Legrand 56661 Datasheet
Legrand 56661 Datasheet
CONTENTS Page
1. Description . . . . . . . . . . . . . . . . . . . . . 1
2. Use . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3. Range . . . . . . . . . . . . . . . . . . . . . . . . 1-3
4. Dimensions . . . . . . . . . . . . . . . . . . . . 4-8
5. Connection . . . . . . . . . . . . . . . . . . . . . 9
6. Technical characteristics . . . . . . . . . 9-10
7. Wiring diagrams . . . . . . . . . . . . . . 11-15
8. Standards . . . . . . . . . . . . . . . . . . . 16-18
9. Accessories . . . . . . . . . . . . . . . . . . . . 19
1. DESCRIPTION 3. RANGE
• Product for distributing power close to equipment 3.1 Single socket units
• Supply of several current types (amps/volts) for industrial and/or • Single socket units with switch (surface and panel mounting version)
domestic pin configuration 16 and 32 A
• Power supply for one or more devices • Single socket units with switch and rail (surface and panel mounting
• Protection of users and circuits: version) 16 and 32 A
- off-load connection and disconnection provided by units • Single socket unit 63 A
equipped with switched socket with double mechanical
interlock Panel Single unit with Single unit with
- protection by MCB, RCBO, RCD (RCCB) mounting switch and switch and rail
• Material: plastic socket with junction box (5 modules)
• Colour: RAL 7035 switch
• IK08
3P+E 0 572 94 0 972 98 0 589 18
• IP44, IP55, IP66 400V 63A
• Classe II 3P+E+T 0 572 95 0 589 10 0 572 99
1/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
M20/M25
CONTENTS 2/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
3. RANGE (continued)
3.5 Self assembly combined units: bases and boxes
1 x 16 or 32 A 2 x 16 A 1 x 63 A
Surface Base for up to Base for up to Base for up to Plain plate
socket sockets socket
mounting box 2 x16 A sockets 4 x16 A sockets 6 x16 A sockets
Pack Cat. No Pack Cat. No Pack Cat. No Pack Cat. No Pack Cat. No Pack Cat. No Pack Cat. No Pack Cat. No
1 0 577 10(7) 1 0 589 38(7) 1 0 577 05(8) 1 0 577 06(8) 5 0 577 12 5 0 577 13(2) 2 0 577 17 5 0 577 15
1 x 16 or 32 A
2 x 16 A or 32 socket 3 x 16 A
Surface Base for up to Base for up to Base for up to Plain plate
A sockets and 1 x 63 A sockets (3)
mounting box 3 x 16 A sockets 6 x16 A sockets x 16 A sockets socket
Take wall mounting lugs
Cat. No. 0 019 69
280 x 125 mm(5) 421 x 125 mm(5) 501 x 265 mm(5) 501 x 405 mm(5)
5-module DIN rail 13-module DIN rail 20-module DIN rail
Pack Cat. No Pack Cat. No Pack Cat. No Pack Cat. No Pack Cat. No Pack Cat. No Pack Cat. No Pack Cat. No
(1) Can take a key-operated lock Cat. No. 0 577 35 - (2) Supplied with blanking plate
(3) To be mounted horizontally except 16 A domestic pin sockets which must be mounted vertically (IP44 with plug inserted)
(4) IP 54 cover closed - IP 44 connected (5) External dimensions: H x W - (6) For faceplate Cat. No. 0 577 17/19
(7) Can be pole-mounted using kit Cat. No. 0 364 46/47/48/49 (see data sheet in e-catalogue for compatibility) - (8) See 1 + 7 - (9) Wiring required for pilot wire
CONTENTS 3/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
501
550
IP 44 Dimensions (mm) IP 55 Dimensions (mm)
Cat. No. A B Cat. No. A B
2P+E 0 566 01 127 122 0 566 21 133 128
LV
3P+E 0 566 05 129 124 0 566 25 134 129 175
16 A
3P+N+E 0 566 06 130 125 0 566 26 135 130
2P+E 0 566 09 138 133 0 566 29 143 138 Panel mounting 63 A single unit with switch
LV
3P+E 0 566 13 138 133 0 566 33 143 138
Cat. Nos. 0 572 94/95
32 A 160
3P+N+E 0 566 14 139 134 0 566 34 144 139 125 129
Refer to these dimensions for similar Cat. Nos.
