ATS420 ATS Controller User Manual V1.0
ATS420 ATS Controller User Manual V1.0
USER MANUAL
ATS 420 ATS CONTROLLER USER MANUAL
Software Version
No. Version Date Note
1 V1.0 2021-07-01 Original release.
2
ATS 420 ATS CONTROLLER USER MANUAL
Symbol Description
Symbol Description
3
ATS 420 ATS CONTROLLER USER MANUAL
Warning
1.The installation of this equipment must be carried out by professionals.
2.When installing and operating the controller, please read the entire instruction
manual first.
3.Any maintenance and commissioning of the equipment must be familiar with all the
equipment.
4.Safety standards and precautions in advance, otherwise it may cause personal
injury or damage to related equipment.
5.After the installation of the controller is completed, please verify that all protection
functions are valid.
Be Care
1.Please keep the good connection of the power supply of the controller. Do not
share the connection lines of the positive and negative electrodes of the battery
with the floating charger.
2.During the operation of the engine, do not disconnect the battery, otherwise it may
cause damage to the controller.
4
ATS 420 ATS CONTROLLER USER MANUAL
Catalogue
Summary................................................................................................................................... 6
Main Features........................................................................................................................... 6
Parameters Display..................................................................................................................7
Parameters................................................................................................................................7
Installation instruction............................................................................................................14
Parameter setting...................................................................................................................22
Fault finding............................................................................................................................ 29
Notes:
1. All rights reserved. No part of this duplication may be reproduced in any material
form (including photocopying or storing in any medium by electronic means or others)
without the written permission of the copyright holder.
2. MEBAY Technology reserves the rights to change the contents of this document
without prior notice.
5
ATS 420 ATS CONTROLLER USER MANUAL
Summary
The controller is a dual power switching ATS controller, dual power intelligent
switch module with programmable, automatic measurement, automatic control and
LCD display functions. Automatic measurement and control can reduce incorrect
operation. It is an ideal option for ATS.
2.8inch LCD screen display with brand new UI design is adapted in this
controller can display related parameters directly. The LCD screen can display
various faults at the same time. Once the generator does not run normally, it can
effectively achieve protection.
There are Chinese/English interface options, more language can be set
according to user’s request. All the parameters can be configured through the front
face buttons or use programmable interface by RS485 or USB to adjust via PC. It has
compact structure, advanced circuits, simple wiring and high reliability, It can be
widely used in various types of power systems.
Main Features
There are two Models under ATS 420 series.
ATS 420: Dual power intelligent switch module.
ATS 420 R: Based on ATS 420, it adds RS485 port.
Dual core 32bit high performance single chip microcomputer.
2.8inch LCD screen, Available in Chinese/English languages, user’s language set
if necessary.
System type can set as: "S1 Mains S2 Mains", "S1 Mains, S2 Gen", "S1 Gen S2
Mains", "S1 GenS2 Gen".
Acrylic material is adapted to protect the screen.
PC material panel, waterproof, oil-proof, UV-resistant, good operation feel and
long service life.
USB Port: parameters can be set even without power through USD port to monitor
in real time.
With RS485 communication port, can achieve "Three Remote" functions via
MODBUS protocol.
Collection and display, gen, mains, power, phase and other parameters.
Applicable for PC Three-stage, PC Two-stage, CB and CC switch.
Automatic/Manual mode. In manual mode, can force the switch to close or open.
Can control two generators to work as Cycle Run mode, Master Run mode and
Balance Run mode.
Suitable for various AC systems (3 phase 4-wires, 3-phase 3-wires, single-phase
2-wire, and 2-phase 3-wire).
Input/output function, status can be shown directly.
Real time clock inside.
Totally 5 relays output, 3 relays function configurable.
Totally 4 configurable switch input, 2 switch function configurable.
Control Protection: Realize automatic ATS switching of generator sets, perfect
fault display and protection functions.
