2012 Building Code

This document summarizes the British Columbia Building Code requirements for railings and guards: 1) Handrails are required on stairs and ramps based on width, as outlined in Table 9.8.7.1. They must be continuous along flights and landings, except where interrupted by doors or changes in direction. 2) Guards are required where there is a fall of more than 24 inches, or a steep slope within 1.2m, to prevent falls. They must resist both horizontal and vertical loads as specified in Table 9.8.8.2. 3) Railings and guards must be designed and installed to withstand significant loads from people leaning or falling against them. Specific requirements

Uploaded by

ygfrost
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views

2012 Building Code

This document summarizes the British Columbia Building Code requirements for railings and guards: 1) Handrails are required on stairs and ramps based on width, as outlined in Table 9.8.7.1. They must be continuous along flights and landings, except where interrupted by doors or changes in direction. 2) Guards are required where there is a fall of more than 24 inches, or a steep slope within 1.2m, to prevent falls. They must resist both horizontal and vertical loads as specified in Table 9.8.8.2. 3) Railings and guards must be designed and installed to withstand significant loads from people leaning or falling against them. Specific requirements

Uploaded by

ygfrost
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

2012 BC Building Code

Items associated to Railings and Guards


9.8.7. Handrails

9.8.7.1. Required Handrails

1. Except as provided in Sentences (2) to (4), handrails shall be installed on stairs and
ramps in accordance with Table 9.8.7.1.

Table 9.8.7.1.
Number of Sides of Stair or Ramp Required to Have a Handrail
Forming part of Sentence 9.8.7.1.(1)

Location of Handrails Serving Stairs Handrails Serving Ramps


Stair or
Ramp Stairs < 1 100 mm Stairs Ramps < Ramps
Wide (43”) ≥ 1 100 mm 1 100 mm ≥ 1 100 mm
Wide (43”) Wide Wide

Straight Curved All Straight or All


Curved

Number of Sides Required to Have a Handrail

Within a 1 1 1 1 2
dwelling unit

All other 1 2 2 2 2
locations(1)

Notes to Table 9.8.7.1.:

1. See Sentences 9.8.7.1.(2), (3) and (4) for exceptions.

2. Where a stair or a ramp is required to be at least 2 200 mm wide due to the occupant
load, a handrail shall be installed such that no position on the stair or ramp is more than
825 mm from a handrail.

Ie. The maximum width on a ramp is 32” without a grabbable rail


3. Handrails are not required for stairs and ramps serving a single dwelling unit, where
A. a) interior stairs have not more than 2 risers,
B. b) exterior stairs have not more than 3 risers, or
C. c) ramps rise not more than 400 mm.

Ie. No exterior railing is required if you have 3 steps or less

4. Only one handrail is required on exterior stairs having more than 3 risers provided such
stairs serve not more than one dwelling unit.

Ie. As long as you don’t have any open falling points, you only need 1 railing for the steps
(Example, if you have a wall protecting the other side, you don't need a grab rail up that side)

9.8.7.2. Continuity of Handrails

1. Except as provided in Sentence (2), at least one required handrail shall be continuous
throughout the length of the stair or ramp, including landings, except where interrupted
by
A. a) doorways, or
B. b) newel posts at changes in direction.

2. For stairs or ramps serving a single dwelling unit at least one required handrail shall be
continuous throughout the length of the stair or ramp, except where interrupted by
A. doorways,
B. landings, or
C. newel posts at changes in direction.

ie. On a front step or stairs of a deck, there should always be a railing extending from the
bottom of the stairs to the landing that is fully connected. The continuous rail only needs to be
present on one side of the step, as long there is a guard protecting an open falling point.

Figure 1:​ ​The railing extends from the bottom step to the landing, indicating a pass of code
Figure 2:​ ​The grab rail extends from the bottom step to the landing, so even though the railing
on the right does not extend all the way to the landing, it will still pass code because it is just
acting as a guard.

9.8.7.3. Termination of Handrails

1. Handrails shall be terminated in a manner that will not obstruct pedestrian travel or
create a hazard

An end post for picket railings or end caps for handrails are considered safe and will not
obstruct the travel of a pedestrian

2. Except for stairs and ramps serving only one dwelling unit at least one handrail at the
sides of a stair or ramp shall extend horizontally not less than 300 mm beyond the top
and bottom of each flight or ramp.

ie. In complexes with multiple units, the railing needs to extend horizontally past the bottom step
and the landing edge by 1 foot each.
9.8.7.4. Height of Handrails

1. The height of handrails on stairs and ramps shall be measured vertically from the top of
the handrail to
A. a straight line drawn tangent to the tread nosings of the stair served by the
handrail, or
B. the surface of the ramp, floor or landing served by the handrail.

