User Manual Transmitter Digital Physicochemistry ACTEON 5000
User Manual Transmitter Digital Physicochemistry ACTEON 5000
1. GENERAL ..............................................................................................................4
1.1 Safety instructions .................................................................................................................................... 4
1.2 Labeling .................................................................................................................................................... 4
3. INSTALLATION ...................................................................................................16
3.1 Description and mounting of the controller. ............................................................................................... 16
3.1.1 Description of the front face. ..................................................................................................... 16
3.1.2 Equipment required. .................................................................................................................. 16
3.1.3 Outline drawings of the ACTEON 5000. ................................................................................... 17
3.2 Electrical connections. .................................................................................................................................. 18
3.2.1 Safety instructions – Installation. .............................................................................................. 18
3.2.2 Description of the wiring............................................................................................................ 19
5. SETTING UP ........................................................................................................24
5.1 Initial start-up. .............................................................................................................................................. 24
5.2 Installation of digital sensors. ....................................................................................................................... 25
5.3 Selection of the parameters. ......................................................................................................................... 25
6. PROGRAMMING .................................................................................................28
6.1 Main menu. .................................................................................................................................................... 28
6.2 Description of the menus. ............................................................................................................................. 28
6.2.1 Configuring the digital inputs. ................................................................................................... 28
6.2.2 Configuring the On/Off inputs. .................................................................................................. 35
6.2.3 Configuring the Analog inputs. .................................................................................................. 36
6.2.4 Configuring the ACTEON 5000. ............................................................................................... 40
6.2.5 Configuring the Analog outputs. ............................................................................................... 41
6.2.6 Configuring the relay outputs. ................................................................................................... 44
6.2.7 Configuring the Recording output. ............................................................................................ 48
6.2.8 Configuration of digital outputs: Ethernet or RS485 MODBUS slave series. ........................... 48
8. MAINTENANCE ...................................................................................................52
8.1Maintaining the transmitter:......................................................................................................................... 52
8.2 Maintenance of digital sensors: .................................................................................................................... 53
8.2.1 OPTOD sensor. ........................................................................................................................ 53
8.2.2 NTU sensor: Turbidity. .............................................................................................................. 55
8.2.3 PHEHT sensor: pH/Temperature. ............................................................................................. 57
8.2.4 ORP sensor: REDOX/Temperature. ......................................................................................... 58
8.2.5 C4E sensor: 4-electrode conductivity. ...................................................................................... 59
8.2.6 CTZN sensor: Inductive conductivity. ....................................................................................... 60
8.2.7 VB5 – MES 5 sensor: Sludge blanket detection – Sludge blanket detection/Suspended
Solid/Turbidity. ................................................................................................................................... 61
8.2.8 StacSense probe. ..................................................................................................................... 62
9. TROUBLESHOOTING .........................................................................................64
In order to maintain and ensure the good working order of the device, users must comply with the
safety precautions and warnings featured in this manual.
1.2 Labeling
Prior to any installation or start-up operation, check all the labels and symbols affixed to the
measurement device.
This symbol indicates there is a risk of electric shock or electrocution associated with the
use of the device.
This symbol indicates that the measuring device cannot be disposed of as conventional
waste.
The ACTEON 5000 label on the right-hand face indicates the required power supply and the device's
serial number.
Casing
Dimensions (WxHxD) 213 x 185 x 84 mm
Weight 950 g
Material Grey ABS
Ingress protection rating IP 65
Front face Non-reflective polyester
The digital sensors in the PONSEL range are equipped with galvanic isolation and can perform digital
signal processing to optimize the reliability of the measurements and data sent to the ACTEON 5000
terminal.
All the data regarding the calibration, calibration history, users and measurements is processed
directly within the sensor and transmitted via a Modbus RS-485 link.
The range of digital sensors can be used to measure a variety of parameters: temperature, dissolved
oxygen, pH, redox potential, conductivity (4-electrode or inductive measurement principle), turbidity
and suspended solids.
The OPTOD dissolved oxygen sensor applies the luminescence-based optical measurement
technology and measures reliably and accurately without requiring calibration.
With no consumables or maintenance required, the OPTOD sensor gives an immediate return on the
investment. The only intervention required is to replace the DO disk every two years.
Since it does not consume oxygen, the OPTOD sensor can be used in all media; even when there is a
very weak flow of water.
The body is made of passivated 316 L stainless steel or Titanium for applications in corrosive media.
Measurements
Measurement principle Luminescence-based optical measurement
0.00 to 20.00 mg/L
Measurement ranges 0.00 to 20.00 ppm
0-200%
Resolution 0.01
+/- 0.1 mg/L
Accuracy +/- 0.1 ppm
+/- 1 %
Response time 90% of the value in less than 60 seconds
Recommended measurement frequency >5s
Water movement No circulation required
Temperature compensation Via an NTC thermistor
Storage temperature - 10 °C to + 60 °C
Temperature measurement range 0 °C to 50 °C
Accuracy + /- 0.5 °C
Signal interface Modbus RS-485 (or SDI-12)
Power supply for sensor 5 to 12 volts
Standby: 25 µA
When sending via RS-485 (1 measurement/second): 4.4 mA
Power consumption When sending via SDI-12 (1 measurement/second): 7.3 mA
Current pulse: 100 mA
Warm-up time: 100 mS
Sensor
Dimensions Diameter: 25 mm; Length not including cable: 146 mm
Weight Stainless steel version: 450 g (sensor + 3 m of cable)
Titanium version: 300 g (sensor + 3 m of cable)
Material in contact with the medium Passivated 316L stainless steel. New: Titanium body
Maximum pressure 5 bar
Cable 9-wire shielded conductor, uncoated-strand polyurethane
sleeve
Ingress protection rating IP68
This PONSEL sensor is fitted with an Ag/AgCl reference electrode, used to measure pH and redox, in
a "PLASTOGEL"® KCl-saturated plasticized electrolyte.
