Chapter 32 Exterior Wall Cladding-IV (Wall Systems in Glass)
Chapter 32 Exterior Wall Cladding-IV (Wall Systems in Glass)
CHAPTER
32 Cladding–IV
(Wall Systems in Glass)
CHAPTER OUTLINE
32.1 GLASS-ALUMINUM CURTAIN WALLS 32.6 ENVIRONMENTAL PERFORMANCE CRITERIA FOR
A GLASS CURTAIN WALL
32.2 ANCHORAGE OF A STICK-BUILT GLASS
CURTAIN WALL TO A STRUCTURE 32.7 OTHER GLASS-ALUMINUM WALL SYSTEMS
32.3 STICK-BUILT GLASS CURTAIN WALL DETAILS 32.8 NONTRADITIONAL GLASS WALLS
Transparency, luminosity, and elegance are the reasons for the popularity of glass walls in
modern architecture. Most glass walls are constructed with aluminum sections to support
the glass. In other words, the glass panes (also called lites) are held within vertical and hori-
zontal aluminum framing members. Therefore, they share some of the characteristics of
their smaller counterparts—the aluminum windows, discussed in Chapter 31. However,
there are many differences between the two: scale, aesthetic character, performance properties,
design, detailing, and installation.
Three commonly used glass-aluminum wall system systems are
• Glass-aluminum curtain walls
• Punched and strip glazing systems
• Storefront systems
The vast majority of contemporary buildings include one or more of these systems in the
same building. The reasons include the unparalleled opportunity provided by them to
obtain the maximum amount of daylight and view, the cost savings compared with other
exterior wall cladding systems, and the recent technological advances in the thermal and
structural performance of glass wall systems.
Of the three systems listed above, the most frequently used and the most complex is the
glass-aluminum curtain wall system, which is presented here in detail. The other two sys-
tems (strip system and storefront system) are discussed to the extent that they differ from
the curtain wall system. Finally, the chapter deals with nontraditional glass wall systems—
systems that do not include aluminum sections to support the glass.
777
Part 2 32.1 GLASS-ALUMINUM CURTAIN WALLS
Materials and Systems
of Construction Because of their common use, glass-aluminum curtain walls (or simply glass curtain walls)
are constantly evolving in their design and performance. Therefore, a succinct classification
that includes all contemporary glass curtain walls is impossible. The American Architec-
tural Manufacturers Association (AAMA), an association of the manufacturers of windows
and curtain walls, however, classifies glass curtain wall systems into five types based on their
anatomy:
• Stick-built (or, simply, stick) systems
• Unitized systems
• Unit and mullion systems
• Panel systems
• Column cover and spandrel systems
These systems are illustrated in Figure 32.1. The stick system is the oldest and the most
widely used system. The remaining four systems are different from the stick system because
they consist of prefabricated wall units similar to the (opaque) curtain wall panels.
FIGURE 32.1 Types of glass curtain walls—the stick system. (Illustration adapted from AAMA, Curtain Wall Design Guide, 1996, with
permission)
778
(b) UNITIZED SYSTEM
Anchor A unitized system consists of framed wall units that are shop-
fabricated, preassembled, and generally preglazed. The units are
designed so that the vertical and horizontal members in adjacent
units interlock to form common mullions and rails. The units may be
one or two stories high. They are anchored to the building’s structural
Spandrel frame in essentially the same way as the mullions in the stick system.
beam The advantage of this system is its greater degree of quality
control resulting from shop fabrication. Its disadvantages are the
Preassembled greater shipping cost because of the added bulk from assembled
unit units, the need of a greater degree of protection of units during
transporation, and a lower degree of field adjustment.
