Transformer Loading and On-Load Phasor Diagrams
Transformer Loading and On-Load Phasor Diagrams
Transformers can provide a voltage on their secondary winding but to transfer electrical power between their input and
output they need to be loaded
In the previous transformer tutorials, we have assumed that the transformer is ideal, that is one in which there are no core
losses or copper losses in the transformers windings. However, in real world transformers there will always be losses
associated with transformer loading as the transformer is put “on-load”. But what do we mean by: Transformer
Loading.
Well first let’s look at what happens to a transformer when it is in this “no-load” condition, that is with no electrical load
connected to its secondary winding and therefore no secondary current flowing.
A transformer is said to be on “no-load” when its secondary side winding is open circuited, in other words, nothing is
attached and the transformer loading is zero. When an AC sinusoidal supply is connected to the primary winding of a
transformer, a small current, IOPEN will flow through the primary coil winding due to the presence of the primary
supply voltage.
With the secondary circuit open, nothing connected, a back EMF along with the primary winding resistance acts to limit
the flow of this primary current. Obviously, this no-load primary current ( Io ) must be sufficient to maintain enough
magnetic field to produce the required back emf. Consider the circuit below.
Ad
Grammarly Install
An in-phase current, IE which supplies the core losses (eddy current and hysteresis).
o
A small current, IM at 90 to the voltage which sets up the magnetic flux.
Note that this no-load primary current, Io is very small compared to the transformers normal full-load current. Also due
to the iron losses present in the core as well as a small amount of copper losses in the primary winding, Io does not lag
o
behind the supply voltage, Vp by exactly 90 , ( cosφ = 0 ), there will be some small phase angle difference.
We use cookies on our website to give you the most relevant experience by remembering your preferences and repeat visits.
By clicking “Accept All”, you consent to the use of ALL the cookies. However, you may visit "Cookie Settings" to provide a
controlled consent.
The secondary current, IS which is determined by the characteristics of the load, creates a self-induced secondary
magnetic field, ΦS in the transformer core which flows in the exact opposite direction to the main primary field, ΦP.
These two magnetic fields oppose each other resulting in a combined magnetic field of less magnetic strength than the
single field produced by the primary winding alone when the secondary circuit was open circuited.
This combined magnetic field reduces the back EMF of the primary winding causing the primary current, IP to increase
slightly. The primary current continues to increase until the cores magnetic field is back at its original strength, and for a
transformer to operate correctly, a balanced condition must always exist between the primary and secondary magnetic
fields. This results in the power to be balanced and the same on both the primary and secondary sides. Consider the
circuit below.
Transformer “On-load”
We use cookies on our website to give you the most relevant experience by remembering your preferences and repeat visits.
By clicking “Accept All”, you consent to the use of ALL the cookies. However, you may visit "Cookie Settings" to provide a
controlled consent.
We know that the turns ratio of a transformer states that the total induced voltage in each winding is proportional to the
Cookie Settings Accept All
number of turns in that winding and also that the power output and power input of a transformer is equal to the volts
times amperes, ( V x I ). Therefore:
But we also know previously that the voltage ratio of a transformer is equal to the turns ratio of a transformer as:
“voltage ratio = turns ratio”. Then the relationship between the voltage, current and number of turns in a transformer can
be linked together and is therefore given as:
Transformer Ratio
Where:
NP/NS = VP/VS – represents the voltage ratio
NP/NS = IS/IP – represents the current ratio
Note that the current is inversely proportional to both the voltage and the number of turns. This means that with a
transformer loading on the secondary winding, in order to maintain a balanced power level across the transformers
windings, if the voltage
We use cookies is stepped
on our website up, you
to give the current
the mostmust be stepped
relevant down
experience and vice versa.
by remembering yourInpreferences
other words,
and “higher voltage
repeat visits.
— By
lower current” or “lower voltage — higher current”.
clicking “Accept All”, you consent to the use of ALL the cookies. However, you may visit "Cookie Settings" to provide a
controlled consent.
As a transformers ratio is the relationships between the number of turns in the primary and secondary, the voltage across
each winding, and the current through the windings, we can rearrange the above transformer ratio equation to find the
valueCookie
of anySettings
unknown Accept All
voltage, ( V ) current, ( I ) or number of turns, ( N ) as shown.
The total current drawn from the supply by the primary winding is the vector sum of the no-load current, Io and the
additional supply current, I1 as a result of the secondary transformer loading and which lags behind the supply voltage
by an angle of Φ. We can show this relationship as a phasor diagram.
If we are given currents, IS and Io, we can calculate the primary current, IP by the following methods.
We use cookies on our website to give you the most relevant experience by remembering your preferences and repeat visits.
By clicking “Accept All”, you consent to the use of ALL the cookies. However, you may visit "Cookie Settings" to provide a
controlled consent.
We use cookies on our website to give you the most relevant experience by remembering your preferences and repeat visits.
By clicking “Accept All”, you consent to the use of ALL the cookies. However, you may visit "Cookie Settings" to provide a
controlled consent.
Actual real life, transformer windings have impedances of both XL and R. These impedances need to be taken into
account when drawing the phasor diagrams as these internal impedances cause voltage drops to occur within the
transformers windings. The internal impedances are due to the resistance of the windings and an inductance drop called
the leakage reactance resulting from the leakage flux. These internal impedances are given as:
So the primary and secondary windings of a transformer possess both resistance and reactance. Sometimes, it can be
more convenient if all these impedances values are combined together on the same side of the transformer to make the
maths calculations a little easier.
It isWepossible
use cookies on our
to move thewebsite
primaryto give you the most
impedances relevant
to the experience
secondary side orbythe
remembering
secondaryyour preferences
impedances and primary
to the repeat visits.
side.