6
ATS 420 ATS CONTROLLER USER MANUAL
Parameters Display
S1/S2 Voltage status
S1/S2 Frequency
Current real-time status
S1/S2 Switch status
S1/S2 Phase voltage
S1/S2 Work status
Input/Output status
Total Power-on time
Alarm number and account
Alarm type (Warn Alarm, Fault Alarm)
Alarm event
Inputs, outputs number
Input status, S1/S2 closing input, 1~2 are configurable ports
Output status, S1/S2 closing output, 1~3 are configurable ports
Real-time clock
Current date/time
Parameters
Options Parameters
Working voltage DC 8V----36V Continuous
Standby:24V:MAX 2W
Power consumption
Working:24V:MAX 3W
1P2W 30VAC-360VAC (ph-N)
2P3W 30VAC-360VAC (ph-N)
S1 AC Voltage Input
3P3W 60VAC-620VAC (L-L)
3P4W 30VAC-360VAC (ph-N)
1P2W 30VAC-360VAC (ph-N)
2P3W 30VAC-360VAC (ph-N)
S2 AC Voltage Input
3P3W 60VAC-620VAC (L-L)
3P4W 30VAC-360VAC (ph-N)
MAX Accumulating Time 99999.9Hours (Min Store time:6min)
Closing S1 output 250V/10 AMP Non-contact normally Open output
7
ATS 420 ATS CONTROLLER USER MANUAL
8
ATS 420 ATS CONTROLLER USER MANUAL
9
ATS 420 ATS CONTROLLER USER MANUAL
Cable cross
No. Function Description
sectional area
1 Non-contact normally Open output 1.5mm2
S1 Close Output
2 Capacity: 250V/10A 1.5mm2
3 Non-contact normally Open output 1.5mm2
S2 Close Output
4 Capacity: 250V/10A 1.5mm2
5 Normally Close 1.5mm2
Aux.
6 COM 250V/5 AMP Relay contact Output 1.5mm2
Output 1
7 Normally Open 1.5mm2
8 A1 1.5mm2
9 B1 S1 AC System 3P4W voltage input 1.5mm2
10 C1 For single phase, only connect A1, N1 1.5mm2
11 N1 1.5mm2
12 A2 1.5mm2
13 B2 S2 AC System 3P4W voltage input 1.5mm2
14 C2 For single phase, only connect A2, N2 1.5mm2
15 N2 1.5mm2
16 B- Connected with negative of starter battery. 1.5mm2
17 B+ Connected with positive of starter battery. 1.5mm2
Detect the S1 ATS closing status,
18 S1 Close Output 1.5mm2
Ground connected is active.
Detect the S2 ATS closing status,
19 S2 Close Output 1.5mm2
Ground connected is active.
20 Aux. Input 1 User-defined. 1.5mm2
21 Aux. Input 2 Ground connected is active. 1.5mm2
22 RS485_B- RS485 Communication Port 1.0mm2
23 RS485_A+ A 120 Ω shielded wire and good grounding 1.0mm2
24 RS485_SCR are recommended 1.0mm2
25 Normally Close 1.5mm2
Aux. Default: ATS Power L
26 COM 1.5mm2
Output 2 250V/5AMP Relay contact Output
27 Normally Open 1.5mm2
28 Normally Close 1.5mm2
Aux. Default: ATS Power N
29 COM 1.5mm2
Output 3 250V/5AMP Relay contact Output
30 Normally Open 1.5mm2
USB-B For PC operation and control
10
ATS 420 ATS CONTROLLER USER MANUAL
L1 L2 L3 N
S1 POWER INPUT S2 POWER INPUT
R1 R2
S1 S2
T1 T2
N1
MBS1 N2
S2 CLOSE INPUT
FIRE SWITCH
20A
10A
10A
20A
10A
10A
GND
1 2 3 4 25 8 9 10 11 28 18 19 16 27 12 13 14 15 30
A1 B1 C1 N1 A2 B2 C2 N2
S1 CLOSE S2 CLOSE S1 AC VOLTAGE INPUT S2 AC VOLTAGE INPUT
OUTPUT OUTPUT (AC0-300V) (AC0-300V)
(10A) (10A)
MODE:ATS420 USB
MAX 5A RS485
(DC8-36V)
16 17 7 6 5 20 21 22 23 24
- +
Remote
Start
Generator B A SCR
AUX. INPUT 1
AUX. INPUT 2
B+ B-
BATTERY
11
ATS 420 ATS CONTROLLER USER MANUAL
L1 L2 L3 N
R1 R2
S1 S2