Surface or panel mounting 16/32 A single unit with rail and switch
320
Fix.100
2P+T 0 566 40/41 290 125 155 0 566 60/61 300 125 155
LV
16
LV
3P+T 0 566 53 295 125 155 0 566 73 310 125 155
32 A
3P+N+T 0 566 54 295 125 155 0 566 74 310 125 155
Refer to these dimensions for similar Cat. Nos. Ø 3,5
Fix.107
Surface mounting 63 A single unit with switch (without rail)
Cat. Nos. 0 572 98/0 589 10
10
Ø 3,5 90
Fix.107
120
125
170
CONTENTS 4/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
5
F ix .95
10°
Fix. 350
441
Entry to drill
Max. M25 25
18
100
128 25
180
Entry
18 to drill
Max. M25 128
2 sockets with MCB and transformer 140 140
Cat. No. 0 589 20
265 122
Entry to drill 2 sockets with MCB
Fix.174 Max. M32 31
Cat. Nos. 0 589 30/32
125 Entry to drill
Max. M32
Fix. 86
10 107
31
Fix.350
441
Fix. 290
361
25
Entry to drill
Max. M25 25
52 88 17
128 128
Entry to drill
Max. M25
31
Fix. 290
361
Fix. 350
25
441
17
31
Fix. 290
361
25
17
CONTENTS 5/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
Max. M32
Entry to drill
Rail fixed
by 2
Fix. 351
421
screws
Cover with
20 window
Entry to drill
23 Max. M20
111
Max. M32
Entry to drill
25
Entry to drill
88 Max. M25 Rail fixed
52 by 2
128 screws
Max. M25
Fix. 210
Entry to drill
501
Fix. 200
20
47 93
Entry to drill A
Max. M20
A
0 589 35 119
0 589 36 120
CONTENTS 6/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
5
Maxi M32
Fix. 210
501
Rail fixed
Fix. 200
by 2
screws
Maxi M20
20
47 93 46
Max. M32
Entry to drill
5
Maxi M32
Fix. 210
501
Fix. 200
Maxi M20
20
140 140 46
18
Maxi M32
Fix. 350
441
Maxi M25 25
52 88 76,5
CONTENTS 7/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
Maxi M32
5
Fix. 210
220
Fix. 350
280
441
Fix. 95
5
maxi
M25
20
Maxi M25 25 18 25
maxi
23 M20
140 140 76,5
18
Faceplates
Cat. Nos. 0 577 12/13/15/17
Cat. Nos. 0 577 00/20
125 107
Fix. 70 31
maxi
130
M32
5
Entry
to
drill
Fix. 351
421
46
20
maxi
23 M20
Entry
to
drill
130
5
Fix. 290
361
Entry
to drill
Max.
