SRV6KIL Manual
SRV6KIL Manual
The following special messages may appear throughout this manual or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
The addition of this symbol either to a “Danger” or “Warning” safety
label indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential
personal injury hazards. Obey all safety messages that follow this
symbol to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Product Handling Guidelines
WARNING
RISK OF ELECTRIC SHOCK
The output terminals of the UPS are energized as the utility circuit breaker is
on and the input voltage is applied to input terminals. Be sure to turn off the
utility circuit breaker to de-energize the output terminals.
Failure to follow these instructions can result in death or serious injury.
• When grounding cannot be verified, disconnect the equipment from the utility
power outlet before installing or connecting to other equipment. Reconnect the
power cord only after all connections are made.
• Connection to the branch circuit (mains) must be performed by a qualified
electrician.
• The protective earth conductor for the UPS carries the leakage current from the
load devices (computer equipment). An insulated ground conductor is to be
installed as part of the branch circuit that supplies input power to the UPS. The
conductor must have the same size and insulation material as the grounded and
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
• Replace the battery at least every 5 years or the battery is at the end of its
service life, whichever is earlier.
• Replace the battery immediately when the UPS indicates battery
replacement is necessary.
• Replace batteries with the same number and type of batteries as originally
installed in the equipment.
• Replace the battery immediately when the UPS indicates a battery
over-temperature condition, or when there is evidence of electrolyte
leakage. Power off the UPS, unplug it from the AC input, and disconnect
the batteries. Do not operate the UPS until the batteries have been
replaced.
• *Replace all battery modules (including the modules in External Battery
Packs) which are older than one year, when installing additional battery
packs or replacing the battery module(s).
Failure to follow these instructions can result in injury.
* Contact APC by Schneider Electric Worldwide Customer Support to determine the
age of the installed battery modules.
For the recycling battery information, please go to apc.com/recycle.
• Servicing of user replaceable batteries should be performed or supervised by
personnel knowledgeable about batteries and required precautions. In this case,
batteries is not user replaceable.
• APC by Schneider Electric uses Sealed Maintenance Free Valve Regulated Lead
Acid battery. Under normal use and handling, there is no contact with the
internal components of the batteries. Over charging, over heating or other
misuse of batteries can result in leakage of battery electrolyte.
• CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate the battery or batteries. Released material is harmful to
the skin and eyes. It may be toxic.
• CAUTION: Failed batteries can reach temperatures that exceed the burn
thresholds for touchable surfaces.
• Before replacing batteries, remove conductive jewelry such as chains, wrist
watches, and rings. High energy through conductive materials could cause
severe burns.
Product Description
The APC by Schneider Electric Easy UPS is a high performance, uninterruptible
power supply (UPS). The UPS helps to provide protection to electronic equipment
from utility power blackouts, brownouts, sags, surges, small utility fluctuations and
large disturbances. The UPS also provides battery backup power to connected
equipment until utility power returns to normal levels or the batteries are fully
discharged.
This user manual is available on the enclosed Documentation CD and on the APC by
Schneider Electric Web site, www.apc.com.
RS-232 cable
89a
suo 13
36 7a
suo 1
Optional Accessories
Refer to the APC by Schneider Electric Web site, www.apc.com, for available
accessories.
NOTICE
RISK OF EQUIPMENT DAMAGE
• The UPS must be used indoors only.
• The installation location should be sturdy to withstand the weight of the
UPS.
• Do not operate UPS where there is excessive dust or where the
temperature or humidity are outside specified limits.
Failure to follow these instructions can result in equipment damage.
SRV6KRIL SRV10KRIL
SRV5KRIL
SRV6KIL SRV10KIL
Operating • 0 to 40 °C at rated load
• 40 to 45 °C linearly derated to 85% of maximum load
capacity
Temperature
• 45 to 50 °C linearly derated to 75% of maximum load
capacity
Storage –15 to 60 °C
Operating • 0 to 1,000 m: Normal operation
• 1,000 to 3,000 m: The output power reduces @ 1% for
Elevation every 100 m increase in elevation
• > 3,000 m: UPS will not work
Storage 0 to 15,000 m
Humidity 0 to 95% relative humidity, non-condensing
International Protection Code IP20
Pollution Degree 2
NOTE: Charge the battery module at least once in every six months during storage.
