Megadysc Dynamic Voltage Sag Corrector - 800 Amp, 208 Volt: User Manual
Megadysc Dynamic Voltage Sag Corrector - 800 Amp, 208 Volt: User Manual
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, DySC, i-Sense, MegaDySC, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.
New and Updated This table contains the changes made to this revision.
Information Topic Page
Fault Protection 33
Notes:
Chapter 1
Introduction Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 2
Installation System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
SR System Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ER System Layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
System Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Pre-Installation Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Preparing the SR System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Preparing the ER System for SBS layout . . . . . . . . . . . . . . . . . . . . . . . . 15
Preparing the ER System for BTB layout . . . . . . . . . . . . . . . . . . . . . . . 16
System Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Mechanical Interconnection of Cabinets . . . . . . . . . . . . . . . . . . . . . . . 17
MegaDySC Floor Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electrical Interconnections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Electrical Supply and Load Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
MegaDySC System Installation Connections Checklist. . . . . . . . . . 24
Chapter 3
Communication Remote Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Modbus TCP/IP Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
i-Sense® Voltage Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Chapter 4
Applying Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Chapter 5
Operation System Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
MegaDySC Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Automatic Bypass Switchboard Operation . . . . . . . . . . . . . . . . . . . . . . . . . 30
Automatic Bypass Switchboard Operating Instructions . . . . . . . . . . . . . 31
Automatic System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Manual Transfer to Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . 31
Manual Transfer to MegaDySC System . . . . . . . . . . . . . . . . . . . . . . . . 31
Transient Voltage Surge Suppressor (TVSS). . . . . . . . . . . . . . . . . . . . . . . . 32
Troubleshooting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Normal Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Fault Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Diagnostic Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Chapter 6
Display Screen Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Home Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Mechanical Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
System Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Voltage Sag Events. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Voltage Sag Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Voltage Sag Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Voltage Sag RMS Voltage Charts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Voltage Sag Notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
System Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
System Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
System Event Detail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
System Event Notification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Model Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Run System Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Diagnostics Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Chapter 7
Maintenance Preventative Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Servicing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Automatic Circuit Breakers, Safety Interlocks and Stored Energy . 52
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Automatic Bypass Switchboard Fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . 53
MegaDySC and ER Cabinet Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Chapter 8
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.
Resource Description
MegaDySC Dynamic Voltage Sag Corrector - 400 Amp Model Provides information on installation, operations,
User Manual 1608M-UM001 maintenance and specifications.
MegaDySC Dynamic Voltage Sag Corrector - 800 Amp Provides information on installation, operations,
Models User Manual -1608M-UM002 maintenance and specifications.
MegaDySC Dynamic Voltage Sag Corrector - 800 Amp Provides information on installation, operations,
Extended Run Models User Manual - 1608M-UM004 maintenance and specifications.
Industrial Automation Wiring and Grounding Guidelines, Provides general guidelines for installing a Rockwell
publication 1770-4.1 Automation industrial system.
Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and
other certification details.
Notes:
The MegaDySC corrector reports these voltage sag events through its integrated
touch screen display and provides system status, voltage sag notification and
history, runtime statistics and system history in a simple and intuitive touch-
based user interface.
Installation
System Components The Standard Run (SR) MegaDySC® system consists of two enclosures including
one 800A MegaDySC module and one automatic bypass switchboard. The
Extended Run (ER) MegaDySC system consists of three enclosures including
one 800A MegaDySC module, one Extended Run (ER) module and one
automatic bypass switchboard. The enclosures are shipped separately and must be
mechanically and electrically interconnected at the time of installation.
The 800A MegaDySC module houses the static bypass and voltage sag-
correction electronics. The ER module houses the ER energy storage capacitors.
The automatic bypass switchboard houses the maintenance bypass circuit breaker
(CBB), the MegaDySC input (CBI) and output (CBO) circuit breakers,
automatic controls and the i-Sense® voltage-monitoring sensor.
6+,33,1*63/,7
&$%/((175<3/$7(
72321/<
&86720(5,23/$7(
72321/<
ER System Layout The ER MegaDySC system can be configured in two ways: with the ER module
mounted to the right of the 800A MegaDySC module (side-by-side), or with the
ER module mounted behind the 800A MegaDySC module (back-to-back). ER
SBS System Layout shows the side-by-side (SBS) system layout. ER BTB System
Layout shows the back-to-back (BTB) system layout.
IMPORTANT The desired system layout, SBS or BTB, must be identified before cabinets are
mounted as described in System Mounting on page 17.