M25
17,5 25
72
CONTENTS 8/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
CONTENTS 9/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
Housing Window
Nitric acid 5% . . . . . . . . . . . . . . . . . . . . . . . . . - ++ Resistance to chemical agents at ambient temperature according to risk of
Sulfuric acid 10% . . . . . . . . . . . . . . . . . . . . . . . + ++ exposure by spraying
Hydrochloric acid 30% . . . . . . . . . . . . . . . . . . . . + (++) excellent resistance (continuous exposure)
(+) good resistance (long-term exposure)
Perchloric acid 70% . . . . . . . . . . . . . . . . . . . . . . + (-) limited resistance (brief exposure possible)
Hydrofluoric acid 70% . . . . . . . . . . . . . . . . . . . - ++ (--) poor resistance (exposure to be avoided)
Chromic acid 50% . . . . . . . . . . . . . . . . . . . . . . + +
Phosphoric acid 30% . . . . . . . . . . . . . . . . . . . . + +
Weak acids
Diluted acetic acid < 25% . . . . . . . . . . . . . . . . ++ ++
Citric acid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ++ ++
Lactic acid . . . . . . . . . . . . . . . . . . . . . . . . . . . . ++ ++
Formic acid . . . . . . . . . . . . . . . . . . . . . . . . . . . - -
Uric acid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ++ +
Animal oils and fats
Lard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . + -
Butter, cream . . . . . . . . . . . . . . . . . . . . . . . . . . ++ ++
Vegetable oils and fats
Linseed oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . ++ -
Groundnut/olive oil . . . . . . . . . . . . . . . . . . . . . ++ +
Castor oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ++ ++
Glycerin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . - -
Mineral oils and fats
Paraffin (vaseline) . . . . . . . . . . . . . . . . . . . . . . ++ ++
Engine oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -
Silicone oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . ++ ++
Cutting oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . + -
Hydraulic fluid . . . . . . . . . . . . . . . . . . . . . . . . . + --
Hydrocarbons
Unleaded petrol . . . . . . . . . . . . . . . . . . . . . . . . + -
Diesel oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . + +
Kerosene . . . . . . . . . . . . . . . . . . . . . . . . . . . . . + +
White spirit . . . . . . . . . . . . . . . . . . . . . . . . . . . . + -
Chlorinated solvents
Trichloroethylene . . . . . . . . . . . . . . . . . . . . . . . - --
Trichloroethane . . . . . . . . . . . . . . . . . . . . . . . . - -
Perchloroethylene . . . . . . . . . . . . . . . . . . . . . . - --
Methyl chloride . . . . . . . . . . . . . . . . . . . . . . . . -- --
Carbon tetrachloride . . . . . . . . . . . . . . . . . . . . - --
Chloroform . . . . . . . . . . . . . . . . . . . . . . . . . . . . --
Aromatic solvents
Benzen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . - -
Toluene . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . - -
Xylene . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . - -
Alphatic solvents
Hexane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . - +
Heptane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fluoride solvents
Trichlorofluoromethane . . . . . . . . . . . . . . . . . . - --
Ketones
Acetone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -- --
Methyl ethyl ketone . . . . . . . . . . . . . . . . . . . . . -- --
Ethyl acetate . . . . . . . . . . . . . . . . . . . . . . . . . . -- --
Terpenes
Turpentine . . . . . . . . . . . . . . . . . . . . . . . . . . . . - -
CONTENTS 10/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
7. WIRING DIAGRAMS
Cat. No. 0 589 20
CONTENTS 11/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
CONTENTS 12/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
CONTENTS 13/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
CONTENTS 14/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
CONTENTS 15/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
8. STANDARDS
• EN 60309-1 and IEC 60309-1 (conception)
• EN 60309-2 and IEC 60309-2 (interchangeability)
• EN 60309-4 and IEC 60309-4 (with locking device)
• EN 60529 and IEC 60529
• EN 62262 and IEC 62262
• EN 610439-1 and IEC 61439-1
The IEC 60439 standard series has been replaced by the IEC 61439 standard series. This series describes the construction and verification require-
ments for low-voltage switchgear assemblies.
It is applicable to electricity distribution in industry, construction sites and household environments.
IEC 61439-1 defines the general rules, and cannot be used alone.
For each context of use, an IEC 61439- X standard is applicable. All the points discussed refer systematically to the relevant chapter of IEC 61439-1,
adding any details or amendments associated with the context of use.
• IEC 61439-2: Power switchgear assemblies
• IEC 61439-3: Distribution boards intended to be operated by ordinary persons (DBO)
• IEC 61439-4: Particular requirements for assemblies for construction sites (ACS)
Important points in relation to switchgear assemblies:
• Original manufacturer: Organisation that has carried out the original design and associated verification of an assembly
• Assembly manufacturer: Organisation taking responsibility for the completed assembly.
