YD PTO Service Manual
YD PTO Service Manual
Manual
Generator
and Control
943-0020
8-88
PdnW In USA. Redistribution or publication of this document
by any means, is strictly prohibited.
Safety Precautions
Before operatlng the generator set, read the Operator's Do not wear loose clothing or jewelry in the vicinity of mov-
Manual and become familiar with it and the equipment. Safe ing parts, or while working on electrical equipment. Loose
and efflclent operatlon can be achleved only If the e q u l p clothing and jewelry can become caught in moving parts.
ment Is properly operated and malntalned. Many accidents Jewelry can short out electrical contacts and cause shock
are caused by failure to follow fundamental rules and precau- or burning.
tions.
If adjustment must be made while the unit is running, use
The following symbols, found throughout this manual, alert you extreme caution around hot manifolds, moving parts, etc.
to potentiallydangerousconditions to the operator, service per-
sonnel, or the equipment. ELECTRICAL SHOCK CAN CAUSE SEVERE PER-
SONAL INJURY OR DEATH
B t This symbol warns of Immediate haz- Remove electric power before removingprotectiveshields
ards whlch will result In severe personal Injury or or touching electrical equipment. Use rubber insulative
death. mats placed on dry wood platforms over floors that are
metal or concrete when around electrical equipment. Do
lirWAR"Gl Thissymbol refers to a hazard or unsafe not wear damp clothing (particularly wet shoes) or allow
practlce whlch can result in severe personal Injury skin surface to be damp when handling electrical equip-
or death. ment.
U s e extreme caution when working on electrical cornpo-
1- This symbol refers to a hazard or unsafe nents. High voltages can cause injury or death. DO NOT
practlce whlch can result in personal Injury orprod- tamper with interlocks.
uct or property damage.
Follow all applicable state and localelectrical codes. Have
all electrical installationsperformed by aqualified licensed
FUEL AND FUMES ARE FLAMMABLE. Fire and explosion electrician. Tag open switches to avoid accidental closure.
can result from improper practices.
DO NOT CONNECT GENERATOR SET DIRECTLY TO
DO NOTfillfueltankswhile engine is running, unlesstanks ANY BUILDINGELECTRICALSYSTEM. Hazardousvolt-
are outside the engine compartment. Fuel contactwithhot ages can flow from the generator set into the utility line.
engine or exhaust is a potential fire hazard. This creates a potentialfor electrocution or property dam-
age. Connectonly through an approvedisolation switch or
DO NOT permit any flame, cigarette, pilot light, spark, or an approved parallelingdevice.
other ignition source near the generator set or fuel tank.
GENERAL SAFETY PRECAUTIONS
Fuel lines must be adequately secured and free of leaks.
Fuel connection at the engine should be made with an ap- Coolants under pressure have a higher boiling point than
proved flexible line. Do not use copper piping on flexible water. DO NOT open a radiator or heat exchanger pres-
lines as copper will become brittle if continuouslyvibrated sure cap while the engine is running. Allow the generator
or repeatedly bent. set to cool and bleed the system pressure first.
Be sure all fuel supplies have a positive shutoff valve. Benzene and lead, found in some gasoline, have been
Do not smoke while servicing lead acid batteries. Lead identified by some state and federal agencies as causing
acid batteries emit a highly explosive hydrogen gas that cancer or reproductive toxicity. When checking, draining
can be ignited by electrical arcing or by smoking. or adding gasoline, take care not to ingest, breathe the
fumes, or contact gasoline.
EXHAUST GASES ARE DEADLY
Used engine oils havebeen identifiedby somestate orfed-
Provide an adequate exhaust systemto properly expeldis- era1 agencies as causing cancer or reproductive toxicity.
charged gases. Visually and audibly inspect the exhaust When checking or changing engine oil, take care not to in-
daily for leaks per the maintenanceschedule. Ensure that gest, breathe the fumes, or contact used oil.
exhaust manifolds are secured and not warped. Do not
use exhaust gases to heat a compartment. Provide appropriate fire extinguishers and install them in
convenient locations. Consult the localfire department for
Be sure the unit is well ventilated. the correct type of extinguisherto use. Do not use foam on
electrical fires. Use extinguishers rated ABC by NFPA.
MOVING PARTS CAN CAUSE SEVERE PERSONAL
Make sure that rags are not left on or near the engine.
INJURY OR DEATH
Remove all unnecessary grease and oil from the unit. Ac-
Keep your hands, clothing, and jewelry away from moving cumulated grease and oil can cause overheating and en-
parts. gine damage which present a potential fire hazard.
Before starting workon the generator set, disconnedstart- Keep the generator set and the surrounding area clean
ing batteries, negative (-) cable first. This will preventacci- and free from obstructions. Remove any debris from the
dental starting. set and keep the floor clean and dry.
Make sure that fasteners on the generator set are secure. Do notworkonthisequipment when mentally or physically
Tighten supports and clamps, keep guards in position over fatigued, or after consuming any alcohol or drug that
fans, drive belts, etc. makes the operation of equipment unsafe.
Ls-9
2 GENERATORIVOLTAGEREGULATOR 2-1
Generator Description .............................................. 2-1
Generator Operation ................................................ 2-2
Voltage Regulator.................................................. 2-3
............................................. 2-5
Optional Circuit Breaker
3 GENERATORIREGULATOR TROUBLESHOOTING ............ ............. 3-1
:
ComponentLocations ............................................... 3-1
Preparation ...................................................... 3-1
Troubleshooting Procedures........................................... 3-2
.................. 3-3
Flow Chart A. No AC Output Voltage at Rated Engine Speed
........3-4
Flow Chart B. Unstable AC Output Voltage. Engine Stable at Rated Speed
...................... 3-4
Flow Chart C. AC Output Voltage Too High or Too Low
................................ 3-5
Flow Chart D. Exciter Field Breaker Trips
Flow Chart E. Unbalanced AC Output Voltage............................. 3-6
............. 3-7
Flow Chart F. No AC Output Through Set Mounted Circuit Breaker
4 GENERATORIREGULATOR TESTSIADJUSTMENTS ..... ..................4-1
i
General .......................................................... 4.1. .
[A] Testing AC Residual Voltage...................................... 4-1
................................................
[B] Flashing the Field 4-1
[C] AC Voltage Regulator Replacement ................................. 4-2
........................................ 4-2
[D] Testing Rotating Rectifiers
....................................
[E] Testing Exciter Stator ....... 4-3
!
............................................
[F] Testing Exciter Rotor 4-4
[GI Testing Main Rotor Windings...................................... 4-5
....................................... 4-6
[HI Testing Main Stator Winding
[J] Wiring Harness Check ........................................... 4-7
[K] Voltage Regulator VRAS-2 Adjustment............................... 4-7 .
................................... 4-9
[L] Voltage Adjust Potentiometer R21
................................... 4-10
[MI Testing AC Load Circuit Breaker
.GENERATOR DISASSEMBLYIASSEMBLY ............ ................... 5-1
General .......................................................... 5-1
Disassembly ...................................................... 5.1 .
Reassembly ...................................................... 5-3
WIRING DIAGRAMS ................................................. 6-1
iii
Redistribution or publication of this document
by any means, is strictly prohibited.
.
M-1641
FIGURE 1-1. ONAN NAMEPLATE
lAWARNING I
INCORRECTSERVICEOR REPLACEMENTOFPARTS CANRESULTINSEVERE
PERSONAL INJURY, DEATH, AND/OR EQUIPMENT DAMAGE. SERVICE PER-
SONNELMUSTBE QUALIFIED TO PERFORM ELECTRICALAND/OR MECHAN-
ICAL SERVICE.
The generator rotor is directly coupled to the engine The composite illustration in Figure 2-2 shows the
flywheel with a flexible drive disc. The engine speed generator output and control/meter leads for the var-
- determines output frequency. A centrifugal blower on ious voltage codes that may appear on the nameplate.
the drive disc pulls cooling air through the end bell and The number of wires is dependent upon the model and
discharges it through an outlet near the blower. selected code options. Voltage codes B and N (single-
phase units), and F and H (3-phase units) have four
A ball bearing in the end bell supports the rotor shaft. leads. Voltage codes L and Z have 12 output leads for ,
The end bell is attached with four studs that thread into 3-phase, broad-range connections.
the generator adapter casting. The exciter stator mounts
DRIVE
DISC END BELL
BLOWER m
6-1202-1
2-1
Redistribution or publication of this document
by any means, is strictly prohibited.
Voltage code reconnection diagrams appear in Section GENERATOR OPERATION
4. Generator/Regulator Tests/Adjustment, and in Sec- Power generation involves the generator components
tion 6. Wiring Diagrams. Generator sets ordered from shown in Figure 2-3. These componentsare italicized in
Onan with the optional circuit breaker have the leads the following text. A permanentmagnetembedded in an
connected for the nameplate voltage. exciterstatorfield pole beginsthe voltage build-up pro-
cess as the generator set starts. Single-phase AC volt-
CONTROL AND METER LEADS- age, taken from a main stator winding, is connected to
TAPS OFF MAIN STATOR WINDING the VRAS-2 voltage regulatoras a referencefor regulat-
*SINGLE PHASE ONLY ing the generator output voltage. The regulator DC out-
CODES B AND N (3,53)
*1,4
put is coupled to the exciter stator.
THREE PHASE
CODES LAND Z (15,515): 4,7,8,9,10 The exciter rotor producesthree-phase AC voltage that
CODES F AND H (7,9X): 7,8,9,10
is converted to DC by the full wave rotating rectifier
assemblies. The DC voltage excites the rotor main field
winding to produce main stator AC for the load.
SINGLE PHASE
REGULATOR
CODES F, N (17,9X
THREE PHASE
ES-1315-1
-----
LAMJ
_.
*
I - __ ---m---
--0- DC
STATOR STATOR
ES-1322-2
2-2
Redistribution or publication of this document
by any means, is strictly prohibited.