The Plastogel® electrolyte is in direct contact with the external environment without interposition of
capillary or porous material. There is therefore no risk of fouling or deactivating the reference
electrode.
The electrode used to measure the pH is a pH-sensitive glass bulb (made from special glass) welded
to the end of a crystal tube, and the electrode for Redox measurements is a platinum disk.
The measuring principle is based on nephelometry: a diode emits infrared light (850 nm) and an IR
receiving diode, set to one side at an angle of 90°, detects the amount of scattered light (standardized
measurement). The sensor can be calibrated using a Formazine standard.
This very economical optical technology requires very little maintenance and no consumables.
Measurements
Measurement principle Scattering of IR at 90°
Measurement ranges 0 to 4,000 NTU in 5 ranges: 0 to 4,500 mg/L range
▪ 0 - 50 NTU Calibration:
▪ 0 – 200 NTU 0-500 mg/L range, as per
▪ 0 – 1,000 NTU standard NF EN 872
▪ 0 – 4,000 NTU range >500 mg/l as per standard
▪ AUTO range NF T 90 105 2
Measurements
Measurement principle Inductive conductivity sensor with temperature compensation
Conductivity measurement range 0.0 to 100.0 mS/cm
Resolution 0.1
Salinity measurement range 5-60 g/kg
Operating temperature 0 to 50 °C
Temperature compensation Via an NTC thermistor or an external measurement
Measurement accuracy of T°C 0.1 °C over a range of 0-40 °C
Response time T90<30 s
Storage temperature -10 °C to 60 °C
Signal interface Modbus RS-485 and SDI-12
Measurement refresh rate < 1 second maximum
Power supply for sensor 5 to 28 volts, max. voltage: 30 V
Automatic standby of < 50 µA, warm-up time: 100 ms
When sending via Modbus RS-485/ Range 0-100 mS/cm
Power consumption
Vin 5V Vin 12 V Vin 24 V
1 31 mA 15.5 mA 11.5 mA
measurement/s
Max. current peak of 700 mA for 2 mS, 350 mA for 150 mS
Sensor
Dimensions Max. diameter: 62.4 mm, Length: 196 mm
Weight 700 g
Materials in contact with the medium EPDM, PVC, stainless steel
Maximum pressure when immersed 5 bar
Cable/connection hardware 9-wire shielded conductor, uncoated-strand polyurethane
sleeve
Ingress protection rating IP68
The measuring principle of this sensor is based on the attenuation of the UV signal, centered on 254
nm, through an optical slot of 2 or 50mm (two models available). The sensor delivers observed fluid
temperature measurements, SAC254 spectral attenuation coefficient (unit: 1/m), CODeq, BODeq and
TOCeq equivalents in mg/l. Finally, the equivalent unit in turbidity is FAU (Formazine Attenuation Unit).
The sensor also incorporates internal temperature measurements to optimize optical measurement.
For the main parameter SAC254 and the turbidity equivalence, the sensor is directly calibrated in clear
water in two steps, by successive activation of the two optical sources, UV and green radiation.
Measurements
UV optics (254 nm) based on absorptiometry
Measurement principle Turbidity compensation by optical measurement at 530 nm
(green)
Optical path 2 mm :
SAC254 : 0-750 1/m
CODeq: 0-1300 mg/L
BODeq : 0-350 mg/L
TOCeq : 0-500 mg/L
Turbidity eq : 0-500 FAU
Measuring range
Optical path 50 mm :
SAC254 : 0-30 1/m
CODeq : 0-50 mg/L
BODeq : 0-15 mg/L
TOCeq : 0-20 mg/L
Turbidity eq : 0-40 FAU
SAC254: 0.01 1/m
Resolution
Turbidity eq : 0.01 to 1 FAU
SAC254: +/- 3%
Accuracy
Turbidity eq: +/- 7%
Optical measure : < 5s
Response time (T90)
Temperature : < 3mn
Temperature measurement
Measuring principle T°C NTC
Operating temperature 0.0 °C to + 40, 0°C
Resolution 0,01 °C
Accuracy +/- 0.5 °C
Storage temperature -10°C to + 50°C
Index of protection IP 68
Signal interface Modbus RTU (RS-485) / SDI-12 (TTL)
Speed of measurement refresh Max : 1 measure / 2s
Sensor Power Supply 5.4 to 26 VDC
Data for 12VDC voltage:
Standby: <10 µA
Consumption Maximum current peak: 400mA (1.5ms)
Average current (1 measure/2s): 30 mA
Energy for 1 measure (1.5s): 300µWh
Sensor
Weight 1600 – 1800 g depending on optical path (cable not included)
Materials in contact with the Body: 316 stainless steel (1.4401)
environment
Maximum pressure Optical windows: Quartz (Corning 7980)
Cable/ connections Cable: Bare Thread Polyurethane Sheath
1 Touch screen
2 Screws securing lower cover (2 screws)
3 Upper cover – do not open.
4 Lower cover - remove to make electrical
connections
5 Four cable glands
The ACTEON 5000 unit is shipped with a bag containing 2 mounting brackets (with 2 pan head
screws) and a set of 12 connectors (two 5-contact connectors, three 4-contact connectors, three 3-
contact connectors, three 2-contact connectors and one 1-contact connector to connect up the power
supply).
Equipment required for installing the unit and for making the electrical connections:
- PH1x75 mm cross head screwdriver for attaching the unit's mounting brackets and for the screws
securing the cover which protects the electrical connections,
- 2.0 x 75 mm flat-blade screwdriver for working on the various electrical connection terminals.
To mount the ACTEON 5000 on a wall, use M5 screws (with a head size of < 10.8).