Anchor
Mullion
Spandrel
beam
Preassembled
unit
Anchor
Spandrel
beam
Preassembled
unit
FIGURE 32.1 (continued ) Types of glass curtain walls—unitized system, unit and mullion system, and panel system. (Illustrations adapted
from AAMA, Curtain Wall Design Guide, 1996, with permission)
779
Column cover
Spandrel
beam
FIGURE 32.1 (continued ) Types of glass curtain walls—column cover and spandrel system. (Illustration adapted from AAMA, Curtain Wall
Design Guide, 1996, with permission)
Office
floors
Parking
floors
FIGURE 32.2 (a) The progress in the installation of a stick-built glass curtain wall on an office building in which the lower floors are parking
floors and the upper floors are office floors. See also Figure 32.2(b).
780
In this photograph, the glazing of the Office
curtain wall on the parking floors of the floors
building shown in Figure 32.2(a) is almost
complete. Now the framing for the curtain
wall on the office floors has begun. As
shown here, the mullions are installed first,
followed by the rails.
Parking
This (part of the) photograph shows the
floors
progress in the installation of rails on the
office floors. Because an office floor has
separate spandrel and vision glass areas,
there will be three rails per floor.
FIGURE 32.2 (b) The progress in the installation of a stick-built glass curtain wall on an office building in which the lower floors are parking
floors and the upper floors are office floors; see also Figure 32.2(a).
781
I-shaped expansion splice is inserted
into the tubular part of the lower mullion
and fastened to it. The tubular part of
the upper mullion length slides freely over
the splice with a snug fit. A gap is left
between the two mullions for movement,
as shown in the lower photograph.
See also Figures 32.4, 32.5(b) and (c).
Top of spandrel
beam
782
Upper mullion
Mullion span
Lower Spandrel
mullion beam
Expansion joint
EX ANCHOR DETAIL
Mullion span
Mullion span
Upper mullion
DL ANCHOR EX ANCHOR
Expansion
splice
Expansion joint
Mullion span
Mullion span
Spandrel
DL ANCHOR beam DL ANCHOR
Lower mullion
Mullion span
EX ANCHOR EX ANCHOR
Dead-load
Dead-load support
support
(a) Single-span mullion support system (b) Twin-span mullion support system
Each mullion length spans from floor to floor and is Each mullion length spans two floors and is provided
provided with one dead-load anchor support at the top with a DL anchor support at alternate floors. Each
from which the mullion is hung. The first mullion length, mullion slides freely at both ends over the expansion
however, begins with a dead-load support at the foundation splices. At these ends, the mullion is anchored to EX
and is anchored to an EX anchor at the top. The tubular anchors.
part of the second mullion length slides freely over the
expansion splice in the lower mullion (see Figure 32.3).
FIGURE 32.4 Support systems for single-span and twin-span curtain wall mullions. Observe that each mullion has only one dead-load
support.
783
Part 2 A NCHORING A M ULLION TO A DL OR EX A NCHOR
Materials and Systems
of Construction Figure 32.5 shows the anchorage details of a mullion to a DL anchor and an EX anchor.
Anchoring a mullion to a DL anchor (or an EX anchor) is a two-step process. The first
step includes providing a temporary connection between the mullion and the anchor,
Figure 32.5(b). After all mullion lengths are correctly aligned, a permanent connection
between the mullion and the anchor is made.
A permanent connection requires field drilling into the mullion through predrilled holes
in the anchors, Figure 32.5(c), (d), and (e). Predrilled holes in anchors provide for field
adjustment to cater to the (allowed) dimensional variations in the structural frame of the
building.
As with other curtain walls (precast concrete, GFRC, natural stone, etc.), the anchorage
system of a glass curtain wall to the building’s structure is typically provided by the curtain
wall’s manufacturer. The installation of the wall is generally done by the manufacturer’s
own installation crew or by an approved third-party installer. For some simple curtain walls
that utilize a manufacturer’s standard sections, an installer may provide all detailing assist-
ance to the architect.
784
Two same-size round holes in anchor
for DEAD-LOAD support of mullion.
Erector field drills into the mullion
through the more suitable of the two
holes for permanent connection of
the mullion to the anchor.