6+,33,1*63/,7
6+,33,1*63/,7
&$%/((175<3/$7(
72321/<
&86720(5
,23/$7(
72321/<
6+,33,1*63/,7 6+,33,1*63/,7
6+,33,1*63/,7
&$%/((175<3/$7(
72321/<
&86720(5,23/$7(
72321/<
$8720$7,& $
0(*$'\6& (502'8/(
%<3$66
6:,7&+%25' 02'8/(
6+,33,1*63/,7
System Clearance The two automatic bypass switchboard doors are hinged on the left, the 800A
MegaDySC module door is hinged on the left, and the ER Module door is
hinged on the right. Clearance must be given to allow the doors to swing fully
open as shown in the SR System Layout on page 12, the ER SBS System Layout
on page 13, and the ER BTB System Layout on page 14.
Only front access and top access are required for installation and commissioning.
Rear access and left side access should be maintained when possible, to simplify
future maintenance tasks.
Pre-Installation
Configuration
IMPORTANT Perform system configuration steps before mounting and anchoring.
Follow instructions for: Preparing the SR System, or Preparing the ER System for
SBS layout, or Preparing the ER System for BTB layout on page 16.
1. Remove all tan-colored masking dots, blue-colored tape, and all plastic
sheets.
2. Remove all eight plastic 13 mm hole plugs in the right side of the
switchboard cabinet.
3. Remove and save for later step: four hex-head bolts with lock washer and
flat washer in left side of MegaDySC cabinet. [tool required: 9/16-inch
wrench or socket]
1. Remove all tan-colored masking dots, blue-colored tape, and all plastic
sheets.
2. Remove all eight plastic 13 mm hole plugs in the right side of the
switchboard cabinet.
3. Remove and save for later step: four hex-head bolts with lock washer and
flat washer in left side of MegaDySC cabinet. [tool required: 9/16-inch
wrench or socket]
4. Remove two 75 mm electrical knock-outs (EKO) in the bottom-right side
of MegaDySC cabinet. Refer to Figure 4 on page 16.
5. Remove the two front-most 13 mm plastic hole plugs in the right side of
the MegaDySC cabinet. Leave the two rear-most hole plugs in place. Refer
to Figure 4 on page 16.
6. Remove two 63 mm EKOs in bottom-left side of ER storage cabinet. Refer
to Figure 5 on page 16.
7. Remove and save for later step: two hex-head bolts with lock washer and
flat washer in left side of ER storage cabinet. [tool required: 9/16-inch
wrench or socket]. Refer to Figure 5 on page 16.
8. Remove tie plate from the top of the ER storage cabinet, discard the sheet
of padding material, and replace the tie plate and screws—tie plate is not
needed for the SBS layout.
1. Remove all tan-colored masking dots, blue-colored tape, and all plastic
sheets.
2. Remove all eight plastic 13 mm hole plugs in the right side of the
switchboard cabinet.
3. Remove and save for later step: four hex-head bolts with lock washer and
flat washer in left side of MegaDySC cabinet. [tool required: 9/16-inch
wrench or socket]
4. Remove two electrical knock-outs (EKO) in the bottom-rear panel of
MegaDySC cabinet.
5. Remove the cover plate from the bottom-rear of the ER storage cabinet.
Save the cover and screws for possible later use—they are not needed for
the BTB layout.
System Mounting The MegaDySC system is provided with interconnect bus links between
cabinets; proper line-up is critical. The system must be configured as shown in SR
System Layout, ER SBS System Layout, or ER BTB System Layout. The system
must be placed on a flat level surface or shimmed during installation to achieve
the same effect.
The 800A MegaDySC module is shipped separately from the automatic bypass
switchboard and the ER Module. The 800A MegaDySC module, the automatic
bypass switchboard and the ER Module must be mechanically interconnected
with the supplied hardware and each enclosure must be secured to the floor
(Refer to Mechanical Interconnection of Cabinets on page 17 and MegaDySC
Floor Mounting on page 19).
The cabinets should be brought tightly together and all interconnection bolts
should be installed and tightened before tightening the anchor bolt connections.
To attach the 800 A MegaDySC module to the automatic bypass switchboard use
two sets of 3/8-16 [inch-thread/inch] hardware (this is the hardware that was
removed and saved during the pre-installation configuration). All hardware
should be installed from the automatic bypass switchboard side and threaded into
the PEM nuts located in the 800A MegaDySC module. Each hardware
connection set consists of one 3/8-16 x 1.0 in. bolt, one 3/8 in. split lock washer,
and one 3/8 in. flat washer assembled as shown in Figure 6 and Figure 7. Tighten
each bolt to 20 N•m [180 in•lb]. The required wrench size is 9/16 in.