Physical
The equipment is heavy. Follow all lifting guidelines.
UPS SRV5KRIL SRV6KRIL SRV10KRIL
Power Module SRVPM5KRIL SRVPM6KRIL SRVPM10KRIL
Battery Pack SRV240RLBP-9A
Dimensions with Power 240 x 600 x 760 mm
package Module (9.45 x 23.62 x 29.92 in)
Height x Width x Depth
Battery 250 x 580 x 870 mm
Pack (9.84 x 22.83 x 34.25 in
Dimensions without Power 86.5 x 438 x 615 mm
package Module (3.41 x 17.2 x 24.21 in)
Height x Width x Depth
*D1=580 mm (22.83 in); *D2=638 mm (25.19 in)
Battery 133 x 438 x 606 mm
Pack (5.24 x 17.2 x 23.86 in)
Depth
D1 D2
Dep th
D2
Electrical
SRV6KRIL SRV10KRIL
SRV5KRIL
SRV6KIL SRV10KIL
Capacity 5 kVA / 5 kW 6 kVA / 6 kW 10 kVA / 10 kW
Nominal output voltage 230 VAC
Other programmable voltage 220 VAC, 240 VAC
Efficiency at rated load > 94%
Output voltage regulation ±1% static
Output voltage distortion • 1% max. for full linear load
• 4% max. for full RCD load (100% VA, 0.8 PF)
Frequency - On battery 50/60 Hz ± 0.1 Hz
Frequency - AC mode (auto-sensing) 50/60 Hz ± 4 Hz
Crest factor 3:1
Waveform Sinewave
Output connection Terminal
Bypass Internal
Bypass range 185 to 250 VAC ± 1%
suo1520a
Rack-Mount Installation
NOTE: Applicable only for SRV5KRIL/SRV6KRIL/SRV10KRIL models.
CAUTION
RISK OF FALLING EQUIPMENT
• The UPS is heavy. Always practice safe lifting techniques adequate for the
weight of the equipment.
• Do not lift the UPS by holding the front panel display.
• Always install the UPS at the bottom of the rack.
• Given the heavy weight, the use of rack-mount brackets is mandatory
during rack installation (guide with L-shaped support).
• Always use the recommended number of screws to secure brackets to the
UPS.
• Install the UPS above the Battery pack.
• Secure the unit in the rack using all the screws supplied for the purpose.
Failure to follow these instructions can result in minor or moderate injury
and equipment damage.
• Before installing the UPS and the battery pack in the 19 inch rack, be sure that a
shelf is fitted in the rack and the shelf is capable of withstanding the weight of
the UPS and the battery pack.
UP S
ck
ry P a
B atte
suo1929a
NOTE: Install the battery pack in the rack. Refer to the user manual supplied with the
battery pack for details.
Install the rack-mount brackets to the Lift the UPS and slide it into rack.
UPS.
04 a
suo14
x8
suo1 930a
UP S
P
XLB
suo1932a
CAUTION
RISK OF ELECTRIC SHOCK
• Adhere to all national and local electrical codes.
• All electrical work must be performed by a qualified electrician.
• Turn off all power to this equipment before working on the equipment.
• Switch the external circuit breaker off. Practice lockout/tagout procedures.
• Do not wear jewelry when working with electrical equipment.
• Select wire size and connectors according to national and local codes.
Failure to follow these instructions can result in moderate injury.
Backfeed protection
DANGER
RISK OF VOLTAGE BACKFEED
In systems where Backfeed protection is not part of the standard design, an
automatic isolation device (Backfeed protection option or other device meeting
the requirements of IEC 62040-1 or IS 16242, (Part 1)) must be installed to
prevent hazardous voltage or energy at the input terminals of the isolation
device. The device must open within 15 seconds after the upstream power
supply fails and must be rated according to the specifications.
Failure to follow this instruction will result in death or serious injury.
When the UPS input is connected through external isolators that when opened
isolates neutral, below label must be placed at UPS input terminals.
DANGER
RISK OF VOLTAGE BACKFEED
• There is no standard Backfeed protection inside the UPS. Isolate UPS from
AC supplies.
• Check for Hazardous Voltage between all terminals including the protective
earth before working on the UPS.
Failure to follow this instruction will result in death or serious injury.
• Be sure to isolate the UPS before working on it.
• UPS do not have an inbuilt standard backfeed protection. During installation an
additional external isolation device must be installed in UPS system.
Circuit Breaker
PE
L N PE
suo1550a
Input/Output hardwiring
NOTICE
RISK OF DAMAGE
Do not use this UPS for Two phase (Line to Line) input configuration. The
UPS needs a neutral connection to work properly. Operation without Neutral
may damage the unit or connected load.
Failure to follow these instructions can result in equipment damage.
Easy UPS
Battery Pack
suo1410b
x2
1. Locate the battery connector cover on rear panel of UPS and battery pack.
2. Remove the screws securing the cover and remove the cover.
3. Connect the ground wire to the ground terminal in the UPS and battery pack.
4. Plug one end of the battery cable (supplied) connector into the battery connector
receptacle on the rear side of the UPS and the other end of the battery cable
connector into the battery connector receptacle on the rear side of the battery
pack.
5. Secure the battery connectors to the battery connector receptacles on both the
UPS and the battery pack by fastening the screws removed in step 2.
CAUTION
RISK OF ELECTRIC SHOCK
• All electrical work must be performed by a qualified electrician.
• Turn off all power to this equipment before working on the equipment.
• Disconnect the mains power and internal batteries before installing or
servicing the UPS or connected equipment
• UPS AC hardwired and pluggable outlets may be energized by remote or
automatic control at any time.
• Practice lockout/tagout procedures
• Do not wear jewelry when working with electrical equipment.
Failure to follow these instructions can result in moderate injury.
1. Connect equipment to UPS. Refer “Hardwiring” on page 14 for details.
2. Connect battery pack to UPS. Refer “Connect the Battery Pack” on page 17 for
details.
3. Connect input utility power to the UPS. Refer “Hardwiring” on page 14 for
details.
4. Turn on the circuit breaker of the battery pack.
Start the UPS
Press the POWER ON/OFF button located on the front panel of UPS until a beep is
heard. The Status LED will illuminate green.
• The battery charges to 90% capacity during the first five hours of normal
operation.
• Do not expect full backup time during this initial charge period.
Cold start the UPS
Use cold start feature to supply power to connected equipment from the UPS
batteries.
Press the POWER ON/OFF button located on the front panel of UPS until a beep is
heard. The front panel display will illuminate.
Press the POWER ON/OFF button again to supply battery power to the connected
equipment.
Turn off the UPS
To turn off the UPS, press and hold the POWER ON/OFF button on the front panel
display until a beep is heard.
suo 14 11a
Connect the USB cable from the rear of the UPS to the protected device such as a
server.
For a server or other devices with an operating system, load the SchneiderUPS CD
and follow the on-screen set-up instructions.
A built-in serial port is also available for additional communication options with
serial cable.
Additional communication options are available via the built-in intelligent slot. Visit
to APC by Schneider Electric Web site, www.apc.com for more information.
Loosen the screws of terminal 1 and 2 in Remove the metal link between
the EPO connector. terminals 1 and 2.
x2
1 2
1 2
3a
suo 141
suo1412 a
Connect N/C relay contacts1 between Secure the EPO connector screws of
terminals 1 and 2 of the EPO terminal terminals 1 and 2.
block. Use 0.5 to 1 mm2 wire. x2
1 2 1 2
4a a
suo 141 suo1415
NOTE: If the N/C contact is open, the UPS will turn off. Power to the connected
equipment will be immediately turned off.
The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only
to other SELV circuits. The EPO interface monitors circuits that have no
determined voltage potential. Such closure circuits may be provided by a switch
or relay properly isolated from the utility. To avoid damage to the UPS, do not
connect the EPO interface to any circuit other than an unused circuit.