A 213 mm
B 185 mm
C 84 mm
a1 179.3 mm
b1 125 mm
b2 111.3 mm
c1 71.5 mm
c2 53.5 mm
A 225
B 198
C 165
D 178.5
E 198
Diagram 2: Outline drawing for the ACTEON 5000 unit – wall mounting
Isolate the power supply to the measuring device before performing any electrical connection work.
The electrical wiring and cabling work must be performed exclusively by authorized
personnel.
Due to the risk of electrocution, systematically isolate the power supply to the controller
before performing electrical connection work.
Open the unit's lower cover to access the controller's wiring terminals.
Unscrew the two screws which hold the lower protective cover.
Before removing the cover, loosen all the cable glands so that the cables can slide in and out.
Figure 3 shows the transmitter's wire connection zone when the lower protective cover is removed.
Diagram 3: Photograph showing the terminals on the circuit card
Diagram 4: Diagram of the terminals affixed (as a self-adhesive label) to the protective cover
ET1 ET1
GND GND
ET2 ET2
GND GND
3 – Digital Two digital sensor inputs
sensors V- sensor power supply: Black GND GND
Shielding – Yellow and Green GND SHIELD
RS485 - INPUT RS485 - Green B B
Output 2: NC R2 R2
Output 2: Switch C2 C2
Output 2: NO T2 T2
6 – USB USB port USB
For downloading data
7 – Ethernet Ethernet option ETH
Analog input 1
Input 1: - GND GND
Input 1: + EA1 EA1
Diagram 5: Sensor connection for a cable length of 15 meters or less, and of more than 15 meters.
The figure below shows the data displayed on the home screen when two sensors are connected to
the ACTEON 5000. In this specific case, a pH/Temperature combined sensor and an oxygen sensor
are connected to the ACTEON 5000.
1 8
2
9
3 10
11
4 12
5
13
6
14
15
16
18 17
1 Primary parameter measured by sensor 1 10 State of the two analog outputs: in this
example, analog output 1 is assigned to
sensor No.1. The red mark indicates
4 mA.
2 Stability indicator for the primary 11 State of Relay 1. In this example, relay 1
parameter measured by sensor 1 is assigned to sensor 1 and is in an open
position.
3 Real-time value of the primary parameter 12 Unit for the secondary parameter
measured by sensor 1 measured by sensor 2
4 Primary parameter measured by sensor 2 13 Real-time value of the secondary
parameter measured by sensor 2
5 Stability indicator for the primary 14 State of the two analog outputs: in this
parameter measured by sensor 2 example, analog output 1 is assigned to
sensor No.2. The red mark indicates 4
mA.
6 Real-time value of the primary parameter 15 State of Relay 2. In this example, relay 2
measured by sensor 2 is assigned to sensor 2 and is in an open
position.
7 Secondary parameter measured by 16 Navigation icon used to access the main
sensor 1 menu
8 Unit for the secondary parameter 17 Logos representing the analog outputs
measured by sensor 1
9 Real-time value of the secondary 18 Secondary parameter measured by
parameter measured by sensor 1 sensor 2
Table 2: description of the home screen.
If only one sensor is connected to the ACTEON 5000 then lines are displayed in the lower part of the
display where the parameter information and units would normally appear.
The device has a touch screen so that the user can navigate through the various menus using the
icons listed in the table below.
Icon Functionality
Opens the Main Menu containing all the main programming functions for the device.
This icon appears on the home screen.
Opens the menu used to modify the Modbus address for the digital sensors.
Indicates an unusual situation, and provides information which can be consulted. When
it appears on the home screen, it indicates that the sensor is currently in a special state
which may be consulted by pressing on the value displayed.
When the transmitter is switched on, the home screen (i.e. the main measurement screen) appears
with no indication of the sensor(s) installed if no sensors have yet been configured.
If the sensors connected have already been configured, measured values may be displayed (primary
and secondary parameters).
As an initial step, the operator can set the display language, the date format and the date and time.
➢ Setting the language:
To access the language menu, follow the sequence shown below from the home screen:
At the home screen, select the Main menu icon, then the Device settings icon, and finally the
Language icon.
➢ Setting the date and time:
From the Device settings menu, select the Date/hour settings icon.
Option Description
Format Used to set the date format: the options are DD/MM/YY, YY/MM/DD and
MM/DD/YY.
Place the pointer on the "Format" line using the up and down navigation icons, then
select the Confirm icon.
Date Select the "Date" line, press the confirm icon and then set the date by changing the
values on the screen which, in order, correspond to the day, month and year. Use
the up and down navigation icons to change the numbers and the Confirm icon to
move from one variable to another.
Hour Used to set the time: select the "Hour" line using the up and down navigation icons,
press the Confirm icon, then set the hour and minutes.
Summer/winter To activate/deactivate automatic change-over to summer or winter time, select the
time "Summer/Winter time" line, confirm with the Confirm icon and select "Yes" or "No".
When sensors are connected to the transmitter for the first time they must be installed by running a
SCAN (to scan the addresses from 1 to 243).
As soon as the transmitter detects a sensor, it displays its address, its serial number (which is also
engraved on the body of the sensor) and a description of the sensor.
In the example above, pH and oxygen sensors have been detected: the pH sensor is at address 24,
the sensor's serial number is SN-PPHRA-0762 and the description of the sensor is
pH/redox/Temperature Ponsel Mesure. The OPTOD sensor is at address 10, the serial number is SN-
PODOA-4032 and its description is OPTOD/Temperature Ponsel Mesure.
The operator can stop the SCAN operation at any time by pressing on the icon.
If no sensor is detected, or 2 sensors have the same address (an address conflict) or a communication
error is detected, then the device displays a warning message accompanied by the icon.
Pressing on the icon accesses the addressing menu (refer to section 6.2.1 for more details
about the addressing function) where the operator can change the sensor's address in the event of an
address conflict (i.e. if 2 sensors have the same address).
