Calculating Heat Loads and Computer Room Cooling Requirements
Calculating Heat Loads and Computer Room Cooling Requirements
uk/blog/calculating-heat-loads-and-server-room-cooling-
requirements
03/06/2019
The recommended relative humidity is 45-50%. This ensures that the room is not too dry which can lead to a
build up of static electricity and not too damp which can lead to condensation build-up on colder plastic and
metal surfaces.
ASHRAE, the American Society of Heating, Refrigerating and Air-Conditioning Engineers, is the leading
body when it comes to cooling and humidity levels in mission critical facilities and datacentres. The
organisation has proposed widening the ambient temperature environment up to 30˚C in order to improve
energy efficiency.
For more information see: https://tc0909.ashraetcs.org/documents/ASHRAE%20Networking%20Thermal
%20Guidelines.pdf
Whilst this higher ambient temperature would reduce the demand on cooling systems and therefore improve
energy usage, it may only be suitable for larger server rooms and datacentres that can incorporate cold and/or
hot-aisle containment. For smaller computer and server room installations this is not cost-effective, and the
only solution is to install some form of air conditioning.
Multiple servers may be installed along with storage devices and network switches and routers. All these items
will generate a heat output that must be accommodated into the cooling requirements calculation.
Whether the servers are floor towers or rack cabinet mounted, they will require adequate air flow around them
and a source of cool air. The most common approach is to install an air conditioning unit. Liquid cooling
solutions are available but are more commonly used within high performance computing environments and
datacentres.
The air conditioner may be wall or ceiling mounted and will be the same as commonly used within an office
environment. These types of air conditioner are known as ‘split units.
Split air conditioner systems are a very efficient way to cool a room. They consist of an indoor unit connected
via copper pipes to an outdoor unit or heat exchanger and compressor. The AC units are supplied with a cooled
refrigerant and internal fans blow air over the evaporator coils into the room.
Heat rises and so the air conditioning unit inside the room is either ceiling-suspended or wall mounted.
However, this unit will only ‘push’ cool air into the room. Inside a server rack, there could be a build-up of
heat referred to as ‘hot-spots’. The airflow within the sever cabinet can be improved by using blanking panels
and allowing adequate room around the individual IT components for air flow. Additional fan trays can also be
installed to draw air through the server cabinet.
Due to the potential for rapid heat spikes within a confined space like a server rack or computer room, it is
important to install environment monitoring. As well as for temperature and humidity, an environment
monitoring system can also detect smoke, fire, and water issues if fitted with the appropriate additional
sensors. For an environment monitoring system to operate effectively, the sensors must be positioned
appropriately within the installation with a suitable air flow for sampling. Within a server rack this can mean
up to 3 pairs of sensors (front and rear) placed on the bottom, middle and to the top of the server rack.
The use an external heat exchanger and compressor prevents a build-up of condensation inside the internal AC
unit. This is one of the issues with portable AC units which will have a tray to store moisture removed from the
air as it is cooled. The condenser tray will require emptying at regular intervals for the portable AC unit to
continue to operate. Alternatively, portable AC units may also have an exhaust pipe that requires routing to the
outside via a doorway or window; both of which provide poor seals to the environment and therefore low
cooling efficiency.
For this application we would therefore consider the nearest sized AC unit which may be a 3 or 5kW system.
Taking the remaining elements for the calculation after floor area we have:
Windows
If the IT closet, computer or server room has no windows then this part of the calculation can be ignored. If
there are windows, then these must be factored depending on whether the windows are south or north facing.
South Window BTU = window Width x Depth (m) x 870 then x 1.5 (if there are no blinds)
North Window BTU = window Width x Depth (m) x 165 then x 1.5 (if there are no blinds)
The total window BTU = Southern Window BTU + Northern Window (BTU)
It is common to allow for 400 BTU per person. The calculation is then:
The total occupant BTU = number of people in the room x 400
For servers the power drawn in by the hardware is converted to heat by the central processing unit (CPU).
Therefore a 900W server will generate 900W of heat. For this calculation it is important to list all the IT
devices including switches, routers and storage devices as well as the servers. The total wattage required for
say a UPS system can be taken for the cooling load in Watts or Kilowatts. For safety add a factor into the
calculation of 1.5 to allow for future expansion.
IT Equipment BTU = Total wattage x 1.5
Other larger electrical systems within the room will also add to the BTU load. An example being an
uninterruptible power supply. The larger the UPS in terms of kVA/kW rating, the higher the heat output. This
will also vary depending on UPS load and battery charge state.
Electrical Lighting
The same process for IT equipment can be repeated for lighting. The final figure is multiplied by 4.25 to give
the lighting BTU but this may be reduced by one third if LED lighting used in place of fluorescent lighting.
Lighting BTU = Total wattage for all lighting x 4.25
The total cooling load is then a summation of the individual calculation as follows:
Floor Area + Window + People + IT Equipment + Lighting = Total Cooling BTU required
and to get the kW divide the Total Cooling BTU by 3412
Total Cooling BTU required / 3412 = Total Cooling kW required
Whilst this is more accurate than the ‘rule of thumb’ calculation it is still general in its approach and can again
only be used as a guide. For a more accurate and complete calculation a site survey is recommended in order to
factor in other site-specific characteristics and requirements and to ensure that the most appropriate cooling
solution technology and correctly sized air conditioner is chosen.
Summary
Climate change continues to push demand for air conditioning and especially within computer and server
rooms that may already be at the edge of their ambient temperature envelope. IT is relatively easy to improve
the cooling air flow within these types of facilities if there is an existing air conditioner to upgrade. For IT
facilities without an existing AC unit the server room cooling requirements must be calculated.
Whilst a quick calculation can be made, it is important for the site to be surveyed by a suitably
qualified HVAC engineer and cooling specialist. Alongside any installed IT network or computer room
cooling solution, it is also important to consider environment monitoring to ensure that sudden heat spikes and
temperature surges generate an alarm condition that can be quickly responded to in order to ensure server
uptime and business continuity.