Fiberhome Micro Module
Fiberhome Micro Module
Product introduction
Fit Atom single cabinet solution, taking the
cabinet as the carrier, integrates power
distribution, UPS, cooling system, monitoring
(with display), with fully enclosed structure, not
affected by internal and external environment. It
occupies a small area, has low noise, and can be
placed in the installation place freely.
Application scenario
It is applied to small and micro computer room,
distributed computer room, edge computing
node computer room, offline business hall, etc.
Simple
l Pre-installed components, ready to use;
l Only one power incoming line is
required;
l No need to install outdoor unit (all-in-
one);
l No need for computer room.
Compact
l Cabinet-type computer room, saving at
least 50% of the area
Safe
l Built-in rack type fire fighting device;
l Fully enclosed cabinet, dust-proof and Integrated framework
moisture-proof;
l Standard C-level lightning protection.
Technical parameter
Basic parameters
Power supply system 220/230/240Vac,50/60Hz
Working temperature 0~40℃
Humidity range 5~95%
0~4000 (When the altitude exceeds 1000m, the capacity needs
Altitude
to be reduced.)
Cabinet System
Cabinet dimension (W×D×H) 600mm×1100mm×2000mm
A single cabinet contains power, cooling, monitoring, and
Cabinet composition
equipment space
Monitoring System
Short message alarm Standard
Mobile phone APP Optional
Water immersion sensor Optional
Temp. & humidity sensor Optional
Door magnetic Optional
Smoke sensor Optional
Large screen display Optional
Battery smart management Optional
Web interview Standard
Video Optional
Technical parameter
Other system
Fire fighting Rack type fire fighting, 1U, optional
Emergency heat dissipation Emergency fans at top of the cabinet, optional
Fit Array Single-row
Intelligent Micro-Module Data Center
Product introduction
Fit Array single-row solution can be
expanded on demand between 2-8 cabinets,
integrates power distribution, UPS, cooling
system, monitoring (with display), with fully
enclosed structure, not affected by internal
and external environment.
Application scenario
It is applied to small computer room, county
economies (enterprise and units), scientific
research institutions, primary and secondary
schools and training institutions, primary and
secondary medical institutions.
Product features
Rapid deployment
l Integrated design, pre-install and debug before
delivery, only simply assembling at site. It can be
used after power line connection;
l No site surveys, little reliance on the environ-
ment, no need for computer room installation,
rapid deployment in various scenarios.
High efficient and energy saving
l The hot and cold aisles are closed and isolated,
which can make full use of the cold capacity;
l Row-level or rack-mounted air-conditioning for
refrigeration, installed close to the server
equipment, shortening the refrigeration path;
l A dop t high- e f f i c i e n c y U P S s y s t e m , h i g h -
efficiency energy-saving system.
Reliable
l Fully enclosed design, anti-dust and anti-noise;
l Support N+1, 2N use, ensure the safe running of
IT device to the greatest extent
Technical parameter
Basic parameters
Power supply system 380/400/415Vac,50/60Hz, 3Ph+N+PE
Aisle type Single-row, cold aisle, hot aisle, fully closed
Protection level IP20
Working temperature -20~45℃
Cabinet number 1~8
IT cabinet number 1~6
Maximum power consumption of IT load 50kVA
Single cabinet maximum power density 10kVA
Installation type Unrestricted
IT cabinet load-bearing Static: 1500kg
W×1400×2000; 600≤W≤4800 (include air conditioner)
Overall dimension W×D×H (mm)
W×1200×2000; 600≤W≤4800 (exclude air conditioner)
Cooling system
Power input 380/400/415Vac, 50/60Hz, 3Ph+N+PE
Cooling capacity 12.5kW
Air conditioner configuration 1+0,1+1,2+0,2+1
Cooling mode Air-cooled
Moisture heat ratio 1
Installation type Row level
Monitoring System
Support WEB remote interview, short message alarm, multi-
Monitoring platform
module unified management
Local interface Standard
Water immersion sensor Optional
Smoke sensor Optional
Door magnetic Optional
Temp. & humidity sensor Optional
APP Optional
Access control Optional
Video Optional
Fit Atrix Double-row
Intelligent Micro-Module Data Center
Product introduction
Fit Atrix double-row micro-module adopts
integrated solution, integrates cabinet system,
power distribution system, cooling system,
monitoring system and complex wiring system. It
has high density modular, high reliability and
safety, rapid flexible deployment and high
efficient energy saving.
Application scenario
It is applied to medium and large machine rooms,
prefecture-level and national-level economies
(enterprise, unit), supercomputing center, university,
large integrated hospital, traffic command center
and power dispatching command center.
Product features
Easy to use
• Standard component and structure makes it can
be quickly deployed on demand;
• Product prefabricated, plug and play, no need of
complex configuration;
• Unified monitoring, smart management, mobile
operation and maintenance,simple and relax.
High efficient
• Efficient modular UPS for flexible configuration;
• Near-end refrigeration, airtight channels, isolation of
hot and cold air flows, eliminating local hot spots.
Safe
l Pow er s u p p l y a n d d i s t r i b u t i o n s y s t e m N + 1 / 2 N
architecture design ensures the safe and stable
operation of the computer room;
l Closed aisles adopt movable skylight, linking with fire
fighting system, not affecting gas fire extinguishing.
Technical parameter
Basic parameters
Single row closed cold/hot aisle (L×D×H)
L×2400mm×2000mm, L≤15m, cabinet depth 1200mm
L×2300mm×2000mm, L≤15m, cabinet depth 1100mm
L×2400mm×2200mm, L≤15m, cabinet depth 1200mm
L×2300mm×2200mm, L≤15m, cabinet depth 1100mm
Micro-module dimension
Double row closed cold/hot aisle (L×D×H)
L×3600mm×2000mm, L≤15m, cabinet depth 1200mm
L×3400mm×2000mm, L≤15m, cabinet depth 1100mm
L×3600mm×2200mm, L≤15m, cabinet depth 1200mm
L×3400mm×2200mm, L≤15m, cabinet depth 1100mm
Cabinet number Single row: 2~24; double row: 6~48
Power supply type 380/400/415Vac,50/60Hz, 3Ph+N+PE
Single module IT power 200kW
Single cabinet maximum power 20kW/R
Reliability level Up to GB50174 A level Tier 3
Installation type Cement floor installation or raised floor installation
0~1000m (more than 1000m needs to be used with reduced
Altitude
capacity)
Cabinet system
600mm×1100mm×2000mm; 600mm×1200mm×2000mm;
Dimension (W×D×H) 600mm×1100mm×2200mm; 600mm×1200mm×2200mm;
800mm×1100mm×2000mm; 800mm×1200mm×2200mm
Available space 42U/47U
Protection level IP20
Cooling system
Air-cooled: 25kW (half cabinet), 40kW (full cabinet)
Cooling capacity
Water-cooled: 30kW (half cabinet), 65kW (full cabinet)
Indoor unit dimension (W×D×H) 300×1200×2000mm, 600×1200×2000mm
Input power 380Vac
UPS system
Input voltage 380V/400/415Vac, 50/60Hz, 3Ph+N+PE
Output power factor 1
Rate capacity ≤200kVA
Overall efficiency ≥96.5%
AC lightning protection D level