T1 T2
N1 N2
S1 CLOSE INPUT
S2 CLOSE INPUT
20A
10A
10A
20A
10A
10A
Contactor Contactor
8 9 10 11 16 1 2 18 19 3 4 16 12 13 14 15
A1 B1 C1 N1 A2 B2 C2 N2
GND
GND
S1 AC VOLTAGE S1 CLOSE S2 CLOSE S2 AC VOLTAGE
INPUT(AC0-300V) OUTPUT (10A) OUTPUT (10A) INPUT(AC0-300V)
MODE:ATS420 USB
AUX. OUTPUT 2
AUX. OUTPUT 3
Generator B A SCR
AUX. INPUT 1
AUX. INPUT 2
B+ B-
BATTERY
12
ATS 420 ATS CONTROLLER USER MANUAL
L1 L2 L3 N
R1 R2
S1 S2
T1 T2
N1 N2
MCH MCH
MN MN
MX MX
XF XF
20A
10A
10A
20A
10A
10A
Breaker Breaker
GND
8 9 10 11 18 1 2 27 26 16 29 30 3 4 19 12 13 14 15
A1 B1 C1 N1 A2 B2 C2 N2
S1 CLOSE
S2 CLOSE
INPUT
INPUT
MODE:ATS420 USB
MAX 5A RS485
(DC8-36V)
16 17 7 6 5 20 21 22 23 24
- +
Remote
Start
Generator B A SCR
AUX. INPUT 1
AUX. INPUT 2
B+ B-
BATTERY
13
ATS 420 ATS CONTROLLER USER MANUAL
Installation instruction
The controller is fixed by two special fixing members and screws, and the screws
of the metal fasteners cannot be too tight.
Panel Cutout: W116mm*H90mm.
Note: If the controller is installed directly in the genset shell or other fluctuated
equipment, the rubber pad must be installed.
NOTE:
In case of floating charger connect charger output to battery positive and negative
directly, then, connect battery positive and negative poles to controller positive and
negative power supply.
Note: All outputs of the controller are relay contacts. The maximum current
capacity is described in the "Parameters" in this manual. Please use it in the relay
current capacity. If an extended relay is needed, add a continuous current diode
(when the extended relay coil is DC) or a resistance-capacitance loop (when the
extended relay coil is AC) to both ends of the coil to prevent interference with the
controller or other equipment.
14
ATS 420 ATS CONTROLLER USER MANUAL
If withstanding voltage test is conducted after the controller has already been
installed onto the control panel, please unplug all controller terminal connections in
order to prevent high voltage from damaging it.
Alarm UP
Warning OK/Setting
Running Down
S1 Close/Open S2 Close/Open
Auto Pressing this key will set the module into auto mode.
In the main screen, Press the for 3 seconds to enter into manual start operation
interface.
16
ATS 420 ATS CONTROLLER USER MANUAL
Press / key to choose parameters (the current line was highlighted with black)
and then press Confirm key to confirm.
1. Return Notes and function description
2. Stop to test When test machine has been chosen, and if this item is selected,
genset start signal will disconnect immediately and it will stop
TEST OFF-LOAD or TEST ON-LOAD operation.
3. Test on load It will send out a start generator signal immediately. After gen
voltage is normal, the ATS will transfer the load to mains
immediately regardless the mains is normal or not.
4. Test off load It will send out a start signal immediately. After gen voltage is
normal, if mains voltage is normal, the ATS will not act. If mains
voltage is abnormal, ATS will transfer the load to generator.
