30RAP Start-Up Procedure
30RAP Start-Up Procedure
IF YES, WAS IT NOTED ON THE FREIGHT BILL, AND HAS A CLAIM BEEN FILED
WITH THE SUPPLIER? YES NO
DESCRIPTION ____________________________________________________________________________
_________________________________________________________________________________________
1. UNIT IS INSTALLED LEVEL AS PER THE INSTALLATION INSTRUCTIONS. YES NO
5. ELECTRICAL CIRCUIT PROTECTION HAS BEEN SIZED AND INSTALLED PROPERLY. YES NO
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300221-01 Printed in U.S.A. Form 30RAP-7T Rev. A Pg CL-1 5-21 Replaces: 30RAP-6T
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
7. CHILLED WATER PUMP STARTER INTERLOCKED WITH CHILLER. YES NO
9. WATER LOOP VOLUME GREATER THAN MINIMUM REQUIREMENTS. (See Table 30). YES NO
NOTE: GLYCOL CONCENTRATIONS ABOVE 30% MAY REQUIRE A FLOW SWITCH RE-CALIBRATION.
11. OUTDOOR PIPING WRAPPED WITH ELECTRIC HEATER TAPE, YES NO
INSULATED AND OPERATIONAL.
SIGNATURE REQUIRED
Design Information
CAPACITY CEAT EWT LWT FLUID TYPE FLOW RATE P.D.
5. VERIFY COMPRESSOR MOUNTING BOLT TORQUE IS 7-10 FT-LB (9.5-13.5 N-M). YES NO
6. LEAK CHECK UNIT. LOCATE, REPAIR AND REPORT ANY REFRIGERANT LEAKS. YES NO
CL-2
III. Unit Start-Up (cont)
OPERATING DATA:
RECORD THE FOLLOWING INFORMATION FROM THE PRESSURES AND TEMPERATURES MODES WHEN
MACHINE IS IN A STABLE OPERATING CONDITION:
PRESSURE/TEMPERATURE
CIRCUIT A CIRCUIT B
DISCHARGE PRESSURE DP.A DP.B
SUCTION PRESSURE SP.A SP.B
SATURATED CONDENSING TEMP SCT.A SCT.B
SATURATED SUCTION TEMP SST.A SST.B
RETURN GAS TEMPERATURE RGT.A RGT.B
LIQUID LINE TEMPERATURE*
DISCHARGE LINE TEMPERATURE*
*Readings taken with a digital thermometer.
CL-3
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Compressor Running Current — All readings taken at full load.
COMPRESSOR MOTOR CURRENT L1 L2 L3
COMPRESSOR A1
COMPRESSOR A2
COMPRESSOR A3
COMPRESSOR B1
COMPRESSOR B2
COMPRESSOR B3
CL-4
III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY “UNIT”. PRESS DOWN ARROW KEY TO DISPLAY “OPT1”.
PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW.
