Check that hangers are secure and that the base of fan-coil unit is level
in two horizontal directions.
Pipings
Do not use contaminated or damaged copper tubings. If pipings, evaporator or condenser are exposed or
had been opened for 15 seconds or more, vacuum and purge with field supplied refrigerant. Generally, do
not remove plastic/rubber plugs/caps from fittings, tubings and coils until ready to connect suction or liquid
line into fittings.
Operational Check
After all electrical wiring is completed and the system is charged with refrigerant, make sure unit is operating
properly. Check that:
a) Condenser fans are running, with warm air blowing off the condenser coil.
b) Evaporator blowers are running and discharging cool air.
c) Suction line inside condensing unit feels cool.
d) Liquid line inside condensing unit feels warm.
Electrical Connection
As wiring regulations differ from country to country, please refer to your LOCAL ELECTRICAL CODES for
field wiring regulations and ensure that these are complied with. Besides, observe the following general
precautions:
a) Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring
work.
b) Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit
breaker for over-current protection should be provided in the exclusive line.
c) The unit must be GROUNDED to prevent possible hazard due to insulation failure.
d) All wiring must be firmly connected.
e) Electrical wiring must not touch the refrigerant piping, compressor and any moving parts of the fan
motors.
65
Installation (Outdoor)
Location For Installation Of The Condensing Units
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve
maximum cooling capacity, the location selected should fulfill the following requirements:-
a) Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit cannot be
drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the
unit.
b) Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacle which block air
intake or discharge.
c) The location must be well ventilated, so that the unit can draw and distribute plenty of air thus lowering
the condensing temperature.
d) A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.
e) A place protected from direct sunlight. Otherwise use an awning for protection, if necessary.
f) A place where the hot air discharge and operating sound level will not annoy the neighbors.
g) The location must not be susceptible to dust or oil mist.
CAUTION:If the condensing unit is operated in an atmosphere containing oils (including machine
oils), salt (coastal area), sulphide gas (near hot spring, oil refinery plant), such substances
may lead to failure of the unit.
66
Field Piping
To ensure satisfactory operation and performance, the following points should be noted for the field piping
arrangements of the complete refrigerant cycle.
a) Liquid loops or oil traps must be provided according to the position of the outdoor and the indoor units (depending on
whether the indoor unit is above or below the outdoor unit).
b) Field supplied filter dryer should be provided as close to the expansion valve(s) of the indoor unit (evaporator) as
possible.
c) Field supplied sight glass must be assembled and mounted as shown in the figure.
Always choose the shortest piping path and follow the recommendations as shown below :
CAUTION:
1) Our guarantee on the performance of our air-conditioners is strictly revoked if the height, length and/or the
number of bends of the refrigerant piping system installed is beyond the limit above.
2) Bendings must be carefully made so as not to crush the pipe. Use a pipe bender to bend a pipe as far as
possible.
Installation Clearance
A) For MMC – D/DR series (Single/Multiple Condensing Unit)
When two or more outdoor units are installed in a location, they must be positioned such that one unit will not be taking
the hot discharge air from another to avoid hot air short circuiting.
This also applies when two or more units are installed one above the other. Below are the installation clearance
guidelines :
2x 3x 4x
Model MMC 075/100/125/150 D/DR
MMC 075/100/125/150 D/DR MMC 075/100/125/150 D/DR MMC 075/100/125/150 D/DR
A (mm) 300 600 600 600
B (mm) 1000 1000 1000 1000
C (mm) 1500 1500 2000 2000
67
SERVICE
PANEL
INSTALLATION CLEARANCE
Vacuuming
After the system pipings are properly connected, connect the
flexible hoses to the correct charging nipples as shown in the
diagrams. Ensure that flexible hose from charging nipples are
connected to vacuum pump via standard servicing valves and
pressure gauges (gauge manifold). Vacuum the air conditioner
system to at least 500 microns Hg.
Charging
Before charging, the vacuum must be held at 500 microns Hg
for at least 15 minutes, then break vacuum by charging R-22
refrigerant. Operate the unit for 15 minutes and ensure that
refrigerant charges is of correct quantity by monitoring running
current and suction and liquid line pressures. Suction and
discharge pipe pressures should be in the region of 75 psig
and 275 psig generally.
68
Guidelines Of Field-Charging Air Conditioning Systems With Copeland Scroll
Compressors
These guidelines are intended for use with Copeland Scroll compressors only with R22, R407C, R134a,
R404A, R507, and R410A refrigerants. They do not apply to Copeland reciprocating compressors or
competitive Scroll compressors.
