Module 3
Module 3
Principle 1
Principle 10
All premises intended for human habitation, occupancy or
Each fixture directly connected to the drainage system shall
use shall be provided with a supply of pure and wholesome
be equipped with a water-sealed trap
water, neither connected with unsafe water supplies nor
subject to hazards of backflow or back-siphonage
Principle 11
Principle 2 The drainage pipes piping system shall be designed to
provide adequate circulation of air free from siphonage,
Plumbing fixtures, devices and appurtenances shall
aspiration or forcing of trap seals under ordinary use
be supplied with water in sufficient volume and
pressure adequate to function satisfactorily and without
undue noise
Principle 12
Vent terminals shall extend to the outer air and installed to
Principle 3 prevent clogging and the return of foul air to the building
Plumbing shall be designed and adjusted to use
the minimum quantity of water consistent with proper
performance and cleaning Principle 13
Plumbing systems shall be subjected to such tests to
effectively disclose all leaks and defects in the
Principle 4 workmanship
Devices for heating and storing water shall be so designed
and installed as to prevent dangers from explosion through
overheating Principle 14
Substance which will clog the pipes, produce explosive
mixtures, destroy the pipes or their joints or interfere unduly
Principle 5 with the sewage-disposal process shall not be allowed to
enter the building drainage system
Every building abutting on a street, alley or easement with a
public sewer shall connect its plumbing fixtures to the Principle 15
sewer system
Proper protection shall be provided to prevent
contamination of food, water, sterile goods and similar
materials by backflow of sewage. When necessary, the
Principle 6
fixture, device or appliance shall be connected indirectly
Each family dwelling unit shall have at least one water with the building drainage system
closet, one kitchen type sink, a lavatory and a bathtub or
shower to meet the basic requirements of sanitation and
personal hygiene
Principle 16
No water closet shall be located in a room or compartment
which is not properly lighted and ventilated
Principle 17
If there is no sewer system in the area, suitable provision
shall be made for the disposal of building sewage by
some accepted method of sewage treatment and disposal,
such as a septic tank
Let's start from the sources of water like lakes, rivers,
reservoirs and dams. From there, water shall be released in
Principle 18 bulk volumes and shall be distributed through large main
distribution pipes by Manila Water or Maynilad bringing the
Where a plumbing drainage system may be subject supply of water to various communities. In the residential
to backflow of sewage, suitable provision shall be made setting, these large main distribution pipes are sometimes
to prevent its overflow in the building laid underneath the main roads across the main entrance of
various villages, subdivisions, and small communities. The
portion of these main water distribution pipes serves as the
Principle 19 main water supply for various villages, subdivisions, and
small communities, and even for various industrial and
Plumbing systems shall be maintained in serviceable commercial users. Some subdivisions have their own local
condition by Registered Master Plumbers water tank which provides water for their community.
Water is distributed to its users through network of
underground pipes connecting the main distribution pipes
Principle 20 to the pipes connected inside each household. Upon
reaching a household, the water can now be used from
All plumbing fixtures shall be installed properly spaced, to
various plumbing fixtures connected by pipes inside their
be accessible for their intended use
house. The end-product of all used water in all forms of
processes, or waste waters, are now discharged and
collected by a different set of plumbing fixtures connected
Principle 21 by waste water pipes inside the building towards a sewage
disposal system. These waste waters are then disposed
Plumbing shall be installed with due regard to the
through sanitary sewer lines and storm water sewer
preservation of the strength of structural members and the
lines for those storm water runoffs. These waste waters
prevention of damage to walls and other surfaces through
are treated in sewage treatment plants or STP to remove
fixture usage
harmful components that contaminates the water. After the
thorough process of treatment, the treated waters are
then discharged in natural bodies of water like lakes and
Principle 22 rivers, or in reservoirs and dams, to undergo its natural
process of treatment. Then the cycle goes full circle by
Sewage or other waste from plumbing system which may starting on these sources of water.
be deleterious to surface or sub-surface waters shall not be
discharged into the ground or into any waterway, unless 3.2. Design Provisions for Plumbing
first rendered innocuous through subjection to
some acceptable form of treatment Based on our previous discussion, plumbing is the art and
technique of installing pipes, fixtures, and other apparatuses
in buildings from bringing in the supply, liquids, substances,
and/or ingredients and removing them. Focusing on the
previous plate activity for waterline system, plumbing
system enables the distribution of clean water in the building
through various components such as:
Plumbing Cycle
1. Water Service Entrance
Only a small percentage of the total volume of water in the
world is used for human consumption. Most of these This consists of the main distribution pipe from the
volumes are either stored in ice caps, glaciers, or in the source of water i.e. local subdivision tank, and the
oceans. Water, for it to be continuously sourced from, pipe connecting this to the water supply piping
undergoes a cycle which describes its phases from its system of the building.
sources i.e. reservoirs, lakes, rivers, up to its end-users like 2. Water Meter
me and you, until it goes back again to its sources, and vice
versa. It is a cycle of continuous effort to maintain and A device used to measure the amount of water
secure an optimum supply of water for its users. consumption in a building. This screens the water
before they enter the water supply piping system Closed Coupled Flush Tank
with certain attachments i.e. gate valves, check Low Flush Tank
valves, which regulates the flow of water. High Flush Tank
3. Main Distribution Pipe Water Closets according to Mounting
This is the main pipe that delivers water from the Floor-mounted
outside source towards the connecting pipes inside Wall-hung
the building.
Water Closets according to Flushing Action
4. Branch Pipes (fixtures)
Wash down
This includes all branch pipes connected from the Reverse trap
main distribution pipe inside the building to the
Siphon jet
fixtures inside bathrooms and other areas which
Siphon vortex
will receive water.
Direct flush valve
5. Riser
This is used for buildings of two-storeys and up to Other types of Water Closets include:
distribute water towards the upper floor levels. Squat type
6. Valves and Control Washout
Various valves are available for use in plumbing Setting Water Closets
system with a main function to regulate the flow of
water and other liquids inside the pipes. Although Water closets are set from its center to the surface of a side
there are certain differences among these valves, wall with a minimum distance of 0.375m. Center-to-center
but they similarly function the same. spacing of water closets are set at a minimum of 0.75m.
7. Storage Tanks
There are cases that buildings employ the usage of
water tanks to ensure continuous supply of water
amidst any water interruption incident from its
sources. Aside from determining the capacity of the
tank to be used based on various factors i.e. number
of occupants, the pump required to supply water in
the tank including the pressure requirements for
inflow and outflows should be strictly considered.
Plumbing Fixtures
Plumbing fixtures are classified into: soil, scullery, and
bathing.
Soil Fixtures Urinals
These fixtures are responsible for the collection of various Types of urinals are specified as wall hung, pedestal, trough,
waste water that shall be disposed in soil pipes. Soil and stall. Urinals are set 0.30m from its center to the surface
pipes are pipes that discharges waste water that are of a side wall. 0.60m is the minimum center-to-center
sometimes classified as black water. Black water is a term distance set between two urinals. It is considered that
used to refer waste water that contains solid wastes and the flushing urinals should be done through automatic flushing
the typical liquid wastes. Soil fixtures includes: water tanks or flushometer valves provided that these valve are
closets, urinals. self-closing type that discharges predetermined quantity of
water. No manually-controlled flushometer valve should be
Water Closets used to flush group urinals, as evident in most trough-type
urinals found in public restrooms i.e. bus terminals
Types of water closets are classified according to flushing,
flush tank type, mounting, and flushing action.
Water Closets according to Flushing
Scullery Fixtures
These fixtures consists of those that are responsible for
kitchen, dining, and cooking utensils i.e. kitchen sinks, and The Revised National Building Code of the Philippines has
washing various materials or small items i.e. lavatories, provided an index number which defines the adequate sizing
laundry areas. These fixtures commonly discharges various for the trap that in turn defines the size of branch pipes to be
grey waste water through waste pipes. Waste pipes are pipes used for the fixture. This index number is called the Fixture
that discharges waste water that are sometimes classified as Unit Rating or the FU Rating.
grey water. Grey water is a term used to refer waste water
that only contains pure liquid wastes with occasional
minimal solid wastes which are not from any human or
animal defecate. Other scullery fixtures include: slop sinks,
bar sinks,
Kitchen Sinks
Typical materials used for kitchen sinks are stainless steel,
cast iron enamels, formed steel coated with porcelain
enamel
Laundry Tubs
Typical materials used for laundry tubs are stainless steel,
cast iron enamels, formed steel coated with porcelain
enamel
Lavatories
This fixture unit rating of plumbing fixtures shown in the
Lavatory types are either pedestal, wall hung,
table is based on the size of the trap required for each
pullman/countertop, trough.
fixture. The fixture unit equivalent of fixtures and devices
Bathing Fixtures not shown in the table shall be based on the rated discharge
capacity in liters per second in accordance with the table
These fixtures are primarily responsible for bathing. These shown below.
fixtures commonly discharges various grey waste water
through waste pipes. Bathing fixtures include: bathtubs,
whirlpool baths, Jacuzzi, bidets.
Bidet
Bidets are set at 0.375m from the center of bidet to the
surface of a side wall, and 0.75m minimum center-to-center
distance set between bidets.
Floor Drains
Shower receptors, dams, curbs, are installed in the bathroom The table shown below corresponds to the maximum trap
to prevent the escape of water that might overflow or flood loading including its pipe size and fixture unit rating, in
inside the bathroom during bath. These shall be at accordance with the Revised National Plumbing Code of the
least 25.4mm lower than the outside floor, nor be less Philippines. Exception: This maximum trap loading does not
than 51mm or more than 228mm from the top of the dams apply on self-service laundries.
or curbs to the top of the drain.
Shower Compartment
Shower compartments should have a minimum interior area
of 0.6m2 and shall be capable of encompassing
a 762mm diameter circle. This area shall be maintained
from a point above the shower drain to a height 1.78m with
no protrusions other than the fixture valve, shower head, and
safety grab rails. This is to ensure that the person using the
compartment is given adequate space to freely move around
the compartment during bath. Drains for gang shower rooms
i.e. public shower area in resorts, shall be spaced not more
than 4.9m apart.
We've discussed the subsystems and components of a waste
waterline system including the different types of pipe used
Changes in Direction of Excreta Drainage Flow
Drainage pipes and waste pipes connects various fixtures Traps
towards their point of disposal i.e. septic tank. These pipes
should be properly connected to maintain smooth movement As discussed on the previous module, these are fittings or
of wastes inside these pipes. Correct types of pipes based on devices that provide a liquid seal which prevents the
its shape and certain configuration should be used. The backflow of foul air inside the building. A typical example
direction of wastes through these pipes changes from of this is a P-trap. To know how a P-trap looks like, you
horizontal to vertical i.e. horziontal drainage branch lines might try looking at the pipes below your kitchen sink. That
connected to a vertical stack, or horizontal to horizontal i.e. curved pipe underneath your kitchen sink is a P-trap. There
horizontal drainage line connected to another horizontal are certain kinds of traps that are prohibited under the
drainage line, should be used with proper type of pipe. Revised National Plumbing Code of the Philippines. These
includes those traps with movable parts or concealed interior
Some provisions in these direction changes in pipes partitions, and the S-trap. In relation to this, no fixture
includes: should be double-trapped as a single trap is adequate enough
to perform its function. It is required by the code that each
plumbing fixture connected to a drainage line shall be
separately trapped with an approved water seal trap, except
those with integral traps i.e. water closets. Other trap
requirement based on the code is as follows:
Interceptors, Clarifiers, and Separators A fitting or device that provides a liquid seal which prevents
the backflow of foul air inside the building. From the
An Interceptor is a device designed and installed to separate word trap, it traps the air inside the pipes.
and retain undesirable matters from normal wastes and
permits normal sewage or liquid wastes to discharge into the Branch Pipes/Branch Line
disposal terminal by gravity. An example of this is a grease This refers to any part of the piping system other than the
trap as shown below. Based on the Revised National main, riser, or stack. These pipes are connected to various
Plumbing Code of the Philippines, interceptors should have fixtures which discharges waste water.
a water seal of not less than 152mm deep, and should be
provided with proper ventilation. Stack
On the other hand, clarifiers are settling tanks built with A vertical main pipe of a system extending through one or
mechanical means for continuous removal of solids being more stories and/or extended through the roof.
deposited by sedimentation. These are used to remove solid
particulates or suspended solids from liquid for clarification Waste Pipe
and/or thickening. An example of a clarifier is shown below. This type of pipe only conveys waste water or liquid waste
Notice that the image on the left contains wastes inside the free of any fecal matter
clarifier, while the image on the right shows the retained
solid wastes inside the clarifier once the liquid component of Soil Pipe
the waste has been removed.