(14.3 mm).
To attach the MegaDySC cabinet to the ER storage cabinet in the SBS layout,
install the two 3/8-16 interconnection bolts along the front of the cabinets, as
shown in detail B of Figure 6. Tighten each bolt to 20 N•m[180 in-lb].
To attach the 800A MegaDySC Module to the ER Module in the BTB layout,
remove the tie plate from the top of the ER cabinet, discard the sheet of padding
material, and install the tie plate between the two cabinets using four sets of 1/4-
20 [inch-threads/inch] screws as shown in Figure 6 on page 18. Tighten each
screw to 6.7 N•m [60 in-lb]. The screw heads are Phillips head.
Finally, after all interconnection hardware is installed; tighten the anchor bolt
connections to the torque specified by the anchor manufacturer.
DETAIL B
SCALE 1 : 8
DETAIL A
SCALE 1 : 8
Figure 9 - Floor Mounting Detail – ER System SBS Layout
Required Anchor Locations
;
Figure 10 - Floor Mounting Detail – ER System BTB Layout
;
Electrical Interconnections
WARNING: Equipment must be earth-grounded according to local and
national electric codes. Failure to supply proper equipment grounding may
result in electrical shock or death.
The 800A MegaDySC Module is shipped separately from the automatic bypass
switchboard and the ER Module. The customer is responsible for system
mounting and electrical supply and load connections. All interconnecting bus
bars and power cables are provided and will be connected by a factory-trained
technician during commissioning. At commissioning the bus links will be
connected between the automatic bypass switchboard and the 800A MegaDySC
Module. A control wiring cable is also provided in the automatic bypass
switchboard and must be connected to the 800A MegaDySC Module. This
control cable is routed through two large holes, one in the automatic bypass
switchboard and one in the 800A MegaDySC Module, located at the bottom
front of the enclosures. The cable is plugged into the associated terminal block
located in the lower, left corner of the 800A MegaDySC Module. In ER systems,
two other cable harnesses are routed between the 800A MegaDySC Module and
the ER Module.
Electrical Supply and Load Electrical termination hardware is supplied with each system. One box contains
all needed hardware for one system installation. The box is labeled:
Connections
MEGA DySC SE
CUSTOMER CONNECT HARDWARE KIT
The incoming 3-phase electrical service and outgoing load cables enter through
the top of the switchboard enclosure and connect to the appropriate bus
locations. To access the main electrical terminals:
The cable entry plate may be fitted for conduit or cable ladder as needed. The
other top panels may also be removed if needed. All panels must be replaced after
installation. Locations of the main electrical terminals are shown in Figure 12 and
Figure 13.
&21'8,7(175<$5($
&21'8,7(175< )25&$%/((175<3/$7(
$5($)25&86720(5 5(029(72372
,23/$7(5(029(723 '5,//$1'381&+
72'5,//$1'381&+
6<67(0*5281'6
1(875$/
:,5(
6<67(0621/<
28738772
3527(&7('/2$'6
87,/,7<,1387
'(7$,/9,(:)25
,1387$1'287387
&211(&7,216
Remote Diagnostics Customer-accessible dry contact-closures are available for relaying the state of the
circuit breakers and the state of the MegaDySC system. Connect to terminal
(TB1 Customer Contacts) block TB1 at the top of the left compartment of the automatic bypass
switchboard. See Figure 15 for connection details. The contact ratings are: 10 A
@ 240V AC resistive, 7 A @ 240V AC inductive, 10 A @ 28V DC resistive, and
8 A @ 24V DC inductive.
• CBB Closed (CR3A) – Contact is closed when the bypass circuit breaker
(CBB) is closed. Contact is open when CBB is open.
• CBI Closed (CR4A) - Contact is closed when the input circuit breaker
(CBI) is closed. Contact is open when CBI is open.
• CBO Closed (CR5A) - Contact is closed when the output circuit breaker
(CBO) is closed. Contact is open when CBO is open.
• DySC Alarm (CR7A) – Contact is closed when there is an active alarm on
the MegaDySC system. Contact is open when there is no alarm on the
MegaDySC system.
Modbus TCP/IP The MegaDySC system status and other items are communicated over a Modbus
TCP/IP connection. This can be accessed through RJ45 port number 5 on the
Communication Ethernet switch in the automatic bypass switchboard. Contact
Rockwell Automation technical support for protocol details.
The i-Sense requires communication over the Internet. The i-Sense should be
connected through RJ45 port number 5 on the Ethernet switch in the automatic
bypass switchboard.
