30RAP Start-Up Procedure

This document provides a checklist for starting up a 30RAP liquid chiller. It includes steps to [1] check the equipment for any issues, [2] verify proper installation of the chiller and water system, and [3] start and test the operation of the chiller unit. The checklist collects project details, ensures safety practices are followed, and guides the user through measuring performance data to confirm correct operation.

Uploaded by

Hunter Bercow
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views

30RAP Start-Up Procedure

This document provides a checklist for starting up a 30RAP liquid chiller. It includes steps to [1] check the equipment for any issues, [2] verify proper installation of the chiller and water system, and [3] start and test the operation of the chiller unit. The checklist collects project details, ensures safety practices are followed, and guides the user through measuring performance data to confirm correct operation.

Uploaded by

Hunter Bercow
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

START-UP CHECKLIST FOR 30RAP LIQUID CHILLER

(Remove and use for Job File)

NOTE: To avoid injury to personnel and damage to equipment or


property when completing the procedures listed in this start-up
checklist, use good judgment, follow safe practices, and adhere
to the safety considerations/information as outlined in preced-
ing sections of this Controls, Start-Up, Operation, Service, and
Troubleshooting document.
I. Project Information
Job name ______________________________________ Installing contractor________________________________
Address ______________________________________ Sales office ______________________________________
City ____________________State_____ Zip ___________ Start-up performed by______________________________
Unit
Model _______________________________________ Serial _________________________________________

II. Preliminary Equipment Check (To Be Performed By Installing Contractor)


IS THERE ANY PHYSICAL DAMAGE?  YES  NO

IF YES, WAS IT NOTED ON THE FREIGHT BILL, AND HAS A CLAIM BEEN FILED
WITH THE SUPPLIER?  YES  NO

DESCRIPTION ____________________________________________________________________________

_________________________________________________________________________________________
1. UNIT IS INSTALLED LEVEL AS PER THE INSTALLATION INSTRUCTIONS.  YES  NO

2. POWER SUPPLY AGREES WITH THE UNIT NAMEPLATE.  YES  NO

3. ELECTRICAL POWER WIRING IS INSTALLED PROPERLY.  YES  NO

4. UNIT IS PROPERLY GROUNDED.  YES  NO

5. ELECTRICAL CIRCUIT PROTECTION HAS BEEN SIZED AND INSTALLED PROPERLY.  YES  NO

6. ALL TERMINALS ARE TIGHT.  YES  NO

7. ALL PLUG ASSEMBLIES ARE TIGHT.  YES  NO

8. REMOVE SHIPPING BRACKETS FROM COMPRESSORS.  YES  NO

Chilled Water System Check (to be performed by installing contractor)

1. SYSTEM HAS BEEN PROPERLY CLEANED AND FILLED.  YES  NO

2. ALL CHILLED WATER VALVES ARE OPEN.  YES  NO


II. Preliminary Equipment Check (Cont)
3. ALL PIPING IS CONNECTED PROPERLY.  YES  NO

4. ALL AIR HAS BEEN PURGED FROM THE SYSTEM.  YES  NO

5. CHILLED WATER PUMP IS OPERATING WITH THE CORRECT ROTATION.  YES  NO

6. CHILLED WATER PUMP CONTROLLED BY CHILLER.  YES  NO

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300221-01 Printed in U.S.A. Form 30RAP-7T Rev. A Pg CL-1 5-21 Replaces: 30RAP-6T
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
7. CHILLED WATER PUMP STARTER INTERLOCKED WITH CHILLER.  YES  NO

8. INTEGRATED 40 MESH Y STRAINER CLEAN.  YES  NO

9. WATER LOOP VOLUME GREATER THAN MINIMUM REQUIREMENTS. (See Table 30).  YES  NO

10. PROPER LOOP FREEZE PROTECTION PROVIDED TO _____ °F (°C).  YES  NO


ANTIFREEZE TYPE _____________________ CONCENTRATION __________%.
IF OUTDOOR AMBIENT IS BELOW 32 F (0° C) THEN ITEMS 11-13 HAVE TO BE
COMPLETED TO PROVIDE COOLER FREEZE PROTECTION TO –20 F (–29 C). (REFER
TO WINTER SHUTDOWN FOR PROPER COOLER WINTERIZATION PROCEDURE.)

