Phasor Measurement Unit Application-Based Fault Allocation and Fault Classification
Phasor Measurement Unit Application-Based Fault Allocation and Fault Classification
Corresponding Author:
Satyendra Pratap Singh
Department of Electrical Engineering, Faculty of Electrical Engineering,
Arya college of Engineering and Information Technology
SP-42, Arya 1st Old Campus Rd, RIICO Industrial Area, Kukas, Jaipur, Rajasthan 302028, India
Email: [email protected]
1. INTRODUCTION
In the present, if we see anywhere we found that everything is modernized for obtaining a more
efficient and reliable outcome. Now, it is clear that for every modern appliance operation, we required
electrical energy. As we know that world population increases day by day, therefore with this the requirement
for energy also increases continuously. For full fill this energy requirement we need a large size grid. The
large size grid has more possibility of occurring abnormality in it that is a fault. This problem makes the grid
less efficient and less reliable. For increasing the efficiency and reliability of the grid it is necessary to find
out the abnormality cause and reduce or mitigate way. After finding the fault mitigation way we can improve
the efficiency and reliability of the grid. In this reference, various types of research are carried out and more
work also pursuing in this field. In them, some developed methodologies for obtaining the fault location in
the line are the theory of traveling wave [1]–[3], impedance-based fault location technique [4]–[6],
autoregressive integrated moving average (ARIMA) method [7], novel traveling phase component based
fault location method [8], phasor measurement unit (PMU) based fault location [9]–[12]. These developed
methodologies are able to find out the location of a fault in the line. The above-mentioned methods of finding
fault location plays a major role in the transition of the traditional grid into the modernized grid or in other
words smart grid.
In the current scenario, we use an advanced technology PMU. It is a measurement device, that is
able to provide phasor measurement of the bus at which it is installed and also able to provide the current
phasor of a branch which are adjacent to it, due to these features it is used for monitoring purpose in power
system [13]. The high accuracy and high reporting rate measurements of phasor and frequency enabled many
new system monitoring and control tools, such as oscillation detection and damping control, system
disturbance detection and location, and linear state estimation [14]–[16]. The PMU is also equipped with a
global positioning system (GPS), therefore, PMU-provided measurement data can be calculated in real-time
due to timestamping and synchronization. The communication infrastructure for a wide area measurement
system (WAMS) is explained with proper attention to the cost of the system and formulated in the optimal
cost problem [17].
This paper proposes a PMU application-based approach that gives fault location and fault type
classification in line. This approach uses the voltage and current frequency measurement and representation
of this measurement in the form of characteristics is done with the help of the scoping tool. The proposed
approach is able to find the source side and load side fault and location and also able to make a classification
of fault types that occurred in line.
The paper is organized into five sections in them: section 1 is the introduction, section 2 contains
faults and their types, section 3 contained fault allocation and fault classification approach, section 4 gives
test results, and section 5 comprises a conclusion.
Int J Adv Appl Sci, Vol. 12, No. 1, March 2023: 15-26
Int J Adv Appl Sci ISSN: 2252-8814 17
We can also identify the short circuit type of fault, if any phase has an increased current value then
the occurred fault is a shunt type of fault. The short circuit-type fault is divided into two parts in them one is
a symmetrical fault and the other is an asymmetrical fault. Short circuit fault is classified into two parts
namely symmetrical and asymmetrical fault. The symmetrical fault also has two parts that are line to line to
line (LLL) and line to line to line to ground (LLLG) fault and the asymmetrical fault is categorized into three
parts namely line to ground (LG), line to line (LL), and line to line to ground (LLG) fault.