Slotted hole
in mullion
Slotted hole in
anchor
DL anchor
Pour stop engineered
to support the loads
785
PRACTICE QUIZ
Each question has only one correct answer. Select the choice that best 7. In a single-span mullion system for a glass curtain wall,
answers the question. a. one dead-load anchor is provided at every floor level.
1. A stick-built glass curtain wall consists of b. two dead-load anchors are provided at every floor level.
c. one dead-load anchor is provided at every alternate floor level.
a. mullions and glass.
d. two dead-load anchors are provided at every alternate floor level.
b. rails and glass.
e. only one dead-load anchor is provided for the entire height of
c. mullions, rails, and glass.
the wall.
d. mullions, rails, and preassembled units.
e. preassembled units and glass. 8. In a twin-span mullion system for a glass curtain wall,
a. one dead-load anchor is provided at every floor level.
2. A unitized glass curtain wall consists of
b. two dead-load anchors are provided at every floor level.
a. mullions and glass.
c. one dead-load anchor is provided at every alternate floor level.
b. rails and glass.
d. two dead-load anchors are provided at every alternate floor level.
c. mullions, rails, and glass.
d. mullions, rails, and preassembled units. e. only one dead-load anchor is provided for the entire height of
e. preassembled units and glass. the wall.
3. Glass curtain walls in which aluminum framing sections are specially 9. In a single-span mullion system for a glass curtain wall,
profiled for a particular project are a. one expansion anchor is provided at every floor level.
a. rare because of the prohibitive cost of manufacturing custom b. two expansion anchors are provided at every floor level.
profiles. c. one expansion anchor is provided at every alternate floor level.
b. uncommon because of the extremely high cost of manufacturing d. two expansion anchors are provided at every alternate floor level.
custom profiles. e. only one expansion anchor is provided for the entire height of
c. not uncommon because the cost of custom profiles can be the wall.
recovered from a few repeat mid-sized to large projects. 10. In a twin-span mullion system for a glass curtain wall,
d. fairly common because the cost of custom profiles can be a. one expansion anchor is provided at every floor level.
recovered from one large project. b. two expansion anchors are provided at every floor level.
4. In a stick-built glass curtain wall, the mullions are typically spaced at c. one expansion anchor is provided at every alternate floor level.
a. 2 ft to 4 ft on center. b. 4 ft to 6 ft on center. d. two expansion anchors are provided at every alternate floor level.
c. 6 ft to 10 ft on center. d. 10 ft to 15 ft on center. e. only one expansion anchor is provided for the entire height of
e. as needed for the project. the wall.
5. In a stick-built glass curtain wall, the rails are typically spaced at 11. The width of an expansion joint between adjacent mullion lengths in
a. 2 ft to 4 ft o.c. b. 4 ft to 6 ft o.c. a typical stick-built glass curtain wall
c. 6 ft to 10 ft o.c. d. 10 ft to 15 ft o.c. a. is generally 1 in. standard.
e. as needed for the project. b. is generally 12 in. standard.
c. is generally 14 in. standard.
6. A stick-built glass curtain wall is anchored to the building’s structure d. is generally 161
in. standard.
through e. must be determined on a project-by-project basis.
a. mullions. b. rails.
c. both mullions and rails. d. none of the above.
786
Mullion
Rail snapped over shear blocks
Sealant
Mullion
Shear block, one on
each end of a rail
Screw
Screw spline in shear block to spline in
fasten shear block to mullion shear
block
Shear
block
Rail
Length of rail is 1/16 in. shorter
than clear distance between Bottom cover is snapped onto the
mullions to allow thermal rail after the rail has been
expansion and contraction of rail snapped to shear blocks
FIGURE 32.6 Typical connection between rails and mullions of a stick-built glass curtain wall.