2. Except as provided in Sentences (3) and (4), the height of handrails on stairs and ramps
shall be
A. not less than 865 mm (34”), and
B. not more than 965 mm (38”)

This applies in cases when the falling point is 24”- 72”

3. Where guards are required, handrails required on landings shall be not more than
1070mm (42”) in height.

This applies in cases when the falling point greater than 72”

4. Handrails installed in addition to required handrails need not comply with Sentence (2).

Case 2 also applies from 0”-24”


9.8.7.5. Ergonomic Design

1. A clearance of not less than 50 mm shall be provided between a handrail and any
surface behind it.

Ie. There need to be 2 inches of space between a grab rail or railing from the wall

2. All handrails shall be constructed so as to be continually graspable along their entire


length with no obstruction on or above them to break a handhold, except where the
handrail is interrupted by newels at changes in direction.

Ie. Wrapping a railing around a post will no longer pass code, as the railings transitions to being
perpendicular to the direction of travel, meaning that it will not be continually graspable

9.8.7.6. Projections into Stairs and Ramps

1. Handrails and constructions below handrails, including handrail supports and stair
stringers, shall not project more than 100 mm into the required width of a stair or ramp.
(See also Articles 9.8.2.1. And 9.8.5.2.)

A stringer is the 2x12 wood that typically supports the stairs. Section 9.8.7.1. Point 1C
can be modified to 900mm because of railings on each side projecting into the walking space.

​ oad Requirements​)
9.8.7.7. Design and Attachment of Handrails (L

1. Handrails and any building element that could be used as a handrail shall be designed
and attached in such a manner as to resist
A. a) a concentrated load at any point of not less than 0.9 kN, and
B. b) for handrails other than those serving a single dwelling unit, a uniformly
distributed load of 0.7kN/m.

2. Where a handrail serving a single dwelling unit is attached to wood studs or blocking, the
attachment shall be deemed to comply with Sentence (1) where
A. the attachment points are spaced not more than 1.2 m apart,
B. the first attachment point at either end is located no more than 300 mm from the
end of the handrail, and
C. The fasteners consist of not less than 2 wood screws at each point, penetrating
not less than 32 mm into solid wood.
See diagram for clear explanation
9.8.8. Guards

9.8.8.1. Required Guards

1. Except as provided in Sentences (2) and (3), every surface to which access is provided
for other than maintenance purposes, including but not limited to flights of steps and
ramps, exterior landings, porches, balconies, mezzanines, galleries and raised
walkways, shall be protected by a guard on each side that is not protected by a wall for
the length where
A. there is a difference in elevation of more than 600 mm (24”) between the walking
surface and the adjacent surface, or
B. the adjacent surface within 1.2 m of the walking surface has a slope of more than
1 in 2.

Ie. Every space that has a fall point greater than 24” (2 risers) must be protected by a guard or if
it is as steep a previously described

2. Guards are not required


A. at loading docks,
B. at floor pits in repair garages, or
C. where access is provided for maintenance purposes only.

3. Where an interior stair has more than 2 risers or an interior ramp rises more than 400
mm, the sides of the stair or ramp and the landing or floor level around the stairwell or
ramp shall be protected by a guard on each side that is not protected by a wall.

This means that any falling point above 24” must be protected by a guard, which can be either a
railing or a wall

9.8.8.2. Loads on Guards

1. Guards shall be designed to resist the specified loads prescribed in Table 9.8.8.2.
Table 9.8.8.2. Specified Loads for Guards
Forming part of Sentence 9.8.8.2.(1)
Table 9.8.8.2.
Specified Loads for Guards
Forming Part of Sentence 9.8.8.2.(1)

Minimum Design Loads

Location of Guard Horizontal Load Horizontal Load Evenly


Applied Inward or Applied Inward or Distributed
Outward at any Outward on Vertical Load
Point at the Elements Applied at the
Minimum Required Within the Guard, Top of the
Height of the Guard Including Solid Guard
Panels and Pickets

Guards within 0.5 kN/m OR 0.5 kN applied over a 1.5 kN/m


dwelling units and concentrated load of maximum width of
exterior guards 1.0 kN applied at any 300mm and a height
serving not more point of 300 mm
than 2 dwelling
units

Guards serving Concentrated load of Concentrated load of 1.5 kN/m


access walkways to 1.0 kN applied at any 0.5 kN applied at any
Equipment, point point on individual
platforms, elements
contiguous stairs
and similar areas

All other guards 0.75 kN/m OR Concentrated load of 1.5 kN/m


concentrated load of 0.5 kN applied at any
1.0 kN applied at any point on individual
point(1) elements

Notes to Table 9.8.8.2.


