Outline
PV
PV Array
Configuration
Introduction
As temperature increases:
• Current increases
marginally
• Voltage decreases
significantly
• Power decreases
correspondingly
Power
The output power can be calculated as:
Determine the expected maximum PV power output of module
at that area.
Example 1
The specification of a PV panel Sunceco
300W is given. The panel is exposed to the
following ROC:
• Cell temperature: 65 oC
• Irradiance 800 W/m2
• dirt 2%
• no shading
• Factor due to mismatch is 1.0
• Light Induced Degradation (LID) is 2.5%
on the zeroth year.
Solution
Short circuit
current and
Open circuit
Voltage
Current
The output current of a PV
module can be determined
as:
Example 2
• By using the same PV panel and ROC as in Example 1, determine the
expected short circuit current.
Solution
Voltage
• The output voltage of a PV module can be determined as:
Example 3
• By using the same PV panel as in Example 1, determine the expected
open circuit voltage:
Solution