VOLTAGE REGULATOR Switches on the regulator provide flexibility to test and
Description set the torque-matching function for different engine/
generator combinations.When properly set, the regula-
The VRAS-2 voltage regulator (Figure 2-4) provides tor is able to maintain output voltage within reasonable
switch selections that alter its sensing and command limits under transient conditions. It allows use of the
signals for maximum performancein a variety of genera- engine's full power to prevent an unstable response.
tor sizes and applications. Review the sections titled
Operation Modes and Operating Stability, then the Non- Torque-Matching:Even though the voltage regula-
Adjustments section for switch locations and settings tor can also be switch-selected to a non-torque-
specific for the generator set kilowatt rating. matching constant voltage mode, independent of
9
Operating Stability
Different regulator gain compensation is required
because of differences in the exciter and main field time
constants of various generator sizes. The VRAS-2 volt-
age regulator is switch-selectable to a kilowatt range
that best suits the generator set application.
0 -
.SwitchesS2 and S3 Determine the mode of regula-
tion (Torque-Matched or Non-Torque-Matched).
Refer to Table 2-1.
REGULATION MODE
GENSET STABILITY 60 Hz 50 Hz NON-
kW RANGE TORQUE-MATCHING TORQUE-MATCHING TORQUE-MATCHING
SI-1 S1-2 s2 S3-1 S3-2 S2 S3-1 S3-2 52 S3-1 S3-2
R32
VOLTAGE ADJUST _.
. .
c
SC-1516-4
s3 ’ R34
DO NOT ADJUST
(SEE TEXT)
ON
"
1r' GENERATOR
OUTPUT
TRIP
OFF
.RESEl
ES-1564-4
-
SIDE VIEW HANDLE POSITIONS
TRANSFORMER
I
ES-1564-3 FIGURE 2-6- GENERATOR-MOUNTED CIRCUIT BREAKER
2-6
Redistribution or publication of this document
by any means, is strictly prohibited.
Section 3. Generator/Regulatoa
Troubleshooting
COMPONENT LOCATIONS A few simple checks and a valid troubleshooting proce-
The following listing of components with their locations dure can quickly locate the trouble source and cut ser-
are referenced in the troubleshooting charts of the Trou- vice time. The following are inspectionareas often over-
bleshooting Procedures section. The charts will only be looked when troubleshooting.
calling them by name, so become familiar with their loca-
tions before proceeding. Other components are located 0 Check modifications, repairs, and replacements per-
on the control panel and are not listed here. formed since the last satisfactory operation of the set
to be sure that all generator leads are correctly con-
0 AC Output Circuit Breaker: Mounted in the generator nected. A loose or incorrect wire terminal connection,
AC output box. or an open circuit breaker overlooked when replac-
ing a part could cause problems. A thorough visual
0 Voltage Regulator VRAS-2: Inside the control box. check can quickly eliminate these potential problems.
0 Terminal Board TB27: Inside the control box. 0 Visually inspect the components of the VRAS-2 Volt-
age Regulator. Look for dust, dirt, or moisture and
0 Current Transformers CT27, 22, and 23: Inside the cracks in the printed conductors or solder connec-
generator AC output box. tions. Burned resistors and arcing tracks are readily
identifiable. Do not mark on the board with a graphite
0 Rotating Rectifiers: Within the generator end bell on pencil as this can cause leakage or short circuit
the exciter rotor. between components. Visually inspect the exciter
rotor assembly for burned components, broken wires,
loose connections, and carbon tracks caused by arc-
PREPARATION ing between parts or between parts and ground. Also
Before preparing or starting any troubleshooting proce- check for shorted paths between terminals caused by
dure, be sure to disable the generator set by disconnect- dust, dirt, and moisture.
ing the starting battery cables (negative [-] cable first).
Unless absolutely sure that panel instruments are accurate, use
portable test meters for troubleshooting.
Accidental starting of the generator
l33EiGl set can cause severe personal injury
or death during service procedures. Be sure to disable
ACAUT~ON To prevent meter damage,
ohmmeter checks must be made
the generator set by disconnecting the starting battery with the generator set stopped and the starting bat-
cables (negative1-1cable first). tery disconnected.
3-1
Redistribution or publication of this document
by any means, is strictly prohibited.
TROUBLESHOOTING PROCEDURES After determining the problem, refer to the applicable
The information in this section is divided into Trouble- troubleshooting flow chart. Start at the chart upper left-
shooting Flow Charts as follows: hand corner and answer all the questions either YES or
NO. Follow the chart until the problem is found, perform-
A. No AC output Voltage at Rated Engine Speed ing the referenced Adjustment and Test Procedure(s)
following the flow charts.
B. Unstable AC Output Voltage, Engine Stable at
Rated Speed. The referenced components in the flow charts and in the
C. AC Output Voltage Too High or Low. Adjustment and Test Procedures can be found on the
D. Exciter Field Breaker Trips. electrical schematic in Figure 3-1, and on assembly and *
E. Unbalanced AC Output Voltage. wiring diagrams.
F. No AC Output Through Set-Mounted Circuit
Breaker.
COMPONENT DESCRIPTION
REF DESCRIPTION
SC-1618
3-2
Redistribution or publication of this document
by any means, is strictly prohibited.