• After installation, make certain there are no metal filings or any conductive
debris in or on any components inside the cabinets.
• Verify MegaDySC system voltage rating matches AC source voltage.
• Verify all input and output terminations including grounding have been
completed and properly tightened.
• Replace all covers. Close and lock all cabinet and switchboard doors.
• Allow commissioning technicians to complete connections and initial
checks
• Apply power from the upstream branch protection device when instructed
to do so by the commissioning technicians.
• After commissioning, follow instructions on the Automatic Bypass
switchboard to put the system into Normal mode. The load is now being
monitored by the MegaDySC system. The display should show “OK” in
the upper left corner.
Notes:
System Description Raw utility power enters and routes through the Automatic Bypass switchboard
to the load. In maintenance bypass mode the power bypasses the MegaDySC®
cabinet and passes directly to the load. In this mode the load is unprotected from
voltage sags. In the Normal operation mode the MegaDySC cabinet is energized
and the power is directed through the MegaDySC, protecting the load. See the
following sections for MegaDySC and Automatic Bypass operation details.
IMPORTANT Operation in Normal Mode requires that the maintenance bypass circuit
breaker (CBB) be open (OFF)—otherwise CBB will short the sag correction
inverter and prevent sag correction.
MegaDySC Operation The MegaDySC section contains three power electronics modules (one module
per phase) and controls that continuously monitor the line voltage. The modules
are series-connected to the input line, and operate by adding the compensating
voltage needed to restore the line to its nominal output. When the utility line
voltage is within normal range the AC static switch components remain closed
and no compensating voltage is added. When an insufficient line voltage event
occurs, the static switches open and the sag-correcting electronics quickly add the
balance of voltage necessary to regulate the load voltage.
The MegaDySC accepts line input power over 3 wires into terminals Rin, Sin, Tin
and provides sag compensated three-phase output power at terminals Rout, Sout,
and Tout when not in the Maintenance Bypass mode. In 4-wire systems the input
Neutral is connected directly to the output Neutral terminal.
Thermal switches are included to activate fans if the cabinet temperature or other
internal temperatures exceed set limits.
A red “FAULT” box is displayed in the upper left-hand corner of the display
when a fault condition is present on the MegaDySC. During this period, sag
correction is disabled and the MegaDySC will continue to bypass the utility
voltage directly to the load through the static bypass path.
An orange “FAULT OVER” box is displayed when the previous fault condition
has cleared. Sag correction will remain inhibited until the reset period expired
(approximately 1 minute). A blue “SYSTEM OFFLINE” box is displayed
Condition Definition Touch Screen Display STATUS text* Inverter Operation Bypass Mode
Normal: 88.5% < V LINE < 110% Green “OK” Standby Static BP
MegaDySC Over-temperature Internal temperature limit exceeded Blue, MegaDySC offline Disconnected Mech. Bypass
Static Switch Failure Open SCR(s) Blue, MegaDySC offline Disconnected Mech. Bypass
Main Fuse Open Open Fuse(s) Blue, MegaDySC offline Disconnected Mech. Bypass
Enclosure Door Open Door Open Blue, MegaDySC offline Disconnected Mech. Bypass
* The Touch Screen will power down if both input and output voltages fall below approx. 75% of nominal
**An error message will be displayed while the red or orange text box is displayed. Refer to Chapter 6 for further information on accessing
fault codes and status history.
Automatic Bypass The automatic bypass switchboard consists of a bypass circuit breaker (CBB), an
input circuit breaker (CBI), and an output circuit breaker (CBO). Under normal
Switchboard Operation operating conditions raw input power is routed through CBI to the input of the
MegaDySC. The output of the MegaDySC is routed to the load through CBO.
CBB is normally open. CBB connects utility power to the load, bypassing the
MegaDySC, when operating in the maintenance bypass mode.
WARNING: Dangerous voltages can still exist within the MegaDySC enclosure
even if the system is in bypass mode. Refer servicing to qualified personnel.
Transient Voltage Surge Over voltage transient protection is provided on the output of the MegaDySC
system. Indicator lights for each phase on the front of the TVSS panel (upper left
Suppressor (TVSS) compartment of the automatic bypass switchboard) are illuminated under
normal operation. In case of a severe over-voltage transient event, internal fuses in
the TVSS module may open. If TVSS operation is compromised, one or more of
the indicator lights will be extinguished. A form C contact is provided inside the
TVSS module for remote fault indication, if desired. Refer to the TVSS user
manual for details on accessing that contact. If a fault is indicated, the TVSS
disconnect fuse block (F14-F15-F16-F17) may be opened to allow servicing of
the TVSS module. Refer servicing to qualified personnel.
