BX IOM DS T131461 en
BX IOM DS T131461 en
__________________________________________________________________________________________________________________
SecuriFire
BX-IOM
Input/output module for
SecuriLine eXtended
The BX-IOM input/output module has a monitored output and a
monitored input.
Fig. 1 BX-IOM
The monitored output is divided into three load ranges and can Interfaces
actuate and monitor a load of between 20 Ω and 1 kΩ.
Addressing and assigning BX-IOM parameters are performed
with PC software via the fire alarm control panel.
Connection example
Here we describe the connection of a consumer with electronic
input switching. When the measurement voltages are low, they
have no regular resistance value for detecting line breaks, which
is why the consumer is loaded directly on its terminals with oh-
mic resistance (e.g. 680 Ω or 1 kΩ, 1 W).
External
power
supply
+
-
GND
L1
SHLD
X1 BX-IOM
1 VEXT
IM1+ X2
Electronic siren
Input SHLD
IM1-
SHLD
+ OM1+
1k L2
- OM1-
Output GND
control GND
L1 1
SHLD
GND
L2
Technical data
Function Input/output module
Operating voltage 12 to 30 VDC
Current consumption 0.43 mA
Signal transmission Serial data transmission, 2-conductor technology
Protection type 66 with housing IP
Ambient temperature -20 to +60 °C
Connection Screw terminals, max. 1.5 mm2
VdS approval applied for
EU certificate of conformity (EN 54-17/18) applied for
Dimensions (H x W x D) 67 x 67 x 20 mm
Dimensions with housing (H x W x D) 94 x 94 x 57 mm
Monitored input
Monitoring voltage 20 to 30 VDC
Monitoring power typ. 3.1 mA
Termination resistance 220 Ω
Line resistance max. 50 Ω
Line length max. 30 m
Galvanical separation by opto-isolator