FLOW CHART A. NO AC OUTPUT VOLTAGE AT RATED ENGINE SPEED
(BWARNING] Many troubleshootingprocedures present hazards which can result in severe personal injury or
death. Only qualifiedsenricepersonnel with knowledge of fuels, electricity, andmachineryhazards
should perform service procedures. Review safety precautions on inside cover page.
I
I
Remove one lead from breaker and
No check continuity with ohmmeter. Is
I breaker open?
N-
do If voltage is unstable, high or low. or
Push to reset breaker. Does generator Yes
AC output voltage build up7 causes breaker to trip, see Flow Charts
B. C. D or E.
No
Flash the exciter stator per TEST
[B]. Does AC output voltage build up?
Yes No
.)
I
Yes
Check exciter stator wiring for
shorts per TEST [J]. Replace bad
wiring.
+
TEST [E]. Replace if bad.
Many troubleshooting procedures present hazards which can result in severe personal injury or
death. Only qualified service personnel with knowledge of fuels, electric@, and machinery hazards
should perform service procedures. Review safety precautions on inside cover page.
‘I
Does AC output voltage build up Check for any loose or broken wires
to 15096 or more of rated voltage y
-es+
-, or connections on voltage regulator
before breaker trips? assembly.
I
No
IC
Check exciter stator winding
per TEST [E]. Replace if bad. I proper, and secure connection. Refer
+
Check exciter rotor winding
to Generator Description, Optional
Voltage Connections, and appropriate
electrical schematic.
1
Check main rotor winding
per TEST [GI. Replace if bad.
1
Check main stator windings
per TEST [HI. Replace if bad.
+
Replace voltage regulator
per TEST [C].
1- Many troubleshooting procedures present hazards which can result in severe personal injury or
death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards
should perform service procedures. Review safety precautions on inside cover page.
Disconnect load from generator (trip Reconnect load and check each phase *.
AC breaker if used). Is output for balanced current. If not within
still unbalanced? 10% of each other, redistribute the load.
I-'
Yes.; Check for correct grounding of generator
+ and'load.
..
..... . . . . . .
Correct'as necessary.
. .
. .
yes
3-6
Redistribution or publication of this document
by any means, is strictly prohibited.
FLOW CHART F. NO AC OUTPUT THROUGH SET MOUNTED CIRCLIIT BREAKER
n~WARN~NG Many troubleshooting procedures present hazards which can result in severe personal injury or
death. Only qualified sewice personnel with knowledge offuels, elecbicity, and machinery hazards
should perfonn sewice procedums. Review safeiyprecautions on inside cover page.
I
: Determine cause of breaker trip. If
not immediately known, stop
generator set and investigate cause.
Circuit overload (per site-
established procedures).
GENERAL
The following tests and adjustments can be performed FLASHING THE FIELD
without disassembly of the generator. They should be
used for testing the generator components and regula- If the residual voltage is missing, it may be necessary to
tor in conjunction with the Troubleshooting Flow Charts restore magnetism by flashing the exciter field. This
in Section 3. All resistance measurements must be requires a 12-volt battery, IO-ampere fuse, momentary-
made with the unit stopped to prevent instrument on switch, and diode assembled as shown in Figure4-2.
damage.
Field flashing can be done during generator set opera-
[AI tion or when stopped. Either method should be suffi-
cient to restore magnetism.
TESTING AC RESIDUAL VOLTAGE
Test for generator residual AC voltage if there is no Incorrect flashing procedure can
power output. A good check point is across terminals 22 damage the voltageregulator. Do not
and 23 at terminal block TB21. See Figure 4-1. Residual keep excitation circuitry connected longer than five
voltage should be 5 to 10 VAC minimum at normal oper- seconds.
ating r/min and no load. The voltage can be as high as
35 to 50 VAC. During Generator Set Operation
If residual voltage is present at TB21, check voltage at 1. Connect the positive lead to VRAS-2 terminal 9 (+)
VRAS-2 terminals 2 and 3.If none, check continuity of and the negative lead to terminal 10 (D) (Figure4-1).
field circuit breaker CB21, wiring, and connections with 2. Start the generator set and operate at normal speed.
the generator set shut down. Close the switch just long enough for the generator
output voltage to build up, but not longer than five
seconds.
Ff I;! TO EXCITER F I E L D
TO DC CONTROL
J I - l .JI-2
cB21
FIELD TB21
CIRCUIT TERMINAL BOARD ES-1792
BREAKER
TO VRAS-2
TERM. TB1-10 TESTING ROTATING RECTIFIERS
F2-)
Two differentrectifier assemblies make up the rotat-
ing rectifier bridge assembly, Figure 4-3. Using an
MOMENTARY-ON
ohmmeter, test each CR rectifier using negative (-)
and positive (+) polarities. Use the following proce-
dure.
TO VRAS-2 12-AMP
TERM. TB1-9
(F1+) DIODE
OHMMETER
10-AMP
FUSE
TFil
ES-1658-2
CR5
CA-1010-9
4-2
Redistribution or publication of this document
by any means, is strictly prohibited.
