Generator Capability Curve
Generator Capability Curve
The generator operating point limits are stated and visualized in the form of the
generator capability curve. The generator load capability curve and generator
operating capability include active power (MW), reactive power (MVAr), and
apparent power (MVA).
Generator Characteristics:
Generator Limitations:
2. MW limit.
The generator stator conductors are operating at their thermal limit. This limit is
due to I square R heating in the stator conductors.
If the generator power factor is altered to a value nearer to UPF, then due to the
lower stator current, the generator stator conductors would be operating well
within their thermal limit.
One of the limitations of generator rating is the maximum current that can be
carried by the armature without exceeding the heating limitations. Therefore, in
the P-Q plane the armature current limit, as shown in Figure, appears as a circle
with a center at the origin and a radius equal to the MVA rating.
• The circle with center at the origin O and radius S= Vt*Ia defines the
region of operation for which armature heating will not exceed a specified
limit.
2. MW Limit:
MW output is limited by turbine output and stator conductor heating. The real
power output of the generator is usually limited to a value within the apparent
power rating by the capability of its prime mover. Maximum prime mover
capability is generally smaller than the maximum active power that is limited by
the generator stator current.
The steady-state stability limit is the maximum power that can be transferred
without the system becoming unstable when the load is increased gradually,
under steady-state conditions.
In the case of a generator operating with a leading power factor, the excitation
and hence flux produced by the rotor is weak. Consequently, the magnetic
coupling between the rotor and stator rotating magnetic fields is also weak. If the
generator is loaded under this condition, a large load angle (rotor angle) is
produced.
When this load angle reaches 90°, the generator is producing the maximum
amount of power for the excitation being used and is said to be operating at its
steady-state stability limit.
Any further increase in load will cause the magnetic fluxes to stretch further and
the load angle to increase further. A point is reached when the rotor is at the 180
Deg position, where there is no magnetic coupling between the rotor and stator.
When this occurs, the rotor will speed up and the generator, instead of giving a
steady output, will only give surges of power as the rotor N pole passes the stator
S pole. This effect is known as “pole slipping” and the generator is now unstable.
The large surges of power, from a mechanical point of view, puts great strain on
the generator to turbine coupling, the bearings, and foundations. From an
electrical point of view, the surges of power will cause current surges and hence
magnetic stresses to all load-carrying components. These surges of power will
also cause the voltages to fluctuate rapidly and cause lights to flash.
To make sure that the generator will remain stable, it must not be operated with
more leading vars than is shown by the stability limit line.
When the generator is operating at a leading power factor, the flux produced by
the rotor is weaker and more flux is able to leak out from the ends of the stator
core. When this flux leaks out from the ends of the stator core, it passes through
the face of each lamination and causes large eddy currents to flow in these
laminations. These eddy currents can cause excessive heating.
CONCLUSION: