0% found this document useful (0 votes)
22 views

KGL Battery Calculation191204

This document calculates the battery requirements for a fire alarm system based on the components included. It lists the standby and alarm currents drawn by each component as well as the total for the system. It then calculates the required standby and alarm times based on NFPA 72 standards. From this it determines the minimum required battery capacity is 51AH and recommends selecting a 120AH battery.

Uploaded by

Faruk Hossain
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views

KGL Battery Calculation191204

This document calculates the battery requirements for a fire alarm system based on the components included. It lists the standby and alarm currents drawn by each component as well as the total for the system. It then calculates the required standby and alarm times based on NFPA 72 standards. From this it determines the minimum required battery capacity is 51AH and recommends selecting a 120AH battery.

Uploaded by

Faruk Hossain
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

BATTERY CALCULATION

STANDBY CURRENT TOTAL STANDBY ALARM CURRENT TOTAL ALARM


DESCRIPTION MODEL NO QTY QTY
PER UNIT (AMPS) CURRENT PER ITEM PER UNIT (AMPS) CURRENT PER ITEM
Central processing Unit CPU-3030D 0.340 X 1 = 0.340 0.000 X 1 = 0
Power Supply AMPS-24E 0.130 X 1 = 0.130 0.000 X 1 = 0
Loop Control Module LCM-320 0.130 X 2 = 0.260 0.000 X 2 = 0
Loop Expender Module LEM-320 0.100 X 1 = 0.100 0.000 X 1 = 0
Repeater Panel LCD-160 0.300 X 1 = 0.300 0.325 X 1 = 0.325
Smoke Detector FSP-851 0.0003 X 240 = 0.072 0.0065 X 240 = 1.56
Heat Detector FST-851 0.0003 X 8 = 0.0024 0.0065 X 8 = 0.052
Multi Detector FAPT-851 0.0003 X 222 = 0.0666 0.0065 X 222 = 1.443
Addresable Input Module FMM-1 0.000375 X 62 = 0.02325 0.005 X 62 = 0.31
Addressable Output Module FRM-1 0.0003 X 66 = 0.0198 0.0065 X 66 = 0.429
NAC Circuit FCM-1 0.000485 X 41 = 0.019885 0.0065 X 41 0.2665
Manual Pull Station F/MCP/Glass 0.000385 X 60 = 0.0231 0.0078 X 60 = 0.468
Horn Cum Strobe P2RL 0 X 167 0 0.133 X 167 22.211
TOTAL SYSTEM TOTAL SYSTEM
1.3570 27.0645
STANDBY CURRENT (AMPS) ALARM CURRENT (AMPS)

TOTAL
TOTAL
SYSTEM
REQUIRED STANDBY REQUIRED ALARM SYSTEM REQUIRED ALARM
REQUIRED STANDBY TIME (HRS) STANDB
Prepared for: CAPACITY (AMP- TIME (HOURS) NFPA ALARM CAPACITY (AMP-
NFPA 72-2002 4.4.1.5.3.1 Y
HOURS) 72-2002 4.4.1.5.3.1 CURRENT HOURS)
CURREN
(AMPS)
T (AMPS)

24 X 1.3570 = 32.56884 0.25 X 27.0645 = 6.7661

REQUIRE
D ALARM ADJUSTED BATTERY
REQUIRED STANDBY CAPACITY TOTAL CAPACITY TOTAL CAPACITY SAFETY
Prepared by: CAPACIT CAPACITY (AMP-
(AMP-HOURS) (AMP-HOURS) (AMP-HOURS) FACTOR
Y (AMP- HOURS)
HOURS)

32.56884 + 6.7661 = 39.3350 39.3350 X 120% = 47.201958


Minimum battery capacity 51AH . Select battery 120AH