and analysis of events in post-dispatch scenarios [25]. Different applications along with the benefits of PMU
are demonstrated in [26]. Low-frequency oscillation can be detected with the help of PMU [27], [28]. The
feature of frequency measurement of PMU is adopted in this approach. Here in this approach, the frequency
of voltage and current are separately measured with the help of PMU. For this purpose, we use MATLAB to
organize PMU-placed two models. This method comprises the study of voltage and current frequency
characteristics during the normal and abnormal conditions of a system. The study is done at the source side
and load side bus. The abnormal condition contains short circuit faults. Under the faulty condition, we record
the voltage and current frequency characteristic at both the source and load side even faults applied at the
load or source side. Finally, we have concluded that if both voltage and current frequency characteristic
shows the same behavior then the fault location will be the source side and if the frequency characteristic
shows the opposite behavior, then the fault location will be on the load side. For the frequency measurement
purpose, we use PMU Bock in MATLAB/Simulink platform that is inspired by the IEEE Std C37.118.1-
2011. The characteristics are observed with help of the scoping tool. Now we explain the approach in a
detailed way that is completed with the following points:
Int J Adv Appl Sci, Vol. 12, No. 1, March 2023: 15-26
Int J Adv Appl Sci ISSN: 2252-8814 19
Figure 7. V and I frequency characteristics for LG, LL, and LLG fault
Figure 8 and Figure 9 shows the voltage and current frequency characteristic during LLL, LLLG,
LG, LL, and LLG respectively. Figure 8 and Figure 9 show the load side voltage and current frequency
variation on the characteristic in the condition when the fault is applied at the source side. From both above
figures it is clear that there is no different frequency characteristic or in other words, both current and voltage
frequency overlap each other, which means both frequency characteristic shows the same behavior. So
according to our fault location deciding methodology, it is clear that the fault is observed at the source side.
Int J Adv Appl Sci, Vol. 12, No. 1, March 2023: 15-26
Int J Adv Appl Sci ISSN: 2252-8814 21
Figure 9. V and I frequency characteristics for LG, LL, and LLG fault
Figure 10. V and I frequency characteristics for LLL and LLLG fault
Figure 11. V and I frequency characteristics for LG, LL, and LLG fault
Figure 12 and Figure 13, show the load side voltage and current frequency characteristics during
LLL, LLLG, LG, LL, and LLG respectively. From Figure 12 and Figure 13, it can be observed that both
voltage and current frequency characteristic shows opposite behavior. Now according to our fault location
deciding methodology, we can confirm that the occurred fault location is at the load side.
Figure 12. V and I frequency characteristics for LLL and LLLG fault
Figure 13. V and I frequency characteristics for LG, LL, and LLG fault
Int J Adv Appl Sci, Vol. 12, No. 1, March 2023: 15-26
Int J Adv Appl Sci ISSN: 2252-8814 23
current frequency characteristic, which means both waveforms overlap with each other. From this result, we
can confirm that there is no fault with this bus.
Figure 14. V and I frequency characteristic during no fault condition at any source bus
Figure 15. V and I frequency characteristics during no fault condition at any load bus
4. TEST RESULTS
4.1. Fault allocation
The following Table 1 and Table 2 show the results of fault allocation in line on the basis of
frequency characteristics during various fault conditions. These tables provide source side and load side bus
results of frequency characteristics for voltage and current. Table 1 shows one source and one load bus,
whereas Table 2 shows one source and two load buses.
5. CONCLUSION
This paper describes an approach for fault allocation and fault classification, this approach
comprises the study of the frequency characteristic of voltage and current during normal and abnormal
conditions. The presented approach confirms the source side and load side fault location and also gives fault
identification of faults in two categories symmetrical and asymmetrical. On the basis of the above-described
method and experiment outcome, we can say that if the source side and load side voltage and current
frequency characteristics have the same behavior, then we can assume that the fault occurs on the source bus
side. If the source side and load side voltage and current frequency characteristics have opposite behavior,
then we can assume that the fault occurs on the load bus side. The given approach is tested on two models at
the MATLAB/Simulink platform and also gives an assurance of good quality results. The major outcomes of
this paper are: i) Here we firstly find that there is no frequency deviation of voltage and current in case of no-
Int J Adv Appl Sci, Vol. 12, No. 1, March 2023: 15-26
Int J Adv Appl Sci ISSN: 2252-8814 25
fault; ii) The frequency characteristic of voltage and current draws the same behavior in case of source side
bus fault; iii) The frequency characteristic of voltage and current draw opposite behavior in case of load side
bus fault; iv) The frequency characteristics of voltage and current approximate same for symmetrical faults;
v) Similarly, the frequency characteristics of voltage and current approximate same for Asymmetrical faults,
and vi). On the basis of the similarity of frequency characteristics, we become able to classify the faults
occurrence identity into two categories namely symmetrical and asymmetrical.