Other typical field charging problems include undercharging, overcharging, moisture or air in the system etc.
In time each one of these problems can cause compressor failure.
Equipment
Minimal equipment is required for field charging. The minimum equipment required to do a satisfactory job
is:-
Set of service gauges
Hoses
Vacuum pump
Vacuum gauge
Scales
Thermometer
Charging Hoses
Most field-charging is done using standard service hoses. Hoses are made in different colors with different
working pressures and with different leak rates but the most important point is the presence or absence of
Shredder valve depressors. Shredder valve depressors severely restrict the flow through the service hoses.
This slows evacuation and vapor charging dramatically. In most cases the Shredder depressor can be
removed but it is simpler to have one set of hoses with and one set without Shredder depressors.
Hose with Shredder valve Depressor Hose without Shredder valve Depressor
Hose selection is important depending whether the system is being evacuated or charged. Charging liquid
from the cylinder into the liquid line should be carried out using an open hose connected to an unrestricted
fitting. This will reduce charging time.
69
Typical service valves found on the Shredder Valves
outdoor unit
Shredder core
Shredder valves provide easy system access for pressure reading and addition of refrigerant. On small
systems, they provide a reasonable connection for evacuation also. However, Shredder valves and the
hoses connected to them can cause very severe pressure drops and can multiply evacuation time by a factor
of 4 or 5.
On the positive side, Shredder valves provide a restriction that slows the speed of liquid charging into the
suction side. When a pressure drop is desirable (charging liquid into suction), connect via a Shredder valve.
When a pressure drop is detrimental (evacuation), connect via an open fitting.
If the installer cannot find the correct charge but the system must be started, refrigerant should be carefully
added to the system until reasonable sub-cooling is measured in the liquid line and reasonable suction
superheat is measured at the compressor suction. Suction and discharge pressures must be monitored
carefully during the charging process.
Charge Limits
Copeland Scroll compressors have the different charge limits for different compressor models as shown in
table below. If the total charge exceeds these limits, the system should have a crankcase heater and/or
pump down cycle and/or accumulator to prevent liquid damage to the compressor. Some systems may
require accumulators to limit liquid floodback even though the charge is lower than the published limit.
Turn the refrigerant cylinder upside down, purge the charging hose and charge liquid through the liquid line
charging port until refrigerant no longer flows or until the correct charge has been weighed in. If additional
charge is required start the system and slowly bleed liquid into the suction side until the system is full.
70
Electronic Vacuum Gauge
Copeland recommends charging liquid in a CONTROLLED manner into the suction side until the
system is full. This recommendation does not hold true for reciprocating compressors where liquid charging
into the suction side could cause severe damage.
Carefully monitor the suction and discharge pressures – ensure that the suction pressure does not fall below
25 psig (1.7 bar) at any time during the charging process.
CAUTION: Manifold Gauge will show cylinder pressure rather than suction pressure if the cylinder valve and
Manifold valve “A” are both open.
There are many ways of charging liquid in a “controlled manner” into the
suction side:-
1. Use valve A on the manifold gauge set
2. Use the valve on the refrigerant cylinder
3. Charge through a Shredder valve
4. Use a hose with a Shredder valve depressor
5. Charge into the suction side at some distance from the compressor.
6. All of the above
A
Charging Procedures - Three phase compressors
The fundamental procedure is the same as for single phase models but the compressor can run in the wrong
direction on starting. If this happens reverse any two phases and start again. Short term reverse rotation will
not damage the compressor.
As compressors get larger the importance of correct field charging procedures grows exponentially.
Unfortunately larger systems are often field charged which leads to many infant failures. All Specter
compressors have internal discharge temperature protectors which are very effective in preventing
dangerously high discharge temperatures during charging. The protection module will trip and lock the
compressor out for 30 minutes. It is not normally necessary to wait 30 minutes for the module to reset. When
the compressor has cooled down the module can be reset by breaking the power supply to the control circuit.
Very often the serviceman does not understand why the module tripped and uses a jumper wire to bypass it.
He continues to charge the system and removes the jumper when charging is complete. The compressor
may or may not run with the protector back in the circuit but it is certain that the compressor has been
damaged and premature failure is inevitable.
71
NEVER JUMPER MOTOR PROTECTORS – there is always a reason for a protector trip.