In an outside-glazed wall, the glass panes are installed from the outside of the building by
workers standing on a scaffold or staging. This method of installing glass is less efficient and
more expensive due to the cost of scaffolding or staging. It is generally used for low- to mid-
rise buildings. The glass in an outside-glazed wall can be secured in two ways:
• Pressure plate–captured glass (Figures 32.7 to 32.9)
• Structural silicone sealant–adhered glass (Figure 32.10)
In an inside-glazed wall, the glass is installed by workers standing on the appropriate
floor of the building. The system is more efficient because it does not require scaffolding or
staging. It is the system of choice for high-rise buildings. However, the cross-sectional
shapes of mullions and rails for the inside-glazed system are more complex than the corre-
sponding shapes for the outside-glazed system.
787
Gasket
Mullion
Pressure
plate
Snap-on
cover Insulating glass unit in vision area of
curtain wall (1 in. thick typical)
Rail
Gasket
FIGURE 32.7 (a) Anatomy of an outside-glazed glass curtain wall (pressure plate–captured glass).
788
Chapter 32
Exterior Wall Cladding–IV
(Wall Systems in Glass)
FIGURE 32.7 (b) In fastening the pressure plates to curtain wall framing members, the glass is
temporarily held by small pressure plate members. After several glass panes are in position, the
temporary pressure plates are removed and replaced by full-length pressure plates.
Custom mullion
Rail
Standard
cover
FIGURE 32.8 A custom cover and custom mullion for an outside-glazed glass curtain wall.
(Photo courtesy of Vistawall Architectural Products)
789
Mullion
Vision Vision
glass glass
P Q
Spandrel Spandrel
glass glass
Inside tape
R Insulating glass
unit
Vision Vision
glass glass Gasket (also
functions as
thermal separator)
Thermal separator
Pressure plate
Detail P fastened to mullion
Snap-on cover
FIGURE 32.9 (a) Typical details of an outside-glazed glass curtain wall (pressure plate–captured glass). Aluminum sections used in the
details are by Vistawall Architectural Products. Other manufacturers provide similar sections.
790
Insulating glass unit (1 in. thick
typical)
Inside glazing tape
Gasket (also functions as
Rail
thermal separator)
DETAIL Q
DETAIL R
FIGURE 32.9 (b) Typical details of an outside-glazed glass curtain wall (pressure plate–captured glass). Aluminum sections used in the
details are by Vistawall Architectural Products. Other manufacturers provide similar sections.
791
Part 2 O UTSIDE -G LAZED W ALLS (S TRUCTURAL S ILICONE
Materials and Systems S EALANT –A DHERED G LASS )
of Construction
Another version of an outside-glazed curtain wall is one in which the glass is held by struc-
tural silicone sealant. In this type of system, the vertical edges of a glass pane are adhered
to the mullions with beads of structural silicone sealant. The mullions in this wall are
similar to those of an outside-glazed wall without the mullion nose. The horizontal edges
of the glass are supported on rails and anchored to them through standard pressure plates,
Figure 32.10. The absence of vertical pressure plates in the system accentuates the hori-
zontality of the covers.
Vision S
glass
Q
Spandrel
glass
R
Mullion
Structural
silicone sealant
Polyurethane
spacer
Insulating glass
unit
FIGURE 32.10 Typical details of an outside-glazed curtain wall (structural silicone sealant–adhered glass). Aluminum section used in the
detail is by Vistawall Architectural Products. Other manufacturers provide a similar section.
792
Spandrel glass; see also
Figure 32.7 Rail
Gasket
Thermal
Mullion separator
Setting
block
Weep holes
here
Snap-on
cover
Weep holes
here
Mullion Thermal
separator Gasket Rail
Cover
Setting block
Weep holes
here
Adapter for
spandrel glass
Deep glazing pockets in mullions allow the glass Weep holes in
to be inserted from within the building. The cover here
open rail at the top of the opening facilitates
the insertion. The opening is closed with a
glazing stop after the glass is in position; see
(b) DETAIL at ceiling level.
is used in the spandrel area (see Figure 32.7(a)). A fire-containment assembly is generally
required to prevent the passage of fire and smoke between the adjacent floors of the build-
ing. This assembly consists of semirigid mineral wool insulation pressure-fitted (and sup-
ported on metal clips) in the space between the curtain wall and the spandrel beam. To
obtain a good seal, the insulation is topped with a liquid-applied, fire-resistive sealant.