Once ACTEON has detected the sensors, the parameters measured by the sensors must be set up.
For each sensor, a primary and a secondary parameter can be selected.
To access the measurement settings menu, follow the sequence shown below from the home screen:
To set up the primary and secondary parameters for sensor 1, select the corresponding icon.
Primary parameter This line lets the operator select the primary parameter for sensor 1,
which shall then be displayed in the upper part of the home screen (refer
to item 3 in Table 2). The next window then lets the operator select from
a list of the parameters measured by sensor No. 1 (up to 4 parameters).
Secondary parameter This parameter shall be displayed in the upper right-hand corner of the
upper part of the home screen (refer to item 7 in Table 2). The next
window then lets the operator select from a list of the parameters
measured by sensor No. 1.
Measurement range The measurement range can only be set for the conductivity and turbidity
parameters, as indicated in the table below.
Temperature units This line is used to select the units in which the temperature parameter
will be displayed (°C or °F).
Refresh rate This line lets the operator select an interval between each measurement
of between 1 and 60 seconds.
Stacsense Temperature
From the home screen, access the main menu using the icon.
Icon Functionality
This menu is dedicated to PONSEL digital sensors and is used to set up the 2 digital
inputs, including: the sensor detection function (SCAN), the setting-up of the
parameters measured by the sensors, the calibration of the sensors and the setting of
each sensor's Modbus address.
This menu is used to set up the two On/Off inputs for the washing, Event, Alert, etc.
functions.
This menu is used to select voltage or current for the analog inputs.
This menu is dedicated to configuring the ACTEON 5000 and is used to: set-up the
screen; consult the hardware/software version and the events log; set the date/time
and language; return to factory settings and set a password.
This menu is used to set up the optional Ethernet digital output and the MODBUS
functionality.
This menu is used to set up the two relay outputs in alarm/fault mode or based on
thresholds.
This menu is used to set up the two analog outputs for the 0/4-2 mA or PID linking
functions.
To access the "Numeric input settings" window from the Main menu, select the icon.
Icon Functionality
This menu lets you scan and detect the PONSEL digital sensors connected to the
ACTEON 5000.
This icon lets the user calibrate the digital sensors and set up the compensation
parameters.
This menu lets the operator modify the Modbus address of a sensor (notably used
when two identical sensors are installed on the device).
This window is used to calibrate the parameters measured by the selected sensor, or to set the
external compensation data.
Icon Functionality
This menu is used to set up the external data used for compensation purposes
Temperature Each sensor is equipped with its own temperature sensor, and the temperature
recorded is considered if temperature compensation is required (for the pH,
oxygen in mg/L and conductivity parameters). However, it is also possible to
enter a fixed external compensation value.
The first line is used to activate the compensation and to access a second line
which is used to adjust this parameter (possible values: 0.00 to 40.00 °C).
Alpha This coefficient can be set for the Non-compensated conductivity parameter
measured by the CTZN sensor (possible values: 0.0 to 6.0 %/°C) in order to
activate linear compensation.
To select the line above or below, or to increase or reduce a value, use the and icons.
The icon confirms the value set for the external compensation data. Any changes made become
effective when the "Communication completed successfully" message appears.
To access the "Calibration settings" menu from the "Calibration: sensor 1 (or 2)" window, select the
"Calibration" icon.
This menu is used to apply the default calibration coefficients set in the factory.
Detailed calibration log: this menu contains the data for the last ten calibrations
(offset/gain) … The coefficients for a specific calibration can be reused.
The Calibration settings window lets the operator: select the parameter to be calibrated; enter the
operator's name; select a calibration mode and set the values of the standards used.
Operator This menu is used to enter the Operator's name (maximum of 13 characters)
which will be saved with the results of a calibration process.
Type This line appears if the parameter selected for calibration is oxygen as a %Sat.
To complete this line, the operator can select either a 2-point calibration
(OFFSET and GAIN) or a single-point calibration (GAIN only).
Mode The options are: "Single" or "Multiple" mode: when several sensors of the same
type are connected, a parameter common to all the sensors can be calibrated.
The "Single" option is used when calibrating one parameter for one sensor, and
"Multiple" is used when calibrating one parameter for 2 sensors (e.g. the
Temperature parameter measured by all the sensors, or the connection of 2 pH
sensors).
Standard 1 In the "Standard 1" window, which only appears if the value can be modified, the
value of the Standard can be set using a number pad and will be used during the
first step of the calibration for the calculation of the OFFSET.
The value which can be set cannot exceed the minimum and maximum values.
Site If a NTU sensor or a MES sensor is connected to the device and when selecting
a calibration in mg/L or in g/L, the calibration process will be saved in a file saved
under the name of the site. Up to 10 sites can be configured, each identified
using 8 characters.
Pressing on the icon validates the setting of the calibration data and starts the first calibration
step ("Standard 1" window).
In the window corresponding to the first step in the calibration, the first line indicates the value of the
N1 standard and the second line presents the measurement delivered by the sensor in contact with
the standard solution.
A message indicates if the value measured by the sensor is stable or not. The confirmation of the first
calibration step (gearwheel icon) initiates the second step ("Standard 2" window).
Once the second calibration step has been confirmed, a summary window appears which presents the
information about the values of the standards used and the coefficients calculated.
The appearance of the icon on a coefficient calculation line indicates that the coefficient has
been confirmed, whereas the icon indicates that the coefficient obtained is out-of-range.
The table below presents the calibration steps for each parameter:
SAC254 Clear water (active UV source) Clear water (530nm (green) active source)
Turbidity eq
The first 3 lines of the "Addressing" window are used to define the serial number of the sensor affected
by the change of address.
After configuring the Serial No. and address, confirm with the icon.
The sensor's serial number is engraved on the body of the sensor and comprises the following
information:
After configuring the Serial No. and address, confirm with the icon. The change made to the
Modbus address becomes effective when the "Communication completed successfully" message
appears.