This type of pipe conveys waste water which includes fecal
Below, you can see the image of the clarifier once the solid matter
wastes left upon the removal of the liquid component of the
waste has been left to dry out. It becomes an earth or soil- Vent Pipe
like material which can be readily disposed. On the second
This type of pipe is used for ensuring the circulation of air
image below, an example of a separator is shown.
and relieving negative pressure exerted on trap seals in the
3.3. Drain-Waste-Vent System system.
Yoke Vent or By-pass Vent On the other hand, ventilation is not required on a primary
settling tank interceptor which discharges through a
A pipe connecting upward from a soil or waste stack below horizontal indirect waste pipe into a secondary interceptor.
the floor and below horizontal connection to an adjacent The secondary interceptor shall be properly trapped and
vent stack at a point above the floor and higher than the vented. Ventilation is not required for those traps serving
highest spill level of fixtures for preventing pressure sinks which are part of the equipment of bars, soda
changes in the stacks. fountains, and counters, need not be vented when
the location and construction of such bars, soda fountains,
Circuit Vent and counters makes it impossible to do so. When such
A group vent pipe which starts in front of the extreme condition exists, such sink shall discharge by means of an
(highest) fixture connection on a horizontal branch and approved indirect waste pipe into a floor sink or other
connects to the vent stack. approved type receptor.
Looped Vent
A vertical vent connection on a horizontal soil or waste pipe Size of Vents
branch at a point downstream of the last fixture connection The sizes of vent piping shall be determined from its length
and turning to a horizontal line above the highest overflow and the total number of fixture units connected. The
level of the highest fixture connected there. This is diameter of an individual vent shall not be less than 32
commonly used in spaces without partitions. mm (1-1/4”) nor less in size than one-half (1/2) the
Wet Vent diameter of the drain to which it is connected.
Each soil or waste stack extending ten or more storeys above A septic tank is a common private sewage disposal system
the building drain shall be served by a parallel vent found in most residential houses and buildings. A septic tank
stack which shall extend undiminished in size from its upper is a watertight covered receptacle designed and constructed
terminal at the roof and connect to the soil or waste stack at to receive the discharge of sewage from a building sewer,
ground level and at every fifth floor levels with a yoke separate solids from the liquid, digest organic matter and
vent at a point below the horizontal soil or waste store digested solids through a period of detention, and
branch connection to the stack and at the nearby vent stack allow the clarified liquids to discharge for final disposal.
above the same floor to provide a relief vent. The waste water stored within a septic tank is further
classified into various components: sludge, scum, and
The size of yoke vent shall be not less in diameter than effluent.
either the soil stack or the vent stack, whichever is smaller.
The yoke vent connection at the vent stack shall be placed Sludge
1.0 m above the floor level and, by means of a wye branch
the solid organic matter that are denser than water and settle
at the soil stack, shall be placed below the fixture branch
at the bottom of the septic tank
serving that floor. See an illustration below based on a
portion of the image above. Scum
lighter organic material that rise to the surface of the water
Sanitary System Problems: Trap Seal Loss Effluent
In order to properly function its trapping ability, traps have a the liquid content of sewage typically found in between the
water seal which prevents foul odors from escaping within sludge at the bottom and the scum at the top
the waste water piping system. This water seal is susceptible
from being removed in the traps due to various factors Aside from these components, bacteria thriving within the
which can be primarily attributed to changes in pressure. septic tank tends to decompose the solid-organic
The direct effect of the minus and plus pressures inside the components of sewage which depletes sewage volume and
system due to inadequate ventilation of traps can be provides space for more sewage intake. Aerobic bacteria in
attributed to the following conditions: a septic tank relies in oxygen to survive, while anaerobic
bacteria can survive in a septic tank without oxygen.
Siphonage which defines the flow of water seal in the waste
pipe due to a plus pressure (push) from the drain and its Based on the Revised National Plumbing Code of the
corresponding minus pressure (pull/suction) from within the Philippines, a typical septic tank has the following minimum
waste pipes. Direct siphonage exists when the water seal is dimensions as shown in the figure
removed due to direct application of the aforementioned below: length at 1500mm; width at 900mm,
pressure conditions. On the other hand, momentum and; depth at 1200mm.
siphonage is due to the pressure induced by the waste water
discharges form the upper waste water pipes to the waste
water pipe directly below it. Design Criteria
Plans
plans should show all dimensions, reinforcing, structural by the estimated waste/sewage design flow rate for various
calculations, and other pertinent data, as needed building occupancies; or by the number of fixture units of all
plumbing fixtures; whichever is greater.
Quality of Design
The capacity of any one septic tank and its drainage system
it shall be such as to produce a clarified effluent of shall also be limited by the soil structure classification in its
acceptable standards and shall provide adequate space for drainage field
sludge and scum accumulations
Location
Materials It should not be located underneath the house, at
it shall be constructed of durable materials, not subject to least 1.5m from the building/structure, at least 1.5m from
excessive corrosion or decay, and shall be watertight property line adjoining a private property, at
least 15.20m away from the nearest water supply well or
Compartments water streams i.e. river, and at least 3m from nearby trees.
it shall have a minimum of two compartments
SEWERS
First Compartment it shall not be less than two-
thirds capacity of the total capacity of tank, not less There are three degrees or grades of waste water: grey
than 2m3 liquid capacity, shall be at least 0.9m width water, black water, and storm water. Grey water are waste
and 1.5m long. Liquid depth not less than 0.6m nor more water with the exception of human wastes which are
than 1.8m typically from laundries, wash basins, sinks, and tubs. Black
water are waste water which contains solid and liquid
Second Compartment it shall have a maximum of one- human wastes. Both grey and black water are collected and
thirds of the total capacity of the tank; minimum of 1m3 discharge to the private sewage disposal system i.e. septic
liquid capacity tank. On the other hand, storm water are waste water made
up of rainwater.
In septic tanks having over 6m3 capacity, the secondary
compartment should be not less than 1.5m in length, and In relation to these waste waters, sewers are used which
maintain a slope of 1:10 at the bottom of the digestion functions as an underground conduit for carrying off
chamber to collect the sludge and make it easily accessible drainage water and waste matter. Sanitary sewers carries
from the manhole regular sanitary wastes only which terminates in sewage
treatment plants to undergo treatment. Intercepting sewers,
Size of Pipe Inlet and Outlet also known as collecting sewers, receives sewage flow from
a number of branching sewer lines and conducts these
The inlet and outlet pipes shall have a diameter size not less
wastewater to a specific treatment plant. To facilitate
than the sewer pipe. The vertical legs of inlet and outlet
sewage flow, these sewer lines are sloped at an angle of 1:50
pipes shall have a diameter size not less than the sewer pipe
or 2% which tends to bring these pipes deeper into the
nor less than 104.6mm
ground until its no longer feasible to bury such sewer lines
Length and Location of Inlet and Outlet underneath. Lifting stations are placed at certain intervals
and pumps or sewage ejectors are used to lift the waste from
The inlet and outlet pipe shall extend 101.6mm above and at one lower end to its adjacent higher end to maintain
least 304.8mm below the water surface. continuity of sewage flow; sewers terminate at the disposal
plant or treatment plant.
The invert of the inlet pipe shall be at a level not less than
50.8mm above the invert of the outlet pipe. It is imperative that drainage pipes of all buildings shall be
connected to the public sewer, in accordance with the
Air Space
provisions from the Revised National Plumbing Code of the
The side walls shall extend 228.6mm above liquid depth. Philippines. When not available, they shall be connected to
The cover of septic tank shall be at least 50.8mm above the an approved private sewage disposal system. A public sewer
back vent openings. may be considered as not being available if it is more than
61 meters from any proposed building or exterior drainage
Partition facility.
An inverted fitting equivalent in size to the tank inlet, but in Some considerations which tends to damage public sewers
no case less than 104.6mm in diameter, shall be installed in or private sewage disposal systems includes:
the inlet compartment side of the baffle with the bottom of
the fitting placed midway in the depth of the liquid. improper discharging of various substances such as
ashes, cinders, solids, rags, flammable, poisonous,
Wooden baffles are prohibited. explosive liquids or gases, oils, grease, and other
things whatsoever which would cause damage to
Structure
the public sewer or private disposal system
Its structure shall be capable of supporting an earth load of
no rain, surface or subsurface waters shall
not less than 14.4kPa
discharge into any excreta drainage system
Capacity
no cesspool and septic tank effluents, seepage pit or
The capacity of septic tanks is determined by the number of under drain system shall be connected to the
bedrooms or apartment units in dwelling occupancies; excreta building sewer leading to a public sewer
main
no commercial food waste grinder shall be Gutter
connected to a private or public sewage disposal
system it is usually located along the entire perimeter of the roof to
collect rainwater.
Installation of Sewers
Downspout
Building sewers shall be run in practical alignment at a it is located every eight to ten meters and at every corner of
uniform slope of not less than 2% or 21 mm/m toward the the roof, but to avoid clogging of pipes, it is best to locate
point of disposal. An exception to this provision defines that them every four to six meters.
when it is impractical due to depth of street sewer, structural
features or to adverse arrangement of building, to obtain a Strainer or Roof Drain
slope of 2%, sewers 102 mm and 152 mm in diameter may it is used to prevent clogging of pipes.
have a slope of not less than 1% (10.5 mm/m) and those 203
mm diameter and larger may have a slope of not less than Shoe
0.5% (5.3 mm/m). it is the end point of the downspout which discharges storm
water from the downspout to its adjacent catch basin or the
No building sewer shall be installed less than 0.6 meters soil ground.
from the outer face of any building foundation, nor less than
0.3 meters below the finish surface of the ground. Catch Basin
Building sewer or drainage pipe of clay or materials which a storm water drain which collects rainwater from the roof
are not approved for use within a building shall not be laid through downspouts.
in the same trench as water pipes unless:
Storm Line a series of pipes which connects each catch
- the bottom of the water pipe is 0.3 meters above the basin and transports its waste water to its intended public
top of the sewer pipe sewer line through a system of underground piping.
- the water pipe is placed on a solid shelf excavated
at one side of the common trench with a minimum 3.4. Water Supply Pipe Size Calculation
horizontal distance of at least 0.3 meters from the Determination of the proper water supply pipe size involves
sewer or drain pipe obtaining various essential data prior following detailed
Water pipes crossing sewer or drainage pipe of clay or processes which affects the flow of water from its source
materials which are not approved for use within a building towards its end point. Although there are a lot of varying
shall be laid a minimum of 0.3 meters clear above the sewer fixtures in a building, one must focus on how to properly
or drain pipe. deliver water to a certain fixture located farthest and highest
from the water supply source. It will require an optimum
Water pipe joint shall be installed not less than 3 meters amount of water pressure to raise the water supply towards
away from sewer line in both directions. such fixture in a building.
3.3.3. Storm Water System Step 1: Required Data
Storm water is a waste water that is made up of rainwater. Prior calculations, we need to obtain essential data such as
Aside from the typical drainage system discharging waste pressure at the main distribution line of your water source.
water from various fixtures inside a building, storm water This pressure must conform to the minimum daily service
drainage is used to properly discharge rainwater from the pressure in the area to foresee such scenario when the water
building's roof or roof decks. Storm water drainage pipes or pressure is at its lowest. The code specifies that
rainwater pipes shall not be used as soil pipes, as waste the minimum water pressure in the main supply should be
pipes, and even as vent pipes. at least 103kPa (15psi) and that the maximum water
pressure in the main supply should not be greater
There are three major systems for collecting storm water: than 551kPa (80psi). If the pressure is below minimum, an
natural, combined, and independent. approved type of pump must be installed to aid in delivering
Natural System a storm water system that only involves water through the supply pipes. In excess of the specified
roofs to divert rainwater towards the ground without using maximum pressure, an approved type of regulator must be
any roof gutters or downspouts, typically used when installed to reduce the pressure to its optimum. Aside from
rainwater are collected in cisterns. the water pressure, the total fixture load in the water supply
piping system must be determined in terms of
Independent System also known as the separate system, WSFU. Water supply fixture unit (WSFU) is a numerical
this brings collected rainwater directly to its water reservoirs weighing factor to account for water demand of various
or a public storm drainage line outside the building. plumbing fixtures. It is an index number to put all fixtures
on a common basis in terms of water supply consumption.
Combined System in this storm water piping system, both The Revised National Plumbing Code of the Philippines has
storm water with sanitary wastes are collected and provided a list of various fixtures and its corresponding
discharged in a public sewer line this is prohibited since it WSFU as shown in the tabulated data below.
mixes up both grey, black, and storm water within its pipes.
Step 2: Required pressure at the fixture Calculate the total equivalent length of the pipes.