• User: Party who will specify, purchase, use and/or operate the assembly, or someone acting on their behalf.
Assembly manufacturer obligations
• Obligation to comply with the design and construction rules of IEC61439-x
• Obligation to test as per IEC61439
• Obligation to furnish a “Design Verification”
• Obligation to provide specific information:
On a label (or similar) attached to the product, legible on the installed product for some of the information to be provided.
In the “assembly manufacturer’s” technical documentation for the remaining information to be provided (characteristics, handling instructions,
installation, operation, maintenance).
Responsibilities:
The user is responsible for clearly specifying the installation and operating conditions (site, ambient temperatures, etc.).
The original manufacturer is responsible for carrying out the design, original manufacture, associated verifications and producing the technical docu-
mentation and verifications.
The assembly manufacturer producing an assembly is responsible for carrying out the mandatory tests and verifications. They must also issue a
design verification and ensure compliance with information requirements.
The assembly manufacturer, if converting, supplementing or modifying an assembly in accordance with IEC61439, is responsible for carrying out
further verifications, carrying out further tests, and providing further design and information verifications. In other words, in this case, the original
manufacturer loses its status as an assembly manufacturer.
Note:
As regards the latter paragraph, the rationale applies for subsequent maintenance operations, with the exception of the replacement of a component
if it is replaced by an identical apparatus to that specified on the verification or equivalent if its heat dissipation, once connected, is less than or equal
to the original apparatus.
Legrand offering:
All of the items in these two product ranges have been modified and verified in order to meet IEC61439-2 and/or IEC61439-3 requirements.
For all of these items, Legrand is classified as both an “original manufacturer” and as an “assembly manufacturer” as per the standard. We remain
at your disposal to provide verifications.
The conditions of use (voltage, currents, ambient temperatures, etc.), assembly and wiring must correspond to the actual use.
Based on the conditions of installation and use provided by the customer, our teams verify whether the envisaged configuration is eligible for the
target IEC61439-X standard. If this is the case, following the order of the “bespoke” product, our teams will be able to provide the compliance
documents on request.
CONTENTS 16/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
These units are compatible with the IEC 61439-2 and/or IEC 61439-3 standards.
The compliance of the complete assembly is henceforth obligatorily within the remit of the “assembly manufacturer” (manufacturer finalising
assembly and wiring). The manufacturer of the ready-to-assemble cabinet is not in a position to guarantee compliance, failing knowledge of the
conditions of use and the possibility of carrying out the tests and verifications required by the standard. Hence, the verifications, tests, certificates
and documents to be furnished are the responsibility of the manufacturer finalising the wiring. Therefore, the assembly manufacturer is responsi-
ble for the certification of the complete assembly with its equipment.
In brief: Standard or configured Legrand P17 equipped units suitable for qualifying for IEC61439-X offer installer clients a “ready-to-install” solution
that is “verified, tested, validated as per the standard criteria”. The compliance documents are made available and make reference to the inspec-
tion body once the product is installed and used under the defined conditions.
Assembly tests:
The assembly must be tested with each circuit charged to its Rated current multiplied by the RDF coefficient of the cabinet without exceeding the
Total current InA of the unit.
Where:
Overheating:
The standard stipulates maximum overheating levels not to be exceeded, when thermal stabilisation is achieved, on the input terminals, on the
device handles, on accessible surfaces. etc.
Moreover, integrated products (circuit breakers, RCDs, connectors, etc.) must operate under temperature conditions permitted by their reference
standard. Inside the unit, the ambient temperature is greater than its external temperature. Despite this, the products should function correctly.
As regards circuit breakers, the nominal characteristics are dependent on the temperature in their vicinity.
The equipped units have been tested at an external ambient temperature of 20°C, therefore greater inside. The indicated currents account for this.
For other ambient temperature values, it is necessary to refer to the circuit breaker derating chart.