In addition to the fire-containment assembly, the entire spandrel area of the curtain wall
is provided with mineral wool insulation placed behind the spandrel glass. To prevent con-
densation between the glass and the insulation, a vapor retarder is provided in this area.
This generally consists of an aluminum foil lamination on the insulation’s interior face.
Where a high degree of condensation potential exists, a metal panel (referred to as a metal
back pan) should be specified in place of an aluminum foil lamination.
793
Part 2
Materials and Systems
of Construction
Ceiling
Rail
Snap-on closure
IGU in vision
area
Spandrel
glass; see Gypsum board
also Figure
3.27 Light-gauge steel
stud wall with
insulation
DETAIL at sill level Perimeter fire containment cover over aluminum framing
Space between
glass curtain wall
and structural
frame
Floor slab
FIGURE 32.13 Typical floor-level, sill-level, and ceiling-level details of an outside-glazed glass curtain wall. Note the fire-stopping in the
space between the spandrel beam and curtain wall.
794
PRACTICE QUIZ
Each question has only one correct answer. Select the choice that best 16. As shown in this text, a glass curtain wall in which the glass is
answers the question. structural silicone adhered is glazed from the
12. The width of an expansion joint in the rails of a typical stick-built a. building’s interior. b. building’s exterior.
glass curtain wall c. (a) or (b).
a. is 1 in. standard. b. is 12 in. standard. 17. In a glass curtain wall with pressure plate–captured glass, there are
1 1
c. is 4 in. standard. d. is 32 in. standard. a. no covers.
e. must be determined on project-by-project basis. b. covers in both horizontal and vertical directions.
c. covers only in the horizontal direction.
13. In a stick-built glass curtain wall, the mullions are erected first and
d. covers only in the vertical direction.
the rails are inserted between them.
a. True b. False 18. As shown in the text, a glass curtain wall with structural silicone–
adhered glass
14. A shear block is used
a. has no exterior covers.
a. at a mullion expansion joint to allow the mullion to move.
b. has exterior covers in both horizontal and vertical directions.
b. at the dead-load anchor of a mullion.
c. has exterior covers only in the horizontal direction.
c. at the expansion anchor of a mullion.
d. has exterior covers only in the vertical direction.
d. to connect a rail to adjacent mullions.
e. none of the above. 19. A typical glass curtain wall is provided with weep holes to drain
infiltrating water even though it is sealed from both the inside and
15. A glass curtain wall in which the glass is pressure plate captured is
the outside with gaskets or tapes.
glazed from the
a. True b. False
a. building’s interior. b. building’s exterior.
c. either (a) or (b).
795
(a) Using a crane,
unitized curtain wall
elements are
carried up from the
delivery truck to
the building facade
(c) The new unit being forced over the (projecting) splice (d) Anchorage of unit to the floor structure, providing
dead-load support
FIGURE 32.14 Installation of a unitized curtain wall element.
796
Chapter 32
Steel (or stainless steel) channel. Two or three Exterior Wall Cladding–IV
channels can be nested for added strength. (Wall Systems in Glass)
Aluminum mullion
FIGURE 32.16 A tall glass wall with standard curtain wall sections anchored to an interior structural steel vertical member to provide lateral-
load support to aluminum mullions. In this building, a steel pipe support is used. In taller walls, vertical steel trusses are common.
A IR -I NFILTRATION C ONTROL
In the United States, the maximum air infiltration allowed through a glass curtain wall is
typically 0.06 cfm/ft2 under an inside-outside air pressure difference of 1.57 psf. In Canada,
the requirement is three times more stringent—that is, 0.02 cfm/ft2 under an air pressure
difference of 1.57 psf.