REFERENCES
[1] J. Duan, “Single terminal traveling wave method for hybrid line ground fault location based on EEMD and SDEO,” in APAP
2019-8th IEEE International Conference on Advanced Power System Automation and Protection, 2019, pp. 815–819, doi:
10.1109/APAP47170.2019.9225068.
[2] Y. Zhao, S. Shi, G. Zhang, H. Ma, and X. Dong, “Single-ended traveling wave based fault location for single-phase-to-ground in
power distribution lines,” in IET Conference Publications, 2020, vol. 2020, no. CP771, pp. 6 pp.-6 pp., doi:
10.1049/cp.2020.0080.
[3] Z. Jianwen and D. Jiaxin, “Traveling wave fault location for lines combined with overhead-lines and cables based on empirical
wavelet transform,” in 2019 IEEE 2nd International Conference on Electronics and Communication Engineering, ICECE 2019,
2019, pp. 285–289, doi: 10.1109/ICECE48499.2019.9058522.
[4] S. Das, S. Santoso, and S. N. Ananthan, “Error sources in impedance‐based fault location,” in Fault Location on Transmission
and Distribution Lines, Wiley, 2022, pp. 95–127.
[5] N. M. Khoa, M. V. Cuong, H. Q. Cuong, and N. T. T. Hieu, “Performance comparison of impedance-based fault location methods
for transmission line,” International Journal of Electrical and Electronic Engineering and Telecommunications, vol. 11, no. 3, pp.
234–241, 2022, doi: 10.18178/ijeetc.11.3.234-241.
[6] M. Nemati, M. Bigdeli, and A. Ghorbani, “Impedance-based fault location algorithm for double-circuit transmission lines using
single-end data,” Journal of Control, Automation and Electrical Systems, vol. 31, no. 5, pp. 1267–1277, 2020, doi:
10.1007/s40313-020-00620-w.
[7] D. P. M. De Souza, E. Da Silva Christo, and A. R. Almeida, “Location of faults in power transmission lines using the ARIMA
method,” Energies, vol. 10, no. 10, p. 1596, 2017, doi: 10.3390/en10101596.
[8] S. Sawai, R. N. Gore, and O. D. Naidu, “Novel traveling wave phase component-based fault location of transmission lines,” in 9th
IEEE International Conference on Power Electronics, Drives and Energy Systems, PEDES 2020, 2020, pp. 1–5, doi:
10.1109/PEDES49360.2020.9379861.
[9] M. Ahmadinia and J. Sadeh, “A new PMU-based fault location scheme considering current transformers saturation,” in 2020 28th
Iranian Conference on Electrical Engineering, ICEE 2020, 2020, pp. 1–4, doi: 10.1109/ICEE50131.2020.9260641.
[10] S. V. Unde and S. S. Dambhare, “PMU based fault location for double circuit transmission lines in modal domain,” in IEEE
Power and Energy Society General Meeting, 2016, vol. 2016-Novem, pp. 1–4, doi: 10.1109/PESGM.2016.7741819.
[11] A. Mouco and A. Abur, “Improvement of fault location method based on sparse PMU measurements,” in 2017 North American
Power Symposium, NAPS 2017, 2017, pp. 1–5, doi: 10.1109/NAPS.2017.8107263.
[12] M. Ahmadinia and J. Sadeh, “An accurate pmu-based fault location scheme for shunt-compensated transmission lines,” Iranian
Journal of Electrical and Electronic Engineering, vol. 17, no. 4, pp. 1927–1927, 2021, doi: 10.22068/IJEEE.17.4.1927.