Additional charge
Based on liquid pipe size per meter length:
Liquid Pipe Size, inch Additional Charge, kg/meter
1/4” 0.02
5/16” 0.04
3/8” 0.05
1/2” 0.10
5/8” 0.17
3/4” 0.26
7/8” 0.37
Note: Refer to the table of the Recommended Maximum Pipe Length.
72
Special Precautions For R407c
Special Precautions When Dealing With Refrigerant R407C Unit
2) Components
Mixture weight composition R32(23%), R125(25%), R134a(52%)
3) Characteristic
• R407C liquid and vapor components have different compositions when the fluid evaporates or condenses. Hence,
when leak occurs and only vapor leaks out, the composition of the refrigerant mixture left in the system will change
and subsequently affect the system performance. DO NOT add new refrigerant to leaked system. It is
recommended that the system should be evacuated thoroughly before recharging with R407C.
• When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous or liquid phase.
Hence when charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to make
certain that only original composition of R407C is being charged into the system.
• POE oil is used as lubricant for R407C compressor, which is different from the mineral oil used for R22 compressor.
Extra precaution must be taken not to expose the R407C system too long to moist air.
a) Filter-dryer must be installed along the liquid line for all R407C air conditioners. This is to minimise the
contamination of moisture and dirt in the refrigerant system. Filter-dryer must be of molecular sieve type. For a
heat-pump system, install a two-way flow filter dryer along the liquid line.
b) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to moist air.
Residual POE oil in the piping and components can absorb moisture from the air.
73
c) Ensure that the compressor is not expose to open air for more than the recommended time specified by
its manufacturer (typically less than 10 minutes). Removed the seal-plugs only when the compressor is
about to be brazed.
d) The system should be thoroughly vacuumed to 1.0 Pa (-700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
e) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.
R32/R125/R134
f) Normally, the R407C cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However, if
the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.
Invert cylinder
Dip-pipe
without dip-pipe
Liquid
withdrawal
g) When servicing leak, the top-up method, commonly practiced for R22 system, is not recommended for
R407C system. Unlike R22 where the refrigerant is of a single component, the composition of R407C,
which made-up of three different components, may have changed during the leak. Consequently, a
top-up may not ensure that the R407C in the system is of original composition. This composition shift
may adversely affect the system performance. It is recommended that the system should be evacuated
thoroughly before recharging with R407C.
74
Servicing And Maintenance
The design concept of the Condensing Unit is such that all servicing can be done from the front and side of the unit.
Upon removal of front and side panel, all the electrical "terminal box", fan and motor assembly and compressor are easily
accessible.
Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surfaces once
quarterly. However, if a unit is installed in area subjected to much oil, mist and dust, the coil must be regularly cleaned by
qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and proper operation. Otherwise, the
systems life span might be shortened.
CAUTION
When the compressor is to be stopped for a long time, the crankcase heater should be energized for at least
6 hours before start of operation.
Do not charge OXYGEN, ACETYLENE or other flammable and poisonous gases into the refrigeration cycle
when performing a leakage test or an airtight-test. These types of gases are extremely dangerous, because
explosion can occur.
It is recommended that nitrogen or refrigerant be charged for these types of tests.
The air conditioner must not re-start within 3 minutes after shutdown. (These models are equipped with a crankcase
heater with the compressor).
Make sure the air conditioner is properly grounded by checking the ground terminal.
MAINTENANCE
For superb performance and lasting durability, please do not forget to conduct proper and regular maintenance.
75
Operation
Electrical Connection
Wiring regulations about wire diameter differs from country to country. Please refer to your LOCAL
ELECTRICAL CODES for field wiring rules. Be sure that installation comply with such rules and regulations.
General Precaution
Ensure that the rated voltage of the unit correspond to the name plate before carrying out proper wiring
according to the wiring diagram.
Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit breaker
for over-current protection should be provided in the exclusive line.
The unit must be GROUNDED to prevent possible hazard due to insulation failures
Every wiring must be firmly connected.
Every wiring should not touch the refrigerant piping, compressor and any moving parts of fan motor.
Operational Check
After all wiring is completed and the system is charged with refrigerant, make sure the unit is operating
properly. Check that :-
Condenser fans are running with warm air blowing off the condensing unit.
Evaporator blowers are running and discharging cool air from ducts.
Suction line and liquid line pressures are in the region of 75 psig and 275 psig respectively.
