Short Circuit Current For Transformer
Short Circuit Current For Transformer
Example for 33/11 kV, 10 MVA (Supply Test Voltage = 400 Volt)
10% of Vsupply = 400 x 10/100 = 40 V
Ipri = 175 Amp
Vpri (kV) = 33 kV
Z% =9%
Z% = 40 x 175
33 x 23.569
Z%= 9.00 %
3 Phase Fault = ?
Fault Amax =?
Isc = 10% Vsupply x Ipri
Vpri (kV) x Z%
Pick-up current
▪ pickup is defined as that minimum current that starts an action.
▪ pickup current of an overcurrent relay is the minimum value of
current that will cause the relay to close its contacts.
▪ For an induction disk overcurrent relay, pickup is the minimum
current that will cause the disk to start to move and ultimately
close its contacts.
▪ For solenoid-actuated devices, tap or current settings of these
relays usually correspond to pickup current.
➢ Means of adjusting the time taken by the relay to trip once the current
exceeds the set value
Where,
T.M.S = T/ Tm
T -is the required time of operation
Tm -is the time obtained from the relay characteristics curve at TMS 1.0
and using the Plug Setting Multiplier (PSM) equivalent to the maximum
fault current
4
Instantaneous Setting
11/0.433 kV
2.5MVA, 8%(Z%)
IF
i) Pick up
Say 120% of full FLC
Pick up of relay = 1.2 x Iflc = 1.2 x 3333.5 = 1.2 x 3333.5 x 5 =
5