[13] D. L. Waikar, S. Elangovan, A. C. Liew, and S. H. Sng, “Real-time assessment of a symmetrical component and microcontroller
based distance relay,” Electric Power Systems Research, vol. 32, no. 2, pp. 107–112, 1995, doi: 10.1016/0378-7796(94)00900-O.
[14] J. Ma, T. Wang, Z. Wang, and J. S. Thorp, “Adaptive damping control of inter-area oscillations based on federated Kalman filter
using wide area signals,” IEEE Transactions on Power Systems, vol. 28, no. 2, pp. 1627–1635, 2013, doi:
10.1109/TPWRS.2012.2223721.
[15] S. Shankar, K. B. Yadav, A. Priyadarshi, and V. Rathore, “Study of phasor measurement unit and its applications,” in Lecture
Notes in Electrical Engineering, vol. 699, 2021, pp. 247–257.
[16] S. You et al., “Disturbance location determination based on electromechanical wave propagation in FNET/GridEye: A
distribution-level wide-area measurement system,” IET Generation, Transmission and Distribution, vol. 11, no. 18, pp. 4436–
4443, 2017, doi: 10.1049/iet-gtd.2016.1851.
[17] S. P. Singh and S. P. Singh, “Optimal cost wide area measurement system incorporating communication infrastructure,” IET
Generation, Transmission and Distribution, vol. 11, no. 11, pp. 2814–2821, 2017, doi: 10.1049/iet-gtd.2016.1983.
[18] G. P. Bhandari and R. Gupta, “Fault analysis of service-oriented systems: A systematic literature review,” IET Software, vol. 12,
no. 6, pp. 446–460, Dec. 2018, doi: 10.1049/iet-sen.2018.5249.
[19] N. Kumari, S. Singh, R. Kumari, R. Patel, and N. A. Xalxo, “Power system faults: A review,” Ijert, vol. 4, no. 02, pp. 1–2, 2016,
doi: 10.17577/IJERTCONV4IS02020.
[20] A. S. Mubarak, A. S. Hassan, N. H. Umar, and M. Nasiru, “An analytical study of Ppower system under the fault conditions using
different methods of fault analysis,” Advanced Research in Electrical and Electronic Engineering, vol. 2, no. 10, pp. 113–119,
2015, [Online]. Available:
https://www.researchgate.net/publication/318350683An_Analytical_Study_of_Power_System_under_the_Foult_Conditons_using
_different_Methods_of_Fault_Analysis.
[21] A. Yadav and Y. Dash, “An overview of transmission line protection by artificial neural network: Fault detection, Fault
classification, Fault location, and Fault direction discrimination,” Advances in Artificial Neural Systems, vol. 2014, pp. 1–20,
2014, doi: 10.1155/2014/230382.
[22] P. Bunnoon, “Fault detection approaches to power system: State-of-the-art article reviews for searching a new approach in the
future,” International Journal of Electrical and Computer Engineering (IJECE), vol. 3, no. 4, 2013, doi:
10.11591/ijece.v3i4.3195.
[23] J. L. Blackburn and T. J. Domin, Protective relaying. CRC Press, 2014.
[24] A. G. Phadke, “Synchronized phase measurement in power system,” IEEE Computer Applications in Power, vol. 6, no. 2, pp. 10–
15, 1993, doi: 10.1109/67.207465.
[25] J. De La Ree, V. Centeno, J. S. Thorp, and A. G. Phadke, “Synchronized phasor measurement applications in power systems,”
IEEE Transactions on Smart Grid, vol. 1, no. 1, pp. 20–27, 2010, doi: 10.1109/TSG.2010.2044815.
[26] D. Novosel and K. Vu, “Benefits of PMU technology for various applications,” in o sustavu vođenja EES-a HK, 2006, pp. 1–13,
BIOGRAPHIES OF AUTHORS
Int J Adv Appl Sci, Vol. 12, No. 1, March 2023: 15-26