REF Protection
REF Protection
April 2023
White Paper | Restricted Earth Fault Protection (64R) in Resistive Grounded Transformer (Comprehensive
Analysis) | SgurrEnergy- www.sgurrenergy.com
Abstract
Transformer is considered vital equipment in transmission and distribution network. Power
Transformer is typically considered the costliest equipment for any substation/switchyard project
and is expected to serve a lifecycle of 35 years*. Considering the significant cost associated with
power transformers and the relatively long outage time in case of failure of the same equipment,
it is emphasizing the importance of implementing effective protection strategies to prevent or
mitigate such events.
Below listed are the commonly used protections for power transformers†:
Backup over current (50/51) and earth fault (50N/51N) protection.
Differential Protection (87T).
Restricted Earth fault protection (64R).
Thermal overload protection (49).
External Trip function (i.e. Buchholz relay, Pressure Relief Valve etc.).
The protection of power systems and the grounding of electrical equipment are interdependent.
It is important to note that the type of grounding that is chosen for a power system can have a
substantial impact on the selection of the protection scheme.
Power Transformer HV (high voltage) and LV (low voltage) winding can have multiple
configurations like star or delta on either side. With both the windings system grounding can also
have multiple cases such as solid, resistive, reactive or grounding transformer. Each of the
selected configurations has a certain impact on the protection system and the same shall be
ensured in the Design and Engineering phase of the project.
In the case of a power transformer having Delta-Star configuration with resistance or reactance
grounding, whenever in zone line to ground fault occurs at the low voltage (LV) side, certain
difficulties are encountered with regard to the implementation of differential protection. These
challenges include the following:
The magnitude of reflected fault current at the HV side varies with the location of the line
to ground fault at the LV side.
Up to some extent the reflected fault current at the HV side in case of ground fault‡ at LV
side winding, is less compared to the relay setting.
The sensitivity of differential protection is inadequate to ensure complete winding
protection.
This paper aims to examine the aforementioned technical challenges and suggest a mitigation
method.
*
According to CERC (Central Electricity Regulatory Commission) norms.
† We have considered 6MVA, 11/6.6kV as Power Transformer for case study purpose.
‡ ground fault has the meaning Line to Ground fault (in zone) in this paper.
White Paper | Restricted Earth Fault Protection (64R) in Resistive Grounded Transformer (Comprehensive
Analysis) | SgurrEnergy- www.sgurrenergy.com
Problem Statement
In a power system, the transformer is grounded through a resistor, reactor or using grounding
transformer and the single line to ground fault current at the LV side is limited by means of the
type of grounding method utilized. By limiting the ground fault, the transformer differential
protection is not enough sensitive to protect the complete winding as the reflected fault current
varies with fault location and up to some extent reflected current at HV remains below the settled
value.
Background
Consider a Delta-Star transformer with a neutral grounding resistor.
T = Turn Ratio.
White Paper | Restricted Earth Fault Protection (64R) in Resistive Grounded Transformer (Comprehensive
Analysis) | SgurrEnergy- www.sgurrenergy.com
m x V2phase
Fault current If = (4)
R
Where,
Due to the L-G fault at LV winding, the effective turn ratio (Te) of the transformer is computed as:
N
T𝑒 = (N2 ) x m (5)
1
I2Phas m x V2phase
= If = (6)
e R
I1Phase = Te x I2Phase
= m x T x I2Phase
m x V2phase
= mxTx
R
V2phase
I1Phase = m2 x T x (7)
R
From the equation (6) and (7) we can state that:
I2Phase ∝ m
I1Phase ∝ m2
The above equations describe the relationship between HV and LV side currents in a transformer
during a line-to-ground fault in LV winding.
The equations demonstrate that the LV side fault current is directly proportional to the distance
from the neutral, while the HV side fault current is proportional to the square of the distance from
the neutral. This relationship is further illustrated in the below graph.
White Paper | Restricted Earth Fault Protection (64R) in Resistive Grounded Transformer (Comprehensive
Analysis) | SgurrEnergy- www.sgurrenergy.com
1
Fault Current (LV)
0.9
Reflected fault Current at HV
0.8
% of Winding (from neutral)
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
0.1
0.4
0.7
1
0.97
0.13
0.16
0.19
0.22
0.25
0.28
0.31
0.34
0.37
0.43
0.46
0.49
0.52
0.55
0.58
0.61
0.64
0.67
0.73
0.76
0.79
0.82
0.85
0.88
0.91
0.94
% of respective maximum L-G fault current
HV Winding = 11kV
LV Winding = 6.6kV
NGR = 15.877Ω
HV CT ratio = 350/1A
LV CT ratio = 550/1A
White Paper | Restricted Earth Fault Protection (64R) in Resistive Grounded Transformer (Comprehensive
Analysis) | SgurrEnergy- www.sgurrenergy.com
= 6351V
Turn Ratio:
V2phase
T =
V1phase
6351
=
66000
= 0.1667
Using equation number (7), reflected fault current per phase at HV side with 100% winding (m=1):
max. V2phase
I1phase = m2 x T x
R
6351
= 12 x 0.1667 x
15.877
= 66.67A
The reflected fault current on HV side is a function of fault location ‘m’ and can be calculated for
various fault location in transformer winding.
Unprotected
3 0.20 104.97 0.20 7.21 0.040 Region
§
Refer equation (6).
**
Refer equation (7).
White Paper | Restricted Earth Fault Protection (64R) in Resistive Grounded Transformer (Comprehensive
Analysis) | SgurrEnergy- www.sgurrenergy.com
Sr.No. m (%) I2phase (A)§ I2phase / If I1phase (A)** I1phase / I1max
White Paper | Restricted Earth Fault Protection (64R) in Resistive Grounded Transformer (Comprehensive
Analysis) | SgurrEnergy- www.sgurrenergy.com
References
Network protection and Automation Guide by Alstom.
Monograph of IEEEMA articles of Dr. K Rajamani, Rev 05, 2022.
This white paper will help to understand constrains with system grounding selected and mitigation plan to select proper
protection for Power Transformer. This document is prepared only for reference to understand protection system
concept. Intent of this document is not to show any project specific calculation/scheme, which can be utilized directly in
project. We welcome readers to share their observations, suggestions, or queries on our email id specified.
White Paper | Restricted Earth Fault Protection (64R) in Resistive Grounded Transformer (Comprehensive
Analysis) | SgurrEnergy- www.sgurrenergy.com