(1) The load that creates the most critical condition shall apply.
(2) See Sentence (2).

Notes to Table 9.8.8.2.:


1. The load that creates the most critical condition shall apply.

2. Where the width and spacing of balusters in guards within dwelling units and in exterior
guards serving not more than 2 dwelling units is such that 3 balusters can be engaged
by a load imposed over a 300mm width, the load shall be imposed so as to engage 3
balusters.

3. None of the loads specified in Table 9.8.8.2. need be considered to act simultaneously.
4. For guards within dwelling units and for exterior guards serving not more than 2 dwelling
units, Table 9.8.8.2. need not apply where the guard construction used has been
demonstrated to provide ​effective performance​.

This means that for a railing serving 1 or 2 units, the strengths in the table do not necessarily as
long as the balusters provide effective performance

9.8.8.3. Height of Guards

1. Except as provided in Sentences (2) to (4), all guards shall be not less than 1 070 mm
high (42”)
2. All guards within dwelling units shall be no less than 900 mm high (36”).
3. Exterior guards serving not more than one dwelling unit shall be not less than 900 mm
high where the walking surface served by the guard is not more than 1 800 mm (71”)
above the finished ground level.

For a stair/landing elevation height of 2 feet to 6 feet, you must have a guard that is a minimum
of 36”

4. Guards for flights of steps, except in required exit stairs, shall be not less than 900 mm
high.

If it is a flight of steps, the minimum guard height is 36”

5. The height of guards for flights of steps shall be measured vertically from the top of the
guard to a line drawn through the leading edge of the treads served by the guard.

See 9.8.7.7. Point #2

9.8.8.4. Guards for Floors and Ramps in Garages

1. Except for floors of garages referred to in Section 9.35., where garage floors or ramps
are 600 mm or more above the adjacent ground or floor level, every opening through a
garage floor and the perimeter of floors and ramps that have no exterior walls shall be
provided with

A. a continuous curb not less than 150 mm in height, and


B. a guard not less than 1 070 mm above the floor level.

2. Vehicle guardrails shall be designed for a concentrated horizontal load of 22 kN applied


outward at any point 500 mm above the floor surface. (See A-4.1.5.14. and 4.1.5.15.(1)
in Appendix A.)

9.8.8.5. Openings in Guards

1. Except as provided in Sentence (2), openings through any guard that is required by
Article 9.8.8.1. shall be of a size that will prevent the passage of a spherical object
having a diameter of 100 mm (4”) unless it can be shown that the location and size of
openings that exceed this limit do not represent a hazard. (See A-9.8.8.5.(1) and (2) in
Appendix A.)

The maximum picket spacing is 4” for residential

2. Openings through any guard that is required by Article 9.8.8.1. and that is installed in a
building of industrial occupancy shall be of a size that will prevent the passage of a
spherical object having a diameter of 200 mm unless it can be shown that the location
and size of openings that exceed this limit do not represent a hazard. (See A-9.8.8.5.(1)
and (2) in Appendix A.)

The maximum picket spacing is 8” for commercials in which there is no chance of children
passing by. Mostly applies for industrial work spaces with only workers walking past.

3. Unless it can be shown that the location and size of openings that do not comply with the
following limits do not represent a hazard, openings through any guard that is not
required by Article 9.8.8.1. and that serves a building of other than industrial occupancy,
shall be of a size that:

A. will prevent the passage of a spherical object having a diameter of 100 mm, or
B. will permit the passage of a spherical object having a diameter of 200 mm.

9.8.8.6. Design of Guards to Not Facilitate Climbing

1. Guards required by Article 9.8.8.1., except those in industrial occupancies and where it
can be shown that the location and size of openings do not present a hazard, shall be
designed so that no member, attachment or opening facilitates climbing.

Climbing can be facilitated by things like horizontal spindles or other horizontal components to
grab on to.

2. Guards shall be deemed to comply with Sentence (1) where all elements protruding from
the vertical and located within the area between 140 mm and 900 mm above the floor or
walking surface protected by the guard conform to at least one of the following Clauses:

A. they are located more than 450 mm horizontally and vertically from each other,
B. they provide not more than 15 mm horizontal offset,
C. they do not provide a toe-space more than 45 mm horizontally and 20 mm
vertically, or
D. they present more than a 2-in-1 slope on the offset.

Details about the climbing points near the railing.

9.8.8.7. Glass in Guards

1. Glass in guards shall be


A. safety glass of the laminated or tempered type conforming to
CAN/CGSB-12.1-M, “Tempered or Laminated Safety Glass,” or
B. wired glass conforming to CAN/CGSB-12.11-M, “Wired Safety Glass.”