Where lower air infiltration is required, curtain wall systems, which provide a rate of up
to 0.01 cfm/ft2 under an inside-outside air pressure difference of 6.24 psf, are available.
NOTE (Note that a 1.57-psf air pressure difference is equivalent to that exerted by a wind speed of
cfm is an acronym for cubic 25 mph. Similarly a 6.24-psf air pressure difference is equivalent to that created by a
feet per minute. 50-mph wind speed; see Chapter 3.
Air-infiltration control not only conserves energy but also reduces ice buildup on the
exterior of curtain wall components. Ice buildup is caused by the condensation of water
vapor that escapes from the building’s interior along with air. When the ice melts, the melt-
water may leak into the building’s interior. Therefore, a more stringent air-infiltration-
control criterion is generally needed in colder climates.
R AINWATER - AND M ELTWATER -P ENETRATION C ONTROL
Water-penetration control (of both rainwater and meltwater) is perhaps the most important
nonstructural performance requirement of a glass curtain wall. Glass curtain wall systems are
NOTE generally designed to ensure no water penetration when tested under a static air pressure differ-
ence (between the inside and the outside) that is at least 20% of the inward structural design
AAMA and Water wind load on the curtain wall. Thus, if the inward structural design wind load on the wall is 50
Penetration psf, the system is tested for water penetration under a static air pressure difference of at least 10
The American Architectural psf. A more stringent water-penetration criterion is required for buildings located in areas sub-
Manufacturers Association jected to frequent and intense wind-driven rain. In addition to conforming to the static pres-
(AAMA) defines water penetra- sure criterion, a glass curtain wall is required to conform to dynamic pressure test criterion.
tion as the appearance of Water-penetration control is accomplished in different ways by system manufacturers; it
uncontrolled water other than typically includes adequate drainage in the aluminum joinery and glazing pockets. For
condensation on the interior
example, in the stick-built glass curtain wall described earlier, weep holes are provided in
face of any part of the cur-
tain wall.
the pressure plates and snap-on covers that drain the water to the outside. The architect’s
details must also ensure the management of water entering the curtain wall from a nonglass
facade that is above the curtain wall, where such a facade exists.
U-V ALUE , S OLAR H EAT G AIN , AND C ONDENSATION R ESISTANCE
These three interrelated criteria are a function of the type of glass, the type of aluminum
framing (thermally improved or not), and the center-to-center spacing of framing mem-
bers, as explained in Chapter 30. The architect must specify their values in consultation
with the HVAC consultant (who also needs these values to design the building’s HVAC
system and to meet the energy code requirements).
V APOR D IFFUSION A NALYSIS
As previously stated, interior water vapor may result in ice buildup on curtain wall framing
and condensation of water vapor in the building’s interior. These issues are particularly criti-
cal in cold climates, where a vapor analysis of the curtain wall system is generally required.
S OUND T RANSMISSION
Glass curtain walls in buildings located in areas where high levels of exterior noise are
present (e.g., near airports or busy highways) may need a higher sound-transmission-loss
specification than other areas.
798
H URRICANE I MPACT R ESISTANCE AND S EISMIC R ESISTANCE Chapter 32
Exterior Wall Cladding–IV
Because of Florida’s experience with extensive wind damage to glass curtain walls from hur- (Wall Systems in Glass)
ricanes, several coastal cities in the United States are requiring that glass curtain walls be
missile-impact resistant, particularly in the lower floors of the building. Similarly, because
of California’s experience with earthquake damage to glass curtain walls, resistance to shaking,
glass drifting, and horizontal movement of components is required for buildings in seismi-
cally active areas.
S TOREFRONT S YSTEM
A storefront is a large glass-aluminum wall that is generally one story tall and extends from
the ground to the second floor of the building. Three major differences distinguish a cur-
tain wall from a storefront. They are:
(a) The storefront wall lies under the second-floor structure of the building and (unlike
a curtain wall), it is not spaced away from the structural frame of the building.
