Multi-Compressor Refrigeration Systems
Multi-Compressor Refrigeration Systems
Research Paper
H I G H L I G H T S
A R T I C L E I N F O A B S T R A C T
Article history: A set of 14 HP variable refrigerant flow air conditioning system (VRF AC) with multi-compressor has been
Received 18 October 2015 designed, and the output capacity control strategy of compressor(s) including the switching control model
Accepted 28 December 2015 of standard compressor has been built. In the output capacity control model, a certain suction pressure
Available online 21 January 2016
is used as the pressure control target to adjust the output capacity of compressors, and a little pressure
fluctuation is taken into account to amend the target pressure. Furthermore, in the compressor switch-
Keywords:
ing control model, the most favorable operation frequency region is determined on base of the energy
Variable refrigerant flow (VRF)
efficiency characteristic and noise characteristic of the compressor. And, in order to solve the large fluc-
Inverter-driven compressor
Output capacity of compressor tuation problem of the system running and frequent ON-OFF action of the standard compressor, the equal
Energy efficiency ratio output capacity switching principle can be used to determine the thermo-on and thermo-off switched
frequency points, and control the switching process of the compressor. Experiments demonstrate the
feasibility of this control strategy to ensure the stability and reliability, improve the energy efficiency
and reduce the compressor noise.
© 2016 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.applthermaleng.2015.12.102
1359-4311/© 2016 Elsevier Ltd. All rights reserved.
Q. Tu et al./Applied Thermal Engineering 99 (2016) 280–290 281
As an example of VRF AC with an inverter-driven compressor and orator also changed due to the coupled system dynamics. It was
a standard compressor, the adjustment process of output capacity concluded that a control algorithm should also include the EEV in
is described in detail below. order to maintain the pressure of the second evaporator at the
At the beginning of the operation, only the inverter-driven com- desired value.
pressor starts to run, and the standard compressor keeps standby Obviously, these authors [4,6–13] mainly concentrated on the
status. When the indoor thermal load increases, the compressor im- study about the control method of EEV to adjust the refrigerant flow
proves the output capacity subsequently. If the output capacity of rate to achieve good refrigeration effect. But they did not study the
the inverter-driven compressor still cannot meet the indoor thermal adjustment method of the inverter-driven compressor to realize
load demand, the standard compressor will start to work. So, it is stable running.
necessary to properly determine the frequency switching point and Wu et al. [14] proposed a control strategy for VRF with three
switching course of the standard compressor to ensure the high ef- indoor units, in which the suction pressure was taken as the
ficiency, low noise and stable operation. For example, if the frequency controlled variable to modulate the compressor speed, and at the
switching point is set as a high value, it will result in high noise of same time, the room air temperatures were used to regulate the
the compressor. Furthermore, the total output capacity of the two opening of the individual EEVs. A self tuning fuzzy algorithm with
compressors exceeds the thermal load demand, thus, the inverter- a modifying factor was incorporated in the controller. Controlla-
driven compressor sharply decreases the running frequency, and the bility tests showed that the proposed control strategy with fuzzy
standard compressor stops. And then the control process results in control algorithm could achieve the desired control accuracy for
insufficient output capacity. So the inverter-driven compressor is the controlled parameters. Lin and Yeh [15] proposed the control
required to increase the running frequency, and even the standard strategy with flow distribution capability for multi-evaporator air
compressor starts to work again. So repeatedly, the system has been conditioners to accommodate different thermal demands in differ-
in an unstable operation state. On the other hand, if the frequency ent rooms. The structure in the control strategy is based on a
switching point is set as a low value, it will result in insufficient low-order, linear model obtained from system identification. To
output capacity even if the standard compressor works. It will take determine appropriate control parameters, theorems regarding
a long time to adjust the operation frequency of the inverter- stability of the closed-loop system were given. Tu et al. [16]
driven compressor to meet the thermal load demand gradually. So studied the heating control strategy of VRF AC with multi-module
the long adjustment course affects the consumers’ usage, and the outdoor units, and proposed the heating control model including
system has been in a state of instability. heating frequency adjustment, module switching condition and
Thus, it becomes more and more necessary to study the control frequency allocation model. But the control strategy and control
strategy of the multi-compressor’s output capacity to realize the model are suitable for the system with only one compressor in a
stable switching process of the compressor, to achieve good refrig- module, but not for multi-compressor in a module. Moreover, Tu
eration results, gain high energy efficiency, and make low noise. et al. [17] studied the control strategy of the digital scroll compres-
Masuda et al. [6] developed a control method for VRF with two sor switching and built the control model of compressor output
indoor units, which could control the refrigeration flow rate of the capacity, in which the average suction pressure in an adjustment
indoor units individually and respond to the cooling loads. Shi [7] period was taken as the current pressure to regulate the output
proposed the cycle superimposition control method to study the capacity. But the model cannot be used in the inverter-driven
control strategy for VRF AC. Park et al. [8] presented a model to compressor, but the digital compressor.