When mains volt recovers to normal, the ATS will transfer the
load to mains. At this time the start generator signal still
continuously outputs.
5. Cycle When this is chosen, oil engine start signal will output circularly
Run Start according to master status. Circular output time can be set by the
users. If oil engine fault occurs, it won't send start signal to the oil
engine. If it transfers to manual mode, it will keep current status
and stop circular start time counting.
Requirements needed:
1. In automatic mode.
2. Set output to S1/ S2 start normally open output
3. Set input to remote start input.
4. <Cycle running time> and <Cycle stop time> should be programmed.
5. Set the system type as S1 Gens & S2 Gens.
6. Set proper < Wait Running > time, and set default delay to 60s.
Manual start
Press and manual mode indicator is on, which means controller is in manual
mode.
Press , S1/S2 open relay outputs immediately, if S1/S2 close input is inactive, the
S1/S2 power supply disconnects with load.
17
ATS 420 ATS CONTROLLER USER MANUAL
NOTE: For the ATS without neutral position, it is invalid to press key.
Remote start/stop
Send remote start/stop signals using MODBUS protocol via RS485 port.
Remote Stop:Disconnect the start signal, i.e. stop the running genset.
Remote Start:Output the start signal, i.e. start the genset.
Auto start/stop
Input port start/stop operation
Set input port as "Remote Start On Load" or "Remote Start Off Load", both could not
be set simultaneously.
Remote Start on Load:When the input is active, genset close relay will active after
genset is normal; when the input inactive, genset will stop automatically.
Remote Start off Load:When the input is active, mains close relay will active after
mains is normal; genset close relay will active when the mains is abnormal while
genset is normal; when the input inactive, genset will stop automatically.
18
ATS 420 ATS CONTROLLER USER MANUAL
Master Run
Mater genset will be start when remote start signal is active. During the start process,
if there is genset fault alarm (genset supply delay overtime or genset fault input is
active), fail to close or load inhibit alarm occurs, the starting genset will be stop
immediately and the additional genset will be start automatically.Otherwise, the
master run genset will running continuously until the remote start signal deactivated.
Balance Run
The gensets which has the shortest running hours will be start when remote start
signal is active. During the start process, if there is genset fault alarm (genset supply
delay overtime or genset fault input is active), fail to close or load inhibit alarm occurs,
the starting genset will be stop immediately and the additional genset will be start
automatically. Otherwise, the current genset will running continuously until the remote
start signal deactivated.
In system "S1 Gen S2 Gen" to start/stop genset should meet following several
conditions:
1) It is active in Auto mode;
2) System set as "S1 Gen S2 Gen";
3) Output port should be set as "S1 Genset Start" and "S2 Genset Start ";
4) Input port should be set as "S1 Genset Fault Input", "S1 Genset Fault Input" and
"Remote Start On Load" or "Remote Start Off Load";
5) Should set start mode when "S1 Gen S2 Gen" system is selected;
6) Should configure setting "Genset Supply Delay",If start mode is cycle run, also
should set "S1 Cycs Run Time" and "S2 Cycs Run Time";
Among input ports, "S1 Genset Fault Input" and "S2 Genset Fault Input" are
selective setting, Genset fault can be judged by "Genset Supply Delay" and there no
need to inquire the fault alarm via input port.When S1, S2 start type configured as
"Not Used", there is no start genset signals output
Manual mode is selected by pressing the button; a LED besides the button will
illuminate to confirm the operation.
Press S1 button, S1 close relay will active, after the close delay has expired,
S1 close relay will deactivated and the S1 take load. Press S1 button again
(Invalid for the ATS without Open Control), S1 open relay will active, after the open
delay has expired, S1 open relay will deactivated and the S1 off load.
Press S2 button, S2 close relay will active, after the close delay has expired,
S2 close relay will deactivated and the S2 take load. Press S2 button again
19
ATS 420 ATS CONTROLLER USER MANUAL
(Invalid for the ATS without Open Control), S2 open relay will active, after the open
delay has expired, S2 open relay will deactivated and the S2 off load.