1- Disconnectall leadsfrom the assemblyto be tested.
2- Connect one ohmmeter test lead to F1+ stud and
[El
connect the other test leadto CRl, CR2, and CR3 in
TESTING EXCITER STATOR
turn. Record resistance value of each rectifier. Test the exciter stator (Figure 4-4) for open or shorted
3. Connect one lead to F2- stud and connect other test windings and grounds as follows.
lead in turn to CR4, CR5, and CR6. Record resist-
ance value of each rectifier. Testing For Open or Shorted Winding
4. Reverse ohmmeter test leads in Steps 2 and 3 and Use a Wheatstone Bridge or digital ohmmeter for this
record resistancevalue of each rectifier. test. Disconnect F1+ and F2- exciter field leads from the
terminal block in the generator end bell. Resistance
5. All resistance readings should be high in one test should be 14.5 ohms f10% at 77OF (25OC).
and low in the other test. If any reading is high or low
in both tests, rectifier assembly is defective.
Testing for Grounds
Use23 to 26 inch pounds(2.6 to 2.9 Nom) torque when replacing Connect a megger or insulation resistance meter that
nuts of F1+ and F2- leads, CRl, CR2, CR3, CR4, CR5, and CR6. applies 500 VDC or more between the field and the
exciter stator lamination. Be sure both exciter leads are
disconnected from the terminal block. Reading should
be 100,000 ohms or greater. If not, the exciter stator is
F1. F2 questionable and may require removal for oven drying
LEADS
and retest. A shorted stator must be replaced.
F1. F2
STATOR LEADS
LAMINATIONS I
WHEATSTONE
CA-1010-10 BRIDGE OR
DIGITALOHMMETER
MEGGER OR
INSULATION
RESISTANCE
METER CA-1010-11
EXCITER ROTOR
ASSEMBLY
EXCITER ROTOR
CRl
MEGGER OR
INSULATION
WHEATSTONE RESISTANCE
BRIDGE OR METER
DIGITAL OHMMETER
TESTING WINDING FOR GROUNDS
TESTING WINDING RESISTANCE
CONNECTIONDIAGRAM
ES-1794
Testing For Open or Shorted Winding 1. Remove rotor leads F1+ and F2- from the rotating
Perform this test with a known, accurate instrument rectifier assemblies.
such as a digital ohmmeter.
Be sure to remove both rotor
1. Remove rotor leads
rectifier assemblies.
i+ and F2- from the rotating 7. leads so the rotating rectifiers
are isolated. Failure to do this will damage the
rectifiers.
2. Check resistance across F1+ and F2- leads. The
resistance values at 77OF (25OC) should be as 2. Connect test leads between one of the two leads
shown in Table 4-1. If not, replace the defective and the rotor shaft. Meter shouldread 100,000 ohms
rotor with a new, identical part. or greater.
3. If less than 100,000 ohms, the rotor is questionable
and may require removal for oven drying and retest.
4. Replace a grounded rotor with a new identical part.
!
DIGITAL
OHMMETER
t c y ]
MAIN ROTOR
LEADS F1+. F2-
CA-1010-8
RESISTANCE
METER
4-5
Redistribution or publication of this document
by any means, is strictly prohibited.
TABLE 4-1. MAIN ROTOR RESISTANCE
ZRESISTANCE VS CODE
MEGGER OR
INSULATION
RESISTANCE
METER
THREE PHASE MODEL.S
EST BETWEEN WIRE P I4IRS
Tl-T4 T7-Tl0 T3-,T6
ES-1795
4-6
Redistribution or publication of this document
by any means, is strictly prohibited.
TABLE 4-2. MAIN STATOR RESISTANCE
'RESISTANCE VS CODE
[Jl
WIRING HARNESS CHECK VOLTAGE REGULATOR VRAS-2
ADJUSTMENT
1. Inspect all wires for breaks, loose connections, and After replacement, the voltage regulator VRAS-2
reversed connections. Refer to applicable wiring adjustment is performed as follows. Also refer to the
diagram. VRAS-2 Regulator Specifications in this section.
2. Removewires from terminals at each end and using
an ohmmeter, check each wire end to end for conti- 1. Open the control panel doors. Refer to Figure 4-8
nuity or opens. for the proper setting of SI (Stability Range) and S2,
3. Using an ohmmeter, check each wire to other wires S3 (Mode Selection) switches.
and to ground for possible shorts or insulation 2. Control with AC meter option: Refer also to adjust-
breaks under areas covered by wrapping material. ment [K]. Control without ACmeter option:Connect
4. Reconnect or replace wireslharness per the appli- an accurate voltmeter to VRAS-2/TB1-2 and -3
cable wiring,diagram. terminals.
3. Startthe generator set and operate to bring temper-
ature up to normal.
4. As a precaution against electrical shock, place an
insulating mat or a dry wood platformon the floor in
front of the control panel.