NOTE: GLYCOL CONCENTRATIONS ABOVE 30% MAY REQUIRE A FLOW SWITCH RE-CALIBRATION.
11. OUTDOOR PIPING WRAPPED WITH ELECTRIC HEATER TAPE,  YES  NO
INSULATED AND OPERATIONAL.

12. COOLER HEATERS INSTALLED AND OPERATIONAL.  YES  NO

13. CRANKCASE HEATERS (IF EQUIPPED) ARE SECURELY ATTACHED, OPERATIONAL,

CUT ALONG DOTTED LINE


AND ENERGIZED TO REMOVE ANY LIQUID FROM THE COMPRESSOR.  YES  NO

SIGNATURE REQUIRED

PRELIMINARY START-UP COMPLETE.

INSTALLING/MECHANICAL CONTRACTOR ____________________________________ DATE_________________

III. Unit Start-Up (Qualified individuals only. Factory start-up recommended.)

Design Information
CAPACITY CEAT EWT LWT FLUID TYPE FLOW RATE P.D.

CUT ALONG DOTTED LINE


1. ALL CABLES AND THERMISTORS HAVE BEEN INSPECTED FOR CROSSED WIRES.  YES  NO

2. ALL THERMISTORS ARE FULLY INSERTED INTO WELLS.  YES  NO

3. COMPRESSOR OIL LEVEL IS CORRECT.  YES  NO

4. VERIFY CRANKCASE HEATERS (IF EQUIPPED) HAVE BEEN ENERGIZED


FOR 24 HOURS.  YES  NO

5. VERIFY COMPRESSOR MOUNTING BOLT TORQUE IS 7-10 FT-LB (9.5-13.5 N-M).  YES  NO

6. LEAK CHECK UNIT. LOCATE, REPAIR AND REPORT ANY REFRIGERANT LEAKS.  YES  NO

7. VOLTAGE IS WITHIN UNIT NAMEPLATE RANGE.  YES  NO

8. CONTROL TRANSFORMER PRIMARY CONNECTION SET FOR PROPER VOLTAGE.  YES  NO

9. CONTROL TRANSFORMER SECONDARY VOLTAGE =

CL-2
III. Unit Start-Up (cont)

10. CHECK VOLTAGE IMBALANCE: A-B A-C B-C


AVERAGE VOLTAGE = (A-B + A-C + B-C)/3
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =
VOLTAGE IMBALANCE = ____________% (MAX. DEVIATION/AVERAGE VOLTAGE) X 100
VOLTAGE IMBALANCE LESS THAN 2%.  YES  NO
(DO NOT START CHILLER IF VOLTAGE IMBALANCE IS GREATER THAN 2%.
CONTACT LOCAL UTILITY FOR ASSISTANCE.)

11. VERIFY COOLER FLOW RATE.  YES  NO


PRESSURE ENTERING COOLER ________ psig (kPa)
PRESSURE LEAVING COOLER ________ psig (kPa)
COOLER PRESSURE DROP ________ psig (kPa)
Psig X 2.31 ft/psi = ________ ft of water
kPa X 0.334 m/psi ________ m of water
COOLER FLOW RATE ________ gpm (l/s) (See Cooler Pressure
Drop Curves from
Installation Instructions)

12. FLOW SWITCH OPERATION CHECKED.  YES  NO

Start and Operate Machine. Complete the Following:

1. COMPLETE COMPONENT TEST.  YES  NO

2. CHECK REFRIGERANT AND OIL CHARGE.  YES  NO

3. RECORD COMPRESSOR MOTOR CURRENT.  YES  NO

4. RECORD CONFIGURATION SETTINGS.  YES  NO

5. RECORD OPERATING TEMPERATURES AND PRESSURES.  YES  NO

6. PROVIDE OPERATING INSTRUCTIONS TO OWNER’S PERSONNEL. Instruction Time ________ hours.

OPERATING DATA:

RECORD THE FOLLOWING INFORMATION FROM THE PRESSURES AND TEMPERATURES MODES WHEN
MACHINE IS IN A STABLE OPERATING CONDITION:

PRESSURE/TEMPERATURE
CIRCUIT A CIRCUIT B
DISCHARGE PRESSURE DP.A DP.B
SUCTION PRESSURE SP.A SP.B
SATURATED CONDENSING TEMP SCT.A SCT.B
SATURATED SUCTION TEMP SST.A SST.B
RETURN GAS TEMPERATURE RGT.A RGT.B
LIQUID LINE TEMPERATURE*
DISCHARGE LINE TEMPERATURE*
*Readings taken with a digital thermometer.

