Performing Transformer Vector Group Test
Performing Transformer Vector Group Test
Prepared by
Ir Kamarul Ariffin Yahya
UPT-P27 Lead Electrical Engineer
P27 AMT Supervisor – Electrical
Page 1 of 6
1.0 Introduction
A vector group is the International Electrotechnical Commission (IEC) method of categorizing the high-
voltage (HV) windings and low-voltage (LV) winding configurations of three-phase transformers and the
difference in phase angle between them.
The vector group is indicated by a code consisting of two or three letters, followed by one or two numeric
digits.
The HV winding is designated with an uppercase letter, followed by LV windings designated with a
lowercase letter. Following the letter code is the digits (in clock system) which indicates multiples of 30°
phase angle different between the windings, with HV winding is taken as a reference.
Dy1
LV lags HV by 30°
Yd1
LV lags HV by 30°
Dy11
LV lags HV by 330°
LV lead HV by 30°
Yd11
LV lags HV by 330°
LV lead HV by 30°
Page 2 of 6
Phase displacement: Phasor rotation is always counterclockwise (internationally adopted convention –
universal rule in relay testing world).
Picture above shows A-B-C phase sequence since A attains its maximum value first with respect to the
reference in counterclockwise phasor direction followed by B phase 120° later, and C phase 240° later
than the A phase.
Parallel operation: Transformers connected in parallel must have the same vector group; mismatching
phase angles will result in circulating current and other system disturbances. There is no technical
different between Dy1 and Dy11 in terms of performance. The only factor affecting the choice between
one and the other is system phasing, i.e. whether the transformer need to parallel with another source.
Page 3 of 6
2.0 Vector Group Test Procedure
Following are the steps procedure to perform Transformer vector group test:
1. Ensure terminal are open & short the primary and secondary R phase externally. This is ensure 1L1
and 2L1 are in phase.
2. Apply three phase voltage to the primary of the transformer (415 volts).
3. Measure the voltages.
4. Check the equations by using values.
Page 4 of 6
4.0 Developing equation: Analysis Test Result for Dyn11
Minimum 4 equation to be establish to verify vector group Dyn11, mainly “equal”, “more than”, “less
than”, and “addition”.
Page 5 of 6
5.0 Developing equation: Analyze Dyn1 against Test Result
Minimum 4 equation to be establish to verify vector group Dyn1, mainly “equal”, “more than”, “less
than”, and “addition”.
Conclusion: Transformer under test does not satisfy Dyn1 vector group.
Page 6 of 6