Troubleshooting Notes Refer servicing to qualified and factory authorized personnel. Opening the
MegaDySC cabinet door will shut down the MegaDySC system and force an
automatic mechanical bypass. Refer to manual bypass instructions to perform a
seamless transfer of power before opening the enclosure door for servicing.
Normal Mode
The NORMAL mode for the MegaDySC is Input Breaker (CBI) and Output
Breaker (CBO) closed. The bypass breaker (CBB) must be open or the
MegaDySC will not be able to correct voltage sags. There is a red indicator light
on the bypass enclosure that is lighted when the bypass is closed. The green “OK”
status box should be shown on the touch screen display. The green “OK” box
indicates that the voltage at the output of the MegaDySC is within the +10%, -
13% normal window. Refer to Table 1 for operational conditions and indications.
Bypass Mode
The BYPASS mode for the MegaDySC is for Input Breaker (CBI) and Output
Breaker (CBO) to be open. The bypass breaker (CBB) must be closed to provide
power to the load while the MegaDySC is being serviced.Refer to Automatic
Bypass Switchboard Operation on page 30 or the placard on the bypass
switchboard for instructions on transferring the system into and out of bypass
mode.
Test Mode
The TEST mode for the MegaDySC is for Input Breaker (CBI) to be closed and
Output Breaker (CBO) to be open. The bypass breaker (CBB) must be closed to
provide power to the load while the MegaDySC is being tested off-line.
Fault Protection
Fault protection is provided by a variety of protection devices including
electronic, circuit breakers and fuses.
CBI and CBO are set to protect the MegaDySC conductors. If an upstream
circuit breaker is present, CBB is typically coordinated to allow the upstream
breaker to be the primary protection for the branch circuit.
In addition, each module has an electronic current limit function that will
protect the inverter module from peak over currents during sag protection
operation.
IMPORTANT In the event of the operation of any over current protection function, check the
touch screen display on the MegaDySC for error codes that may indicate the
type of over current condition.
Each of CBB, CBI, CBO contains an electronic trip unit with adjustable trip
settings. Refer to label on the Automatic Bypass Switchboard for circuit breaker
factory settings.
Diagnostic Indicators
IMPORTANT Record any Alarm or System Event messages seen on the display before
contacting Technical Support.
IMPORTANT Alarm types 1, 2, and 3 may result in momentary interruption of power to the
load before transferring to mechanical bypass. Types 4 through 6 will result in a
seamless transfer to mechanical maintenance bypass, without interruption.
Notes:
When the system first starts, a welcome screen displaying the MegaDySC
product logo appears. This screen disappears after 5 seconds, when the “Home”
screen appears.
The touch screen is optimized for use with a plastic stylus or bare finger.
IMPORTANT To recalibrate from any screen, hold anywhere on the screen for 10 seconds.
You will see a small progress bar at the bottom of the screen. When the
progress bar reaches 100 percent, the calibration screen will open.
Home Screen The “HOME” screen of the display provides a snapshot view of the status of the
entire system (See Figure 21). You can return to this screen from any other screen
by pressing the “HOME” button. After 5 minutes of inactivity (i.e. not pressing
the screen), the touch screen will automatically return to the “HOME” screen.
The “HOME” screen is divided into four main areas described inTable 2.
Mechanical Bypass
Some systems equipped with a mechanical bypass display the bypass status in the
System Status panel on the Home Screen. When the mechanical bypass is closed,
the DySC unit is bypassed and voltage sags on the line will NOT be corrected.
System Status The “System Status” screen displays the real-time overall system status. Reach this
screen by pressing “STATUS” on the “HOME” screen or the “Status” area at the
top of the “HOME” screen
Figure 23 - System Status Summary Figure 24 - - System Status Waveforms
Mechanical Bypass
Some systems equipped with a mechanical bypass will display the bypass status in
the System Status panel on the Status Screen. When the mechanical bypass is
closed, the DySC unit is bypassed and voltage sags on the line will NOT be
corrected.
Voltage Sag Events A voltage sag is defined as the period when input RMS voltage drops to less than
88.5% of the rated DySC voltage. Details of each voltage sag and corresponding
MegaDySC protection are captured and saved to the voltage sag log.
Note: Use the up/down arrows to navigate through the list. Press the “SELECT” button to view additional details about
the voltage sag
The worst-case RMS voltage recorded during the event is displayed in the upper
window along with the corresponding voltage percentage and the event duration.