Washing: used with an external washing system, for which one On/Off
output would be connected to the ACTEON 5000. The washing activation
signal activates Automatic Maintenance Mode for the relay and analog
outputs (refer to sections 6.2.5 and 6.2.6). A note regarding the activation
and ending of the washing shall be recorded in the Events log (refer to
section 6.2.4).
I2: Function Programming of On/Off Input No.2 (see above for the configuration of
On/Off Input No.1)
Inactive
Washing
Event
Alert
I1: Signal min For a Current input: can be set to a value between 0 and 20 mA
For a Voltage input: can be set to a value between 0 and 10V
I1: Signal max For a Current input: can be set to a value between the minimum value set
up in the "Signal min" line and 20 mA.
For a Voltage input: can be set to a value between the minimum value set
up in the "Signal min" line and 10 V.
I1: Average Used to set the number of measurements, from 1 (instantaneous value) to
50, from which the moving average is calculated.
I1: Refresh rate This line lets the operator select the interval between each measurement.
The possible values are:1 to 60 seconds.
I1: Source signal 1 min This line lets the operator set the minimum value to between -9999.99 and
9999.9
I1: Source signal 1 This line lets the operator set the maximum value to between the minimum
max value set on the "Source signal 1 min" line and 9999.9.
I1: Source signal 1 This line lets the operator arrange the information displayed on the home
display screen (refer to Table 2 for parameter display details)
Not displayed
Sens 1. Prim. Meas.: the measurement shall be displayed in the space
allocated to the primary parameter for sensor 1 (item 3 on the home screen)
Sens 1. Sec. Meas.: item 9 on the home screen.
I1: User desig. A free text field for entering the user's designation (maximum of
13 characters).
I1: Source signal 1 Can be set from 0 to 50 % (the default is 1 %) and is used to define when
stability delta the arrow on the home screen will indicate that the measurement is stable if
the parameter measured has been set as the primary parameter for sensor
1 or 2 (refer to items 2 and 5 in Table 2)
The name of the file must be of the form "CONFANA2.csv" and must
contain the following information:
Line 1 of the csv file: a description (not more than 16 characters) of the
calculated source signal.
Line 2: a blank line containing no characters.
Lines 3 to 32: a number of conversion points in the form of portions of a
straight line Source signal 2 = f(Source signal 1).
To activate the conversion, plug the stick into the ACTEON 5000's USB port
(refer to item 6 of diagram 3) and wait for the small green LED located
above the USB port to stop flashing.
Then navigate to menu I2: Source signal 2 and select the "Active" option.
I1: Source signal 2 Can be set from 0 to 50 % (the default is 1 %) and is used to define when
stability delta the arrow on the home screen will indicate that the measurement is stable if
the parameter measured has been set as the primary parameter for sensor
1 or 2 (refer to items 2 and 5 in Table 2)
Setting up Input 2
I2: Signal min For a Current input: can be set to a value between 0 and 20 mA
For a Voltage input: can be set to a value between 0 and 10V
I2: Signal max For a Current input: can be set to a value between the minimum value set
up in the "Signal min" line and 20 mA.
I2: Average Used to set the number of measurements, from 1 (instantaneous value) to
50, from which the moving average is calculated.
I2: Refresh rate This line lets the operator select the interval between each measurement.
The possible values are:1 to 60 seconds.
I2: Source signal 1 min This line lets the operator set the minimum value to between -9999.99 and
9999.9
I2: Source signal 1 This line lets the operator set the maximum value to between the minimum
max value set on the "Source signal 1 min" line and 9999.9.
I2: Source signal 1 This line lets the operator arrange the information displayed on the home
display screen (refer to Table 2 for parameter display details)
Not displayed
Sens 1. Prim. Meas: the measurement shall be displayed in the space
allocated to the primary parameter for sensor 1 (item 3 on the home screen)
Sens 1. Sec. Meas.: item 9 on the home screen
Sens 2. Prim. Meas: item 6 on the home screen
Sens 2. Sec. Meas.: item 13 on the home screen.
I2: User desig. A free text field for entering the user's designation (maximum of
13 characters).
I2: Source signal 1 Can be set from 0 to 50 % (the default is 1 %) and is used to define when
stability delta the arrow on the home screen will indicate that the measurement is stable if
the parameter measured has been set as the primary parameter for sensor
1 or 2 (refer to items 2 and 5 in Table 2)
The name of the file must be of the form "CONFANA2.csv" and must
contain the following information:
Line 1 of the csv file: a description (not more than 16 characters) of the
calculated source signal.
Line 2: a blank line containing no characters
To activate the conversion, plug the stick into the ACTEON 5000's USB port
(refer to item 6 of diagram 3) and wait for the small green LED located
above the USB port to stop flashing.
Then navigate to menu I2: Source signal 2 and select the "Active" option.
I2: Source signal 2 Can be set from 0 to 50 % (the default is 1 %) and is used to define when
stability delta the arrow on the home screen will indicate that the measurement is stable if
the parameter measured has been set as the primary parameter for sensor
1 or 2 (refer to items 2 and 5 in Table 2)
From the main menu, select the icon to open the ACTEON 5000 settings window.
Icon Functionality
Screen settings: A menu used: to set how long the backlight stays on for (from 1 to
60 minutes); to set the brightness (from 10 to 100 %); and to recalibrate the screen.
A screen recalibration is only necessary when ACTEON 5000 is switched on for the
first time, or after a software upgrade.
Events log: an information-only menu which lists all the events together with their time-
stamping and with the option to transfer this data to a USB stick via the icon
Date/time settings: a menu used to set the date and time, to choose the date format,
and to enable/disable automatic summer/winter time change-over.
Return to factory settings: used to reset all the ACTEON 5000's settings to the
defaults set during manufacture.