Automatic operation
Auto mode is selected by pressing the button; a LED besides the button will
illuminate to confirm the operation. The controller will select S1 power or S2 power
according to the preset "master set" and control the genset to start according to the
preset conditions.
ATS Power L2
ATS Power N
ATS Power L
A1 A2 N1 N2 A1 A2 B1 B2
25 26 27 28 29 30 25 26 27 28 29 30
20
ATS 420 ATS CONTROLLER USER MANUAL
The following is the prompt information and status display, also including
warning/alarm status.
NO. Item Description
When there is fault alarm occurs, the indication will be
Please reset the displayed when change the genset mode to Auto
1
alarm Mode manually.
Show in status bar
After S1 was already closed, the indication will be
S1 was already
2 displayed when "S2 close" button is pressed.
closed
Show in status bar
After S2 was already closed, the indication will be
S2 was already
3 displayed when "S1 close" button is pressed.
closed
Show in status bar
Cycle Run Start Mode is active when "S1 Gens S2
Cycle Gen Start
4 Gens" system is active.
Mode
Show in status bar
Balance Run Start Mode is active when "S1 Gens S2
Balance Gen Hours
5 Gens" system is active.
Mode
Show in status bar
Master Run Start Mode is active when "S1 Gens S2
Master-Slave Gen
6 Gens" system is active.
Start Mode
Show in status bar
Current mode is Auto mode.
7 Auto Mode
Show in status bar
Current mode is Manual mode.
8 Manual Mode
Show in status bar
Parameter setting
Enter the edition page
Please set the parameters according to below steps:
1) In the any status and there is no alarm, please press for 3 seconds to enter
the parameter setting mode. The default password is “07623”.
2) Press and add number 1, press to reduce number 1, press to turn
the digit into right, press once done. Then system comes into menu after
confirmation of password setting. The screen will display error if password is
wrong. The correct password should be put after pressing any button.
22
ATS 420 ATS CONTROLLER USER MANUAL
3) Press to turn the digit into upper position, press to turn the digit into
lower position, press to get into parameters setting page.
4) Press to shift up the parameters, press to shift down the parameters,
press to get into parameter changing page.
5) Press to add number 1, press to reduce number 1, press to turn
the digit into right, press once done. If the parameters setting is in the valid
setting range,then it can be saved, if not, it can not be saved.
6) Press to save the parameters and exit from edition page.
7) Press to revert back to last class if in any setting position.
Revert back to default: put password "97011" when coming into parameters
setting, then all the parameters can be set as defaults.
Note: the data can’t be saved if the user didn’t press to confirm the setting.
Parameter list.
1) Basic setting
No Parameter Range (default) Notes
0-English
0 Language Language option.
1-简体中文
S1 Available The delay from S1 voltage abnormal
1 1-3600S(10S)
Delay to normal.
S1 Unavailable The delay from S1 voltage normal to
2 1-3600S(5S)
Delay abnormal.
S2 Available The delay from S2 voltage abnormal
3 1-3600S(10S)
Delay to normal.
S2 Unavailable The delay from S2 voltage normal to
4 1-3600S(5S)
Delay abnormal.
0: S1 Master
5 Master-Slave Set 1: S2 Master Main and backup generator selection
2: No Master
0: S1 Mains S2 Gen
1: S1 Gen S2 Mains
6 System Type Set Select the system type of S1, S2.
2: S1 Mains S2 Mains
3: S1 Gen S2 Gen
0: Single Phase,2-Wire
1: 2-Phase,3-Wire AC power supply mode for closing
7 AC System
2: 3-Phase,3-Wire output.
3: 3-Phase,4-Wire
AC system rated voltage value, used
8 Rated Voltage 0-600V (220V)
to calculate the alarm value.
AC system voltage upper limit. If the
Over Volt Set value is greater than the upper limit, it
9 0-200%(120%)
Value will be abnormal. It will be disabled
when the maximum value is 200.
23
ATS 420 ATS CONTROLLER USER MANUAL
2)Switch setting
NO Parameter Range(default) Notes
1 Close Time 1-20S(5S) Pulse time of close relay
2 Open Time 1-20S(5S) Pulse time of open relay
Interval time from S1 switch open to S2 switch
3 Transfer Interval 0-9999(1S) close; or from S2 switch open to S1 switch
close.
When the breaker fail to open for the first time,
then the module will close for the second time
and the Again Close Delay begins, after the
4 Again Close Delay 0-20S(1S)
delay has expired, if still failed to open for the
second time, the module will send out fail to
open alarm.
When the breaker fail to close for the first time,
5 Again Open Delay 0-20S(1S) then the module will open for the second time
and the Again Open Delay begins, after the
24
ATS 420 ATS CONTROLLER USER MANUAL
3)Generator setting
Range
NO Parameter Notes
(defaults)
When the genset is ready to start, start delay
Gen Start
1 0-9999S(1S) begins, after the start delay has expired, start
Delay
signal will be initiated.
When the genset is ready to stop, stop delay
2 Gen Stop Delay 0-9999S(5S) begins, after the stop delay has expired, stop
signal will be initiated.
0: Cycles Gens
1: Master-Slave
Gen-Gen Start
3 Gens Generator start mode.
Mode
2: Balance Gens
Hours
S1 Cycles
4 0-9999Min(720Min) Gens cycle start S1 running time.
Work Time
S2 Cycles
5 0-9999Min(720Min) Gens cycle start S2 running time.
Work Time
When the start signal is active, the start delay
Genset will be initiated. If the gen voltage lasts abnormal
6 0-9999S(120S)
Available Time after the delay has expired, "Genset Fault" alarm
will be initiated.
Battery Under "Battery Under Volts" alarm will be initiated if the
7 0-100V(10V)
Volt Set Value battery voltage has fallen below the set value.
Battery Under
"Battery Under Volts" alarm will be removed if
8 Volt Return 0-100V(10.5V)
the battery voltage has exceeded the set value.
Value
Battery Over "Battery Over Volts" alarm will be initiated if the
9 0-100V(30V)
Volt Set Value battery voltage has exceeded the set value.
25
ATS 420 ATS CONTROLLER USER MANUAL
Battery Over
"Battery Over Volts" alarm will be removed if the
10 Volt Return 0-100V(29.5V)
battery voltage has fallen below the set value.
Value
4)Input/Output setting
No Parameter Range(defaults) Notes
0-25(2:Remote 0: Disable: Disable this digital function
1 AUX.INPUT 1
start on Load: ) 1: Forced Open: No matter the genset is in
manual mode or Auto mode, when the input
is active, this will force the breaker to
transfer the ATS to OFF position. "No
Breaking" ATS is unavailable.
2: Remote start on Load: When the mains
power is normal, the generator set will start
to output and the generator will close.
3: Remote start Off Load: When the mains
power is normal, the generator set starts to
output and the power generation is not
closed.
0-25(1:Forced 4: S1 Fault Input: When the unit is turned on
3 AUX.INPUT 2
Open) cyclically, the unit fails and cannot be
started.
5: S2 Fault Input: When the unit is turned on
cyclically, the unit fails and cannot be
started.
6: Breaker Trip Input: Switch trip fault input.
7: S1 Master Input: Force S1 to be active.
8: S2 Master Input: Force S2 to be active.
9:Test lamp: LED indicators on the panel are all
on; LCD backlight is on; LCD screen is
dark;
10-25: Reserved
0-40(11: Gens 0: Disable: Disable this relay function.
9 AUX.OUTPUT 1
Start Output) 1: Common Alarm: Output when the unit has
0-40(20: ATS any alarm, until the alarm is reset.
11 AUX.OUTPUT 2
Power L) 2: Common Fault Alarm: Output when the unit
has any fault alarm, the controller will open
until the alarm resets.
3: Common Warn Alarm: It is output when the
unit has any warning alarm, until the alarm
is reset.
