The document is a schedule of loads and computations for an electrical system. It lists 11 circuits with descriptions of the loads connected on each circuit such as lighting outlets, convenience outlets, compressors, testing machines, and air conditioning units. It calculates the total voltage amps (VA) and amps (A) for each circuit and the overall system. The summary selects wire sizes and conduit sizes based on the load calculations with the goal of having a 125 amp main circuit breaker and meeting code requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views

ELECTRICAL

The document is a schedule of loads and computations for an electrical system. It lists 11 circuits with descriptions of the loads connected on each circuit such as lighting outlets, convenience outlets, compressors, testing machines, and air conditioning units. It calculates the total voltage amps (VA) and amps (A) for each circuit and the overall system. The summary selects wire sizes and conduit sizes based on the load calculations with the goal of having a 125 amp main circuit breaker and meeting code requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SCHEDULE OF LOADS & COMPUTATIONS

OUTLETS SWITCHES NO. OF


DESCRIPTION OF LOADS VA AMPS AT VOLTS SIZES OF WIRE SIZES OF CONDUIT
CKT NO. LIGHTING CONVENIENCE S1 S2 S3 3WS POLES

1 11 3 2 LIGHTING OUTLETS 1100 4.78 15 AT 2 230 2 - 2.0mm ² SQ. THWN 20 mm o PVC

2 12 CONVENIENCE OUTLETS 2160 9.39 20 AT 2 230 2 - 3.5mm ² SQ. THWN 20 mm o PVC

3 1 COMPRESSION MACHINE 1518 6.6 20 AT 2 230 2 - 3.5mm ² SQ. THWN 20 mm o PVC

4 1 UNIVERSAL TESING MACH. 1000 4.35 20 AT 2 230 2 - 3.5mm² SQ. THWN 20 mm o PVC

5 1 MUFFLE FURNACE 18400 80 90 AT 2 230 2 - 35mm² SQ. THWN 1/2-inch PVC—Sch 80

6 1 LABORATORY OVEN 1000 4.35 20 AT 2 230 2 - 3.5mm² SQ. THWN 20 mm o PVC

1 ACU- 1.50 HP 1119 4.86 30 AT 2 230 2 - 5.5mm² SQ. THWN 20 mm o PVC


7
ACU- 1.50 HP 1119 4.86 30 AT 2 230 2 - 5.5mm² SQ. THWN 20 mm o PVC
8 1

9 SPARE 1000 4.35 20 AT 2 230 2 - 3.5mm ² SQ. THWN 20 mm o PVC

10 SPARE 1000 4.35 20 AT 2 230 2 - 3.5mm ² SQ. THWN 20 mm o PVC

11

TOTAL 89 40 12 3 10 2 29416 127.89

PROPERTY LINE PROPERTY LINE I= 29416 / 230 + 0.25 (4.86) = 128.146 AMPS.
SERVICE SERVICE USE= 2-30mm² THHN & 1- 8.0mm² THHN in 32mmØ RSC PIPE
ENTRANCE ENTRANCE CB= 125 AMPS, MCCB, 10 KAIC, 2P, 240V
PROPERTY LINE

PROPERTY LINE

PROPERTY LINE

PROPERTY LINE
ELECTRICAL DESIGN ANALYSIS:
wp wp

a S2ab
b
GENERAL LIGHTING: USED= 2-30mm² THHN & 1-8.0mm² THHN
ACU

67.5 SQM. x 24 VA / SQM. ------------------------------------------------------ 1620.0 VA. in 32mmØ RSC PIPE


b a
USED= 2-2.0mm² THHN & 1-2.0mm² THHN in 25mmØ PVC PIPE PER CIRCUIT LOAD

MACHINES:
1 CKT. x 1518 VA / CKT. -------------------------------------------------------- 1518.0 VA.
1 CKT. x 1000 VA / CKT. -------------------------------------------------------- 1000.0 VA.
4138.0 VA.
APPLICATION OF DEMAND FACTOR
FIRST 3000 VA @ 100% DF. ----------------------------------------------------- 3000.0 VA.
REMAINDER @ .35% DF. ------------------------------------------------------- 3200.4 VA.
g co 6200.4 VA.
d c
S2cd UNIVERSAL TESTING
MACHINE
COMPRESSION
MACHINE OTHER LOAD:
ACU
S1g
2- ACU 1119 VA @ 100% DF --------------------------------------------------- 2238.0 VA
S1f d c PB co MUFFLE
FURNACE co LABORATORY
OVEN USED= 2-5.5mm² THHN & 1-2.0mm² THHN in 25mmØ PVC PIPE
TOILET

TOILET

f PER CIRCUIT LOAD


S1e 1- OVEN 1000 VA @ 80 % DF. ------------------------------------------------- 800.0 VA.
SHOWER

SHOWER

e 2- MUFFLE FURNACE 18400 VA @ 80 % DF. ----------------------------- 14700.0 VA.


2- SPARE 1000 VA @ 100% DF ------------------------------------------------ 2000.0 VA.
PROPERTY LINE PROPERTY LINE
USED= 2-3.5mm² THHN & 1-2.0mm² THHN in 25mmØ PVC PIPE
PER CIRCUIT LOAD
CONNCETED LOAD 19738.0 VA.

PANEL SERVICE ENTRANCE CONDUCTOR & EQUIPMENT


I= 19738.0 / 230 + 0.25 (4.86)= 86.07 AMPS
1 LIGHTING LINE LAY-OUT 2 POWER LINE LAY-OUT USED= 2-30mm² THHN & 1-8.0mm² THHN in 32mmØ RSC PIPE
E 1 SCALE E 1
MAIN CB= 125 AT/ AF, 240 V. 2P, MCCB.
1:100MTS SCALE 1:100MTS
3 PANEL BOARD DIAGRAM
SERVICE ENTRANCE CONDUCTOR
E 1 N T S
I= 19.09 + 19.09 = 38.18 AMPS.
USED= 2-14mm² THHN & 1-8.0mm² THHN in 25mmØ RSC PIPE

ARCHITECT ENGINEER PROJECT TITLE OWNER SHEET CONTENTS R.A. 545 REVISIONS SHEET NO.

PRC NO. PRC NO. DATE: DESCRIPTION


PROPOSED: This drawing as an instrument of
PTR PTR service, is the property of the E
DATE DATE MATERIAL TESTING LABORATORY ALEXIES B RAMOS Architect and should not be
ARCHITECT
copied, reproduced or duplicated 1
PLACE PLACE without the written consent of
TIN said author/s.
TIN CHECKED BY: PAGE__ OF SHEET__