ID: Unique ID within the list (0-60) to identify the voltage sag
Time: Start time of the voltage sag
RMS: Worst-case RMS voltage (L-N) and percent of rated voltage across all phases
Sag Summary
Duration: Duration of the voltage sag
Frequency: Frequency of the line prior to the start of the voltage sag
Temperature: Internal temperature of the MegaDySC prior to the start of the voltage sag
Line Voltage: Line RMS voltage and percent of rated (L-N). Voltages ≤ 80% of nominal are
Sag Magnitude displayed in red.
Load Voltage: Load RMS voltage and percent of nominal (L-N).
The “Correction Result” is displayed in a box in the upper-right-hand corner of the “Event
Summary” section. The “Correction Result” conveys how the MegaDySC performed correcting
the voltage sag. The possible values are:
Protected: The output RMS voltage on all phases is ≥ 85 percent of nominal and the
Correction Result MegaDySC correction was active for the duration of the voltage sag (will be displayed in
green).
Run Error: An unexpected system event occurred during the sag (will be displayed in orange)
Run Inhibited: The MegaDySC system was inhibited when the sag occurred (will be displayed
in orange).
Note: The “Voltage Sag Detail” for the most recent event can also be accessed by pressing the “Last Voltage Sag” area of the “HOME”
screen.
Line voltage is shown in red and load voltage is shown in green. By pressing the
check boxes in the right column, you can toggle each data series Off and On as
well as enable y-axis auto-scaling.
Note: 300 cycles = 5.0 seconds at 60 Hz or 6 seconds at 50 Hz.
System Events The MegaDySC tracks all operational events which are classified into five groups
based on severity.
Auto-Resetting The MegaDySC will reset within 60 seconds. No user action is required.
User action may be required to correct a problem. The MegaDySC will reset 60
User Attention seconds after the error condition is corrected.
For system events that cause circuit breaker CBI to open a manual reset of the
Manual-Reset DySC system will be required.
For events classified as Call Service, factory trained service support will be
Call Service required. Contact Rockwell Automation technical support.
Event ID: Unique ID within the list (0-39) to identify the event.
Code: Abbreviation of the event followed by a numeric event code in parentheses. (For a
Type list of codes and abbreviations see Table 10 on page 50
Severity: Severity of the event
Description: Name of the event see Table 10 on page 50
Location: The location in the system where the event originated (i.e. Phase A, Phase B,
Phase C, etc.).
Area: The specific area within the location where the event originated (i.e. Inverter, etc.).
Component
Reading: a data value relevant to the System Event may be recorded in some cases, e.g.,
detail for an “Inverter Over-Current” alarm would include a reading of the causal high
current value. The reading “N.A.” is displayed if no appropriate data value exists.
Pressing the “OK” button will open the “System Event Detail” screen. The event
will appear in the event list after the event is over. The window can be closed by
pressing the “CANCEL” button or waiting 15 seconds.
When the event condition clears, a new dialog box will be displayed. Press “OK”
to view the complete event detail, or “CANCEL” to close the dialog box (See
Figure 33).
If a “Call Service” severity event is detected, record the event details including:
name, description, location, and reading. Contact product support immediately.
If the event clears, the touch screen will automatically go back to normal
operation.
System Configuration
Press the “CONFIG” button at the bottom of the “HOME” screen to enter the
“System Configuration” screen (See Figure 34). The “SET SYSTEM CLOCK”
and “CALIBRATE TOUCH SENSOR” functions are described at the start of
this chapter.
Model Information
Touch “VIEW MODEL INFORMATION” to go to the “Model Information”
screen. (See Figure 35).
Diagnostics Mode
This is not a user function. It is numerical code protected for authorized service
personnel.
Preventative Maintenance The MegaDySC system requires very little preventative maintenance. Check the
system periodically for proper air flow and status indicator operation.
Monthly Checks
• Check that the touch screen display is working and no active events are
displayed.
• Verify that the bypass switch is in the NORMAL mode.
• Update system time, if needed, Figure 20 on page 38.
• Use a soft cloth to clean the touch display. DO NOT USE harsh detergent,
abrasive sponges, alcohol, ammonia, toluene, or acetone on the touch
display.
• Verify air intake and exhaust filters are not covered or obstructed.
– Air filters for the MegaDySC will require periodic cleaning, with the
frequency depending on the environment. Filters are located on the
front side of the MegaDySC, and can be accessed with the door closed.
The MegaDySC need not have power removed for this operation.
Remove grill covers by unscrewing the thumb screw on the left side and
sliding the filter retainer up; the washable foam filter pads are behind
the grill cover. Gently wash the foam filter pads as needed with a light
non-abrasive soap and water mixture. Towel-dry; do not wring-out.