By clicking “Accept All”, you consent to the use of ALL the cookies. However, you may visit "Cookie Settings"
The combined values of R and L impedances are called “Referred Impedances” or “Reflected Values”. The object here to provide a
controlled consent.
is to group together the impedances within the transformer and have just one referred value value of R and XL to either
the primary or the secondary side in our calculations as shown.
Cookie Settings Accept All
So for example, to refer a secondary resistance of 2Ω to the primary side that has a turns ratio of 8:1 will result in a new
2
primary resistive value of: 2 x 8 = 128Ω, while a primary resistance of 2Ω will result in a secondary resistive value
of: 0.03125Ω.
Voltage regulation is expressed as a percentage (or per unit) of the no-load voltage. Then if E represents the no-load
secondary voltage and V represents the full-load secondary voltage, the percentage regulation of a transformer is given
as:
So for example, a transformer delivers 100 volts at no-load and the voltage drops to 95 volts at full load, the regulation
would be 5%. The value of E – V will depend upon the internal impedance of the winding which includes its resistance,
R and more significantly its AC reactance X, the current and the phase angle.
Also voltage regulation generally increases as the power factor of the load becomes more lagging (inductive). Voltage
regulation with regards to the transformer loading can be either positive or negative in value, that is with the no-load
voltage as reference, the change down in regulation as the load is applied, or with the full-load as reference and the
change up in regulation as the load is reduced or removed.
In general, the regulation of the core type transformer when the transformer loading is high is not as good as the shell
type
Wetransformer. This
use cookies on ouriswebsite
becauseto the
giveshell typemost
you the transformer has betterby
relevant experience flux distribution
remembering duepreferences
your to the interlacing ofvisits.
and repeat the coil
windings.
By clicking “Accept All”, you consent to the use of ALL the cookies. However, you may visit "Cookie Settings" to provide a
controlled consent.
In the next tutorial about Transformers we will look at the Multiple Winding Transformer which has more than one
primary winding
Cookie Settingsor more thanAllone secondary winding and see how we can connect two or more secondary windings
Accept
together in order to supply more voltage or more current to the connected load.
Read more Tutorials inTransformers
1. Transformer Basics
2. Transformer Construction
3. Transformer Loading
4. Multiple Winding Transformers
5. The Autotransformer
6. The Current Transformer
7. Three Phase Transformers
8. Audio Transformer
9. Transformer Voltage Regulation
156 Comments
Join the conversation
Error! Please fill all fields.
Your Name
Email Address
Write your comment
here
Submit
Frank
Excellent! I love how the topic it’s analysied to simple complexity… and understanding.
Excellent content.
Thank you
Great Content
Truly one of the best tutorials on web! God bless you all and more power to all of you.
Thank you very much.
Good job
Nice please I want to know different voltage transformer is being coil make
Hi!
So you told that secondary voltage is due to the magnetic flux from the primary current. But, why my real practice
shows that sec. voltage is always totally in phase with the primary voltage and not with the prinary current?
And I could not create situation or loads when secondary voltage was in phase with its supposed originator – the
primary current (which is not totally in phase with the primary voltage)?
Assuming a standard voltage transformer. If only a voltage was applied to the primary winding there would
be no secondary output voltage as there would be no magnetic flux induced in the core. As transformer
works on the principle of electromagnetic induction. When a primary current flows driven by the presense of
the primary voltage and frequency through the coil winding, magnetic lines of force (flux) are created which
transfers energy from the primary side to the secondary side. The flow of current in the primary winding
We use cookies on and
creates our website to give
drives the you thefield
magnetic mostso
relevant experience
that when by remembering
the primary current is your preferences
increasing, and repeat
magnetic linesvisits.
of force
By clickingexpand
“Acceptoutward
All”, you
from the primary and cut the secondary winding. Thus a voltage is induced into the a
consent to the use of ALL the cookies. However, you may visit "Cookie Settings" to provide
controlled secondary
consent. winding when the alternating magnetic lines of force cut across it. Therefore, it is the flow of
current in the primary which causes a voltage to be induced across the secondary due to the action of mutual
induction. Accept All
Cookie Settings
Since the primary winding is effectively an inductor, the phase angle between the primary voltage (Vp) and
current (Ip) would depend on the windings resistance and leakage reactance, which in practical transformers
is very small. The power rating of a transformer is obtained by simply multiplying the current by the voltage
to obtain a rating in Voltamperes, (VA). The power consumed by the secondary load depends on its
impedance and power factor. If Is lags Vs by an angle (phi) this is mirrored back onto the primary winding
so Ip lags Vp by the same amount giving the power factor of the transformer for a particular load. Thus as
you state, the primary and secondary voltages will always be in-phase due to the secondary phase angle.
Posted on May 16th 2022 | 9:27 am
Reply
Hem Raj
Really superb article. But I hv a question that is it possible difference in secondary voltage when checked with
neutral.
Verygood
+989170276397
Masha Allah
We use
. amcookies on ourwith
very happy website
thistoPDF
give you the most relevant experience by remembering your preferences and repeat visits.
By clicking “Accept All”, you consent to the use of ALL the cookies. However, you may visit "Cookie Settings" to provide a
controlled
Postedconsent.
on April 30th 2021 | 8:02 am
Reply
Abhay
Cookie Mishra
Settings Accept All
This site give best explanation, i was searching for it, and i am so happy that i found it.
Posted on March 07th 2021 | 10:37 am
Reply
Close
We use cookies on our website to give you the most relevant experience by remembering your preferences and repeat visits.
By clicking “Accept All”, you consent to the use of ALL the cookies. However, you may visit "Cookie Settings" to provide a
controlled consent.