COOLER EWT EWT


COOLER LWT LWT
OUTDOOR-AIR TEMPERATURE OAT
CONTROL POINT CTPT
PERCENT TOTAL CAPACITY CAP
LEAD/LAG LEAVING FLUID DLWT (DUAL CHILLER CONTROL ONLY)
III. Unit Start-Up (cont)

CL-3
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Compressor Running Current — All readings taken at full load.
COMPRESSOR MOTOR CURRENT L1 L2 L3
COMPRESSOR A1
COMPRESSOR A2
COMPRESSOR A3
COMPRESSOR B1
COMPRESSOR B2
COMPRESSOR B3

CONDENSER FAN MOTOR CURRENT L1 L2 L3


FAN MOTOR 1
FAN MOTOR 2
FAN MOTOR 3
FAN MOTOR 4
FAN MOTOR 5
FAN MOTOR 6

CUT ALONG DOTTED LINE


FAN MOTOR 7
FAN MOTOR 8
FAN MOTOR 9
FAN MOTOR 10

COOLER PUMP MOTOR CURRENT L1 L2 L3


COOLER PUMP 1
COOLER PUMP 2

Record Software Versions


MODE — RUN STATUS
PRESS ENTER AND ESCAPE KEYS SIMULTANEOUSLY TO OBTAIN SOFTWARE VERSIONS.

SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY

CUT ALONG DOTTED LINE


MBB CESR-131460- _ _-_ _
EXV CESR-131172- _ _-_ _
AUX1 CESR-131333- _ _-_ _
VERS EMM CESR-131174- _ _-_ _
MARQ CESR-131171- _ _-_ _
NAVI CESR-131227- _ _-_ _
CXB CESR-131173- _ _-_ _

CL-4
III. Unit Start-Up (cont)

PRESS ESCAPE KEY TO DISPLAY “UNIT.” RECORD CONFIGURATION SETTINGS BELOW.

UNIT (Configuration Settings)

SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY


UNIT CONFIGURATION
SIZE UNIT SIZE XXX
SZA.1 COMPRESSOR A1 SIZE XX TONS
SZA.2 COMPRESSOR A2 SIZE XX TONS
SZA.3 COMPRESSOR A3 SIZE XX TONS
SZB.1 COMPRESSOR B1 SIZE XX TONS
SZB.2 COMPRESSOR B2 SIZE XX TONS
SZB.3 COMPRESSOR B3 SIZE XX TONS
UNIT
SH.SP SUPERHEAT SETPOINT XX.X F
FAN.S FAN STAGING SELECT XX
EXV EXV MODULE INSTALLED YES/NO
A1.TY COMPRESSOR A1 DIGITAL? YES/NO
MAX.T MAXIMUM A1 UNLOAD TIME XX SEC
FN.SQ CONDFAN SEQ FOR SSN 2214 YES/NO
VLTS UNIT VOLTAGE XXX
F.POL NUM POLES IN FAN X

PRESS ESCAPE KEY TO DISPLAY “UNIT”. PRESS DOWN ARROW KEY TO DISPLAY “OPT1”.
PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW.

OPTIONS1 (Options Configuration)

SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY


UNIT OPTIONS 1 HARDWARE
FLUD COOLER FLUID X
MLV.S MINIMUM LOAD VALVE SELECT YES/NO
CSB.E CSB BOARDS ENABLE ENBL/DSBL
CPC COOLER PUMP CONTROL ON/OFF
PM1E COOLER PUMP 1 ENABLE YES/NO
PM2E COOLER PUMP 2 ENABLE YES/NO
PM.P.S COOLER PMP PERIODIC STRT YES/NO
PM.SL COOLER PUMP SELECT X
OPT1
PM.DY COOLER PUMP SHUTDOWN DLY XX MIN
PM.DT PUMP CHANGEOVER HOURS XXXX HRS
ROT.P ROTATE COOLER PUMPS NOW YES/NO
PMP.O COOLER PUMP OPERATION X
PM.HT PUMP HIGH TEMP CUT OFF XX.XF
EMM EMM MODULE INSTALLED YES/NO
CND.T CND HX TYP 0=RTPF 1=MCHX 0/1
MOPS EXV MOP SET POINT XX
APPR CONFIG APPROACH SETPOINT XX

CL-5
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
III. Unit Start-Up (cont)

PRESS ESCAPE KEY TO DISPLAY “OPT1”. PRESS DOWN ARROW KEY TO DISPLAY “OPT2”.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.