Place the filter and grill cover back into their location and replace the
screw caps by rotating clockwise until finger tight. Replace filter if
damaged. Consult Rockwell Automation technical support for
replacement filters. Replacement filters must be no more restrictive to
air flow than the original equipment filters.
Event Code Code Name Full Name Severity Area Event Description Event Resolution
1 POWER_ON DySC Power On Informational Unit Power re-applied to the DySC. No action needed.
4 T_FAN_ST Fan Test Start Informational Unit Start acknowledgment of DySC fan test. No action needed.
Start acknowledgment of DySC 0.5 cycle inverter
5 T_IN_ST_1 Inverter Test (.5 cycles) Start Informational Unit No action needed.
test.
Start acknowledgment of DySC 3 cycle inverter
6 T_IN_ST_2 Inverter Test (3 cycles) Start Informational Unit No action needed.
test.
7 T_IN_ST_3 Inverter Test (5.5 seconds) Start Informational Unit Start acknowledgment of DySC 5.5 second No action needed.
inverter test.
9 EXTERNAL External Inhibit Auto-Resetting Inverter Controller is inhibited by another phase controller. Review event details from other phase controllers.
11 RUN_TO Inverter Run Timeout Auto-Resetting Inverter DySC inverter had a total cumulative runtime of No action needed.
more than rated.
12 LIM_CYCLE Inverter Limit Cycle Timeout Auto-Resetting Inverter
Power was re-applied more than once within a 58 No action needed.
second period.
Verify ambient temperature is within DySC
Static Static switch heatsink temperature was greater
13 STAT_OT Static Switch Over-Temperature User Attention specification. Check for damaged fans. Check for dirty
Switch than maximum rating.
or obstructed air filters.
Inverter inhibited because load current exceeded Reduce load. In parallel DySC systems, verify proper
14 OVERLOAD Overload User Attention Unit
maximum rating. current sharing among slave cabinets.
Positive or negative half of DC bus voltage Verify line voltage is within ratings. Verify proper DySC
15 DC_OV DC Bus Over-Voltage User Attention Inverter
exceeded maximum rating. application. Call service.
Verify DySC is online and line voltage is within ratings.
16 CNTRL_UV Controller Power Under-Voltage User Attention Inverter DySC control power supply is out of tolerance.
Call service.
DySC output voltage was less than 80% of Verify line voltage is within ratings. Verify proper DySC
17 OUTPUT_UV Output Under-Voltage User Attention Inverter nominal during sag correction. Sag condition
application.
likely outside of DySC specification.
Inverter current exceeded maximum rating during Verify load current is within ratings. Verify mechanical
18 INV_OC Inverter Over-Current User Attention Inverter sag correction. bypass switch is open. Verify proper DySC application.
19 DC_UV DC Bus Under-Voltage User Attention Inverter DC bus voltage below operational range. Verify line voltage is within ratings. Call service.
DySC output voltage was greater than 115% of
20 OUTPUT_OV Output Over-Voltage Call Service Inverter Call service.
nominal during sag correction.
IGBT pack reported error. Possible sag condition Verify line voltage is within ratings. Verify proper DySC
22 IGBT IGBT Pack User Attention Inverter
outside of DySC specification. application. Call Service.
Inverter not synchronized to line when sag
25 SYNC_ERR Line Synchronization Error Call Service Inverter Call service.
detected.
31 CONFIG Configuration Alert Call Service Inverter Controller configuration has changed. Call service.
32 CNTRL_MEM Controller Memory Busy Auto-Resetting Inverter Controller is loading new data into Flash memory. No action needed.
Event Code Code Name Full Name Severity Area Event Description Event Resolution
Positive and negative halves of the DC bus did not
33 UNBALANCE Start-Up Test: DC Bus Unbalance Call Service Inverter Call service.
charge equally during power up.
Output voltage was detected out of tolerance
34 AC_V_CHK Start-Up Test: AC Voltage Check Call Service Inverter Call service.
during the start-up test.
Controller communication problem detected
35 ROLL_CALL Start-Up Test: Controller Roll Call Timeout Call Service Unit during start-up test. Call service.
36 COM_VER Start-Up Test: Communication Call Service Unit Firmware communication compatibility problem Call service.
Compatibility Mismatch detected during start-up test.
37 CNFG_TO Start-Up Test: Controller Configuration Call Service Unit Controller communication problem detected Call service.
Timeout during start-up test.
Start-Up Test: Controller Configuration Controller firmware configuration problem
38 CNFG_ERR Mismatch Call Service Unit detected during start-up test. Call service.
Start-Up Test: Controller Firmware Check Controller communication problem detected
39 FIRM_TO Timeout Call Service Unit during start-up test. Call service.
Start-Up Test: Controller Firmware Controller firmware revision mismatch detected
40 FIRM_DIFF Call Service Unit Call service.
Revision Mismatch during start-up test.
41 SRL_TO Start-Up Test: Controller Serial Number Call Service Unit Controller communication problem detected Call service.
Check Timeout during start-up test.
42 SRL_DIFF Start-Up Test: Serial Number Mismatch Informational Unit Controller serial number mismatch detected No action needed.
during start-up test.
Phase control board failed to respond to Comm
44 T_INV_TO Inverter Test Timeout Call Service Unit board's Inverter test. Call service.
DySC door was opened. Mechanical bypass
46 DOOR_OPEN DySC Cabinet Door Open Manual Reset Unit Close door. Manually reset DySC.
commanded.
Verify ambient temperature is within DySC
Internal DySC temperature exceeded maximum
47 CRIT_OT Critical Over-Temperature Manual Reset Unit rating. Mechanical bypass commanded. specification. Check for damaged fans. Check for dirty
or obstructed air filters. Manually reset DySC.
One of the DySC fuses was detected open.
48 FUSE_OPEN Fuse Open Call Service Unit Call service.
Mechanical bypass commanded.
Static The SCR on the phase A module was detected
49 OPEN_SCR_A Open SCR Phase A Call Service Call service.
Switch open.
Static The SCR on the phase B module was detected
50 OPEN_SCR_B Open SCR Phase B Call Service Call service.
Switch open.
Static The SCR on the phase C module was detected
51 OPEN_SCR_C Open SCR Phase C Call Service Call service.
Switch open.
52 EXT_MB External Mechanical Bypass Command Manual Reset Unit The DySC was externally commanded to transfer Manually reset DySC.
to mechanical bypass.
A problem was detected with the DySC dynamic
53 DYN_BRAKE Dynamic Brake Error Call Service Unit Call service.
brake controller.
58 PLC_ERR Programmable Logic Controller Error Call Service PLC PLC error detected. Call service.
Servicing
Before attempting any servicing that requires opening the MegaDySC doors first
put the system into Maintenance Bypass mode as described in the section
Automatic Bypass Switchboard Operation on page 30
Figure 16 on page 32 shows the arrangement of circuit breakers CBI, CBO, and
CBB of the Automatic Bypass switchboard. If the MegaDySC cabinet doors are
opened while the system is operating in normal mode the circuit breaker CBB
will automatically close and CBI and CBO will be automatically opened, putting
the system into maintenance bypass mode until it is manually reset. Voltage sag
protection is not possible in the maintenance bypass mode. All doors should be
kept locked to avoid this situation.
Fuses Fast-acting fuses are included to protect the MegaDySC system in the event of a
load-short circuit or other conditions. Fuses are located within the Automatic
Bypass switchboard cabinet, the MegaDySC cabinet and the optional ER storage
cabinet. To maintain protection of the MegaDySC system, fuses must be replaced
with the same or exact replacement type. Replacement fuses are available through
Rockwell Automation Technical Support and should only be replaced by
qualified and factory authorized service personnel.
Refer to the fuse listing label located on the switchboard cover for fuse size and
type. Before replacing a switchboard fuse authorized service personnel will
require removal of power to the Automatic Bypass switchboard by opening and
locking-out the upstream circuit breaker.
A large label inside the door shows fuse locations. A similar label is located within
the optional ER storage cabinet. Fuse types are listed in Table 11. Before
replacing a cabinet fuse, factory authorized service personnel must transfer the
system to maintenance bypass mode. No attempt should be made to service the
MegaDySC if red LEDs located above the DC bus capacitors are lighted.
IMPORTANT A qualified electrician must replace the fuses. Open the front cabinet door(s) to
access the fuse holders and fuses.
To maintain the protection of the MegaDySC system, be sure to replace the fuse
with the same type and rating. These fuses are available through
Rockwell Automation Technical Support.
Rated Voltage SR/ER Heat Loss (W) Heat Loss (BTU/h) Efficiency
3W ER 2400 lb [1089 kg] 1580 lb [717 kg] 1700 lb [771 kg] 5680 lb [2577 kg]
4W ER 2400 lb [1089 kg] 1580 lb [717 kg] 1660 lb [753 kg] 5640 lb [2559 kg]
In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more
information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/services/online-phone.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local
Rockwell Automation representative.
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400