(OPTIONAL)
(OPTIONAL)
76
Sequential Controller LCD Operating Instructions
(Standard for cooling and heatpump units)
1. Sequential controller LCD display
A : Time display
B : Error indication
C : Compressor running display (up to 4
compressors)
D : Key lock display
E : Heater display (up to 2 heaters)
F : Energy saving mode display
G : Compressor defrost cycle display (up to
4 compressors)
H : Operation mode display
I : Temperature set display
2. Operating Guide
2.1 ON/OFF key
Press once to start the air conditioning unit.
Press again to stop the unit.
The operation lamp next to the key lights up and goes off respectively when the unit is running
or not running.
Caution : In the case when the ON/OFF key is pressed immediately after the operation is
stopped, the unit will not restart until 3 minutes later to protect the compressor.
77
7-days timer
Press the ON TIMER key to activate auto-ON timer mode. Under this mode, press the respective
MINUTE, HOUR and DAY key to select the time of the week when the air-conditioning unit is to
automatically start running. Press the ON TIMER key again to save the setting.
Press the OFF TIMER key to activate auto-OFF timer mode. Under this mode, press the respective
MINUTE, HOUR and DAY key to select the time of the week when the air-conditioning unit is to
automatically stop running. Press the ON TIMER key again to save the setting.
Then to activate the 7-days timer, press and hold the TIMER ACTIVE key until the word "TIMER
ACTIVE" appears on the LCD screen. Repeat the same step to disable the 7-days timer.
Test run
Press the TEST key 2 times consecutively to test run the unit.
3. Error Code
When the system is on and an error occurs, the ON/OFF LED on the LCD panel will blink and an error
code is shown. When the system is off and there is a thermistor error, the ON/OFF LED is off but the
error code is still displayed. Each error code represents different message as below
Error Error
code Possible fault code Possible fault
E01 Require manual reset (possible causes) E19 Indoor coil sensor 4 short
E02 Compressor 1 high temperature (overload) E20 Indoor coil sensor 1 open
E03 Compressor 2 high temperature(overload) E21 Indoor coil sensor 2 open
E04 Compressor 3 high temperature(overload) E22 Indoor coil sensor 3 open
E05 Compressor 4 high temperature(overload) E23 Indoor coil sensor 4 open
E06 Compressor 1 high pressure trip / contact open E24 Outdoor coil sensor 1 short
E07 Compressor 2 high pressure trip / contact open E25 Outdoor coil sensor 2 short
E08 Compressor 3 high pressure trip / contact open E26 Outdoor coil sensor 3 short
E09 Compressor 4 high pressure trip / contact open E27 Outdoor coil sensor 4 short
E10 Compressor 1 trip / low R-22 / outdoor abnormal E28 Outdoor coil sensor 1 open
E11 Compressor 2 trip / low R-22 / outdoor abnormal E29 Outdoor coil sensor 2 open
E12 Compressor 3 trip / low R-22 / outdoor abnormal E30 Outdoor coil sensor 3 open
E13 Compressor 4 trip / low R-22 / outdoor abnormal E31 Outdoor coil sensor 4 open
E14 Room sensor short E32 Compressor 1 de-ice
E15 Room sensor open E33 Compressor 2 de-ice
E16 Indoor coil sensor 1 short E34 Compressor 3 de-ice
E17 Indoor coil sensor 2 short E35 Compressor 4 de-ice
E18 Indoor coil sensor 3 short
78
ii) Fix the bottom case onto the wall with the 2 wooden screws provided. Then, insert the 4 connecting
wires (from the main board) through the slot on the lower right.
iii) Connect one end in each of the 4 wires to the terminal block behind the top case as shown below.
The wire that goes into the "GND" terminal at the top case must be connected at the other end to the
“GND" terminal at the main board. The same goes for the "+5V", "B" and "A" connection.
iv) Fasten back the top and bottom case into place. Hook the two upper claws into their respective slots
and snap the lower part shut.
Note : * Cooling or heater model depending on SW1 and SW2 setting. Factory setting for number of
compressor is based on air conditioner models.
2. Number of Heater
Number of Heater SW1(dip1) SW2(dip2)
a. No heater (0 heater) off off
b. 1 heater on off
c. 2 heaters on / off on
79
3. Auto Mode Selection
SW5(dip 5)
a. Auto mode off off
b. Auto mode on on
note that 1.5°C only valid for 2 and 3 compressors model. For 4 compressors model, maximum allowed is
1.0°C.
The default differential temperature is base on number of compressor model, the setting is as below :
Model Diff. Temperature
1 compressor Not applicable
2 compressor 1.5°C
3 compressor 1.0°C
4 compressors 0.5°C
Dip switch 6
a. Fan off off
b. Fan on on
6. Operating Modes
The system has 4 operating modes to select with respect to each model selection:
JH1 Setting
a. Last memory backup JH1 Plugged
b. Without last memory backup JH1 Removed
80
8. Sequential Control For Cool Mode
The starting sequence for indoor fan, outdoor fan and compressors is shown as below:
2 seconds
Start Indoor fan
15 seconds 2 seconds
outdoor fan 1 compressor 1*
15 seconds 2 seconds
outdoor fan 2 compressor 2*
15 seconds 2 seconds
outdoor fan 3 compressor 3*
15 seconds 2 seconds
outdoor fan 4 compressor 4*
2 seconds 2 seconds
Start Indoor fan all 4 way valves
15 seconds 2 seconds
outdoor fan 1 compressor 1*
15 seconds 2 seconds
outdoor fan 2 compressor 2*
15 seconds 2 seconds
outdoor fan 3 compressor 3*
15 seconds 2 seconds 15 seconds 15 seconds
outdoor fan 4 compressor 4* Heater 1* Heater 2*
The compressors will be turned on one by one depending on the on/off conditions shown in the above.
Troubleshooting
When any air conditioner malfunction is noted, immediately switch off the power supply to the unit and
contact the local dealer, if necessary. Some simple trouble shooting tips are given below :
81
The following charts are efficient checking procedures for troubleshooting when these fan-coil units are
combined with condensing units with the unit standard wiring. For dual circuited models, perform the
procedures for each.
No Cooling
Stop
Evaporator
Fan Motor
Faulty No Voltage or Low Voltage Get the Right Voltage
Unit Power
Supply Repair the Power
Single-Phase
Line
Condenser Stop
Fan Motor
Tripped
Overcurrent High Voltage or Low Voltage Get The Right Voltage
Relay For
Condenser Fan Single-Phase Check The Power Supply To The
Motor : Repair Connections When
Necessary
Running
Faulty Coil Burnt Change The Contactor
Condenser Fan
Contactor
Contact Faulty Change The Contacts
82
Insufficient Cooling
Insufficient Cooling
Cycling On
Compressor
Cycling
High Discharge Pressure or Low See "High Discharge Pressure" or
Tripping Suction Pressure "Low Suction Pressure"
Dual Pressure
Switch Clogged Capillary or Pressure Repair Clogging and Replace
Switch The Switch If Required
Running Overcurrent Tripping High Voltage or Low Voltage Get The Right Voltage
Relay For
Compressor Check The Power Line To The
Single-Phase
Compressor : Repair When Necessary
High Discharge Pressure And See "High Discharge Pressure"
High Suction Pressure or "High Suction Pressure"
Loose Connections Tighten The Connections
See "High Discharge
Discharge Gas Tripping High Discharge Pressure And
Pressure" or "Low Suction
Thermostat or Low Suction Pressure
Pressure"
Internal
Thermostat Refrigerant Short Charge or Add Refrigerant. Repair
Refrigerant Leakage Leakage If Detected.
See "High Suction
High Suction Pressure
Pressure"
High Discharge
Pressure
Restricted
Condenser Clogged Condenser Coil Clean The Condenser
Air Flow
Check The Voltage
Low Fan Speed And Get The Right
Voltage
Check The System
Malfunction Of Fan Cycling
And Repair If
High System
Condenser Required
Secure Space For
Air Inlet Circulating Air Flow
Required Air Flow
Temperature
Overcharged Refrigerant Purge The Refrigerant
Low Discharge
Pressure
Excessive
Condenser Malfunction Of Fan Cycling Check The System And Repair The
Air Flow System Components If Required
83
High Suction Pressure
High Suction
Pressure
Evaporator Low
Air Inlet Excessive Fresh Air Intake Reduce The Fresh Air Intake
Temperature
Insufficient Duct Insulation Reinforce The Duct Insulation
Noisy Operation
Noisy Operation
Noisy
Compressor
Shipping Noisy
Unremoved Shipping Bolt(s) Remove The Bolt(s)
Bolt(s)
Overcharged Refrigerant Purge The Refrigerant
Liquid
Refrigerant Low Suction Pressure See "Low Suction Pressure"
