Test Project - Project - VC0-Report
Test Project - Project - VC0-Report
Author
Project: Test Project
Variant: New simulation variant
PVsyst V7.3.1
VC0, Simulation date:
10/25/23 12:11
with v7.3.1
Project summary
Geographical Site Situation Project settings
NayPyiDaw Latitude 19.73 °N Albedo 0.20
Myanmar Longitude 96.10 °E
Altitude 120 m
Time zone UTC+6.5
Meteo data
NayPyiDaw
PVGIS api TMY
System summary
Grid-Connected System Sheds, single array
Simulation for year no 1
System information
PV Array Inverters
Nb. of modules 4200 units Nb. of units 7 units
Pnom total 2562 kWp Pnom total 2100 kWac
Pnom ratio 1.220
Results summary
Produced Energy 4434428 kWh/year Specific production 1731 kWh/kWp/year Perf. Ratio PR 79.97 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Near shading definition - Iso-shadings diagram 6
Main results 7
Loss diagram 8
Predef. graphs 9
Single-line diagram 10
PVsyst V7.3.1
VC0, Simulation date:
10/25/23 12:11
with v7.3.1
General parameters
Grid-Connected System Sheds, single array
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane Nb. of sheds 40 units Transposition Perez
Tilt/Azimuth 25 / 0 ° Single array Diffuse Imported
Sizes Circumsolar separate
Sheds spacing 7.86 m
Collector width 4.95 m
Ground Cov. Ratio (GCR) 63.0 %
Top inactive band 0.02 m
Bottom inactive band 0.02 m
Shading limit angle
Limit profile angle 32.0 °
PV Array Characteristics
PV module Inverter
Manufacturer Jinkosolar Manufacturer Huawei Technologies
Model JKM-610N-78HL4-BDV Model SUN2000-330KTL-H1
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 610 Wp Unit Nom. Power 300 kWac
Number of PV modules 4200 units Number of inverters 7 units
Nominal (STC) 2562 kWp Total power 2100 kWac
Array #1 - Array 1
Number of PV modules 3000 units Number of inverters 5 units
Nominal (STC) 1830 kWp Total power 1500 kWac
Modules 120 Strings x 25 In series
At operating cond. (50°C) Operating voltage 500-1500 V
Pmpp 1663 kWp Max. power (=>25°C) 330 kWac
U mpp 1060 V Pnom ratio (DC:AC) 1.22
I mpp 1568 A Power sharing within this inverter
Array #2 - Array 2
Number of PV modules 1200 units Number of inverters 2 units
Nominal (STC) 732 kWp Total power 600 kWac
Modules 48 Strings x 25 In series
At operating cond. (50°C) Operating voltage 500-1500 V
Pmpp 665 kWp Max. power (=>25°C) 330 kWac
U mpp 1060 V Pnom ratio (DC:AC) 1.22
I mpp 627 A Power sharing within this inverter
PVsyst V7.3.1
VC0, Simulation date:
10/25/23 12:11
with v7.3.1
Array losses
Array Soiling Losses Thermal Loss factor LID - Light Induced Degradation
Loss Fraction 0.5 % Module temperature according to irradiance Loss Fraction 0.5 %
Uc (const) 20.0 W/m²K
Uv (wind) 0.0 W/m²K/m/s
Spectral correction
FirstSolar model
Precipitable water estimated from relative humidity
Coefficient Set C0 C1 C2 C3 C4 C5
Monocrystalline Si 0.85914 -0.02088 -0.0058853 0.12029 0.026814 -0.001781
DC wiring losses
Global wiring resistance 3.4 mΩ
Loss Fraction 0.7 % at STC
System losses
Unavailability of the system
Time fraction 0.5 %
1.8 days,
4 periods
AC wiring losses
Inv. output line up to MV transfo
Inverter voltage 800 Vac tri
Loss Fraction 0.82 % at STC
Inverter: SUN2000-330KTL-H1 Inverter: SUN2000-330KTL-H1
Wire section (5 Inv.) Copper 5 x 3 x 185 mm² Wire section (2 Inv.) Copper 2 x 3 x 120 mm²
Average wires length 200 m Average wires length 0m
PVsyst V7.3.1
VC0, Simulation date:
10/25/23 12:11
with v7.3.1
AC wiring losses
MV line up to Injection
MV Voltage 11 kV
Wires Copper 3 x 50 mm²
Length 300 m
Loss Fraction 0.24 % at STC
AC losses in transformers
MV transfo
Medium voltage 11 kV
Transformer from Datasheets
Nominal power 2000 kVA
Iron Loss (24/24 Connexion) 7.00 kVA
Iron loss fraction 0.35 % of PNom
Copper loss 7.00 kVA
Copper loss fraction 0.35 % at PNom
Coils equivalent resistance 3 x 1.12 mΩ
PVsyst V7.3.1
VC0, Simulation date:
10/25/23 12:11
with v7.3.1
Iso-shadings diagram
Orientation #1
PVsyst V7.3.1
VC0, Simulation date:
10/25/23 12:11
with v7.3.1
Main results
System Production
Produced Energy 4434428 kWh/year Specific production 1731 kWh/kWp/year
Performance Ratio PR 79.97 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.3.1
VC0, Simulation date:
10/25/23 12:11
with v7.3.1
Loss diagram
1986 kWh/m² Global horizontal irradiation
+9.0% Global incident in coll. plane
PVsyst V7.3.1
VC0, Simulation date:
10/25/23 12:11
with v7.3.1
Predef. graphs
Daily Input/Output diagram