Power Wiring
HM-700 Series Human-Machine Interface 1. The input power of HMI using a DC power supply, voltage range of 24 ±
20% VDC, too much or too less will be serious damage to HMI. Regularly
HM-740S / HM-740A check the power supply of DC power source to see if it is stable or not.
2. To avoid electric shock, before connecting to the communications cable or
Installation Instructions download cable, please cut off the HMI power.
3. DC power supply must be properly isolated from the main AC power.
V1.02 2013-08-05 4. Do not let the input circuit of HMI and inductive load (solenoid or
electromagnetic switch), inverter or driver to share the power supply.
1. Installation Instructions 1.1.3. Power wiring method
HMI is the CPI information products, may result in the use of RF interference or 1. Please remove the quick connector from HMI body when wiring.
electromagnetic waves are generated, may affect other appliances, the user must 2. Only one cable can be inserted into the cable socket of quick connector.
ensure compliance with the following installation instructions to ensure the correct 3. 24VDC' anode connect to the terminal marked as a "+", and 24VDC
gases and other substances, or it may result in electric shock or fire. impedance must be less than 100Ω (class3).
3. Serial communication cable and network cable and power cable should be 2. Please use the independent grounding pole, should not connect to the
separated, and must be used to mask the cable, otherwise it may cause grounding conductor of power circuit.
unpredictable problems. 3. Ground conductors should be as short and as large in size as possible.
4. Attention! W hen drilling or work with HMI, you should not let the cut wires or The conductors must always be large enough to carry the maximum short
filler and other impurities fall into the HMI internal . circuit current of the path being considered. Ground conductors should be
connected to a tree from a central star earth ground point. This ensures
that no ground conductor carries current from any other branch.
1 2
4. When FG terminal is connected, pleas e check if the wire is grounded properly. 4. The vent of HMI should not obstructed, otherwise, it may easily cause a
Because improper grounding may result in communication error, electric shock malfunction.
or fire.
1.2. Installation and storage environmental conditions
1.1.5. Communication cable wiring Notes
The product must be kept in the shipping carton before installation. In order to
1. Comply with communication wiring specification for wiring.
retain the warranty coverage, the HMI should be stored properly when it is not
2. Restrict cable length to less than 500 ’(150m) for RS485/422 devices and
to be used for an extended period of time. Some storage suggestions are: :
50’(15m) for RS232 devices to avoid communication problems.
1. The storage location should be dry with no dust, should've better with
3. Proper grounding circuit to avoid bad communication quality.
correctly packaged and placed on a solid shelf surface.
4. Shielded cable must be used for long lengths or cables run in an electrically
2. Store within an ambient temperature range of -20°C~+60°C (-4°F~140°F).
noisy environm ent.
3. Storage location' ambient relative humidity must be within the range of
5. When wiring, should be away from AC power cable and high energy and rapidly
10% to 90% without condensation .
switching DC wiring cable.
4. Do not store in the environment of corrosive gases and liquids .
1.1.6. Operation Notes
5. The suitable installation environm ent : No heat-radiating elements, no
1. HMI should m eet the editing software to plan the screen. Un -planned HMI may
water droplets, no vapor, no dust and oily dust' place; non -corrosive,
not be able start the application, or result in abnormal operation.
flammable gases, liquids spaces; no airborne dust or metallic particles of
2. Shouldn't change the wiring when the power is turned on, or it may result the
places; sturdy no vibration、no electromagnetic noise interference' places.
electric shock or human injure.
3. Do not use a sharp object to touch the panel, or it may cause the panel sunken, 2. Serial port pin definitions
and thus cannot make HMI operate normally.
COM1 – ( Support RS232 / RS485 )
4. The backup data of this product using the rechargeable lithium battery to supply
Pin Pin Definitions
the electric, therefore, do not let the product with power off for a long time (more
1 RS485+
than 6 months) to cause the low battery and let the kept data missi ng (system
2 RS232 RXD
parameter, recipe, resume...) 3 RS232 TXD
1.1.7. Maintenance Checks 4 Terminal resistor for RS485+
1. Prohibiting touch HMI internal, otherwise it may cause electric shock. 5 Signal Ground
2. Prohibiting dismantle the operation panel when power is on, otherwise, it may 6 RS485-
7 RS232 RTS
cause electric shock.
D type / 9P 8 RS232 CTS
3. When the power is off for 3 minutes, should not touch the terminal block,
Female adaptor 9 +5VDC Output ( Maximum 100mA )
otherwise, the residual voltage may cause electric shock.
3 4
COM2/COM3 – ( Support RS232 / RS485 / RS422 )
Pin COM2 Pin Definitions COM3 Pin Definitions
3. Mounting
1 N/A
The dimensions of HM-740 - (unit: mm)
2 RS232 TXD
200.0 185.0
P1 P14 3 RS232 RXD
4 RS232 RTS RS232 TXD
5 RS232 CTS RS232 RXD
6 +5VDC Output ( Maximum 100mA )
150.0
135.0
7 Signal Ground
8 +5V 輸出
Option - ( Max. 100mAAlarm-C
) C
A
9 Alarm Output Alarm-A B
10 1A 120VAC/24VDC Alarm-B
11 Terminal resistor for CTS+ Terminal resistor for RX+
12 RS422 CTS+ RS422 RX+
Front View Rear View
13 RS422 CTS- RS422 RX- 51.0 186.0±0.5
46.0
136.0±0.5
135.0
17 RS422 RX-
18 Terminal resistor for RX-
19 Signal Ground
20 N/A
D type / 25P 21 N/A
22 N/A Side View Cutout dimensions
Female adaptor
23 RS422 RTS+ RS422 TX+ / RS485+
Installation sequence -
24 RS422 RTS- RS422 TX- / RS485-
1. On a fixed panel, follow the recomm endations of mounting diagram to cutting an
25 N/A
area, to install HMI on this panel. As below diagram: (please make sure to
△! COM3 only can be used when COM2 handshaking signals are cancelled (RTS / install the waterproof ring before HMI installation) .
5 6
2. Make sure the fixed piece screw is installed into the HMI fixed holes, and then
the beneath hooked the front cover, screw head is withstand the insides of
4. Specifications:
control box. As below diagram: Item No. HM-740S HM-740A
Type(65K c ol ors ) 5.6” T FT LCD (65536 c olors )
Display
loosen the screw. Pan el Prot ec tion IP65, Dus t-proof , Drop-proof des ign (O -ring wat erproof )
Shell M ateri al Indus trial Plas tic
Vibration r es is tanc e 10~50Hz (x、 y、 z eac h direc tion 2G 30 minutes )
Dimens ions 200(W ) x 150(H) x 51(D) mm
Pan el Cutout 186.0± 0.5(W ) x 136.0± 0.5(H) mm
W eight Approx. 850g
2. Strip 24VDC power cord ( stripping length 7~8 mm ), according to the polarity
Rem arks USB Hos t c an s upply a m axi mum of 5V/150mA
insert the power terminal to the corresponding position.
※ Model t yp e and s pec if ic ation ar e s ubjec ted to c han g e without notif ic ation
3. Using a flat-blade screwdriver to lock tight the power terminal screw.
4. At last, insert the power terminal into HMI power supply end.
7 8