FRONT METER
s2 +
PANELS
S l l
R32
IOLTAGE'ADJUST
L'
Checking Insulation Resistance: Disconnect the load A resistance reading lessthan 100,000 ohms indicatesa
and line conductors from the breaker, and place the ground. Investigatefor possible contamination on the
breaker in the On position. Use an insulation resistance breaker case surfaces, clean if necessary and retest.
meter that will apply at least 500 volts to the test leads.
Measure the insulation resistance between each pole, Checking Contact Resistance: Extensive operation of
and to ground. Also test between the line and load the breaker under load may eventually cause contacts
terminals with the breaker in the Off position. to deteriorate. Test by a Resistance Check, or by a
Voltage Drop Check across the breaker poles.
4-1Q
Redistribution or publication of this document
by any means, is strictly prohibited.
Resistance Check: Checking Shunt-Trip 0pemfion:The shunt-trip feature
is available in varying AC or DC voltages. Proper circuit
1. Disconnect the line and load wires from the circuit breaker model is selected and installed at the factory to
breaker. meet customer requirements.
2. Move the breaker handle to the On position and
checkthe resistanceacrosseach pole (lineto load). Check the shunt-trip function as follows:
3. Resistanceshould be very low (near zero) and rela- 1. Refer to the original equipment order, installation
tively equal across all poles. wiring diagrams, and unit wire routing to identify
and confirm proper AC or DC signal source
Voltage Drop Check: connections.
This test is done with the conductors connected, gener- 2. Check security of the wire connections.
ator set operating, and load applied. As a precaution 3. Apply the appropriate signal voltage (12-, 24-VDC;
against electricalshock, place an insulatingmat or a dry 240-, 480-VAC). The shunt-trip solenoid should
wood platform on the floor to stand on when taking energize and trip the breaker open.
measurements. 4. If the breaker did not trip open, remove the signal
1- Contact with high voltage can cause
severe personal injury or death. Do
source. Perform continuity check of interconnect
wiring and shunt-trip solenoid lead wires. Replace
interconnect wiring if defective.
not touch any exposed wiring or components with any
body part, clothing, tool or jewelry. Do not use non- Checking Auxiliary Contacts: If equipped, the breaker
insulated tools inside the control. Stand on an insulat- will have three leads for wiring to an internal single-
ing mat or dry wood plafform when taking measure- pole, double throw switch. The switch allows connec-
ments. tion of a remote annunciator (see installation wiring
diagrams).
1. Operatethe generator set with the breaker in the On
position and load applied. Perform continuity checks of the switch with the breaker
, 2. Take voltage readings at the line connections, then
the load connections.
in On and Off positions to confirm operation.
3. There should only be slight variation in the voltage Adjusting Magnetic Trip Operation: If equipped with
dropped across each pole of the breaker. Unequal front-adjustable magnetic trip controls, the short circuit
or excessive millivolt drops across the complete protection feature for each pole of the breaker can be
breaker, or one pole, indicates contaminated con- adjusted equally or individually as required. Surge cur-
tacts or loose connections. rent above the trip settings will actuate the trip mecha-
nism. These adjustors are set equally to the high posi-
4. Stop the generator set by placing the Run-Stop- tion at the factory. Consult on-site requirements and
Remote switch in Stop position and disconnecting adjust to proper position.
the battery negative (-) cable.
I. Disconnect the generator set starting battery 10. Remove lead from the overspeed switch (if used),
(negative [-I cable first) before performing service and control leads F l + and F2- from the end bell
procedure. terminal board.
Accidental starting of the 11. Removethe overspeed switch and bracket (if used)
AWARNING aenerator set can cause severe from.the end bell and rotor shaft.
personal injury 0'; death during service proce-
dures. Be sure to disable the generator set by dis- 12. Remove the end bell and exciter stator assembly. It
connecting the starting battery cables (negative[-] may be necessary to pry or jar the assembly loose
cable first). from the main stator assembly.
2. Remove the back grille from the rear of the genera- 13. Use a hoist and safe lifting device (stator handling
tor (six l/4-20 screws). tongs, nylon lifting strap or chain and lifting hooks)
to support the main stator assembly.
3. Remove output box cover by removing four screws
(1/4-20). 14. Remove 12 (M10) screws and lockwashers secur-
ing the main stator assembly to the engine adapter.
4. Open the control box doors and disconnect genera-
.
tor control wires. Check wire stamping legibility to 15. Removethe main stator being careful notto touch or
ease reassembly. If necessary, attach identification drag it on the rotor. Place the stator on its side and
with tape. Arrange leads so they can be .withdrawn block to prevent rolling, especially if placed on a
easily through the control box grommet opening. workbench.
5. Remove four screws (5116-18) and lockwashers Falling, heavy objects can cause
I securing the control box to the generator output
AWARNING severe personal injury or death.
box. Carefully lift the control box free of leads and Be sure to block or support heavy objects to pre-
set aside. vent falling. Wearprotective shoes and keep hands
and feet clear.
6-1153
5-2
Redistribution or publication of this document
by any means, is strictly prohibited.
16. Usinga hoistand sling to supportthe rotor, carefully REASSEMBLY
remove the capscrews that attach the drive disk to Reassembly procedures are basically the reverse of
the engine flywheel (Figure 5-1). disassembly. The following steps should be used as a
guide. Apply the torque specs as specified.
