ECO 1000

CONVENTIONAL - Rate of Rise Thermal Detector


Model ECO1005

Overview
Features
• Low profile design
• Low current draw
• 580C operating temperature
• Operates at 12 and 24VDC
• Remote alarm test feature
• Easy Maintenance
• Range of detector bases available
• Remote LED Option
• Approved to EN54 –5:2000 Class A1R
• Extended warranty 199n/01 G201016 0832-CPD-0066

Description

The ECO1005 thermal detector belongs to System The ECO1005 detector also has an integral LED, which
Sensor’s ECO1000 range of detectors. ECO1000 is illuminates to provide a local alarm signal. This latches
a range of conventional detectors, which have been on,and remains illuminated until the detector is reset by
produced using the latest in manufacturing technology a momentary power interruption. An optional remote LED
and supplied with an array of advanced features, making annunciator may be used to repeat any alarm signal.
them ‘better by design’.
A variety of detector bases can be used with the
The ECO1005 thermal detector uses a state of the art ECO1005 detector, providing application flexibility and
thermal element combined with an application specific compatibility with a wide range of Fire Alarm Control
integrated circuit (ASIC)to provide quick and accurate Panels. All bases are fitted with a shorting spring to
detection of fires. The detector incorporates both rate permit circuit testing prior to fitting the detector and
of rise and static elements and is suitable for all areas have a tamper resistant feature, which when activated
where the ambient conditions do not normally exhibit prevents removal of the detector without the use of a
rapid changes in temperature. tool.

A laser-based hand held Remote Test Unit can be used All System Sensor products are covered by our extended
in conjunction with the range of ECO1000 detectors 3-year warranty.
for alarm test purposes. The unit transmits a coded
message, preventing spurious alarms being generated
by other laser-based devices. With a range of several
metres, the hand held test unit provides an effortless
way of remotely alarm testing the range of ECO1000
detectors and removes the need for any direct physical
access to the detector by the user.
Architect/Engineer Specifications
ECO1005 Rate of Rise Thermal Detector

102mm 50mm

Electrical Specifications
Operating Voltage Range 8 to 30VDC (Nominal 12/24VDC)
Maximum Standby Current @250C 70µA @ 24VDC
Maximum Permissible Alarm Current 80mA (current limited by control panel)

Environmental Specifications
Application Temperature Range (see note 1) -300C to 700C
Humidity 5% to 95% Relative Humidity (non-condensing)

Mechanical Information
Height 40.5mm (plus 9.5mm for standard base)
Diameter 102mm
Weight 70g (plus 45g for standard base)
Wire Gauge for Terminals 0.4mm2 to 2.0mm2
Colour Approximates to RAL9016
Material ABS

Product Range
Bases (see note 2)
ECO1000B Standard Base ECO1000BSD Standard base with Shottky diode
ECO1000R Resistor base 470 Oohm ECO1000BRSD Resistor base 470 Ohm with Shottky diode
ECO1000DB Deep base ECO1000DBSD Deep base with Shottky diode
ECO100DBR Deep resistor base 470 Ohm ECO100DBRSD Deep resistor base 470 Ohm with Schottky diode
ECO1000BREL12L Relay base 12V Latching ECO1000BREL12NL Relay base 12V Non –latching
ECO1000BREL24NL Relay base 24V Latching
Accessories
ECO1000RTU Remote Test Unit
Other Detectors
ECO1002 Photoelectric/Thermal Detector ECO1003 Photoelectric Detector
ECO1004T 780C Fixed Temperature Thermal Detector ECO1005T 580C Fixed Temperature Thermal Detector

Notes
Bases with other resistor values are available to suit the requirements of most Fire Alarm Control Panels.

System Sensor Europe (Technical Services)


Charles Avenue
Burgess Hill
RH15 9TQ
United Kingdom
Tel: +44 (0)1444 238820
Fax: +44 (0)1444 248123
Email: [email protected]
www.systemsensoreurope.com

Copyright © 2005 System Sensor. All rights reserved.


All technical data is correct at time of publication and is subject to change without notice. All trademarks acknowledged.
Installation information: in order to ensure full functionality, refer to the installation instructions as supplied. DSECO1005-07