Often, a storefront is protected by an overhang to control water leakage through
the system.
(b) The glazing system’s performance for structural and nonstructural criteria (air infil-
tration, water penetration, CRF, etc.) is lower than that of a curtain wall.
(c) Rainwater that enters a curtain wall is drained by the (horizontal) rail support of each
individual lite. In a storefront system, the water entering through a lite must travel
vertically down the mullion and be drained at the weep holes at the ground level.
Cable-and-strut truss
Strut
Vertical
steel
truss
800
between the columns or walls supporting the building. Two examples of cable-net- Chapter 32
supported glass walls are shown in Figure 32.18(a) and (b). Exterior Wall Cladding–IV
The horizontal and vertical cables are held together at intersections through special (Wall Systems in Glass)
stainless steel connectors, which also serve as points for securing the glass to the grid. A
typical connector is shown in Figure 32.18(c). The glass panels generally consist of insulat-
ing glass units with laminated and heat-soaked tempered glass.
Because the cables are highly stressed, they impose a large load on the boundary elements
of the opening—the two spandrel beams and the columns (or walls)—which must be
designed to resist this additional load.
FIGURE 32.18 Two examples of cable-net-supported glass walls. Note that all photographs have been taken from inside the buildings.
801
Part 2 D OUBLE -S KIN G LASS W ALLS
Materials and Systems
of Construction Another innovative glass wall system is the double-skin wall system, also referred to as a
bioclimatic glass wall. In this system, two glass walls, separated by 1 ft to 5 ft of air space, are
used. The air space serves as a buffer between the two skins, tempering the outdoor air, and
also serves as a plenum for the building’s HVAC system. The outer skin may include com-
puter-controlled operable glazing and solar shading devices.
Although the primary benefit of a double-skin system is energy conservation, it also pro-
vides effective water-penetration control, better air-infiltration control, higher sound insu-
lation, and so on. The proponents of the system, which has been used extensively in Europe,
claim it to be more sustainable under the present energy prices in Europe, which are con-
siderably higher than those in the United States.
As smart glazing systems with environment-adaptive technologies (e.g., electrochromic
glass) and energy-generating capabilities (e.g., photovoltaic glass) evolve further, double-
skin glass wall systems may become more popular. In that scenario, the outer glass skin may
not only help conserve energy but also generate some energy to power the building.
PRACTICE QUIZ
Each question has only one correct answer. Select the choice that best c. both (a) and (b) above.
answers the question. d. none of the above.
20. The air infiltration rate through a glass curtain wall is specified in 22. In a cable-net-supported glass wall, the glass
terms of a. bears on (horizontal) rails.
a. pounds per square feet. b. is connected to (vertical) mullions.
b. cubic feet per minute. c. both (a) and (b) above.
c. cubic feet under a given inside-outside air pressure difference. d. is supported by a spider-shaped connector.
d. cubic feet per minute under a given inside-outside air pressure e. none of the above.
difference.
23. The environmental performance requirements for a storefront are
e. none of the above.
generally much higher than those for a glass curtain wall.
21. In a glass wall supported by cable trusses, the glass a. True b. False
a. bears on (horizontal) rails.
b. is connected to (vertical) mullions.
REVIEW QUESTIONS
1. Using sketches and notes, explain the differences between a single-span mullion support system and a twin-span
mullion support system for a glass curtain wall.
2. Use three-dimensional sketches to illustrate each of the following:
a. A typical dead-load anchor used in a glass curtain wall
b. A typical expansion anchor used in a glass curtain wall
3. Sketch in three dimensions a typical spider-shaped connector.
4. List the major differences between a glass curtain wall and a storefront.
5. Explain the purpose of the following items and state where they are used: (a) shear block, (b) pressure plate, and
(c) adapter for spandrel glass.
6. Using sketches and notes, explain how we increase the lateral load-bearing capacity of a standard glass-aluminum
wall.
802