0% found this document useful (0 votes)
28 views2 pages

Ax Av Ctel

The AV-CTEL module provides a conventional Class B telephone circuit for monitoring up to 15 existing or new conventional firefighter phones. It connects to an Advanced 55000-820ADV intelligent I/O module and mounts in a deep 4" electrical box. The AV-CTEL module is compatible with Axis AX Series Dynamix I/O relationship programming for firefighter phone operation.

Uploaded by

Jarryd Bato
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views2 pages

Ax Av Ctel

The AV-CTEL module provides a conventional Class B telephone circuit for monitoring up to 15 existing or new conventional firefighter phones. It connects to an Advanced 55000-820ADV intelligent I/O module and mounts in a deep 4" electrical box. The AV-CTEL module is compatible with Axis AX Series Dynamix I/O relationship programming for firefighter phone operation.

Uploaded by

Jarryd Bato
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

AV-CTEL Module

The AV-CTEL module is an Advanced conventional firefighter


phone circuit module which, when interfaced to an Advanced
55000-820ADV intelligent I/O module, provides a conventional
Class B telephone circuit for monitoring existing or new
conventional hpone jacks and/or firefighter emergency phone
boxes.

Up to fifteen (15) standard conventional RC coupled telephone


jacks, firefighter emergency phone boxes and/or Advanced
conventional phone jacks with active indicator (AV-CJACK) can be
connected to a single AV-CTEL module.

The AV-CTEL module mounts to the screw terminals of an


Advanced 55000-820ADV Intelligent I/O relay output and switch
monitor module and mounts in a deep 4" electrical box.

The AV-CTEL is compatible with the Axis AX Series Dynamix I/O


relationship programming for firefighter telephone operation.

Features
SLC Loop Compatible with 55000-820ADV
Class B Conventional Firefighter Telephone circuit
Supports 15 Conventional Firefighter Phones
Deep 4" Square Electrical Box Mounting
Flexible programming
Durable construction
Axis AX Series Dynamix I/O Relationship Programming
Cost-effective and trouble-free installation

Listings and Approvals


ETL ANSI/UL 864 Listed: 101564744NYM-001
NYCFD COA #6105A2

[900-036] 1.1 Page 1 of 2


us.advancedco.com

Wiring Diagram

Specification
Voltage 9-24 Vdc
Operating current 5.65 mA quiescent, 22.9 mA active
Wiring classification Class B
End-of-line resistor 47 kΩ, 9.5 W
Screw terminals Pluggable, 12-22 AWG (Power Limited)
Mounting Deep 4" square with 55000-820ADV
Temperature 32° - 120°F (0° - 49° C)
Humidity 10-95% (non-condensing)

Order Codes and Options


AV-CTEL Conventional Firefighter Phone Circuit Module (requires 55000-820ADV module)
55000-820ADV Intelligent I/O Relay Output and Switch Monitor Module
AV-CJACK Conventional Phone Jack

Check if this document is up to date | Give us feedback


Advanced, 100 South Street, Hopkinton, MA. 01748 T: +508 435 9995 E: [email protected] W: us.advancedco.com
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice.

[900-036] 1.1 Page 2 of 2

You might also like