OPTIONS2 (Options Configuration)

SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY


UNIT OPTIONS 2 CONTROLS
CTRL CONTROL METHOD X
LOAD LOADING SEQUENCE SELECT X
LLCS LEAD/LAG CIRCUIT SELECT X
LCWT HIGH LCW ALERT LIMIT XX.X F
DELY MINUTES OFF TIME XX
OPT2 ICE.M ICE MODE ENABLE ENBL/DSBL

CUT ALONG DOTTED LINE


LS.MD LOW SOUND MODE SELECT X
LS.ST LOW SOUND START TIME 00:00
LS.ND LOW SOUND END TIME 00:00
LS.LT LOW SOUND CAPACITY LIMIT XXX %
ALR.C ALARM RELAY USAGE X
SER.T SERVICE TRIO ENABLE ENBL/DSBL

PRESS ESCAPE KEY TO DISPLAY “OPT2”. PRESS DOWN ARROW KEY TO DISPLAY “CCN”.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
CCN (CCN Network Configuration)

SUB-MODE ITEM ITEM EXPANSION DISPLAY ENTRY


CCNA CCN ADDRESS XXX
CCN CCNB CCN BUS NUMBER XXX

CUT ALONG DOTTED LINE


BAUD CCN BAUD RATE X

CL-6
III. Unit Start-Up (cont)

PRESS ESCAPE KEY TO DISPLAY “CCN”. PRESS DOWN ARROW KEY TO DISPLAY “EXV.A”.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
EXV.A (Circuit A EXV Configuration)
SUB-MODE ITEM ITEM EXPANSION DISPLAY ENTRY
EXV.L EXV OPENING AT LOW LWT XX%
LWT.L LWT FOR EXV MIN OPENING XX° F
EXV.H EXV OPENING AT HIGH LWT XX%
LWT.H LWT FOR EXV MAX OPENING XX° F
MIN.A EXV CIRC.A MIN POSITION XXX.X%
RNG.A EXVA STEPS IN RANGE XXXXX
SPD.A EXVA STEPS PER SECOND XXXXX
POF.A EXVA FAIL POSITION IN% X.XX%
MIN.A EXVA MINIMUM STEPS XXXXX
MAX.A EXVA MAXIMUM STEPS XXXXX
OVR.A EXVA OVERRUN STEPS XXX.X%
EXV.A A.ST.P EXV CIRC A START POS XXX.X%
TYP.A EXVA STEPPER TYPE 0,1
H.SCT HIGH SCT THRESHOLD XXX.X° F
X.PCT OPEN EXV X% ON 2ND COMP XX.X%
X.PER MOVE EXV X% ON DISCRSOL XX.X%
A.PCT PRE-OPEN EXV - FAN ADDING XXX.X%
M.PCT PRE-CLOSE EXV - FAN SUB XXX.X%
S.PCT PRE-CLOSE EXV - LAG SHUT XXX SEC
DELY LAG START DELAY XXX SEC
L.DL.T LOW SH DELTA T - EXV MOVE XXX SEC
SHR.T EXV RATE THRESHOLD XX.X F
L.EX.M LOW SH OVERRIDE EXV MOVE X.X%

PRESS ESCAPE KEY TO DISPLAY “EXV.A”. PRESS DOWN ARROW KEY TO DISPLAY “EXV.B”.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
EXV.B (Circuit B EXV Configuration)
SUB-MODE ITEM ITEM EXPANSION DISPLAY ENTRY
MIN.B EXV CIRC.B MIN POSITION XXX.X%
RNG.B EXVB STEPS IN RANGE XXXXX STEP
SPD.B EXVB STEPS PER SECOND XXXXX
POF.B EXVB FAIL POSITION IN % XXX.X%
EXV.B
MIN.B EXVB MINIMUM STEPS XXXXX STEP
MAX.B EXVB MAXIMUM STEPS XXXXX STEP
OVR.B EXVB OVERRUN STEPS XXX STEP
TYP.B EXVB STEPPER TYPE 0,1

CL-7
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
III. Unit Start-Up (cont)

PRESS ESCAPE KEY TO DISPLAY “EXV.B”. PRESS DOWN ARROW KEY TO DISPLAY “MM”.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.

MM (Motormaster Configuration Settings)

SUB-MODE ITEM ITEM EXPANSION DISPLAY ENTRY


MMR.S MOTORMASTER SELECT X
P.GAN HEAD PRESSURE P GAIN XX.X
MM I.GAN HEAD PRESSURE I GAIN XX.X
D.GAN HEAD PRESSURE D GAIN XX.X
MIN.S MINIMUM FAN SPEED XXX.X%

CUT ALONG DOTTED LINE


PRESS ESCAPE KEY TO DISPLAY “MM”. PRESS DOWN ARROW KEY TO DISPLAY “RSET”.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.

RSET (Reset Configuration Settings)

SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY


RESET COOL TEMP
CRST COOLING RESET TYPE X
MA.DG 4-20 - DEGREES RESET XX.X ΔF
RM.NO REMOTE - NO RESET TEMP XXX.X° F
RM.F REMOTE - FULL RESET TEMP XXX.X° F
RM.DG REMOTE - DEGREES RESET XX.X ΔF
RT.NO RETURN - NO RESET TEMP XXX.X ΔF
RT.F RETURN - FULL RESET TEMP XXX.X ΔF
RT.DG RETURN - DEGREES RESET XX.X ΔF

CUT ALONG DOTTED LINE


DMDC DEMAND LIMIT SELECT X
DM20 DEMAND LIMIT AT 20 MA XXX %
RSET SHNM LOADSHED GROUP NUMBER XXX
SHDL LOADSHED DEMAND DELTA XXX %
SHTM MAXIMUM LOADSHED TIME XXX MIN
DLS1 DEMAND LIMIT SWITCH 1 XXX.X %
DLS2 DEMAND LIMIT SWITCH 2 XXX.X %
LLEN LEAD/LAG CHILLER ENABLE ENBL/DSBL
MSSL MASTER/SLAVE SELECT SLVE/MAST
SLVA SLAVE ADDRESS XXX
LLBL LEAD/LAG BALANCE SELECT X
LLBD LEAD/LAG BALANCE DELTA XXX HRS
LLDY LAG START DELAY XXX MIN
PARA PARALLEL CONFIGURATION YES/NO

CL-8
III. Unit Start-Up (cont)

PRESS ESCAPE KEY TO DISPLAY “RSET”. PRESS DOWN ARROW KEY TO DISPLAY “SLCT”.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW:

SLCT (Setpoint and Ramp Load Configuration)

SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY


SETPOINT AND RAMP LOAD
CLSP COOLING SETPOINT SELECT X
RL.S RAMP LOAD SELECT ENBL/DSBL
SLCT
CRMP COOLING RAMP LOADING X.X° F
SCHD SCHEDULE NUMBER XX
Z.GN DEADBAND MULTIPLIER X.X

PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THE
ARROW KEYS TO SCROLL TO THE SET POINT LED. PRESS ENTER TO DISPLAY SETPOINTS.
RECORD CONFIGURATION INFORMATION BELOW:

SETPOINT

SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY


COOLING SETPOINTS
CSP.1 COOLING SETPOINT 1 XXX.X° F
COOL
CSP.2 COOLING SETPOINT 2 XXX.X° F
CSP.3 ICE SETPOINT XXX.X° F
HEAD PRESSURE SETPOINTS
H.DP HEAD SET POINT XXX.X° F
F.ON FAN ON SET POINT XXX.X° F
HEAD
F.OFF FAN OFF SET POINT XXX.X° F
B.OFF BASE FAN OFF DELTA TEMP XX.X° F
F.DLT FAN STAGE DELTA XX.X ΔF
BRINE FREEZE SETPOINT
FRZ
BR.FZ BRINE FREEZE POINT XXX.X° F

CL-9
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
III. Unit Start-Up (cont)

