Technical Data: Model GPY Electric Fire Pump Controller

This document provides technical specifications for a Model GPY Electric Fire Pump Controller. It lists the controller's withstand ratings for different voltages and frequencies, as well as its horsepower and optional ratings. It also describes the controller's ambient temperature rating, surge suppression, disconnecting means, emergency start handle, locked rotor protector, electrical and pressure readings, pressure and event recorder, and pressure sensing components. The document states it is a marketing document and additional information can be obtained from the factory.

Uploaded by

neng heng
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
45 views1 page

Technical Data: Model GPY Electric Fire Pump Controller

This document provides technical specifications for a Model GPY Electric Fire Pump Controller. It lists the controller's withstand ratings for different voltages and frequencies, as well as its horsepower and optional ratings. It also describes the controller's ambient temperature rating, surge suppression, disconnecting means, emergency start handle, locked rotor protector, electrical and pressure readings, pressure and event recorder, and pressure sensing components. The document states it is a marketing document and additional information can be obtained from the factory.

Uploaded by

neng heng
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Technical Data

Model GPY Electric Fire Pump Controller

Shortcircuit 200V to 208V 220V to 240V 380V to 415V 440V to 480V 575V to 600V
Withstand 60Hz 60Hz 50 Hz / 60Hz 60Hz 60Hz
Rating
HP (kw)

Standard 100kA
5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A
Optional 150kA

Standard 50kA 200 (149) 250 (186) 350 - 450 (261 - 335) 450 - 500 (335 - 373)
5 - 500 (3.7- 373)
Optional 100kA N/A N/A 350 - 500 (261 - 373) 450 - 500 (335 - 373)

Optional 200kA 5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A

Ambient Standard: Optional:


Temperature
Rating
□ 4°C to 40°C / 39°F to 104°F □ 4°C to 55°C / 39°F to 131°F
Controllers built in Dubai, UAE (Tornatech FZE) are supplied standard with 55°C rating.
Surge
Surge arrestor rated to suppress surges above line voltage
Suppression
• Isolating switch and circuit breaker assembly:
- Door interlocked in the ON position
- Isolating switch rated not less than 115% of motor full load current
Disconnecting
- Circuit breaker continuous rating not less than 115% of motor full load current
Means
- Overcurrent sensing non-thermal type, magnetic only
- Instantaneous trip setting of not more than 20 times the motor full load current
• �������������������
Service Entrance
Suitable as service entrance equipment
Rating

Emergency Start • Flange mounted • Integrated limit switch


Handle • Pull and latch activation • Across the line start (direct on line)
• Operate shunt trip to open circuit breaker
Locked Rotor
• Factory set at 600% of motor full load current
Protector
• Trip between 8 and 20 seconds
Electrical • Voltage phase to phase (normal power)
Readings • Amperage of each phase when motor is running
Pressure • Continuous system pressure display
Readings • Cut-in and Cut-out pressure settings
• Pressure readings with date stamp
• Event recording with date stamp
Pressure and
• Under regular maintained operation, events are stored in memory for the life of the controller.
Event recorder
• Data viewable on operator interface display screen
• Downloadable by USB port to external memory device
• Pressure transducer and run test solenoid valve assembly for fresh water application
• Pressure sensing line connection 1/2” Female NPT
Pressure Sensing • Drain connection 3/8”
• Rated for 0-500PSI working pressure (standard display at 0-300PSI)
• Externally mounted with protective cover

This is a Marketing document. Please consult factory if additional information is required.