CL-5
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY “OPT1”. PRESS DOWN ARROW KEY TO DISPLAY “OPT2”.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
PRESS ESCAPE KEY TO DISPLAY “OPT2”. PRESS DOWN ARROW KEY TO DISPLAY “CCN”.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
CCN (CCN Network Configuration)
CL-6
III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY “CCN”. PRESS DOWN ARROW KEY TO DISPLAY “EXV.A”.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
EXV.A (Circuit A EXV Configuration)
SUB-MODE ITEM ITEM EXPANSION DISPLAY ENTRY
EXV.L EXV OPENING AT LOW LWT XX%
LWT.L LWT FOR EXV MIN OPENING XX° F
EXV.H EXV OPENING AT HIGH LWT XX%
LWT.H LWT FOR EXV MAX OPENING XX° F
MIN.A EXV CIRC.A MIN POSITION XXX.X%
RNG.A EXVA STEPS IN RANGE XXXXX
SPD.A EXVA STEPS PER SECOND XXXXX
POF.A EXVA FAIL POSITION IN% X.XX%
MIN.A EXVA MINIMUM STEPS XXXXX
MAX.A EXVA MAXIMUM STEPS XXXXX
OVR.A EXVA OVERRUN STEPS XXX.X%
EXV.A A.ST.P EXV CIRC A START POS XXX.X%
TYP.A EXVA STEPPER TYPE 0,1
H.SCT HIGH SCT THRESHOLD XXX.X° F
X.PCT OPEN EXV X% ON 2ND COMP XX.X%
X.PER MOVE EXV X% ON DISCRSOL XX.X%
A.PCT PRE-OPEN EXV - FAN ADDING XXX.X%
M.PCT PRE-CLOSE EXV - FAN SUB XXX.X%
S.PCT PRE-CLOSE EXV - LAG SHUT XXX SEC
DELY LAG START DELAY XXX SEC
L.DL.T LOW SH DELTA T - EXV MOVE XXX SEC
SHR.T EXV RATE THRESHOLD XX.X F
L.EX.M LOW SH OVERRIDE EXV MOVE X.X%
PRESS ESCAPE KEY TO DISPLAY “EXV.A”. PRESS DOWN ARROW KEY TO DISPLAY “EXV.B”.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
EXV.B (Circuit B EXV Configuration)
SUB-MODE ITEM ITEM EXPANSION DISPLAY ENTRY
MIN.B EXV CIRC.B MIN POSITION XXX.X%
RNG.B EXVB STEPS IN RANGE XXXXX STEP
SPD.B EXVB STEPS PER SECOND XXXXX
POF.B EXVB FAIL POSITION IN % XXX.X%
EXV.B
MIN.B EXVB MINIMUM STEPS XXXXX STEP
MAX.B EXVB MAXIMUM STEPS XXXXX STEP
OVR.B EXVB OVERRUN STEPS XXX STEP
TYP.B EXVB STEPPER TYPE 0,1
CL-7
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY “EXV.B”. PRESS DOWN ARROW KEY TO DISPLAY “MM”.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
CL-8
III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY “RSET”. PRESS DOWN ARROW KEY TO DISPLAY “SLCT”.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW:
PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THE
ARROW KEYS TO SCROLL TO THE SET POINT LED. PRESS ENTER TO DISPLAY SETPOINTS.
RECORD CONFIGURATION INFORMATION BELOW:
SETPOINT
CL-9
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
III. Unit Start-Up (cont)
COMPONENT TEST
USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY “DISP”.
PRESS ENTER AGAIN TO DISPLAY “TEST” FOLLOWED BY “OFF”. PRESS ENTER TO STOP DISPLAY AT
“OFF” AND ENTER AGAIN SO “OFF” DISPLAY FLASHES. “PASS” AND “WORD” WILL FLASH IF PASSWORD
NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR
EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD.
AT FLASHING “OFF” DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY “ON” AND PRESS ENTER. ALL
LED SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE
TO RETURN TO THE “DISP” DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO
ILLUMINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY “TEST”. PRESS ENTER TO STOP DIS-
PLAY AT “OFF” AND ENTER AGAIN SO “OFF” FLASHES. PRESS THE UP ARROW KEY AND ENTER TO
ENABLE THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS “TEST” “ON”. REFER TO THE
TABLE BELOW.
Service Test Mode and Sub-Mode Directory
KEYPAD ITEM COMPLETED
SUB-MODE ITEM DISPLAY COMMENT
ENTRY EXPANSION (YES/NO)
ON/OFF SERVICE TEST MODE To Enable Service Test Mode, move
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display.
CL-10
III. Unit Start-Up (cont)
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display.
CL-11
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
COMMENTS:
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
SIGNATURES:
START-UP CUSTOMER
© 2021 Carrier
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300221-01 Printed in U.S.A. Form 30RAP-7T Rev. A Pg CL-2 5-21 Replaces: 30RAP-6T