Data sheet for three-phase squirrel cage motor
SIMOTICS HV C
Article number 1NB1354-4AA40-4AA0-Z
Options A65+G50+K11+K97+L27+W72
Client order no. Item no.
Order no. Consignment no.
Offer no. Project
Remarks
General data Environmental conditions
Standards/specifications IEC/EN/ISO Coolant temperature 40 °C
Usage area Explosion zone 1 Ambient temperature -20 °C … 40 °C
Type of explosion protection II 2G Ex db eb IIB T4 Gb Installation altitude 1000 m
Electrical data Mechanical data
Rated power P N 375 kW Type of construction IM B3 (IM 1001)
Rated voltage U N 4 kV Degree of protection IP55
Voltage fluctuations ± 5 % (IEC 60034-1) Shaft height 355
Frequency f N 60 Hz Method of cooling IC 411
Frequency fluctuations ± 2% (IEC 60034-1, Area A) Type of insulation MICALASTIC - VPI
Stator circuit Star Rotor winding material Aluminium
Rated current I N -/- A Bearing design Rolling-contact bearing
Number of poles 4 Bearing cooling without
Rated speed n N -/- 1/min Bearing DE -/-
Rated torque M N -/- Nm Bearing NDE -/-
Partial load P / P N 5/4 4/4 3/4 2/4 Direction of rotation clockwise
Efficiency η % -/- -/- -/- -/- Sound pressure level L pA (1m), Tolerance +3dB
Power factor cos φ -/- -/- -/- -/- - no-load 81 dB(A)
Direct on line - load 82 dB(A)
Mode of operation continuous operation (S1) Measuring surface level Ls 17 dB(A)
Appliance Unknown Coating (paint finish) standard coating
Thermal class 155(F) utilized acc. to thermal class 130(B) Color, paint shade RAL 7030
Starting / rated current I A /I N -/- Total weight # 3100 kg
Tolerance I A /I N + 20% (IEC 60034) Rotor weight 495 kg
Starting / rated torque M A /M N -/- Dynamic foundation load at 2- pole terminal short circuit
Breakdown / rated torque M K /M N -/- downward / upward -/- kN / -/- kN
Moment of inertia J 7.0 kg.m²
Type of terminal box
Safe stall time hot / cold -/- s / -/- s
Type of terminal box -/-
Perm. no. of consecutive starts, 3/2
cold/warm * Terminal box, Star connection without
*at max.external moment of 300 kg.m²
inertia Factory location
*U /U N ≥ 90 %, M Last ~ n ², M L ast /M N ≤ 70.0 % Factory location Germany
# These values apply to catalog design with standard environmental conditions.
Offer no. , Item no. Page 1 of 2 Version: 2020.01
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Generiert: 08.10.2020 00:38:43
Special design
A65 6 embedded resistance thermometers Pt 100 without lightning arresters for 3- or 4-wire connection from terminals
G50 Shock pulse measurement (SPM), measuring nipple at D.E. and N.D.E.
K11 Terminal box on top cables from right hand side (view onto DE)
K97 Clockwise rotation
L27 NDE bearing insulation
W72 Additional terminal box Ex e - design / gray cast iron
SIDRIVE IQ View
Enjoy the product in our Augmented Reality App "SIDRIVE IQ
View". Now available for iPad and iPhone in Apple App Store.
Download the App from Apple Store and scan the QR-code.
Offer no. , Item no. Page 2 of 2 Version: 2020.01
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Generiert: 08.10.2020 00:38:43