17. Remove the rotor assembly and place upon wood
block in the horizontal position. The drive disk and 1. Slide the exciter rotor over the generator shaft and
fan should not be resting on anything or distortion woodruff key. Installthe exciter nut and apply torque
may occur. values specified in Figure 5-3.
18. Remove bolts that hold the drive disk and fan to the 2. Connect the main rotor leads to terminals F1+ and
rotor shaft. F2- on the exciter rotor. Torque to values shown.
19. Use a gear puller to remove the end bearing from 3. Press the end bearing onto the rotor shaft. Spacing
the rotor shaft (Figure 5-2). If bearing is to be reused, between the shaft end and bearing side surface
be sure to apply puller to the inner race. must be as specified in Figure 5-3.
lmproper removal of the end 4. Assemble rotor fan and drive disk to the engine
A C A U T ~ O ~ bearing will damage it. If flywheel. Use a hoist and sling to support the rotor.
intended for reuse, the bearing must be pulled off Be sure the drive disk is assembled with the chamfer
by the inner race. on the flywheel side. Apply torque values as shown.
20. Clamp the rotor in a fixed position and remove the 5. With a hoist and safe lifting device, carefully move
exciter rotor lock nut. the main stator into position over the rotor. The
stator leads should exit in the 4 o’clock position.
21. Remove the generator field leads from the exciter
rotor and slide the exciter off the rotor shaft. 6. Secure the main stator to the engine adapter with 12
(M10 x 1.5) screws and lockwashers. Torque bolts
to 39 ft-lb (52 Nom).
ES-1495
FLAT WASHER
,
DETAIL A
10: Place the AC output box .into position.Slide the '15. Carefully'connect all control leads to'their marked
engine harness/grommetrinto the slot lopening. -1erm'inations.
11. Install four (3/8-16) nuts and lockwashers to the 16. Close and secure the control box doors. Do not
end bell studs; then three capscrews and flat install the output box back grille until the overspeed
washers at the front of the AC box. Torque.the end switch setting has been checked.
bell nuts to 20 ft-lb (27 Nam).
17. Connect the generator set starting battery (positive
12. Tighten the output box capscrews. Using a lead [+] lead first) and test generator operation.
hammer, tapthe end bell at the horizontaland verti-
cal plane to relieve stress. Retorque the four end 18. The rimin at which the overspeed switch shuts
bell nuts. down the generator set can be changed by the
adjust screw. Turning this screw in or out changes
13. Assemble wire,conduit to the generator output box. the magnetic air gap. When set correctly, the switch
Connect the generator, 1oad;and auxiliary wires to closes and shuts down 60 hertz units at 2100 r/min
the AC circuit breaker (if used). +90 r/min; 50 hertz units at 1800 r/min +90 rimin.
An accurate frequency meter or strobotach is
14. Set the control box on the .output box. Route all needed to check the overspeed trip point when the
control leads through grommet in control box bot- engine speed is increased (see the engine service
tom. Secure control box with four screws (5/16-18) manual). The air gap must not be less than 0.005
and lockwashers. inch (0.13 mm).
5-4
Redistribution or publication of this document
by any means, is strictly prohibited.
Section 6.Wiring Diagrams
WIRING DIAGRAM DRAWING NUMBER PAGE
Generator Set AC Control Schematic Diagram (W/O Meters)............. 612-6489 . 6-2
Generator Set AC Control Wiring Diagram (W/O Meters) ................. 612-6489 6-3
Generator Set AC Control Schematic Diagram (Meter) .................... 612-6490 6-4
Generator Set AC Control Wiring Diagram (Meter) ......................... 612-6490 6-5
Generator ReconnectionWiring Diagram .................................. 625-2108 6-6
Voltage Regulator InstallationWiring Diagram ............................. 300-3303 6-8
Generator Reconnection Diagram........................................... 98C2193 6-9
. .
VR2 I I I
A 1 I
I
I
I
I
I
.I
I
I jl
I I
I I
6-2
Redistribution or publication of this document
by any means, is strictly prohibited.
WIRING DIAGRAM
_- __
[ =
( I N S I D E VIEW)
I ( I N S I D E VIEW1
H $ $ ~ ~ $
~ ~ ~ ~ , , ~ \ ~ E BACK~WALL
I
& OF~ CABINET
~ ~-VERTICA
L E F T WALL OF TRAY-HORIZONTAI
li
I I
I I
I I
I I
I I
A I
I
I
I
ENERATOR I I
I I NOTES:
GENERATOR I I I . ALL COMPONENTS SHOWN I N DE-ENERGIZED POSITION.
I VR21
GENERATOR
GENERATOR
I A I
I
GENERATOR
4. SEE GENERATOR CONNECTION DIAGRAM FOR INPUT CONNECTION
II
A 5. SEE VOLTAGE REGULATOR INSTALLATION FOR CONNECTIONS
TO VR21.CB21 AND T 6 2 1 .
