GL 34 BTM - Pa2

1. The document provides input data and calculations for an anchor design using the Hilti HST2 M12 anchor with an effective embedment depth of 70mm in C40/50 concrete. 2. The calculations show a resulting tension force of 2.467kN and shear forces of 1.857kN, which are below the anchor capacities for steel strength, pullout strength, concrete breakout strength, and splitting failure. 3. All load cases are within acceptable utilization levels, indicating the anchor design is sufficient for the given loads and conditions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views6 pages

GL 34 BTM - Pa2

1. The document provides input data and calculations for an anchor design using the Hilti HST2 M12 anchor with an effective embedment depth of 70mm in C40/50 concrete. 2. The calculations show a resulting tension force of 2.467kN and shear forces of 1.857kN, which are below the anchor capacities for steel strength, pullout strength, concrete breakout strength, and splitting failure. 3. All load cases are within acceptable utilization levels, indicating the anchor design is sufficient for the given loads and conditions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

GL 34 , BP THK 6 MM

www.hilti-me.com Profis Anchor 2.9.1


Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HST2 M12 hmin1
Return period (service life in years): 50
Seismic/Filling set or any suitable annular gap filling solution
Effective embedment depth: hef = 70 mm, hnom = 80 mm
Material:
Evaluation Service Report: ETA-15/0435
Issued I Valid: 12/21/2017 | -
Proof: SOFA design method + fib (07/2011) - after ETAG testing
Stand-off installation: eb = 0 mm (no stand-off); t = 3 mm
Anchor plate: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm2; gMs = 1.000
lx x ly x t = 150 mm x 130 mm x 3 mm; (Recommended plate thickness: calculated (3 mm))
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm
Base material: uncracked concrete, C40/50, fc,cyl = 40.00 N/mm2; h = 250 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

2 Load case/Resulting anchor forces y

Load case: Design loads


2
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 1.234 1.857 1.857 0.000
x
2 1.234 1.857 1.857 0.000
Tension
max. concrete compressive strain: - [‰]
max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 2.467 [kN]
1
resulting compression force in (x/y)=(0/0): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

3 Tension load SOFA (fib (07/2011), section 10.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 1.234 32.000 4 OK
Pullout Strength* 1.234 18.856 7 OK
Concrete Breakout Strength** 2.467 36.429 7 OK
Splitting failure** 2.467 49.239 6 OK
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
44.800 1.400 32.000 1.234

3.2 Pullout Strength


NRk,p [kN] yc gM,p NRd,p [kN] NSd [kN]
20.000 1.414 1.500 18.856 1.234

3.3 Concrete Breakout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm]
60,000 44,100 1.361 105 210
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 0.986 1.000
k1 N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
11.000 40.745 1.500 36.429 2.467
Group anchor ID
1, 2

3.4 Splitting failure


Ac,N [mm2] A0c,N [mm2] y A,N ccr,sp [mm] scr,sp [mm] y h,sp
60,000 44,100 1.361 105 210 1.352
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N k1
0 1.000 0 1.000 0.986 1.000 11.000
N0Rk,c [kN] gM,sp NRd,sp [kN] NSd [kN]
40.745 1.500 49.239 2.467
Group anchor ID
1, 2

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

4 Shear load SOFA (fib (07/2011), section 10.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 1.857 25.120 8 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 3.713 80.143 5 OK
Concrete edge failure in direction x+** 3.713 21.386 18 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
31.400 1.250 25.120 1.857

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm] k4
60,000 44,100 1.361 105 210 2.200
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 0.986 1.000
N0Rk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
40.745 1.500 80.143 3.713
Group anchor ID
1, 2

4.3 Concrete edge failure in direction x+


lf [mm] dnom [mm] kV a b
70 12.0 2.400 0.084 0.065
c1 [mm] Ac,V [mm2] A0c,V [mm2] y A,V
100 58,500 45,000 1.300
y s,V y h,V y a,V ec,V [mm] y ec,V y re,V y 90°,V
1.000 1.000 1.000 0 1.000 1.000 2.000
V0Rk,c [kN] gM,c VRd,c [kN] VSd [kN]
24.676 1.500 21.386 3.713

5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
steel 0.039 0.074 2.000 1 OK
concrete 0.068 0.174 1.500 9 OK

baN + baV <= 1

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 0.914 [kN] dN = 0.010 [mm]
VSk = 1.375 [kN] dV = 0.254 [mm]
dNV = 0.254 [mm]
Long term loading:
NSk = 0.914 [kN] dN = 0.106 [mm]
VSk = 1.375 [kN] dV = 0.376 [mm]
dNV = 0.391 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are valid
without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in this
calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This means load
re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in
order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required anchor plate thickness with FEM to
limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by
PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and for plausibility!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be followed
to ensure a proper installation.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling the gap
with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
• The compliance with current standards (e.g. EC3) is the responsibility of the user
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

8 Installation data
Anchor plate, steel: S 275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm Anchor type and diameter: HST2 M12 hmin1
Profile: Rectangular hollow, ; (L x W x T) = 125 mm x 50 mm x 2 mm Installation torque: 0.060 kNm
Hole diameter in the fixture: df = 14 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 3 mm Hole depth in the base material: 97 mm
Recommended plate thickness: calculated (3 mm) Minimum thickness of the base material: 140 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use
is required.

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Seismic/Filling set
• Properly sized drill bit • Torque wrench
• Hammer
y

75 75

20
2

65
90

x
65

1
20

75 75

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 0 -45 100 100 - -
2 0 45 100 100 - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.9.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/24/2021
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the
relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you
bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole
responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms
and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to
the absence of errors, the correctness and the relevance of the results or suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the
AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by
carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs,
arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan