GS-SMPP-005 - SM City Pampanga New GSE Controller Parameters and Settings

The document lists parameters and settings for a new DSE 7320 controller, including settings for high engine temperature, low oil pressure, failed to start protection, under and over frequency, under and over voltage, generator overspeed protection, generator underspeed protection, high crankcase internal pressure, and overcurrent relay.

Uploaded by

edzel dayrit
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views1 page

GS-SMPP-005 - SM City Pampanga New GSE Controller Parameters and Settings

The document lists parameters and settings for a new DSE 7320 controller, including settings for high engine temperature, low oil pressure, failed to start protection, under and over frequency, under and over voltage, generator overspeed protection, generator underspeed protection, high crankcase internal pressure, and overcurrent relay.

Uploaded by

edzel dayrit
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SM PAMPANGA

Parameters and settings of new DSE 7320 Controller

*A. High Engine temperature


*G. Generator Overspeed Protection
Low Warning – 90⁰C
Warning – 1979rpm
High Warning – 94⁰C
Shutdown – 1980rpm
Electrical Trip – 96⁰C
Time Delay – 0.5s
Shutdown Trip – 98⁰C

*H. Generator Under Speed Protection


*B. Low Oil Pressure Protection
Shutdown – 1620rpm
Warning - 2.04Bar
Time Delay – 1.5s
Shutdown – 1.02Bar

*I. High Crankcase Internal Pressure – Applicable for


*C. Failed to Start Protection (Over-crank) Electronic Engines Only
Shutdown - 3 start attempts

*J. Overcurrent Relay


*D. Under Frequency Electrical Trip – 2778A
Warning – 56.4Hz Time Delay – 36s
Shutdown – 54Hz J.2 Short Circuit
Time Delay – 2s Electrical Trip – 5052A

Time Delay – 0.01s


Over-frequency

Warning – 63.6Hz

Shutdown – 66Hz

Time Delay – 2s

*E. Generator Under Voltage

Shutdown – 415V

Activation Delay – 1.5s

*F. Generator Overvoltage Relay

Warning – 502V

Shutdown – 505V

Activation Delay – 2s