Password: Used to activate and define a password which prevents information from
being displayed on the screen (a 4 digit code, between 0 and 9999). The universal
emergency code is 3615.
To access the "Analog output settings" window, select the icon in the Main menu.
The functionality offered for the setting up of the two analog outputs is described in the table below:
State of outputs in In Maintenance Mode, the analog outputs may return a value corresponding
MM to:
- the last value measured,
- a fixed (unchanged) value which shall be defined in the "OUT. 1: Value mA
in MM" and "OUT. 2: Value mA in MM" lines.
OUT. 1: Value mA in This line is used to set the value which will be returned by analog output 1
MM when the device is in Maintenance Mode (between 0 and 21 mA).
OUT. 2: Value mA in This line is used to set the value which will be returned by analog output 2
MM when the device is in Maintenance Mode (between 0 and 21 mA).
MM Final tempo (mn) Used to set a time delay which shall begin when the Maintenance is
completed, to allow a period of time for the measurement to stabilize. The
possible values are: 0 to 60 minutes (1 min is the default setting).
OUT. 1: DL type Used to set output 1 to operate within a range of 0-20 mA or 4-20 mA.
OUT. 1: Parameter Used to select the parameter whose value shall be outputted via analog
linked to DL output 1:
Sensor 1: Primary parameter
Sensor 1: Secondary parameter
Sensor 2: Primary parameter
OUT.1 : PID linked Used to select the parameter whose value shall be outputted for the PID
param. function :
Sens.1.pri.meas
Sens.1.sec.meas
Sens.2.pri.meas
Sens.2.sec.meas
OUT.1 : PID Integral Choice between Active (by fault) and Inactive
OUT.1: PID gain Used to set the "responsiveness" of the 4-20 mA output. Possible value: 0 to
40 mA/s
OUT. 2: DL type Used to set output 2 to operate within a range of 0-20 mA or 4-20 mA.
OUT. 2: Parameter Used to select the parameter whose value shall be outputted via analog
linked to DL output 2:
OUT.2 : PID linked Used to select the parameter whose value shall be outputted for the PID
param. function :
Sens.1.pri.meas
Sens.1.sec.meas
Sens.2.pri.meas
Sens.2.sec.meas
OUT.2: PID gain Used to set the "responsiveness" of the 4-20 mA output. Possible value: 0 to
40 mA/s
To access the "Relay output settings" window, select the icon from the Main menu.
State of outputs in In Maintenance Mode, the relay outputs may remain set as:
MM - the last value measured,
- a fixed (unchanged) value which shall be defined in the "R1: State in MM"
and "R2: State in MM" lines.
R1: State in MM In Maintenance Mode, Relay 1 can be set to Open or Closed mode.
R2: State in MM In Maintenance Mode, Relay 2 can be set to Open or Closed mode.
MM Final tempo (mn) Used to set a time delay which shall begin when the Maintenance is
completed. The possible values are: 0 to 60 minutes.
R1 output settings
R1: Active Function Used to set output 1 to one of the following:
Not assigned
Fault alarm
Limit indicator
R1: Alarm tempo (s) A time delay which must elapse prior to the triggering of the relay. Possible
values: 0 to 3600 s.
If Active function: Limit indicator
R1: Limit Value Used to set the value of the Upper or Lower limit
R1: UPPER limit Used to set the value of the UPPER limit
value
R1: Forcing Tempo Minimum time during which the contact (CLOSED or OPEN) shall be
maintained in that state (between 0 and 120 minutes)
R1: LOWER limit Used to set the value of the LOWER limit
value
R1: Hysteresis limit Possible values: 0 to 20 %
%
R1: Tempo Possible values: 0 to 3600 s
R1: Forcing Tempo Minimum time during which the contact (CLOSED or OPEN) shall be
maintained in that state (between 0 and 120 minutes)
R1: Cleaning Period If interval unit, above, defined in minute, the proposed minimum value is 5
minutes.
NOTE: The Closed action is selected when the wiring on the RELAY
terminal block is done in NO (normally open).
R2 output settings
R2: Active Function Used to set output 1 to one of the following:
Not assigned
Fault alarm
Limit indicator
R2: Alarm tempo (s) A time delay which must elapse prior to the triggering of the relay. Possible
values: 0 to 3600 s
If Active function: Limit indicator
R2: Limit Value Used to set the value of the Upper or Lower limit
R2: UPPER limit Used to set the value of the UPPER limit
value
R2: Forcing Tempo Minimum time during which the contact (CLOSED or OPEN) shall be
maintained in that state (between 0 and 120 minutes)
R2: LOWER limit Used to set the value of the LOWER limit
value
R2: Forcing Tempo Minimum time during which the contact (CLOSED or OPEN) shall be
maintained in that state (between 0 and 120 minutes)
R2: Cleaning Period If interval unit, above, defined in minute, the proposed minimum value is 5
minutes.
NOTE: The Closed action is selected when the wiring on the RELAY
terminal block is done in NO (normally open).
See also the paragraph detailing the use of the HYDROCLEAN-P motorized cleaning accessory
coupled to the Nephelometric or optical oxygen turbidity sensor.
Measurement Possible values: 0.0 to 50 %. The measurement will not be recorded if its
variation variation (as a %) from the last recorded value does not meet this
requirement. Default value 1%
Interval The interval between consecutive recordings can be set from 1 to 120
minutes
To download the recorded data, plug the stick into the ACTEON 5000's USB
port (refer to item 6 of diagram 3) and wait for the small green LED located
above the USB port to stop flashing.
Navigate then to the "USB export" menu and select the "Active" option.
The serial digital output is wired to the 3 dedicated contacts terminal block (ground, A and B), mark 8
in the figure in paragraph (3.2.2 Description wiring).
The Ethernet output uses a standard RJ45 base, mark 7 in the figure in paragraph (3.2.2 Description
cabling).
6.2.8.1 Ethernet output (TCP/IP modbus):
Configuration line Fonctionnality
Ethernet Slave Configurable from 1 to 254: the ACTEON 5000 on the network has a
Number defined slave number that is different from other devices connected to the
Gateway Definable, also in 4 fields, to describe the IP of the gateway of the local
network used.
Note that the communication port is the default for modbus TCP: the 502.
NOTE: In a test phase if you connect your ACTEON with a live PC (RJ45 cable connecting the PC
directly to the transmitter) make sure to assign an IP as well as a mask, to your PC, cohesive with the
ACTEON. (see example below)
ACTEON PC
Network mask 255.255.255.0 255.255.255.0
IP (fixed) 192.168.40.40 192.168.40.1 (≠192.168.40.40)
Serial port slave Configurable from 1 to 254: the ACTEON 5000 on the network has a
number defined slave number that is different from other devices connected to the
same network.
Serial port speed The speed of transmission represents the amount of information carried
over a time interval.
Units: bit per second or Bauds.
Seven speed values are available from 2400 to 76800.
The values measured by the two DIGISENS digital sensors connected to the ACTEON input are
accessible remotely via the ACTEON digital output.
Regardless of the connected DIGISENS sensor, the data is classified into two fixed register ranges.
Records are read-only.
The data is refreshed at the same rate as the one displayed on the screen (see configuration of the
digital input, sensor 1 or 2).
Digital sensors OPTOD or nephelometric turbidity can be equipped with a motorized cleaning
accessory, external to the sensor.
The temporal control of this HYDROCLEAN-P accessory can be configured on an ACTEON 5000.
For this purpose, the HYDROCLEAN-P is connected to the RELAY terminal block of the ACTEON
5000.
Wiring sketches:
12VDC Ground and Power from Second Digital
Input Terminal Block
Action: Closed
Isolate the power to the measuring device when performing maintenance work.
Due to the risk of electrocution, disconnect the controller from the power supply
systematically when performing maintenance work on the transmitter.
Do not use a corrosive or inflammable solvent to clean the transmitter. The use of this type of solvent
could damage the device (its screen) and may invalidate the warranty.
After checking that the ACTEON 5000's protective covers are properly closed, wipe the outside of the
transmitter with a soft cloth dampened with a mixture of water and non-corrosive detergent.
General description Oxygen: luminescent membrane sensitive to the oxygen level in the medium
being analyzed. Gaseous exchange between the membrane’s material and
the medium.
Temperature: NTC thermistor.
Materials 316L stainless steel version: polyamide, silicone and quartz; polyurethane
sleeve around cable.
Titanium version: polyamide, silicone and quartz; polyurethane sleeve around
cable.
Servicing After each use, rinse the sensor and the membrane carefully in clean water.
If deposits such as biofilm or sludge persist, wipe the membrane carefully with
a soft cloth or absorbent paper.
Caution: for the titanium version, clean the body of the sensor with acetone
(do not use methylated spirits, ethanol or methanol).
Caution: only unscrew the sieve cap containing the DODISK when replacing
the disk.
If the sieve cap has to be replaced, screw the new sieve cap on slowly to
allow the air to escape slowly.
Storage Keep the membrane hydrated using the protective bag and a dampened
absorbent wad of material (e.g. cotton wool. After being stored in dry
conditions, rehydrate the membrane for 12 hours by immersing the sensor in
water.
Storage temperature - 10 °C to + 60 °C
Using a clean sensor, occasionally check the 0% Sat value by immersing the
Oxygen calibration
sensor in a sulfite solution in water (sulfite concentration <2%). If there is a
zero error, perform a complete calibration of the sensor.
Caution: do not allow the sensor to remain in contact with the sulfite solution
for more than 1 hour.
The 2-point calibration is performed using a sulfite solution (for the offset)
then, after rinsing and drying, the sensor’s gain is determined by exposing the
sensor to moisture-saturated air (or to clean water saturated with air).
Temperature calibration The calibration of the temperature sensor is a 2-step process:
- step 1 (offset): the sensor is placed in a container containing a water bath
and ice,
Operating temperature 0 °C to 50 °C
Storage Place the protective bag over the head of the sensor to prevent the optical
part from being scratched.
Storage temperature
- 10 °C to + 60 °C
Turbidity calibration (in The NTU sensor is an optical sensor which requires very little calibration.
NTU) Using a clean sensor, occasionally check the 0 NTU value by immersing the
sensor in clean, bubble-free water. If there is a zero error, perform a complete
calibration of the sensor (over 1 or 4 measurement ranges).
This procedure requires a formazine solution whose concentration lies
at the mid-point of the measurement range being calibrated. This
solution is prepared from a 4,000-NTU stock solution.
Use a 200 ml volumetric flask when preparing the solutions. Add the required
volume of formazine (refer to the table below) and make up to 200 ml with
distilled water.
Formazine solutions with concentrations of less than 1,000 NTU degrade
fairly quickly; do not keep the solution for more than a few days.
The 2,000 NTU solution can be kept for 2 to 3 weeks in a fridge in an opaque
bottle.
Materials Glass, platinum, PVC, POM-C, Polyamide, Stainless steel 316L (sleeve protecting
the temperature sensor); polyurethane sleeve on cable.
Measurement/Interference When immersing the sensor in the medium to be measured, wait until the sensor's
temperature has stabilized before taking the reading.
Operating temperature 0 °C to 50 °C
Servicing After each use, rinse the sensor carefully in clean water.
pH: If deposits such as biofilm or sludge persist, immerse the sensor in a cleaning
solution (PF-CSO-C-00010) for a few hours and rinse with plenty of water before
use.
Do not use a soft cloth or absorbent paper since the glass bulb is extremely sensitive
to scratching.
Redox: clean the platinum disk using fine, wet abrasive paper (such as P1200 or
P220).
Storage Keep the glass membrane hydrated by adding a few drops of storage solution (PF-
CSO-C-00005) to the protective bag, or using a solution at pH 4. Rinse the glass
bulb with plenty of water before use. If the sensor is stored in dry conditions, soak
the sensor in a pH4 buffer solution for 12 hours before use.
The protective bag absorbs direct impacts on the head of the sensor.
The platinum electrode is kept under dry conditions.
Storage temperature
0 °C to + 60 °C
pH calibration Using a clean sensor, perform a 2-point calibration of the sensor (offset and gain,
e.g. at pH7 and pH4).
Redox verification Using a clean sensor, check the electronic 0 by exposing the sensor to air, and
check a second point using a buffer solution at 240 mV (or 470 mV).
Changing the cartridge In order not to damage the electronic part of the sensor, hold the cartridge in one
hand and unscrew the connecting ring using the other hand. Remove the used
cartridge and insert the new cartridge before re-tightening the connecting ring.
0°C to 50°C
Operating temperature
After each use, rinse meticulously the sensor with clear water.
Maintenance Clean the platinum ring with an abrasive moist paper (type P1200 or P220).
Maintain the head of the sensor hydrated in the protection case with a few
drops of preservation agent solution (PF-CSO-C-00005) or, if it is not
available, with the solution of KCl. Rinse profusely the sensor before use.
Storage
After storage in dry environment, put the sensor in a KCl solution for 12
hours.
The case protects against direct impact on the head of the sensor.
To avoid deteriorating the electronic part of the sensor, take the cartridge in
one hand and unscrew the clamping ring with the other hand. Remove the
Changing the cartridge
used cartridge and put the new cartridge before to screw back the clamping
ring.
Measurement/Interference When immersing the sensor in the medium to be measured, wait until the sensor's
temperature has stabilized before taking the reading.
Operating temperature 0 °C to 50 °C
Servicing After each use, rinse the sensor carefully in clean water.
If deposits such as biofilm or sludge persists in the measurement slit or on the
electrodes, use wet abrasive paper to remove a thin layer off the surface of the
electrodes (type P1200 or P220).
Storage The protective bag absorbs direct impacts on the head of the sensor.
If storing for a short period between measurements, place a wad of cotton wool in
the bottom of the storage bag, dampened with a few drops of buffer solution at
1,413 µS/cm.
Storage temperature - 10 °C to + 60 °C
Conductivity calibration Using a clean sensor, perform a 2-point calibration of the sensor (offset and gain
using a standard solution whose conductivity is suited to the measurement range)
for 1 or all 4 ranges:
EPDM, PVC, 316L stainless steel (sleeve protecting the temperature sensor);
Materials polyurethane sleeve on cable.
Measurement/Interference When immersing the sensor in the medium to be measured, wait until the
sensor's temperature has stabilized before taking the reading.
The sensor is not well suited to measuring in the weakest ranges (0-200
µS/cm).
Operating temperature 0° C to 50 °C
Servicing After each use, rinse the sensor carefully in clean water.
Storage temperature - 10 °C to + 60 °C
Conductivity calibration Using a clean sensor, perform a 2-point calibration of the sensor (offset and
gain using a standard solution whose conductivity is suited to the average
value expected):
For a use of the sensor in mode Sludge Blanket detection the sensor is tested on 1
Sludge blanket
point:
detection in %
- 1 offset with some distilled water (100 %)
Measure/ Interfering When introducing the sensor into a measuring medium, wait for the sensor to stabilize at
temperature before taking the measurement into account.
Operating 0°C to 40 °C
temperature
After each use, rinse the sensor thoroughly with clean water.
Maintenance If biofilm or mud deposits persist, clean the sensor with soapy water and wipe the optical
windows with a soft cloth or absorbent paper.
Equivalent Turbidity The sensor provides equivalent turbidity information in FAU. This parameter is not
parameter calibratable (factory determined slope coefficient). However, the clear water sequence of
SAC 254 with active green light source allows an adjustment of the base signal.
The equivalence parameters COD, BOD and TOC are calculated from the main
Parameters CODeq, parameter SAC254 according to a refined law. The user accesses the independent
BODeq and TOCeq coefficients (offset and slope) for each of these three parameters.
The Stacsense sensor stores the factory coefficients below. These basic coefficients are
accessible at any time by means of the return function to the factory coefficients
Parameter offset FACTORY Slope FACTORY(a)
CODeq 0,0 1,81
BODeq 0,0 0,48
TOCeq 0,0 0,72
(a) Slope values obtained in KHP (potassium hydrogen phthalate) solution in the laboratory.
When the operator name is filled in, the ACTION button appears to inject the
coefficients values into the StacSense sensor.
For example, the user determines these own coefficients of the CODeq refining law from
representative samples, measured both with the StacSense sensor (active factory
coefficients) and in the laboratory (standardized method).
Fault Resolution
Sensor not recognized, - Make sure that the sensor has been connected up correctly.
Short lines displayed - Run a SCAN of the network of sensors (refer to section 5.2).
instead of the - Disconnect the sensor and connect it to the other digital input dedicated
measurement
to the sensor.
- Contact the technical services department.
Unstable - Check that the sensor has been installed under the correct conditions.
measurements - Clean the sensor and check the measuring elements (active disk for the
OPTOD sensor, cartridge/glass bulb for the PHEHT sensor, etc.)
- Run a calibration of the sensor.
- Contact the technical services department.
Current output not - Check the settings for the current output.
working, or value - Check that the wiring is correct.
incorrect - Check that the device is not in Maintenance Mode.
- Disconnect the faulty analog output and connect it to the other analog
output.
- Contact the technical services department.
Frozen screen Press the RESET button on the connection hardware part of the circuit
card (refer to item A in diagram 3).
AQUALABO
115 Rue Michel MARION
56850 CAUDAN
FRANCE