Use one of the following cable types to connect the UPS to the EPO switch.
• CL2: Class 2 cable for general use.
• CL2P: Plenum cable for use in ducts, plenums, and other spaces used
for environmental air.
• CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.
Maintenance Bypass
Maintenance bypass enables the user to isolate the electronic circuitry of the UPS
from the mains and the load without interrupting the load operation by connecting the
loads directly to the bypass utility supply.
• This feature is useful while performing maintenance or service and shall only be
executed by authorized Technical Service Personnel.
• In case of any mains interruption occurs during Maintenance Bypass operation,
all loads on the output will be deenergized. Maintenance Bypass Operation
should not be preferred for long time use.
suo 1830b
Mute / Esc
POWER • Press the POWER ON/OFF button to turn the UPS on.
ON/OFF • Press and hold the POWER ON/OFF button until a beep is heard to turn off
button the UPS.
• Press the POWER ON/OFF button to reset alerts.
Alert The Alert LED illuminates red when the UPS detects an internal error and
LED flashes red for UPS notifications. Refer “Alerts and Notifications” on
page 26 for details.
UP/DOWN Press the UP/DOWN ARROW button to scroll through the main menu options
ARROW and display screens.
button
ENTER Press the ENTER button to enter the menu or to select a menu item/value
button during navigation.
MUTE/ESC Press the MUTE/ESC button:
button • To acknowledge audible alerts and suppress them temporarily.
• To exit a sub menu and return to the main menu.
LCD The display interface options are visible on this LCD screen. Press the
Display UP/DOWN ARROW button to activate LCD, if the display is not illuminated.
Status The Status LED illuminates green when the power is on. The LED
LED indicates two different states of output power:
• Output off: LED flashes. Press POWER ON/OFF button to turn the output
power on.
• Output on: LED illuminates green continuously.
ON BATT
Replace Battery: The battery is not connected securely or the
battery is nearing the end of its service life and should be replaced.
Configuration
Configure UPS parameters
Follow the steps to configure parameters in the UPS:
1. Press the ENTER button.
2. Press the UP/DOWN ARROW buttons to navigate to “Set”.
3. Press the ENTER button.
Test passed.
The UPS has detected a If the UPS does not recover automatically,
DC voltage error. Unit contact APC by Schneider Electric.
will try to auto-recover
from this condition.
Temperature of the unit is Disconnect nonessential equipment from the
rising above the set UPS to reduce the load.
limits. Ensure that ambient temperature is within
limits.
Ensure that adequate clearance is maintained.
UPS has detected a Be sure that there no short circuit at the UPS
charger error. battery terminals.
Press POWER ON/OFF button to start the UPS.
Contact APC by Schneider Electric for all other alert codes.
Troubleshooting
Use the table below to solve minor installation and operation problems. Refer to the
APC by Schneider Electric Web site, www.apc.com for assistance with complex UPS
problems.
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
1. Review the Troubleshooting section of the manual to eliminate common
problems.
2. If the problem persists, contact APC by Schneider Electric Customer Support.
a. Note the model number and serial number and the date of purchase. The
model and serial numbers are located on a label in the rear panel of the unit
and are also available through the LCD display on select models.
b. Call APC by Schneider Electric Customer Support and a technician will
attempt to solve the problem over the phone. If this is not possible, the
technician will issue a Return Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d. Service procedures and returns may vary internationally. For country specific
instructions refer to the APC by Schneider Electric website, www.apc.com.
3. Pack the unit properly to avoid damage in transit. Never use foam beads for
packaging.
Damage sustained in transit is not covered under warranty.
NOTE: Before shipping, always disconnect battery modules in the UPS or
external battery pack.
The disconnected internal batteries may remain inside the UPS or external
battery pack.
4. Write the RMA# provided by Customer Support on the outside of the package.
5. Return the unit by insured, prepaid carrier to the address provided by Customer
Support.
© 2022 APC by Schneider Electric. APC, the APC logo, and Easy UPS are
owned by Schneider Electric Industries S.A.S., or their affiliated companies. All EN 990-91615
other trademarks are property of their respective owners. 03/2022