II
COMPONENT IDENTIFICATION
REF. I DESCRIPTION
. T5-lV51
Tb-lW51
T7-lU21
!
I
T9-lW21
w
TII-IVII I
/
/
A
BRIDGE RECTIFIER
9 F2(XXl T12-IWII !, /
U
M2 I
-n+
52 I
I POSITION I COluTACTS CLOSE0
6-4
Redistribution or publication of this document
by any means, is strictly prohibited.
WIRING DIAGRAM
--
1
I1
!I
(INSIDE VIEW1
I L F T S I D E WALL -VERTICAL
!IROTTOM OF TRAY-HORIZONTAL
S2 I -44
TB2 I
t INSIDE
~--------------
I
I
VIEW)
BACK WALL OF CABINET-VERTICAL
LEFT W A L L OF rRAY IlOliILONTAl
II
I
I
t
s21-43
1.
S21 42
M22- ( +
521-14 I
I A
DS2 I -2 I VR21
us22-2
NOTES:
- c20&’ET!ETE3
DISCONNECT 5. SEE VOLTAGE REGULATOR INSTALLATION FOR CONNECTIONS
TO VR21 .CB21 .R21 AND TB21.
BOTTOM OF CABINET
(INSIDE VIEW)
COMPONENT IDENTIFICATION
REF. DESCRIPTION
TI-IU61 CB21 Field Circuit Breaker
T2-IV6l
CT21-
r4-1~51 I CT23 Current Trans. Assy.
II T5-IV51 ;I
TO CURRENT DS21-
TRANSFORMER
INSTALLATION DS22 Lamp, UpperILower Scale
G21 Generator
M21 Voltmeter, AC
M22 Ammeter, AC
M23 Meter, Frequency
/ R21 Potentiometer, Volt Adjust
/
s21 Switch, Rotary
G2 I GENERATOR
TB21 Terminal Block
VR21 Voltage Regulator, VRAS-2
-
18 -
518
L Z
I10/220V. 50HZ I10/190V. 50HZ 120/208V. 60HZ 220/380V. 50HZ 240/416V. 60HZ
I20/240V. 60HZ' I20/208V. 50HZ I39/24OVI 601-12 240/416V, 50HZ 277/480V. 6OHZ
I27/220V, 501-12 254/440V. 50HZ
.
CT21 CT2I
I
L2
LO
7
3
. . ..
I
I
12 b2 io
8
I
9-!
T5
0 L3
6:.270/380V 60HZ
%:347/600V 60HZ
, .
:
SECOMARY CURRENT TRANSFORMER C O W . 1-2
Tw
CT2 I
I
IA' L I
CT22
L2
LO
T3
6-6
Redistribution or publication
i of this document
by any means, is strictly prohibited.
I PHASE RECONNECTABLE
I SECONDARY UmRENT
IRANSFORWER C O " . 1-3 I
I I10/220V.
115/23OV.
50HZ
60HZ I
120/240V. 60HZ
z: 120/24OV 60HZ
I PHASE
SECONDARY CURRENT
CT2 I
10
L2
CT22
NOTES :
VOLTAGE COOE
7
CBP I
I 'TO DC CONTROL
JI-I ,JI-2
COMPONENT IDENTIFICATION
DESCRIPTION
6-8
Redistribution or publication of this document
by any means, is strictly prohibited.
2201380 VOLT. 3 PHASEGO HBRTZ(c0DE FJ
1201240 VOLT. 3 PHASE60HERTZ (CODE e) 3471600 VOLT. 3 PHASE 60HERTZ (CODE HI
1
CT 21 CT 22 I
GplERAToRCO"E~WlWNGDIAGRAM
(wrmCURRPrrlRAMFORMERSWHP(USED)
LO 11 11
11 I 2 16 1 1 1 1 8 1 1 2 14 I9 1 5 1 7 1.3 110
LO 11 13
E 240/480 3 60 1-2
2
L 120/240 3 60 1-3
115/11O 1 50 1-3 In
:z Ly
110/210 3 50 1-3
120/101 1 60 1-3 LO 11 11 11
L 117/120 1 60 1-3
1 1 4 2 4 0 1 60 1-3 5
110/190 3 50 1-3
-
d
115/200 1 5 0 1-3
z
114208 3 50 1-3 2
14 76 111
127/210 3 50 1-3 13 1 1 18 13 19
I5 110 lnT1
140/41b 3 60 1-2 LO -
L 1&40 3 60 1-2 I L1 L2 L3
5
Y
177180 3 60 1-2
l2e/380 3 50 1-2 ,
I
ia0/400 3 so 1-2 5
2
140/41b 1 50 1-2
,,,
154/440 1 50 1-2 T2 T3 T5 T8 T6 T9 T4 T7
I I
6-9
Redistribution or publication of this document
by any means, is strictly prohibited.
Redistribution or publication of this document
by any means, is strictly prohibited.
Redistribution or publication of this document
by any means, is strictly prohibited.
Onan Corporation
1400 73rd Avenue N. E.
Minneapolis, MN 55432
612-574-5000
Telex: 275477
Fax: 612-574-8087
Onan is a registered trademark of Onan Corporation