analyze the relationship between coefficient of performance (COP) In conclusion, these control methods are not suitable for VRF with
and openings of EEV, operation frequency of the multi-type in- the inverter-driven compressor and the standard compressor(s). And
verter air conditioner. Xia et al. [4] adopted a continuous adaptation the energy efficiency and noise were not considered in the control
of the heat transfer coefficient method to maintain the same su- model at the same time.
perheating during thermo-on periods. In this control strategy, the At present, none of the investigations are concerned on the
suitable refrigerant mass flow rate was distributed to each indoor control strategy of VRF AC with multi- compressor due to the tech-
unit by individually adjusting each EEV to obtain required indoor nology bottleneck and experimental condition restriction. In this
room temperature. Choi and Kim [9] measured the performance of paper, as a study object of VRF AC with multi-compressor, the control
an inverter-driven multi-air conditioner having two indoor units with model is built to control the compressor output capacity and stan-
electronic expansion valves (EEV) by varying indoor loads, EEV dard compressor switching so as to ensure the stable and reliable
opening, and compressor speed, and discussed the operating char- operation, achieve good cooling effects and high energy efficiency,
acteristics and capacity modulation of the inverter-driven multi- and realize low noise running.
air conditioner based on the experimental results. Similarly, Aynur
et al. [10] studied the control method of the refrigerant flow rate
through the indoor unit heat exchanger by adjusting the EEV. Hu 2. Control strategy
et al. [11] developed a set of VRF AC with 5 indoor units. The mea-
sured results show that the regression functions of the relationship 2.1. System principle
between the opening of the electronic expansion valves (EEV) and
the digital compressor output ratio can form the basic parameters The system principle diagram of VRF AC with two compres-
of the system control. Lin and Yeh [12] studied a three-evaporator sors, one inverter-driven compressor and one standard compressor,
air conditioner for a feedback controller design. For the proposed is shown in Fig. 1. For VRF AC with three compressors, the princi-
control structure, the three evaporating temperatures were con- ple diagram is similar to that with two compressors.
trolled by the EEV openings in order to keep the indoor temperatures In Fig. 1, Tda, Tdb, Tao, Tdef, TC1, and TC2 are respectively discharge
at the set points with no steady-state errors. Besides, the compres- temperature of the inverter-driven compressor, discharge temper-
sor speed was used to control the three superheat temperatures ature of the standard compressor, ambient temperature and
associated with the three evaporators. Shah et al. [13] developed condenser coil temperature, temperature in the indoor unit gas pipe
a new methodology for the dynamic modeling of a multi-split VRF and temperature in indoor unit liquid pipe, which are measured by
system. The expansion valve was modeled as an isenthalpic orifice. the relevant temperature sensors. Pd and Ps are respectively dis-
It was found that the EEV of the first evaporator changed, while the charge pressure and suction pressure measured by the relevant
second one was kept constant, and the pressure in the second evap- pressure sensors. EEVa1 and EEVa2 are the electronic expansion
282 Q. Tu et al./Applied Thermal Engineering 99 (2016) 280–290
EEVa1,B Fan M
Tda
Tdb
Capillary Ps Tc1
Indoor Units
Outdoor Unit
Fig. 1. Schematic diagram of VRF AC with multi-compressor.
valves (EEV) in the outdoor unit and the indoor unit, respectively. 3. Control model and method
SV1 is the solenoid valve for pressure balance between Pd and Ps
in order to reduce load when the compressors start. 3.1. Control model of output capacity
E cur = E (f 1→2,1 ) = E (f 1→2,2 ) + E STD 1 (6) Fig. 2. (a) Switch principle diagram of VRF AC with two compressors. (b) Switch prin-
ciple diagram of VRF AC with three compressors.
E INV = E (f INV ) + E STD 1 (10) and f 3→2,3 ≤ f INV ≤ f INV ,max (14)
Table 1
Performance parameters of COMP(a) and COMP(a + b).
Compressor Performance parameter 30 rps 35 rps 40 rps 45 rps 50 rps 55 rps 60 rps 65 rps 70 rps 75 rps 80 rps 85 rps 90 rps
COMP(a) Capacity (kW) 9.15 10.64 12.03 13.54 15.22 16.79 18.04 19.97 21.43 23.06 24.75 26.41 28.23
Power (kW) 3.25 3.77 4.21 4.7 5.23 5.73 6.15 6.8 7.31 7.87 8.49 9.08 9.75
COMP(a + b) Capacity (kW) 22.76 24.25 25.64 27.15 28.83 30.40 31.65 33.58 35.04 36.67 38.36 40.02 41.84
Power (kW) 7.88 8.40 8.84 9.33 9.86 10.36 10.78 11.43 11.94 12.50 13.12 13.71 14.38
and
And then the system works among the whole frequency band.
The output capacity of COMP(a) is adjusted according to Eq. (1). The
output capacity and the running frequency can be written as
3.4.1. Thermo-on condition and switching action of standard 4.2.1. ON-OFF phenomenon
compressor In the control model about the thermo-on condition of the stan-
In cooling mode, when the operation frequency of the inverter- dard compressor, the suction pressure constraint condition (Ps-
driven compressor reaches or exceeds 75 rps lasting for 15 s, at this pre < Ps 0 − 0.5 bar) can make great influence on the stable operation
point, the running time of the system is recorded by the calculagraph, of COMP(b). If the constraint condition is not added in the control
and the suction pressure after 3 min will be predicted in the control model, the thermo-on condition can be satisfied easily. So ON-
program. If the predicted suction pressure does not meet the pres- OFF switching of the standard compressor will occur frequently. In
sure target, the standby standard compressor, which keeps thermo- order to contrastively validate the influence of suction pressure con-
off status for more than 4 min, will start to work. The thermo-on straint condition on the operation status of COMP(b), it is firstly
condition of COMP(b) is given as below. cancelled in the control software to make experiment.
286 Q. Tu et al./Applied Thermal Engineering 99 (2016) 280–290
Fig. 7. Experimental results under the condition of 49 °C DB in the outdoor chamber and 32 °C DB in the indoor chamber.
Q. Tu et al./Applied Thermal Engineering 99 (2016) 280–290 287
Fig. 8. Experimental results under the condition of 21 °C DB in the outdoor chamber and 21 °C DB in the indoor chamber.
The ambient dry bulb temperatures of the outdoor chamber From the analysis above, it demonstrates that the suction pres-
and the indoor chamber of the laboratory were adjusted to be sure constraint condition was essential for stable switching of
49 °C DB and 32 °C DB, respectively. Four 4 HP indoor units, COMP(b).
whose models are DLR-100F/DCZDG, were turned on to make And then in order to verify the essentiality of the constraint con-
high temperature cooling experiment. The experimental results dition, it was added in the control software to make experiment.
are shown in Fig. 7. Taking into account that it is very difficult to make the suction
The experimental results in Fig. 7 show that the system ran un- pressure lower than the pressure target under the condition of the
stably; pressure, frequency and discharge temperature oscillated high temperature refrigeration, the experiment was made under
frequently; and for COMP(b), there existed frequent ON-OFF phe- the condition of 21 °C DB in the outdoor chamber and 21 °C DB in
nomena within 16 min. the indoor chamber.
The analysis shows that when the operation frequency of the When four 4 HP indoor units (DLR-100F/DCZDG) were turned on,
inverter-driven compressor reached 25rps, and the suction pres- and the 1 HP indoor unit (DLR-28F/DCZDG) was kept in thermo-off
sure Ps was about 13bar, larger than then the pressure target, status, COMP(a) ran stably at 39 rps and COMP(b) worked. In order
COMP(b) was turned off. And then, COMP(a) increased the running to make the system suction pressure lower than the pressure target,
frequency because the pressure target was not satisfied. When the and verify the control model with the constraint condition, two 4 HP
frequency reached 75 rps, and the switching condition of COMP(b) indoor units were turned off, and the other two 4 HP indoor units
was met, it started to run. So repeatedly, the frequent ON-OFF phe- were kept in thermo-on status. And then the suction pressure began
nomena of COMP(b) occurred. to decrease, and was lower than the pressure target. When the running
288 Q. Tu et al./Applied Thermal Engineering 99 (2016) 280–290
Fig. 9. Partial parameters drawn from Fig. 8 every 15 s within 3 min before COMP(b) was turned off and within 3 min after COMP(b) was turned off.
frequency reached 25 rps, and the thermo-off switching condition can Experimental results show that it took only 4 min to make the
be met, COMP(b) stopped to work, and then the suction pressure began suction pressure reach the pressure target; the system kept stable
to rise gradually. According to the equal capacity switching princi- running status and there did not exist ON-OFF phenomenon for
ple, COMP(a) increased the operation frequency to be thermo-off COMP(b); and the discharge pressure fluctuated only within 1 bar,
switched frequency point 60 rps. And then, for the suction pressure, and then COMP(a) remained at about 45 rps within 2 min.
there existed a slow downward trend with increase of the frequency Experimental results show that the switching control model and
from 40 rps to 60 rps. And then the output capacity was controlled control process are reasonable.
by suction pressure target. The suction pressure reached the pres-
sure target, quickly. The monitored curve is shown in Fig. 8. 5. Conclusion
A set of data including Pd, Ps, Tda, Tdb, and f INV was drawn from
the experimental curves every 15 s within 3 min before COMP(b) The output capacity control strategy of VRV AC with multi-
was turned off and within 3 min after COMP(b) was turned off. compressors is a key technology, which is directly related to the
Twenty-five sets of data including the data in the current switch- stability, reliability, energy saving and comfort of the system.
ing frequency point 25 rps were shown in Fig. 9, where Ps was Experiments confirmed that if the control model and process are
placed in the secondary vertical coordinate in order to be dis- not reasonable, it will lead to frequent on-off phenomenon of the
played clearly. standard compressor, unstable running, and bad comfort of the
Experimental results show that it took only 2 min to make the system. The following control strategies can solve these problems
suction pressure reach the pressure target; the system met stable and achieve proper running results.
running status and there did not exist ON-OFF phenomenon for
COMP(b); and the discharge pressure fluctuated only about 2 bar, 1. According to the output capacity and power data from the com-
and then COMP(a) remained at 50 rps. pressor manufacturer, the energy efficiency characteristics are
Experimental results show that the switching control model and obtained. The calculated EER shows that the system can obtain
control process are reasonable. higher energy efficiency among the middle frequency band, such
as 55–75 rps; on the contrary, EER is lower among the high fre-
4.2.2. Thermo-on switching of COMP(b) quency band and low frequency band.
The experiment was made under the condition of 30 °C DB in 2. The noise test results show that the noise value rises with in-
the outdoor chamber and 21 °C DB in the indoor chamber to val- crease of the running frequency.
idate the thermo-on switching control and process. The monitored 3. The most favorable operating region of the compressor is de-
curve is shown in Fig. 10. termined according to the energy efficiency and noise
It can be seen that when the four 4 HP indoor units were turned characteristics of the compressor. Furthermore, the character-
on, the operation frequency reached 75 rps, suction pressure was istics can provide the basis for determination of the frequency
about 8.2 bar, larger than the pressure target, which means the switching points.
system is required to improve its output capacity. So COMP(a) de- 4. The compressor switch control model has been established. In
creased running frequency to be thermo-on switched frequency point order to solve the problem of large fluctuations of the system
35 rps, and then COMP(b) was turned on. performance and frequent ON-OFF action of the standard com-
Similarly, twenty-five sets of data were drawn from the exper- pressor, the equal output capacity switching principle can be
imental curves every 15 s within 3 min before COMP(b) was thermo- used to determine the thermo-on and thermo-off switched
on and within 3 min after COMP(b) was thermo-on. Twenty-five sets frequency points, and control the switching process of the
of data were shown in Fig. 11. compressor.
Q. Tu et al./Applied Thermal Engineering 99 (2016) 280–290 289
Fig. 10. Experimental results under the condition of 30 °C DB in the outdoor chamber and 21 °C DB in the indoor chamber.
5. Experiments show that the control strategy is feasible for the E cur Current total output capacity of all the thermo-
stability, reliability and energy saving of the system. on compressors (W)
EER Energy efficiency ratio
Acknowledgements EEV Electronic expansive valve
EEVa1 Opening of EEV in the outdoor unit (PLS)
This work was supported by the National Natural Science Foun- EEVa2 Opening of EEV in the indoor unit (PLS)
dation of China (Grant number 51206083) and Public Welfare Project E (f INV ) Output capacity of the inverter-driven compres-
of Zhejiang Province (Grant number 2012C21063). And the authors sor under different frequencies (W)
would like to thank the financial and experimental support from E INV Output capacity of the inverter-driven compres-
Aux Electric Co., Ltd (Project number 2012-055). sor (W)
E STD1 Output capacity of the first standard compressor
Nomenclature (W)
E STD 2 Output capacity of the second standard compres-
COMP(a) Inverter-driven compressor sor (W)
COMP(a + b) Inverter-driven compressor and one standard f i → j ,i Current switching frequency from i compres-
compressor sor(s) running to j compressor(s) running (rps) i,
COMP(a + b + c) Inverter-driven compressor and two standard j means numbers of compressors, i = 1,2,3; j = 1,2,3.
compressors And i-j = 1, or j-i = 1.
290 Q. Tu et al./Applied Thermal Engineering 99 (2016) 280–290
Fig. 11. Partial parameters drawn from Fig. 10 every 15 s within 3 min before COMP(b) was turned on and within 3 min after COMP(b) was turned on.