By way of example: derating chart of circuit breaker 4 077 84
CONTENTS 17/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
Ambient Temperature / In
In (A) - 25°C - 10° C 0 10° C 20° C 30° C 40° C 50° C 60° C 70° C
0,5 A 0,62 0,6 0,57 0,55 0,52 0,5 0,47 0,42 0,40 0,38
1,5 A 1,9 1,8 1,7 1,7 1,6 1,5 1,5 1,4 1,4 1,3
3,5 A 4,5 4,2 4,0 3,9 3,7 3,5 3,4 3,3 3,2 3,1
5A 6,4 6,0 5,8 5,5 5,3 5,0 4,8 4,7 4,5 4,6
6A 7,5 7,0 6,6 6,4 6,2 6,0 5,8 5,6 5,4 5,3
10 A 12,5 11,5 11,1 10,7 10,3 10,0 9,7 9,3 9,0 8,7
13 A 16,3 15,0 14,3 13,9 13,4 13,0 12,6 12,1 11,7 11,3
16 A 20,0 18,7 18,0 17,3 16,6 16,0 15,4 14,7 14,1 13,5
20 A 25,0 23,2 22,4 21,6 20,8 20,0 19,2 18,4 17,6 16,8
25 A 31,5 29,5 28,3 27,2 26,0 25,0 24,0 22,7 21,7 20,7
30 A 38,3 36,0 34,5 33,0 31,5 30,0 28,8 27,3 26,1 24,9
32 A 41,0 37,8 36,5 34,9 33,3 32,0 30,7 29,1 27,8 26,5
40 A 51,0 48,0 46,0 44,0 42,0 40,0 38,0 36,0 34,0 32,0
50 A 64,0 60,0 57,5 55,0 52,5 50,0 47,5 45,0 42,5 40,0
63 A 80,6 75,6 72,5 69,9 66,1 63,0 59,8 56,1 52,9 49,7
Numerous tests and numerous verifications are stipulated in the standard in order to assess product compliance. (IP, Shock, Fire resistance, Di-
electric voltage, Shock voltage, etc.)
All of these tests have been carried out. They confirm the compliance of the various items in the P17 “bespoke” unit range with the IEC61439-1 +
IEC61439-2 standards and for the most part with IEC61439-1 + IEC61439-3.
Protection
Rated class: class
Min. connection Protection
Cat. Nos. Voltage Frequency diversity IEC 61439-2 InA IEC 61439-3 InA I or class II
cross-section class
factor (double
(mm2)
(RDF) Insulation)
CONTENTS 18/19
P17 combined units Cat. Nos: 0 566 XX - 0 572 XX - 0 577 XX - 0 589 XX
Supplied with lugs to wind the cable for combined unit with:
5 Lexic modules (577 20/589 33): Cat. No. 0 577 37
12 Lexic modules: Cat. No. 0 577 38
18 Lexic modules: Cat. No. 0 577 39
0 577 00/10
0 577 11/20 --- --- ---
For locking the viewing window for optimum safety 0 589 33
0 589 30/31/32
0 589 37/38
--- --- ---
9.3 Emergency stop and emergency break
0 589 40/41
Plates with Osmoz buttons --- --- ---
0 589 42/43
Osmoz emergency stop button
Cat. No. 0 577 40 0 589 50/51/52
0 589 53/54/57
--- ---
For cutting off the power supply to the units
Plate fixed on pre-drilled faceplate
0 598 41 --- --- ---
Supplied in parts ready for assembly
Supplied with push-pull 2 NC contact block
0 598 43 --- --- ---
Osmoz emergency break button
Cat. No. 0 577 45 0 598 46 --- --- ---
For cutting off the power supply to the units
Plate fixed on pre-drilled faceplate 0 589 22/34
Supplied in parts ready for assembly 0 589 35/36 --- --- ---
Supplied with push-pull 1 NO contact blo 0 598 47/48
CONTENTS 19/19