Backing Up
Worn Compressor Parts Replace Or Repair The Compressor
Evaporator Noisy
Knocking Runner Fix The Runner Or Casing Properly
Fan
Worn Bearing Change The Bearing
Strainer
Whistling
Liquid Line Noisy Partially Clogged Clean The Dryer
84
Parts List
Model : MDB075D
1 ASSY, BASE PAN COVER INS. 18 ASSY, SIDE PANEL BIG RIGHT INS.
2 ASSY, BASE PAN INS. 19 ASSY, TOP PANEL INS.
3 ASSY, FRONT PANEL INS. 20 ASSY, SECTION FILTER
4 ASSY, FLANGE BLOWER 21 ASSY, TERMINAL BOX
5 ASSY, BLOWER 22 SCREW, S.T. TRUSS HEAD PHILIP
6 GROMET, MNTG COMPLETE WITH NUT 23 SCREW, SELF TAPPING PAN HEAD
7 ASSY, BRACKET FAN MOTOR 24 SCREW, TRUSS HEAD PHILIP
8 MOTOR 25 NUT, WELD M5
9 CAPACITOR, 6 uF/440V 26 SCREW, WOOD
10 CLAMP, CAPACITOR 27 WASHER, PLAIN
11 SUPPORT, BLOWER BRACKET 28 WASHER, PLAIN
12 ASSY, DRAIN PAN INS. 29 WASHER, SPRING
13 ASSY, COIL TUBING 30 WASHER, SPRING
14 ASSY, COIL SIDE COVER RIGHT INS. 31 BOLT, HEXAGON PAN HEAD
15 ASSY, COIL SIDE COVER LEFT INS. 32 NUT, HEXAGON
16 ASSY, SIDE PANEL LEFT INS. 33 NUT, HEXAGON
17 ASSY, SIDE PANEL SML RIGHT INS.
85
Model : MDB100D
1 ASSY, BASE PAN COVER INS. 18 ASSY, SIDE PANEL BIG RIGHT INS.
2 ASSY, BASE PAN INS. 19 ASSY, TOP PANEL INS.
3 ASSY, FRONT PANEL INS. 20 ASSY, SECTION FILTER
4 ASSY, FLANGE BLOWER 21 ASSY, TERMINAL BOX
5 ASSY, BLOWER 22 SCREW, S.T. TRUSS HEAD PHILIP
6 GROMET, MNTG COMPLETE WITH NUT 23 SCREW, SELF TAPPING PAN HEAD
7 ASSY, BRACKET FAN MOTOR 24 SCREW, TRUSS HEAD PHILIP
8 MOTOR 25 NUT, WELD M5
9 CAPACITOR, 7.5 uF/440V 26 SCREW, WOOD
10 CLAMP, CAPACITOR 27 WASHER, PLAIN
11 SUPPORT, BLOWER BRACKET 28 WASHER, PLAIN
12 ASSY, DRAIN PAN INS. 29 WASHER, SPRING
13 ASSY, COIL TUBING 30 WASHER, SPRING
14 ASSY, COIL SIDE COVER RIGHT INS. 31 BOLT, HEXAGON PAN HEAD
15 ASSY, COIL SIDE COVER LEFT INS. 32 NUT, HEXAGON
16 ASSY, SIDE PANEL LEFT INS. 33 NUT, HEXAGON
17 ASSY, SIDE PANEL SML RIGHT INS.
86
Model : MDB125D
NOTE :
WITH CONTACTOR
87
Model : MDB150D
NOTE :
WITH CONTACTOR
88
Model : MDB150D2
NOTE :