COMPONENT TEST
USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY “DISP”.
PRESS ENTER AGAIN TO DISPLAY “TEST” FOLLOWED BY “OFF”. PRESS ENTER TO STOP DISPLAY AT
“OFF” AND ENTER AGAIN SO “OFF” DISPLAY FLASHES. “PASS” AND “WORD” WILL FLASH IF PASSWORD
NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR
EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD.
AT FLASHING “OFF” DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY “ON” AND PRESS ENTER. ALL
LED SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE
TO RETURN TO THE “DISP” DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO
ILLUMINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY “TEST”. PRESS ENTER TO STOP DIS-
PLAY AT “OFF” AND ENTER AGAIN SO “OFF” FLASHES. PRESS THE UP ARROW KEY AND ENTER TO
ENABLE THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS “TEST” “ON”. REFER TO THE
TABLE BELOW.
Service Test Mode and Sub-Mode Directory
KEYPAD ITEM COMPLETED
SUB-MODE ITEM DISPLAY COMMENT
ENTRY EXPANSION (YES/NO)
ON/OFF SERVICE TEST MODE To Enable Service Test Mode, move

CUT ALONG DOTTED LINE


Enable/Off/Remote Control switch to
TEST
ENTER

OFF. Change TEST to ON. Move


switch to ENABLE.
OUTS OUTPUTS AND PUMPS
ENTER
EXV.A xxx% EXV% OPEN

EXV.B xxx% EXV% OPEN

FAN1 ON/OFF FAN 1 RELAY Condenser fan contactor 1

FAN2 ON/OFF FAN 2 RELAY Condenser fan contactor 2

FAN3 ON/OFF FAN 3 RELAY Condenser fan contactor 3

FAN4 ON/OFF FAN 4 RELAY Condenser fan contactor 4

FAN5 ON/OFF FAN 5 RELAY Condenser fan contactor 5

FAN6 ON/OFF FAN 6 RELAY Condenser fan contactor 6

FAN7 ON/OFF FAN 7 RELAY Condenser fan contactor 7

CUT ALONG DOTTED LINE


FAN8 ON/OFF FAN 8 RELAY Condenser fan contactor 8

V.HPA xx VAR HEAD PRESS% CIRCUIT A

V.HPB xx VAR HEAD PRESS% CIRCUIT B

CLP.1 ON/OFF COOLER PUMP RELAY 1

CLP.2 ON/OFF COOLER PUMP RELAY 2

COMPRESSOR A1 LOAD Digital Scroll option only


DIG.P xxx PERCENT

CL.HT ON/OFF COOLER/PUMP HEATER

CCH.A ON/OFF CRANKCASE HEATER CIRCUIT A

CCH.B ON/OFF CRANKCASE HEATER CIRCUIT B

RMT.A ON/OFF REMOTE ALARM RELAY

NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display.

CL-10
III. Unit Start-Up (cont)

Service Test Mode and Sub-Mode Directory (cont)


KEYPAD ITEM COMPLETED
SUB-MODE ITEM DISPLAY COMMENT
ENTRY EXPANSION (YES/NO)
CIRCUIT A COMPRESSOR TEST
ENTER CC.A1 ON/OFF COMPRESSOR A1 RELAY

DIG.P XXX% COMP A1 UNLOAD PERCENT Digital Scroll option only


CMPA
CC.A2 ON/OFF COMPRESSOR A2 RELAY

CC.A3 ON/OFF COMPRESSOR A3 RELAY

MLV ON/OFF MINIMUM LOAD VALVE RELAY

CIRCUIT B COMPRESSOR TEST


ENTER CC.B1 ON/OFF COMPRESSOR B1 RELAY See Note
CMPB CC.B2 ON/OFF COMPRESSOR B2 RELAY See Note

CC.B3 ON/OFF COMPRESSOR B3 RELAY See Note

NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display.

CL-11
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
COMMENTS:

________________________________________________________________________________________

________________________________________________________________________________________

________________________________________________________________________________________

________________________________________________________________________________________

________________________________________________________________________________________
________________________________________________________________________________________

________________________________________________________________________________________

________________________________________________________________________________________

________________________________________________________________________________________
________________________________________________________________________________________

CUT ALONG DOTTED LINE


________________________________________________________________________________________

________________________________________________________________________________________

________________________________________________________________________________________

________________________________________________________________________________________
________________________________________________________________________________________

________________________________________________________________________________________

________________________________________________________________________________________

________________________________________________________________________________________
________________________________________________________________________________________

SIGNATURES:

START-UP CUSTOMER

CUT ALONG DOTTED LINE


TECHNICIAN _____________________________ REPRESENTATIVE

DATE ___________________________________ DATE

© 2021 Carrier

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300221-01 Printed in U.S.A. Form 30RAP-7T Rev. A Pg CL-2 5-21 Replaces: 30RAP-6T