4: Transition Fault: It includes S1 Fail to Close
0-40(23: ATS alarm, S1 Fail to Open alarm, S2 Fail to
13 AUX.OUTPUT 3
Power N) Close alarm, S2 Fail to Open alarm.
5: S1 Available: Output when S1 power is
normal.
6: S1 Unavailable: Output when S1 power
supply is abnormal.
7: S2 Available: Output when S2 power is
normal.
26
ATS 420 ATS CONTROLLER USER MANUAL
27
ATS 420 ATS CONTROLLER USER MANUAL
5)Module setting
No Parameter Range(default) Notes
0: Manual
The primary modes on power, easy for
1 Primary Modes 1: Auto
user operation.
2: Previous Mode
2 Controller ID 1-255(16) The IP built by controller and PC.
00000-
3 User password Change the password.
65535(07623)
0-4800
4 RS485 baud rate 1-9600 RS485 communication baud rate.
2-19200
1
5 Stop Bit 2 stop bits or 1 stop bit can be set.
2
Current 2016/01/01- Permanent calendar inside, please correct
6
Year/Month/Date 2099/12/31 the date timely.
Permanent calendar inside, please correct
7 Current time 00:00:00-23:59:59
the time timely.
8 Start screen display 0-20.0s (5.0s) Start screen display time,0: No-display.
LCD light will be closed automatically
5.0-6000.0s without any button pressed after delay. If
9 Saving mode
(600.0s) setting as 6000.0s, back light always
lighted.
The time when the page reverts back to
10 Homing display 5.0-600.0s (600.0s) the home page, If setting as 600.0s:
disabled.
Start screen will be opened without any
LOGO delay display 5.0-
11 button pressed after delay, If setting as
under standby 6000.0(6000.0s)
6000.0s: disabled.
12 LCD contrast 50-127(106) Set the LCD display contrast.
6)Working and maintenance setting
No Parameter Range(defaults) Notes
This mode must be under auto mode.
Working plan is disabled once setting as disable.
Disable
Working plan The working plan will be executed according the
1 Every month
format chosen date when setting as every month.
Every week
The working plan will be executed according the
chosen date when setting as every week.
From 1st to 31st
Maintenance
2 Default: the first The date chosen for every month.
date per month
day
Maintenance Monday to Sunday
3 The date chosen for every week.
date per week Default: Sunday
Maintenance
Disabled/with
4 with load or To choose if the genset starts with load or not.
load
not
Maintenance 00:00-
5 Maintenance start time setting.
start time 23:59(00:00)
Maintenance
6 1-120m(5m) Maintenance running time setting.
running time
28
ATS 420 ATS CONTROLLER USER MANUAL
Fault finding
Symptoms Possible Solutions
Check DC voltage.
Controller no
Check DC fuse.
response with power
Check AC Power supply.
Check the system type setting;
Genset Start
Check the output port function type and output settings;
Abnormal
Check various start / stop function settings
Check switch
Check the connection between the controller and the switch;
Genset running while
Check whether the switch type setting is consistent with the
ATS not transfer
switch;
Check ATS power settings and wiring
Check auxiliary output connections, pay attention to normally
Auxiliary Output Error open contact and normally close contact.
Check the output settings in parameters settings.
Check whether the programmable input port is reliably grounded
when the input is valid, and it should be left floating when the
Auxiliary Input input is invalid (Note: If the input port is connected to an
Abnormal excessively high voltage, it may burn the input port);
Input port setting function and input valid type in detection
parameter setting
Check the USB connection.
USB communication Check whether the USB port of the computer is normal.
is abnormal Check whether the USB driver is installed.
Check whether the controller is normally powered on.
Check the connection.
Check if the communication ID number setting is correct.
RS485 cannot
Check if the A and B lines of RS485 are reversed.
communicate
Check if the RS485 communication line driver is installed or not.
normally
Check if the communication port of the PC is damaged.
Add a 120 Ω resistor between the AB of the controller RS485.
29