WITH CONTACTOR
89
Model : MDB200D2 (VERTICAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
90
Model : MDB200D2 (HORIZONTAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
91
Model : MDB250D2 (VERTICAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
92
Model : MDB250D2 (HORIZONTAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
93
Model : MDB300D2 (VERTICAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
94
Model : MDB300D2 (HORIZONTAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
95
Model : MDB400D4 (VERTICAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
96
Model : MDB400D4 (HORIZONTAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
97
Model : MDB500D4 (VERTICAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
98
Model : MDB500D4 (HORIZONTAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
99
Model : MDB075DR
1 ASSY, BASE PAN COVER INS. 18 ASSY, SIDE PANEL BIG RIGHT INS.
2 ASSY, BASE PAN INS. 19 ASSY, TOP PANEL INS.
3 ASSY, FRONT PANEL INS. 20 ASSY, SECTION FILTER
4 ASSY, FLANGE BLOWER 21 ASSY, TERMINAL BOX
5 ASSY, BLOWER 22 SCREW, S.T. TRUSS HEAD PHILIP
6 GROMET, MNTG COMPLETE WITH NUT 23 SCREW, SELF TAPPING PAN HEAD
7 ASSY, BRACKET FAN MOTOR 24 SCREW, TRUSS HEAD PHILIP
8 MOTOR 25 NUT, WELD M5
9 CAPACITOR, 6 uF/440V 26 SCREW, WOOD
10 CLAMP, CAPACITOR 27 WASHER, PLAIN
11 SUPPORT, BLOWER BRACKET 28 WASHER, PLAIN
12 ASSY, DRAIN PAN INS. 29 WASHER, SPRING
13 ASSY, COIL TUBING 30 WASHER, SPRING
14 ASSY, COIL SIDE COVER RIGHT INS. 31 BOLT, HEXAGON PAN HEAD
15 ASSY, COIL SIDE COVER LEFT INS. 32 NUT, HEXAGON
16 ASSY, SIDE PANEL LEFT INS. 33 NUT, HEXAGON
17 ASSY, SIDE PANEL SML RIGHT INS.
100
Model : MDB100DR
1 ASSY, BASE PAN COVER INS. 18 ASSY, SIDE PANEL BIG RIGHT INS.
2 ASSY, BASE PAN INS. 19 ASSY, TOP PANEL INS.
3 ASSY, FRONT PANEL INS. 20 ASSY, SECTION FILTER
4 ASSY, FLANGE BLOWER 21 ASSY, TERMINAL BOX
5 ASSY, BLOWER 22 SCREW, S.T. TRUSS HEAD PHILIP
6 GROMET, MNTG COMPLETE WITH NUT 23 SCREW, SELF TAPPING PAN HEAD
7 ASSY, BRACKET FAN MOTOR 24 SCREW, TRUSS HEAD PHILIP
8 MOTOR 25 NUT, WELD M5
9 CAPACITOR, 7.5 uF/440V 26 SCREW, WOOD
10 CLAMP, CAPACITOR 27 WASHER, PLAIN
11 SUPPORT, BLOWER BRACKET 28 WASHER, PLAIN
12 ASSY, DRAIN PAN INS. 29 WASHER, SPRING
13 ASSY, COIL TUBING 30 WASHER, SPRING
14 ASSY, COIL SIDE COVER RIGHT INS. 31 BOLT, HEXAGON PAN HEAD
15 ASSY, COIL SIDE COVER LEFT INS. 32 NUT, HEXAGON
16 ASSY, SIDE PANEL LEFT INS. 33 NUT, HEXAGON
17 ASSY, SIDE PANEL SML RIGHT INS.
101
Model : MDB125DR
NOTE :
WITH CONTACTOR
102
Model : MDB150DR
NOTE :
WITH CONTACTOR
103
Model : MDB150DR2
NOTE :
WITH CONTACTOR
104
Model : MDB200DR2 (VERTICAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
105
Model : MDB200DR2 (HORIZONTAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
106
Model : MDB250DR2 (VERTICAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
107
Model : MDB250DR2 (HORIZONTAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
108
Model : MDB300DR2 (VERTICAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
109
Model : MDB300DR2 (HORIZONTAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
110
Model : MDB400DR4 (VERTICAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
111
Model : MDB400DR4 (HORIZONTAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
112
Model : MDB500DR4 (VERTICAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
113
Model : MDB500DR4 (HORIZONTAL AIR DISCHARGE)
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
114
Model : MMC075DR
115
Model : MMC100DR
116
Model : MMC125DR
117
Model : MMC150DR
118
DOP :
Americas - 13600 Industrial Park Boulevard, P.O. Box 1551, Minneapolis, MINI 55440 USA (612) 553-5330
Asia - Jalan Pengapit 15/19, P.O. Box 7072, 40702 Shah Alam, Selangor Darul Eshan, Malaysia - Tel: 6-03-5594922 - Fax: 6-03-5506980 - Telex: MA 38521
Europe - 42 Cours Jean Jaurès - 17800 Pons - France - Tél: (33) 46 92 33 33 - Télex: 790 536 F - Télecopie: (33) 46 91 38 33